Utilize more of the DGC-2020HD’s power with the VRM-2020: a rugged, reliable,
remote module which communicates with the DGC-2020HD and provides
excitation to the field of a brushless exciter to achieve precise automatic
voltage regulation (var/PF control).
Features Benefits
• Five pre-position setpoints for each control mode • Expands the already extensive capabilities of the DGC-2020HD by
• Internal tracking between AVR (Automatic Voltage Regulation) and FCR providing field excitation for brushless exciters.
(Field Current Regulation) operating mode setpoints • Enhances protection by implementing up to eight RTD (resistance
• PID stability group with Auto Tune feature temperature device) inputs.
• Real-time metering of field voltage and current • Maintain precise genset control with the VRM-2020’s ±0.25%
regulation accuracy (no load to full load).
• Soft start and voltage buildup control
• The VRM-2020’s potted design provides exceptional reliability in
• Limiting functions include overexcitation (summing point and harsh environments, easily allowing years of worry-free operation.
takeover), underexcitation, underfrequency, and V/Hz limiting
• A rugged power stage creates an easy solution for applications
• Communications via CAN (Controller Area Network) containing high waveform distortion caused by nonlinear loading.
• Integrated generator and exciter protection ensure reliable and
safe operation of the entire system.
Specifications
Power Supply RTD Inputs (optional) Environmental
Nominal: 12 or 24 Vdc Number of Inputs: 8 Operating Temp: -40°C to 70°C (-40°F to 158°F)
Range: 6 to 32 Vdc Rating: 100 Ω platinum or 10 Ω copper Storage Temp: -40°C to 85°C (-40°F to 185°F)
Burden: 1 W at 32 Vdc Setting Range: -50°C to 250°C (-58°F to 482°F) Shock: 15 G in three planes
Accuracy Vibration: 3 to 25 Hz at 1.6 mm (0.063 in.)
Input Power
10 Ω copper: ±0.078 Ω at 25°C peak amplitude, 25 to 2,000 Hz
Range: 150 to 300 Vac
100 Ω platinum: ±0.757 Ω at 25°C at 5 G
Frequency: 50 to 300 Hz
Burden: 517 VA at 3.5 Adc field output Communication Physical
CAN Interface Weight: 1.05 lb (0.476 kg)
Output Power
Differential Bus Voltage: 1.5 to 3 Vdc Dimensions (WxHxD):
Max Continuous: 3.5 Adc at 63 Vdc
Maximum Voltage: -32 to +32 Vdc 4.897 x 5.493 x 1.952 inches
10-Second Forcing: 7.5 Adc at 120 Vdc
Communication Rate: 125 or 250 kbps (124.4 x 139.5 x 49.6 mm)
Regulation Accuracy
Agency/Certifications
Better than ±0.25%, from no load to full load For complete specifications, download the instruction
CSA certified, UL recognized, CE EMC and LVD
manual at www.basler.com.
compliant, NFPA compliant, ABS Tier 3 recognized
AEM-2020
VRM-2020
(Optional)
Bus Stub
CAN-H
CEM-2020
DGC-2020HD
(Optional)
CAN-L
12570 Route 143 • Highland, Illinois 62249-1074 USA 111 North Bridge Road #15-06 Peninsula Plaza
Tel +1 618.654.2341 • Fax +1 618.654.2351 Singapore 179098
email: info@basler.com Tel +65 68.44.6445 • Fax +65 68.44.8902
e-mail: singaporeinfo@basler.com