PLC Programming 9
PLC Programming 9
Voltage / Current
Input / Output Mixture
FX3U -3A-ADP
Before installation, operation, maintenance or inspection of this product, thoroughly read through and
understand this manual and all of the associated manuals. Also, take care to handle the module properly and
safely.
This manual classifies the safety precautions into two categories: and .
Depending on the circumstances, procedures indicated by may also cause severe injury.
It is important to follow all precautions for personal safety.
Store this manual in a safe place so that it can be taken out and read whenever necessary. Always forward it
to the end user.
1. DESIGN PRECAUTIONS
• Make sure to have the following safety circuits outside of the PLC to ensure safe system operation even during
external power supply problems or PLC failure.
Otherwise, malfunctions may cause serious accidents.
1) Most importantly, have the following: an emergency stop circuit, a protection circuit, an interlock circuit for
opposite movements (such as normal vs. reverse rotation), and an interlock circuit (to prevent damage to the
equipment at the upper and lower positioning limits).
2) Note that when the PLC CPU detects an error, such as a watchdog timer error, during self-diagnosis, all
outputs are turned off. Also, when an error that cannot be detected by the PLC CPU occurs in an input/output
control block, output control may be disabled.
External circuits and mechanisms should be designed to ensure safe machinery operation in such a case.
3) Note that the output current of the service power supply for sensors varies depending on the model and the
absence/presence of extension blocks. If an overload occurs, the voltage automatically drops, inputs in the
PLC are disabled, and all outputs are turned off.
External circuits and mechanisms should be designed to ensure safe machinery operation in such a case.
4) Note that when an error occurs in a relay, triac or transistor output device, the output could be held either on or
off.
For output signals that may lead to serious accidents, external circuits and mechanisms should be designed to
ensure safe machinery operation in such a case.
• Do not bundle the control line together with or lay it close to the main circuit or power line.
As a guideline, lay the control line at least 100mm(3.94") or more away from the main circuit or power line.
Noise may cause malfunctions.
• Make sure to ground the shield wire or shield of the shielded cable connected to a special analog input adaptor or
special analog extension block at one point on the PLC.
However, do not use common grounding with heavy electrical systems.
Noise may cause malfunctions.
• Make sure to ground the shield wire or shield of the shielded cable connected to a special analog output adaptor
or special analog extension block at one point on the analog device side.
However, do not use common grounding with heavy electrical systems.
Noise may cause malfunctions.
• Install module so that excessive force will not be applied to the power connectors or terminal blocks.
Failure to do so may result in wire damage/breakage or PLC failure.
(1)
Safety Precautions
(Read these precautions before use.)
2. WIRING PRECAUTIONS
• Make sure to cut off all phases of the power supply externally before attempting wiring work.
Failure to do so may cause electric shock or damages to the product.
• Connect the DC power supply wiring to the dedicated terminals described in this manual.
If an AC power supply is connected to a DC input/output terminal or DC power supply terminal, the PLC will be
burnt out.
• Do not wire vacant terminals externally.
Doing so may damage the product.
• Perform class D grounding (grounding resistance: 100Ω or less) to the grounding terminal on the main unit.
Do not use common grounding with heavy electrical systems.
• When drilling screw holes or wiring, make sure cutting or wire debris does not enter the ventilation slits.
Failure to do so may cause fire, equipment failures or malfunctions.
• Make sure to observe the following precautions in order to prevent malfunctions under the influence of noise:
- Do not bundle the power line or twisted shielded cable together with or lay it close to the main circuit, high-
voltage line, or load line.
Otherwise, noise disturbance and/or surge induction are likely to take place. As a guideline, lay the control line
at least 100mm (3.94") or more away from the main circuit, high-voltage line, or load line.
- Ground the shield of the analog input/output cable at one point on the signal receiving side.
However, do not use common grounding with heavy electrical systems.
• Make sure to properly wire to the European terminal board in accordance with the following precautions.
Failure to do so may cause electric shock, a short-circuit, wire breakage, or damage to the product.
- The disposal size of the cable end should be 9 mm (0.35").
- Tightening torque should be between 0.22 to 0.25 N•m.
- Twist the end of strand wire and make sure there are no loose wires.
- Do not solder-plate the electric wire ends.
- Do not connect more than the specified number of wires or electric wires of unspecified size.
- Affix the electric wires so that neither the terminal block nor the connected parts are directly stressed.
(2)
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition
Foreword
This manual describes the "analog" function of the MELSEC-F FX Series programmable controllers and
should be read and understood before attempting to install or use the unit.
Store this manual in a safe place so that you can take it out and read it whenever necessary. Always forward
it to the end user.
This manual confers no industrial property rights or any rights of any other kind, nor does it confer any patent
licenses. Mitsubishi Electric Corporation cannot be held responsible for any problems involving industrial property
rights which may occur as a result of using the contents noted in this manual.
1
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition
Outline Precautions
• This manual provides information for the use of the FX3U Series Programmable Controllers. The manual
has been written to be used by trained and competent personnel. The definition of such a person or
persons is as follows;
1) Any engineer who is responsible for the planning, design and construction of automatic equipment
using the product associated with this manual should be of a competent nature, trained and qualified
to the local and national standards required to fulfill that role. These engineers should be fully aware of
all aspects of safety with regards to automated equipment.
2) Any commissioning or service engineer must be of a competent nature, trained and qualified to the
local and national standards required to fulfill that job. These engineers should also be trained in the
use and maintenance of the completed product. This includes being completely familiar with all
associated documentation for the said product. All maintenance should be carried out in accordance
with established safety practices.
3) All operators of the completed equipment should be trained to use that product in a safe and
coordinated manner in compliance to established safety practices. The operators should also be
familiar with documentation which is connected with the actual operation of the completed equipment.
Note: the term 'completed equipment' refers to a third party constructed device which contains or uses
the product associated with this manual
• This product has been manufactured as a general-purpose part for general industries, and has not been
designed or manufactured to be incorporated in a device or system used in purposes related to human life.
• Before using the product for special purposes such as nuclear power, electric power, aerospace, medicine
or passenger movement vehicles, consult with Mitsubishi Electric.
• This product has been manufactured under strict quality control. However when installing the product
where major accidents or losses could occur if the product fails, install appropriate backup or failsafe
functions in the system.
• When combining this product with other products, please confirm the standard and the code, or regulations
with which the user should follow. Moreover, please confirm the compatibility of this product to the system,
machine, and apparatus with which a user is using.
• If in doubt at any stage during the installation of the product, always consult a professional electrical
engineer who is qualified and trained to the local and national standards. If in doubt about the operation or
use, please consult the nearest Mitsubishi Electric distributor.
• Since the examples indicated by this manual, technical bulletin, catalog, etc. are used as a reference,
please use it after confirming the function and safety of the equipment and system. Mitsubishi Electric will
accept no responsibility for actual use of the product based on these illustrative examples.
• This manual content, specification etc. may be changed without a notice for improvement.
• The information in this manual has been carefully checked and is believed to be accurate; however, if you
have noticed a doubtful point, a doubtful error, etc., please contact the nearest Mitsubishi Electric
distributor.
Registration
• Microsoft® and Windows® are either registered trademarks or trademarks of Microsoft Corporation in the
United States and/or other countries.
• The company name and the product name to be described in this manual are the registered trademarks or
trademarks of each company.
2
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition Table of Contents
Table of Contents
SAFETY PRECAUTIONS .................................................................................................. (1)
Common Items
1. Introduction A-1
3
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition Table of Contents
4
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition Table of Contents
1. Outline B-3
2. Specifications B-6
3. Wiring B-10
5
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition Table of Contents
8. Troubleshooting B-62
6
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition Table of Contents
1. Outline C-3
2. Specifications C-6
3. Wiring C-10
4. Programming C-15
6. Troubleshooting C-29
7
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition Table of Contents
1. Outline D-3
2. Specifications D-6
3. Wiring D-9
4. Programming D-13
6. Troubleshooting D-21
8
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition Table of Contents
1. Outline E-3
2. Specifications E-6
3. Wiring E-9
9
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition Table of Contents
9. Troubleshooting E-64
10
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition Table of Contents
1. Outline F-3
2. Specifications F-6
3. Wiring F-10
4. Programming F-15
6. Troubleshooting F-26
11
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition Table of Contents
1. Outline G-3
2. Specifications G-6
3. Wiring G-9
4. Programming G-13
6. Troubleshooting G-19
12
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition Table of Contents
FX3U-3A-ADP
(2-channel analog Input, 1-channel analog output)
1. Outline H-3
2. Specifications H-6
3. Wiring H-10
4. Programming H-16
13
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition Table of Contents
6. Troubleshooting H-34
14
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition Table of Contents
FX3U-4AD-PT-ADP
(4-channel Platinum Resistance Thermometer Data Input)
1. Outline I-3
2. Specifications I-6
3. Wiring I-10
4. Programming I-15
5. Troubleshooting I-26
15
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition Table of Contents
FX3U-4AD-PTW-ADP
(4-channel Platinum Resistance Thermometer Data Input)
1. Outline J-3
2. Specifications J-6
3. Wiring J-10
4. Programming J-15
5. Troubleshooting J-26
16
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition Table of Contents
1. Outline K-3
2. Specifications K-6
3. Wiring K-10
4. Programming K-16
5. Troubleshooting K-29
17
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition Table of Contents
1. Outline L-3
2. Specifications L-6
3. Wiring L-10
4. Programming L-16
5. Troubleshooting L-29
18
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition Table of Contents
1. Outline M-3
3. Parameter M-7
4. Auto-Tuning M-18
6. Troubleshooting M-28
Warranty...................................................................................................................................... i
19
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition Table of Contents
MEMO
20
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 1 Introduction
Common Items 1.1 Outline and Features of Analog Control
Common Items
1. Introduction
This manual describes the analog products for the FX3G/FX3U/FX3UC Series PLC.
This chapter describes the analog control methods and applications.
B
FX3UC-4AD
FX3U-4AD
1.1 Outline and Features of Analog Control
For the FX Series, there are 3 types of analog control: Voltage/Current input, Voltage/Current output, and
Temperature Sensor input. C
It is important to select products that are optimum for the purpose of use.
FX3U-4AD-ADP
FX3U Series PLC FX3UC Series PLC FX3G Series PLC
FX3G-2AD-BD
E
FX3U-4DA
Voltage/current input Voltage/current Temperature sensor
control type output control type input control type
•FX3U-4AD •FX3U-4DA •FX3U-4AD-PT-ADP
•FX3UC-4AD •FX3U-4DA-ADP •FX3U-4AD-PTW-ADP
•FX3U-4AD-ADP •FX3U-3A-ADP ••FX3U-4AD-PNK-ADP
•FX3U-3A-ADP
•FX3G-2AD-BD
•FX3G-1DA-BD •FX3U-4AD-TC-ADP
F
FX3U-4DA-ADP
→ Refer to Subsection → Refer to Subsection → Refer to Subsection
1.1.1. 1.1.2. 1.1.3.
FX3G-1DA-BD
Flowmeter, Inverter, etc. Thermocouple,
pressure sensor, etc. platinum resistance
thermometer
sensor
H
FX3U-3A-ADP
In addition to the above applications, the FX3U/FX3UC/FX3G Series PLC can be used for various purposes.
I
FX3U-4AD-PT
-ADP
J
FX3U-4AD-PTW
-ADP
A-1
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 1 Introduction
Common Items 1.1 Outline and Features of Analog Control
→ To determine whether or not a unit can be connected to the PLC, refer to Chapter 3 "System
Configuration Drawings of Analog Products."
A-2
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 1 Introduction
Common Items 1.1 Outline and Features of Analog Control
Common Items
Output the voltage/current signal from the PLC to an inverter, etc. to control the inverter frequency, etc.
Inverter, etc.
FX3U/FX3UC/FX3G Series PLC
FX3UC-4AD
FX3U-4AD
data
block, special
adapter,
expansion board
FX3U-4AD-ADP
the input voltage/current.
→ To determine whether or not a unit can be connected to the PLC, refer to Chapter 3 "System
Configuration Drawings of Analog Products."
FX3G-2AD-BD
→ For detailed description, refer to Section E.
• FX3U-4DA-ADP
→ For detailed description, refer to Section F.
• FX3U-3A-ADP
→ For detailed description, refer to Section H. E
FX3U-4DA
Analog output products for FX3G Series
• FX3G-1DA-BD
→ For detailed description, refer to Section G.
FX3U-4DA-ADP
• FX2N-4DA • FX2N-5A
→ For a detailed description of the other analog output
products, refer to the corresponding manuals.
FX3G-1DA-BD
H
FX3U-3A-ADP
I
FX3U-4AD-PT
-ADP
J
FX3U-4AD-PTW
-ADP
A-3
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 1 Introduction
Common Items 1.1 Outline and Features of Analog Control
Measure the
temperature of the Check the temperature
equipment. using the PLC.
→ To determine whether or not a unit can be connected to the PLC, refer to Chapter 3 "System
Configuration Drawings of Analog Products."
A-4
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 2 Description of Analog Products
Common Items 2.1 Types of Analog Products
Common Items
2. Description of Analog Products
FX3UC-4AD
FX3U-4AD
Analog input/output products are required to perform analog control using the FX Series PLC.
There are 3 types of input/output products: the expansion board, special adapter and the special function
block.
Subsequent subsections explain differences among analog products.
C
2.1.1 Expansion board
FX3U-4AD-ADP
The analog expansion board uses PLC devices to send/receive data to/from the PLC.
FX3G-2AD-BD
• Up to 2*1 analog expansion boards can be connected.
PLC
Analog
expansion board
E
FX3U-4DA
→ For a detailed description of the system configuration, refer to the PLC User’s Manual - Hardware
F
FX3U-4DA-ADP
Edition.
*1. Only 1 analog special adapter can be connected to the FX3G Series PLC(14-point and 24-point type).
When two analog expansion boards are connected to the FX3G Series PLC(40-point or 60-point type),
analog special adapters are not available in the main unit.
G
FX3G-1DA-BD
H
FX3U-3A-ADP
I
FX3U-4AD-PT
-ADP
J
FX3U-4AD-PTW
-ADP
A-5
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 2 Description of Analog Products
Common Items 2.1 Types of Analog Products
RDA
RD
RDB
SDA
SD SDB
SG
FX3U-***-BD
→ For a detailed description of the system configuration, refer to the PLC User’s Manual - Hardware
Edition.
A-6
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 2 Description of Analog Products
Common Items 2.1 Types of Analog Products
3. FX3UC-32MT-LT(-2) PLC
A
Common Items
• Connect the special adapter(s) to the left side of the FX3UC-32MT-LT(-2) PLC.
• An expansion board is needed to connect the special adapter(s).
• Up to 4 analog special adapters can be connected.
Analog special adapters Expansion board PLC
FX3UC-4AD
FX3U-4AD
POWER POWER POWER POWER
RDA
RD
RDB
SDA
SD SDB
SG
FX3U-***-BD C
FX3U-4AD-ADP
Up to 4 Analog adapters can be connected. "***" represents "422", "232", "485", "CNV", or "USB."
→ For a detailed description of the system configuration, refer to the PLC User’s Manual - Hardware Edition.
FX3G-2AD-BD
• Connect the special adapter(s) to the left side of the FX3G Series PLC.
• A connector conversion board is needed to connect the special adapter(s).
• Up to 2*1 analog special adapters can be connected.
E
Analog Connector conversion adapter PLC
special adapters
FX3U-4DA
F
FX3U-4DA-ADP
FX3G-CNV-ADP
FX3G-1DA-BD
analog special adapters are not available in the main unit.
H
FX3U-3A-ADP
I
FX3U-4AD-PT
-ADP
J
FX3U-4AD-PTW
-ADP
A-7
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 2 Description of Analog Products
Common Items 2.1 Types of Analog Products
Up to 8*1 special function units/blocks can be connected (excluding the special adapters).
→ For a detailed description of the system configuration, refer to the PLC User's Manual - Hardware Edition.
A-8
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 2 Description of Analog Products
Common Items 2.2 List of Analog Product Models
Common Items
The analog input/output products compatible with the FX3U/FX3UC/FX3G Series PLC are described below:
FX3UC-4AD
FX3U-4AD
No. of Refer-
Type Range Resolution Function
channels ence
Voltage/current input
FX3G-2AD-BD 2ch
Voltage: 0V to 10V DC 2.5mV(12bits) Combined use of voltage and
current inputs is possible.
D C
Current: 4mA to 20mA DC 8μA(11bits)
FX3U-4AD-ADP
Voltage/current output
Voltage: 0V to 10V DC 2.5mV(12bits)
FX3G-1DA-BD 1ch Voltage and current output. G
Current: 4mA to 20mA DC 8μA(11bits)
FX3G-2AD-BD
No. of Refer-
Type Range Resolution Function
channels ence
Voltage/current input
FX3U-4AD-ADP 4ch
Voltage: 0V to 10V DC 2.5mV(12bits) Combined use of voltage and
C E
Current: 4mA to 20mA DC 10μA(11bits) current inputs is possible.
FX3U-4DA
Voltage/current output
Voltage: 0V to 10V DC 2.5mV(12bits) Combined use of voltage and
FX3U-4DA-ADP 4ch F
Current: 4mA to 20mA DC 4μA(12bits) current outputs is possible.
Voltage/current input/output mixture
Voltage: 0V to 10V DC 2.5mV(12bits)
F
Input
FX3U-4DA-ADP
2ch Current: 4mA to 20mA DC 5μA(12bits) Combined use of voltage/
FX3U-3A-ADP current inputs and voltage/ H
Output Voltage: 0V to 10V DC 2.5mV(12bits) current output is possible.
1ch Current: 4mA to 20mA DC 4μA(12bits)
Temperature sensor input
Compatible with the platinum
G
FX3G-1DA-BD
resistance thermometer
sensor (Pt100).
FX3U-4AD-PT-ADP 4ch Pt100: -50°C to +250°C 0.1°C I
The product can be switched
between "Centigrade" and
"Fahrenheit."
Compatible with the platinum H
resistance thermometer
FX3U-3A-ADP
sensor (Pt100).
FX3U-4AD-PTW-ADP 4ch Pt100: -100°C to +600°C 0.2°C to 0.3°C J
The product can be switched
between "Centigrade" and
"Fahrenheit."
Compatible with
Type K: -100°C to +1000°C 0.4°C thermocouple types K and J.
FX3U-4AD-TC-ADP 4ch The product can be switched L J
Type J: -100°C to +600°C 0.3°C between "Centigrade" and
FX3U-4AD-PTW
"Fahrenheit."
-ADP
A-9
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 2 Description of Analog Products
Common Items 2.2 List of Analog Product Models
No. of Refer-
Type Range Resolution Function
channels ence
Voltage/current input
Voltage: 0.32mV Combined use of voltage and
-10V to +10V DC (with sign, 16 bits) current inputs is possible. The
FX3U-4AD*1 4ch offset/gain can be adjusted.*3 B
Current: 1.25μA
The sampling function is
-20mA to +20mA DC (with sign, 15 bits)
incorporated.
Voltage: 0.32mV Combined use of voltage and
-10V to +10V DC (with sign, 16 bits) current inputs is possible. The
FX3UC-4AD*2 4ch offset/gain can be adjusted.*3 B
Current: 1.25μA
The sampling function is
-20mA to +20mA DC (with sign, 15 bits)
incorporated.
Voltage: 0.32mV Combined use of voltage and
-10V to +10V DC (with sign, 16 bits) current inputs is possible.
The offset/gain can be
FX2NC-4AD*2 4ch *5
Current: 1.25μA adjusted.*3
-20mA to +20mA DC (with sign, 15 bits) The sampling function is
incorporated.
Voltage: 0.63mV Combined use of voltage,
-10V to +10V DC (with sign, 15 bits) current, and thermocouple is
possible. The offset/gain can be
FX2N-8AD*1 8ch *5
Current: 2.5μA adjusted.*3
-20mA to +20mA DC (with sign, 14 bits) The sampling function is
incorporated.
Voltage: 5mV
-10V to +10V DC (with sign, 12 bits) Combined use of voltage and
*1 4ch current inputs is possible. *5
FX2N-4AD
Current: 10μA The offset/gain can be adjusted.
-20mA to +20mA DC (with sign, 11 bits)
Voltage: 2.5mV Combined use of voltage and
0V to 10V DC (12bits) current inputs is impossible.
FX2N-2AD*1 2ch *5
Current: 4μA The offset/gain can be adjusted.
4mA to 20mA DC (12bits) (Common to 2 input channels)
Voltage/current output
Voltage: 0.32mV
Combined use of voltage and
-10V to +10V DC (with sign, 16 bits)
FX3U-4DA*1 4ch current outputs is possible.*4 E
Current: 0.63μA
The offset/gain can be adjusted.
0mA to 20mA DC (15bits)
Voltage: 5mV
-10V to +10V DC (with sign, 12 bits) Combined use of voltage and
FX2NC-4DA*2 4ch current outputs is possible. *5
Current: 20μA The offset/gain can be adjusted.
0mA to 20mA DC (10bits)
Voltage: 5 mV
-10V to +10V DC (with sign, 12 bits) Combined use of voltage and
FX2N-4DA*1 4ch current outputs is possible. *5
Current: 20μA The offset/gain can be adjusted.
0mA to 20mA DC (10bits)
Voltage: 2.5 mV
0V to 10V DC (12 bits) Combined use of voltage and
FX2N-2DA*1 2ch current outputs is possible. *5
Current: 4μA The offset/gain can be adjusted.
4mA to 20mA DC (12bits)
*1. To connect this block to the FX3UC Series PLC, either the FX2NC-CNV-IF or FX3UC-1PS-5V is required.
*2. Connectable with the FX3UC Series PLC only.
*3. The offset and gain of the FX3U-4AD, FX3UC-4AD, FX2NC-4AD and FX2N-8AD cannot be adjusted for
channels using the analog value direct indication mode.
*4. The offset and gain of the FX3U-4DA cannot be adjusted for channels using the analog value mV (or μA)
specification mode.
*5. Refer to the instruction manual of the respective product.
A-10
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 2 Description of Analog Products
Common Items 2.2 List of Analog Product Models
No. of Refer-
A
Type Range Resolution Function
Common Items
channels ence
Voltage/current input/output mixture
Voltage: 0.32mV
Input -10V to +10V DC (with sign, 16 bits) Combined use of voltage and
4ch Current: 1.25μA
-20mA to +20mA DC (with sign, 15 bits)
current is possible.
The offset/gain can be B
FX2N-5A*1 *2
FX3UC-4AD
FX3U-4AD
Voltage: 5mV adjusted.*3
Output -10V to +10V DC (with sign, 12 bits) The scaling function is
1ch Current: 20μA incorporated.
0mA to 20mA DC (10bits)
Voltage: 40mV
Input 0V to 10V DC (8bits) C
2ch Current: 64μA
FX3U-4AD-ADP
The input format is common to 2
4mA to 20mA DC (8bits) channels.
FX0N-3A*1, *4 *2
Voltage: 40mV The offset/gain can be adjusted.
Output 0V to 10V DC (8bits) (Common to 2 input channels)
1ch Current: 64μA
4mA to 20mA DC (8bits) D
Temperature sensor input
FX3G-2AD-BD
Type K: Combined use of voltage,
0.1°C
-100°C to +1200°C current, and thermocouple is
Type J: possible.
0.1°C Compatible with thermocouple
-100°C to +600°C
FX2N-8AD*1 8ch types K, J, and T.
The unit can be switched between
*2
E
Type T:
FX3U-4DA
0.1°C "Centigrade" and "Fahrenheit."
-100°C to +350°C The sampling function is
incorporated.
Type K: Compatible with thermocouple
0.4°C
-100°C to +1200°C types K and J.
FX2N-4AD-TC*1 4ch *2
Type J:
0.3°C
The unit can be switched between
"Centigrade" and "Fahrenheit."
F
-100°C to +600°C
FX3U-4DA-ADP
Compatible with the platinum
resistance thermometer sensor
Pt100:
FX2N-4AD-PT*1 4ch 0.2°C to 0.3°C (Pt100 or JPt100). *2
-100°C to +600°C
The unit can be switched between
"Centigrade" and "Fahrenheit."
Example: Compatible with thermocouple
G
FX3G-1DA-BD
Type K: types K, J, R, S, E, T, B, N, PL II,
-100°C to +1300°C WRe5-26, U, and L.
Compatible with the platinum
resistance thermometer sensor
(Pt100, JPt100).
FX2N-2LC*1 2ch
0.1°C or 1°C
(Depends on the
The unit can be switched between
"Centigrade" and "Fahrenheit." *2
H
FX3U-3A-ADP
*1. To connect this block to the FX3UC Series PLC, either the FX2NC-CNV-IF or FX3UC-1PS-5V is required.
*2. Refer to the instruction manual of the respective product.
-ADP
*3. The offset and gain of the FX2N-5A cannot be adjusted for channels using the analog value direct
indication mode or analog value mV (or μA) specification mode.
*4. The FX0N-3A cannot be connected to the FX3G Series PLC.
J
FX3U-4AD-PTW
-ADP
A-11
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 3 System Configuration Drawings of Analog Products
Common Items 3.1 FX3U Series PLC
FX3U Series
• Flowmeter
RD
RDB
SD
SDA
SDB
European terminal block
• Pressure sensor
SG
A
Up to 4 analog special adapters can be connected.
Analog output
European terminal block
• Inverter, etc.
FX3U-4DA-ADP
A Analog input
• Flowmeter
European terminal block • Pressure sensor
• Signal converter, etc.
A Temperature sensor
input
• Thermocouple
European terminal block
(types K and J)
• Resistance
thermometer
FX3U-4AD-TC-ADP sensor (Pt1000 and
FX3U-4AD-PNK-ADP
Ni1000)
FX3U-4AD-PT-ADP • Platinum resistance
FX3U-4AD-PTW-ADP thermometer
sensor (Pt100)
A-12
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 3 System Configuration Drawings of Analog Products
Common Items 3.1 FX3U Series PLC
Common Items
FX3U Series A , B , and C represent the connecting positions.
For a detailed description of installation, refer to the following manual
supplied with your PLC.
A
B C → Refer to the FX3U Series User's Manual - Hardware Edition.
B
FX3UC-4AD
FX3U-4AD
To connect the special adapters A or the expansion boards B ,
refer to the previous page.
Up to 8 special function blocks can be connected.
C
Analog input
FX3U-4AD-ADP
C • Flowmeter
• Pressure sensor
• Signal converter,
etc.
Terminal block
Analog output D
Special function
FX3G-2AD-BD
• Inverter, etc.
block for FX3U,
FX2N and FX0N
Temperature sensor
input
• Thermocouple
• Platinum resistance
thermometer
E
sensor (Pt100)
FX3U-4DA
• For a detailed description of the connectable special function blocks and system configuration:
→ Refer to the FX3U Series User's Manual - Hardware Edition.
F
FX3U-4DA-ADP
The analog special function blocks shown in the table below can be connected to the FX3U Series PLC:
FX Series Type
Analog special function blocks for
FX3U-4AD, FX3U-4DA
the FX3U
Analog special function blocks for FX2N-8AD, FX2N-4AD, FX2N-2AD, FX2N-4DA, FX2N-2DA, FX2N-5A, G
FX3G-1DA-BD
the FX2N FX2N-4AD-PT, FX2N-4AD-TC, FX2N-2LC
Analog special function blocks for
FX0N-3A
the FX0N
H
FX3U-3A-ADP
I
FX3U-4AD-PT
-ADP
J
FX3U-4AD-PTW
-ADP
A-13
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 3 System Configuration Drawings of Analog Products
Common Items 3.2 FX3UC Series PLC
Analog output
Up to 4 analog special adapters can be connected.
FX3U-4DA-ADP
A
Analog input
•Flowmeter
European terminal block •Pressure sensor
•Signal converter, etc.
FX3U-3A-ADP Analog output
•Inverter, etc.
A Temperature sensor
input
•Thermocouple
European terminal block
(types K and J)
•Resistance
thermometer
FX3U-4AD-TC-ADP sensor (Pt1000 and
FX3U-4AD-PNK-ADP Ni1000)
FX3U-4AD-PT-ADP •Platinum resistance
FX3U-4AD-PTW-ADP thermometer
sensor (Pt100)
A-14
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 3 System Configuration Drawings of Analog Products
Common Items 3.2 FX3UC Series PLC
2. FX3UC-32MT-LT(-2) PLC
A
Common Items
To connect the special function blocks C or the conversion adapters D ,
A C1 D C2
refer to Subsection 3.2.2-2.
B
FX3UC-4AD
FX3U-4AD
your PLC.
→ Refer to the FX3UC Series User's Manual - Hardware Edition.
B A
RDA
Analog input
C
RD
RDB
SD SDB
SG
•Pressure sensor
FX3U-4AD-ADP
FX3U-***-BD*1 FX3U-4AD-ADP •Signal converter, etc.
Analog output
D
Up to 4 analog special adapters can be connected.
FX3G-2AD-BD
FX3U-4DA-ADP
A Analog input
•Flowmeter
FX3U-4DA
•Signal converter, etc.
*2 Analog output
FX3U-3A-ADP
•Inverter, etc.
F
A Temperature sensor
FX3U-4DA-ADP
input
• Thermocouple
European terminal block
(types K and J)
• Resistance
thermometer
FX3U-4AD-TC-ADP
FX3U-4AD-PNK-ADP
sensor (Pt1000 and
Ni1000)
G
FX3G-1DA-BD
FX3U-4AD-PT-ADP • Platinum resistance
FX3U-4AD-PTW-ADP thermometer
sensor (Pt100)
H
FX3U-3A-ADP
I
FX3U-4AD-PT
-ADP
J
FX3U-4AD-PTW
-ADP
A-15
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 3 System Configuration Drawings of Analog Products
Common Items 3.2 FX3UC Series PLC
C1
FX3UC-4AD
C1
Up to 8 special function blocks can be connected.
C1 or C2 Special function
block for FX2NC
FX3UC-1PS-5V
C2
Terminal block
Special function
block for FX3U,
FX2NC-CNV-IF FX2N and FX0N
• For a detailed description of special function block connectability and system configuration:
→ Refer to the FX3UC Series User's Manual - Hardware Edition.
• Use the FX3UC-1PS-5V (extension power supply unit) if the capacity of the 5V DC power supply unit
incorporated in the FX3UC Series PLC is deteriorated.
→ Refer to the FX3UC Series User's Manual - Hardware Edition.
The analog special function blocks shown in the table below can be connected to the FX3UC Series PLC:
FX Series Type
Analog special function blocks for the FX3U FX3U-4AD, FX3U-4DA
Analog special function blocks for the FX2NC FX2NC-4AD, FX2NC-4DA
FX2N-8AD, FX2N-4AD, FX2N-2AD, FX2N-4DA, FX2N-2DA,
Analog special function blocks for the FX2N
FX2N-5A, FX2N-4AD-PT, FX2N-4AD-TC, FX2N-2LC
Analog special function blocks for the FX0N FX0N-3A
A-16
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 3 System Configuration Drawings of Analog Products
Common Items 3.2 FX3UC Series PLC
2. FX3UC-32MT-LT(-2) PLC
A
Common Items
A , B , C , and D represent the connecting positions.
For a detailed description of installation, refer to the following manual supplied with
A C1 D C2 your PLC.
B
→ Refer to the FX3UC Series User's Manual - Hardware Edition.
To connect the special adapters A or the expansion boards B ,
refer to Subsection 3.2.1-2. B
FX3UC-4AD
FX3U-4AD
C1
FX3U-4AD-ADP
FX3UC-4AD
C1
Up to 7 special function blocks can be connected.
FX3G-2AD-BD
Special function •Flowmeter
block for FX2NC C1 •Pressure sensor
•Signal converter, etc.
European terminal block
Analog output
•Inverter, etc.
E
FX3UC-4AD
FX3U-4DA
Temperature sensor
C1 input
•Thermocouple
D •Platinum resistance
European terminal block
thermometer
sensor (Pt100) F
FX3U-4DA-ADP
C1 or C2 Special function
block for FX2NC
FX3UC-1PS-5V
C2
D
G
FX3G-1DA-BD
Terminal block
Special function
block for FX3U,
FX2NC-CNV-IF FX2N and FX0N
H
• For a detailed description of special function block connectability and system configuration:
FX3U-3A-ADP
A-17
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 3 System Configuration Drawings of Analog Products
Common Items 3.3 FX3G Series PLC
1st
board Analog input
Flowmeter
European terminal block
Up to 1 analog expansion board, analog special adapters can be connected.
Pressure sensor
Signal converter, etc.
FX3G-2AD-BD
1st
board
FX3G-1DA-BD
1st
adapter Analog input
Flowmeter
European terminal block
Pressure sensor
Signal converter, etc.
FX3G-CNV-ADP FX3U-4AD-ADP
1st
adapter
Analog output
European terminal block
Inverter, etc.
FX3U-4DA-ADP
1st
Analog input
adapter
Flowmeter
European terminal block Pressure sensor
Signal converter, etc.
Temperature sensor
1st
input
adapter
Thermocouple
European terminal block (types K and J)
Resistance
thermometer sensor
FX3U-4AD-TC-ADP (Pt1000 and Ni1000)
FX3U-4AD-PNK-ADP
Platinum resistance
FX3U-4AD-PT-ADP
thermometer
FX3U-4AD-PTW-ADP
sensor (Pt100)
A-18
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 3 System Configuration Drawings of Analog Products
Common Items 3.3 FX3G Series PLC
Common Items
A , B , and C represent the connecting positions.
For a detailed description of installation, refer to the following manual supplied with to
A
A B C
your PLC.
Refer to the FX3G Series User's Manual - Hardware Edition.
B
Only either A or C
FX3UC-4AD
FX3U-4AD
can be used as 2nd.
European
B 1st terminal Analog input
board block
C 2nd Flowmeter
C
board Pressure sensor
European
Signal converter,
terminal
FX3U-4AD-ADP
block etc.
FX3G-2AD-BD
FX3G-2AD-BD
B European
1st
Up to 2 analog expansion boards, analog special adapters can be connected.
terminal
board
D
block
C 2nd Analog output
board Inverter, etc.
FX3G-2AD-BD
European
terminal
FX3G-1DA-BD block
FX3G-1DA-BD
FX3U-4DA
selected.
A 2nd European
adapter terminal Analog input
A 1st Flowmeter
block
adapter Pressure sensor
B
European Signal converter, F
FX3U-4AD-ADP terminal etc.
FX3U-4DA-ADP
block
FX3U-4AD-ADP A 2nd
adapter European
FX3G-CNV-ADP terminal
A 1st Analog output
block
adapter
European
Inverter, etc.
G
FX3G-1DA-BD
FX3U-4DA-ADP terminal
block
FX3U-4DA-ADP Analog input
A 2nd Flowmeter
adapter European Pressure sensor
A 1st
adapter
terminal
block
Signal converter,
etc.
H
FX3U-3A-ADP
(types K and J)
A 1st
European Resistance
adapter
terminal thermometer
-ADP
A-19
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 3 System Configuration Drawings of Analog Products
Common Items 3.3 FX3G Series PLC
Analog input
C • Flowmeter
• Pressure sensor
• Signal converter,
etc.
Terminal block
Analog output
Special function • Inverter, etc.
block for FX3U
and FX2N
Temperature sensor
input
• Thermocouple
• For a detailed description of the connectable special function blocks and system configuration:
→ Refer to the FX3G Series User's Manual - Hardware Edition.
The analog special function blocks shown in the table below can be connected to the FX3G Series PLC:
FX Series Type
Analog special function blocks for
FX3U-4AD, FX3U-4DA
the FX3U
Analog special function blocks for FX2N-8AD, FX2N-4AD, FX2N-2AD, FX2N-4DA, FX2N-2DA, FX2N-5A,
the FX2N FX2N-4AD-PT, FX2N-4AD-TC, FX2N-2LC
A-20
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 4 Comparison of Performance Specifications
Common Items 4.1 Analog Input
Common Items
4. Comparison of Performance Specifications
The analog product performance specifications are shown in the following tables. Select the optimal product
for your equipment.
B
FX3UC-4AD
FX3U-4AD
4.1 Analog Input
4.1.1 FX3U-4AD-ADP C
FX3U-4AD-ADP
FX3U-4AD-ADP
Specifications
Voltage input Current input
Number of input points 4ch
FX3G-2AD-BD
Absolute maximum input -0.5V,+15V -2mA,+30mA
Offset
Impossible to change Impossible to change
Gain
Digital output 12 bits, binary 11 bits, binary
Resolution 2.5mV(10V×1/4000) 10μA(16mA×1/1600)
E
FX3U-4DA
Overall accuracy
Ambient temperature
±0.5%(±50mV) for 10V full scale ±0.5%(±80μA) for 16mA full scale
:25±5°C
Ambient temperature
:0 to 55°C
±1.0%(±100mV) for 10V full scale ±1.0%(±160μA) for 16mA full scale
F
FX3U-4DA-ADP
Time required for A/D • FX3U/FX3UC Series PLC : 200μs (Data updated every scan time.)
conversion • FX3G Series PLC : 250μs (Data updated every scan time.)
4080 1640
4000 1600
G
FX3G-1DA-BD
Digital output
Digital output
Input characteristics
20.4mA
10.2V
0 10V
Analog input
0 4mA
Analog input
20mA
H
FX3U-3A-ADP
• The photocoupler is used to insulate the analog input area from the PLC.
Insulation method • The DC/DC converter is used to insulate the power supply from the analog inputs.
• Channels are not insulated from each other.
Number of I/O points
occupied
0 point (This number is not related to the maximum I/O points of the PLC.)
I
FX3U-4AD-PT
-ADP
J
FX3U-4AD-PTW
-ADP
A-21
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 4 Comparison of Performance Specifications
Common Items 4.1 Analog Input
4.1.2 FX2N-2AD
FX2N-2AD
Specifications
Voltage input Current input
Number of input points 2ch
0V to 5V DC
4mA to 20mA DC
Analog input range*1 0V to 10V DC
(Input resistance: 250Ω)
(Input resistance: 200 kΩ)
Absolute maximum input -0.5V,+15V -2mA,+60mA
*2,*3
Offset If the digital value is "0":0V to 1V If the digital value is "0":0mA to 4mA*2,*3
If the digital value is "4000":
Gain If the digital value is "4000":20mA*2,*3
5V to 10V*2,*3
Digital output 12 bits, binary
*3
Resolution 2.5mV(10V×1/4000) 4.00μA(16mA×1/4000)*3
Overall accuracy
Ambient temperature:
- -
25±5°C
Ambient temperature:
±1.0%(±100mV) for 10V full scale ±1.0%(±160μA) for 16mA full scale
0 to 55°C
4095 4095
4000 4000
Digital output
Digital input
Input characteristics
20.380mA
10.238V
• The photocoupler is used to insulate the analog input area from the PLC.
Insulation method
• Channels are not insulated from each other.
Number of I/O points
8 points (Taken from either the input or output points of the PLC.)
occupied
*1. For FX2N-2AD, combined use of the voltage and current inputs is not possible.
*2. Use the adjustment volume to adjust FX2N-2AD.
*3. Adjustment of the offset or gain value will change the resolution.
A-22
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 4 Comparison of Performance Specifications
Common Items 4.1 Analog Input
4.1.3 FX3U-4AD
A
Common Items
FX3U-4AD
Specifications
Voltage input Current input
Number of input points 4ch
-10V to +10V DC
-20mA to +20mA DC B
Analog input range 4mA to 20mA DC
FX3UC-4AD
FX3U-4AD
(Input resistance: 200 kΩ)
(Input resistance: 250 Ω)
Absolute maximum input ±15V ±30mA
Offset -10V to +9V*1,*2 -20mA to +17mA*1,*3
Gain -9V to +10V*1,*2 -17mA to +30mA*1,*3 C
Digital output With sign, 16 bits, binary With sign, 15 bits, binary
FX3U-4AD-ADP
0.32mV(20V×1/64000) 1.25μA(40mA×1/32000)
Resolution*4 2.5mV(20V×1/8000) 5.00μA(40mA×1/8000)
Overall accuracy
FX3G-2AD-BD
Ambient temperature: ±1.0%(±400μA) for 40mA full scale
±0.5%(±100mV) for 20V full scale
0 to 55°C Same accuracy for 4mA to 20mA input
zWhen the input mode is set to "0": zWhen the input mode is set to "6":
E
FX3U-4DA
+32640 +16320
+32000 +16000
+20.4mA
+10.2V
-10V 0 -20mA 0
+10V +20mA F
-20.4mA
-10.2V
FX3U-4DA-ADP
Input characteristics*4 -32000 -16000
-32640 -16320
zWhen the input mode is set to "3":
16400
16000 G
20.4mA
FX3G-1DA-BD
0 4mA 20mA
• The photocoupler is used to insulate the analog input area from the PLC.
Insulation method • The DC/DC converter is used to insulate the power supply from the analog inputs. H
• Channels are not insulated from each other.
FX3U-3A-ADP
*1. Adjustment of the offset or gain value will not affect the resolution. In the direct indication mode, however, the
offset/gain cannot be adjusted.
*2. The offset and the gain should satisfy the following condition: I
1V ≤ (Gain - Offset)
FX3U-4AD-PT
*3. The offset and the gain should satisfy the following condition:
3mA ≤ (Gain - Offset) ≤ 30mA
*4. The resolution and the input/output characteristics depend on the selected mode.
-ADP
*5. If 1 or more channels use the digital filter(s), the time required for A/D conversion will be
"5 ms × number of selected channels."
J
FX3U-4AD-PTW
-ADP
A-23
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 4 Comparison of Performance Specifications
Common Items 4.1 Analog Input
4.1.4 FX2N-4AD
FX2N-4AD
Specifications
Voltage input Current input
Number of input points 4ch
-20mA to +20mA DC
-10V to +10V DC
Analog input range 4mA to 20mA DC
(Input resistance: 200kΩ)
(Input resistance: 250 Ω)
Absolute maximum input ±15V ±32mA
*1,*2
Offset -5V to +5V -20mA to +20mA*1,*3
Gain -4V to +15V*1,*2 -16mA to +32mA*1,*3
Digital output With sign, 12 bits, binary With sign, 11 bits, binary
*1
Resolution 5mV(20V×1/4000) 20μA(40mA×1/2000)*1
Overall accuracy
Ambient temperature:
- -
25±5°C
Time required for A/D Normal conversion mode:15ms × number of selected channels
conversion High-speed conversion mode: 6ms × number of selected channels
+2000
+1000
+32mA
-10V 0
+10V -20mA 0
-10.240V
+20mA
-32mA
-2000
Input characteristics -1000
-2048
-1600
zWhen the input is set from 4 mA to 20 mA:
1750
1000
32mA
0 4mA 20mA
• The photocoupler is used to insulate the analog input area from the PLC.
Insulation method • The DC/DC converter is used to insulate the power supply from the analog inputs.
• Channels are not insulated from each other.
Number of I/O points
8 points (Taken from either the input or output points of the PLC.)
occupied
*1. Adjustment of the offset or gain value will not affect the resolution.
*2. The offset and the gain should satisfy the following condition:
1V ≤ (Gain - Offset) ≤ 15V
*3. The offset and the gain should satisfy the following condition:
4mA ≤ (Gain - Offset) ≤ 32mA
A-24
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 4 Comparison of Performance Specifications
Common Items 4.1 Analog Input
4.1.5 FX3UC-4AD
A
Common Items
FX3UC-4AD
Specifications
Voltage input Current input
Number of input points 4ch
-10V to +10V DC
-20mA to +20mA DC B
Analog input range 4mA to 20mA DC
FX3UC-4AD
FX3U-4AD
(Input resistance: 200 kΩ)
(Input resistance: 250 Ω)
Absolute maximum input ±15V ±30mA
Offset -10V to +9V*1,*2 -20mA to +17mA*1,*3
Gain -9V to +10V*1,*2 -17mA to +30mA*1,*3 C
Digital output With sign, 16 bits, binary With sign, 15 bits, binary
FX3U-4AD-ADP
0.32mV(20V×1/64000) 1.25μA(40mA×1/32000)
Resolution*4 2.5mV(20V×1/8000) 5.00μA(40mA×1/8000)
Overall accuracy
FX3G-2AD-BD
Ambient temperature: ±1.0%(±400μA) for 40mA full scale
±0.5%(±100mV) for 20V full scale
0 to 55°C Same accuracy for 4mA to 20mA input
zWhen the input mode is set to "0": zWhen the input mode is set to "6":
E
FX3U-4DA
+32640 +16320
+32000 +16000
+20.4mA
+10.2V
-10V 0 -20mA 0
+10V +20mA F
-20.4mA
-10.2V
FX3U-4DA-ADP
Input characteristics*4 -32000 -16000
-32640 -16320
zWhen the input mode is set to "3":
16400
16000 G
20.4mA
FX3G-1DA-BD
0 4mA 20mA
• The photocoupler is used to insulate the analog input area from the PLC.
Insulation method • The DC/DC converter is used to insulate the power supply from the analog inputs. H
• Channels are not insulated from each other.
FX3U-3A-ADP
*1. Adjustment of the offset or gain value will not affect the resolution. In the direct indication mode, however, the
offset/gain cannot be adjusted.
*2. The offset and the gain should satisfy the following condition: I
1V ≤ (Gain - Offset)
FX3U-4AD-PT
*3. The offset and the gain should satisfy the following condition:
3mA ≤ (Gain - Offset) ≤ 30mA
*4. The resolution and the input/output characteristics depend on the selected mode.
-ADP
*5. If 1 or more channels use the digital filter(s), the time required for A/D conversion will be
"5 ms × number of selected channels."
J
FX3U-4AD-PTW
-ADP
A-25
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 4 Comparison of Performance Specifications
Common Items 4.1 Analog Input
4.1.6 FX2NC-4AD
FX2NC-4AD
Specifications
Voltage input Current input
Number of input points 4ch
-20mA to +20mA DC
-10V to +10V DC
Analog input range 4mA to 20mA DC
(Input resistance: 200kΩ)
(Input resistance: 250 Ω)
Absolute maximum input ±15V ±30mA
Offset -10V to +9V*1,*2 -20mA to +17mA*1,*3
Gain -9V to +10V*1,*2 -17mA to +30mA*1,*3
Digital output With sign, 16 bits, binary With sign, 15 bits, binary
0.32mV(20V×1/64000) 1.25μA(40mA×1/32000)
Resolution*4 2.5mV(20V×1/8000) 5.00μA(40mA×1/8000)
Overall accuracy
zWhen the input mode is set to "0": zWhen the input mode is set to "6":
+32640 +16320
+32000 +16000
+20.4mA
+10.2V
-10V 0 -20mA 0
+10V 20mA
-20.4mA
-10.2V
0 4mA 20mA
• The photocoupler is used to insulate the analog input area from the PLC.
Insulation method • The DC/DC converter is used to insulate the power supply from the analog inputs.
• Channels are not insulated from each other.
Number of I/O points
8 points (Taken from either the input or output points of the PLC.)
occupied
*1. Adjustment of the offset or gain value will not affect the resolution. In the direct indication mode, however, the
offset/gain cannot be adjusted.
*2. The offset and the gain should satisfy the following condition:
1V ≤ (Gain - Offset)
*3. The offset and the gain should satisfy the following condition:
3mA ≤ (Gain - Offset) ≤ 30mA
*4. The resolution and the input/output characteristics depend on the selected mode.
*5. If 1 or more channels use the digital filter(s), the time required for A/D conversion will be
"5 ms × number of selected channels."
A-26
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 4 Comparison of Performance Specifications
Common Items 4.1 Analog Input
4.1.7 FX2N-8AD
A
Common Items
FX2N-8AD
Specifications
Voltage input Current input
Number of input points 8ch
-20mA to +20mA DC B
-10V to +10V DC
FX3UC-4AD
FX3U-4AD
Analog input range 4mA to 20mA DC
(Input resistance: 200 kΩ)
(Input resistance: 250 Ω)
Absolute maximum input ±15V ±30mA
Offset -10V to +9V*1,*2 -20mA to +17mA*1,*3
Gain -9V to +10V*1,*2 -17mA to +30mA*1,*3 C
Digital output With sign, 15 bits, binary With sign, 14 bits, binary
FX3U-4AD-ADP
0.63mV(20V×1/32000) 2.50μA(40mA×1/16000)
Resolution*4 2.5mV(20V×1/8000) 2.00μA(16mA×1/8000)
Overall accuracy
FX3G-2AD-BD
Ambient temperature: ±0.5%(±200μA) for 40mA full scale
±0.5%(±100mV) for 20V full scale
0 to 55°C Same accuracy for 4mA to 20mA input
FX3U-4DA
zWhen the input mode is set to "6":
+16320
+8160
+16000
+8000
+20.4mA
+10.2V
-10V 0
+10V
-20mA 0
+20mA
F
-10.2V
-20.4mA
FX3U-4DA-ADP
Input characteristics*4 -16000
-8000
-16320
Approx.-8160
zWhen the input mode is set to "3":
8200
G
FX3G-1DA-BD
8000
20.4mA
0 4mA 20mA
• The photocoupler is used to insulate the analog input area from the PLC. H
Insulation method • The DC/DC converter is used to insulate the power supply from the analog inputs.
FX3U-3A-ADP
1V ≤ (Gain - Offset)
*3. The offset and the gain should satisfy the following condition:
-ADP
A-27
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 4 Comparison of Performance Specifications
Common Items 4.1 Analog Input
4.1.8 FX3G-2AD-BD
FX3G-2AD-BD
Specifications
Voltage input Current input
Number of input points 2ch
0V to 10V DC 4mA to 20mA DC
Analog input range
(Input resistance: 198.7 kΩ) (Input resistance: 250 Ω)
Absolute maximum input -0.5V. +15V -2mA, +30mA
Offset
Impossible to change Impossible to change
Gain
Digital output 12 bits, binary 11 bits, binary
Resolution 2.5mV(10V×1/4000) 8μA(16mA×1/2000)
Overall accuracy
Ambient temperature:
±0.5%(±50mV) for 10V full scale ±0.5%(±80μA) for 16mA full scale
25±5°C
Ambient temperature:
±1.0%(±100mV) for 10V full scale ±1.0%(±160μA) for 16mA full scale
0 to 55°C
4080 2040
4000
2000
Digital output
Digital output
Input characteristics
A-28
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 4 Comparison of Performance Specifications
Common Items 4.2 Analog Output
Common Items
4.2.1 FX3U-4DA-ADP
Specifications
FX3U-4DA-ADP B
FX3UC-4AD
FX3U-4AD
Voltage output Current output
Number of output points 4ch
0V to 10V DC 4mA to 20mA DC
Analog output range
(External load: 5k to 1MΩ) (External load: 500Ω or less)
Offset
Impossible to change Impossible to change C
Gain
FX3U-4AD-ADP
Digital input 12 bits, binary
Resolution 2.5mV(10V×1/4000) 4μA(16mA×1/4000)
Ambient temperature:
±0.5%(±50mV) for 10V full scale ±0.5%(±80μA) for 16mA full scale
25±5°C
D
Overall accuracy
Ambient temperature:
±1.0%(±100mV) for 10V full scale ±1.0%(±160μA) for 16mA full scale
FX3G-2AD-BD
0 to 55°C
If the external load resistance (Rs) is less than
5kΩ, the accuracy increases as shown in the
Reference following formula: (Increase: 100 mV per 1%) -
47×100
Rs+47
-0.9(%)
E
FX3U-4DA
Time required for D/A • FX3U/FX3UC Series PLC : 200μs (Data updated every scan time.)
conversion • FX3G Series PLC : 250μs (Data updated every scan time.)
10V 20mA
F
Analog output
Analog output
FX3U-4DA-ADP
Output characteristics
4080
4080
4mA
0
Digital input
4000 0 4000
Digital input G
FX3G-1DA-BD
• The photocoupler is used to insulate the analog output area from the PLC.
Insulation method • The DC/DC converter is used to insulate the power supply from the analog inputs.
• Channels are not insulated from each other.
Number of I/O points
0 point (This number is not related to the maximum I/O points of the PLC.)
occupied H
FX3U-3A-ADP
I
FX3U-4AD-PT
-ADP
J
FX3U-4AD-PTW
-ADP
A-29
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 4 Comparison of Performance Specifications
Common Items 4.2 Analog Output
4.2.2 FX2N-2DA
FX2N-2DA
Specifications
Voltage output Current output
Number of output points 2ch
0V to 10V DC
4mA to 20mA DC
Analog output range 0V to 5V DC
(External load: 400Ω or less)
(External load: 2k to 1MΩ)
If the digital value is "0": If the digital value is "0":
Offset*1,*2 0V to 1V 4mA
If the digital value is "4000": If the digital value is "4000":
Gain*1,*2 5V to 10V 20mA
Digital output 12 bits, binary
Resolution 2.5mV(10V×1/4000)*2 4μA(16mA×1/4000)*2
±0.1V ±0.16mA
Overall accuracy
Does not include any load fluctuation. -
Time required for D/A 4ms × number of selected channels
conversion (Operation synchronized with sequence program)
10V 20mA
Analog output
Analog output
Output characteristics
4095
4095
4mA
0 4000 0 4000
Digital input Digital input
If the input data consists of 13 bits or more, only the lower 12 bits will be valid, and the other bits will
be ignored.
• The photocoupler is used to insulate the analog output area from the PLC.
Insulation method
• Channels are not insulated from each other.
Number of I/O points
8 points (Taken from either the input or output points of the PLC.)
occupied
A-30
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 4 Comparison of Performance Specifications
Common Items 4.2 Analog Output
4.2.3 FX3U-4DA
A
Common Items
FX3U-4DA
Specifications
Voltage output Current output
Number of output points 4ch
0mA to 20mA DC
B
-10V to +10V DC
FX3UC-4AD
FX3U-4AD
Analog output range 4mA to 20mA DC
(External load: 1k to 1MΩ)
(External load: 500Ω or less)
Offset -10V to +9V*1,*2 0mA to 17mA*1,*3
Gain -9V to +10V*1,*2 3mA to 30mA*1,*3
Digital input With sign, 16 bits, binary 15 bits, binary C
FX3U-4AD-ADP
Resolution 0.32mV(20V×1/64000)*4 0.63μA(20mA×1/32000)*4
Ambient temperature: ±0.3%(±60μA) for 20mA full scale
Overall accuracy
FX3G-2AD-BD
Time required for D/A
1ms (The number of selected channels will not affect this value.)
conversion
zWhen the output mode is set to "0": zWhen the output mode is "2":
+10.2V
(The dotted line is for mode 3.)
E
20.4mA
FX3U-4DA
+10V
+32640
20mA
0
output
+32000
-32640
32640
4mA
FX3U-4DA-ADP
-10V
-10.2V 0 32000
Digital input
• The photocoupler is used to insulate the analog output area from the PLC.
Insulation method • The DC/DC converter is used to insulate the power supply from the analog output.
• Channels are not insulated from each other. G
FX3G-1DA-BD
Number of I/O points
8 points (Taken from either the input or output points of the PLC.)
occupied
*1. Adjustment of the offset or gain value will not affect the resolution. In the analog value specification
mode, however, the offset/gain cannot be adjusted.
*2. The offset and the gain should satisfy the following condition: H
1V ≤ (Gain - Offset) ≤ 10V
FX3U-3A-ADP
*3. The offset and the gain should satisfy the following condition:
3mA ≤ (Gain - Offset) ≤ 30mA
*4. Adjustment of the offset or gain value will not affect the resolution.
I
FX3U-4AD-PT
-ADP
J
FX3U-4AD-PTW
-ADP
A-31
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 4 Comparison of Performance Specifications
Common Items 4.2 Analog Output
4.2.4 FX2N-4DA
FX2N-4DA
Specifications
Voltage output Current output
Number of output points 4ch
0mA to 20mA DC
-10V to +10V DC
Analog output range 4mA to 20mA DC
(External load: 2k to 1MΩ)
(External load: 500Ω or less)
Offset -5V to +5V*1,*2 -20mA to +20mA*1,*3
15 V or less, and 32 mA or less, and
Gain
Gain - Offset ≥ 1V Gain - Offset ≥ 4mA
Digital output With sign, 12 bits, binary 10 bits, binary
Resolution 5mV(10V×1/2000)*1 20μA(20mA×1/1000)*1
±1.0%(±200μA) for 20mA full scale
±1.0%(±200mV) for 20V full scale
Overall accuracy Same accuracy for 4mA to 20mA output
Does not include any load fluctuation. -
Time required for D/A
2.1 ms (The number of selected channels will not affect this value.)
conversion
zWhen the output mode is set to "0": zWhen the output mode is "2":
(The dotted line is for mode 1.)
+10V 20mA
Analog output
+2047
1023
4mA
-10V 0 1000
Digital input
• The photocoupler is used to insulate the analog input area from the PLC.
Insulation method • The DC/DC converter is used to insulate the power supply from the analog output.
• Channels are not insulated from each other.
Number of I/O points
8 points (Taken from either the input or output points of the PLC.)
occupied
*1. Adjustment of the offset or gain value will not affect the resolution.
*2. The offset and the gain should satisfy the following condition:1
1V ≤ (Gain - Offset) ≤ 15V
*3. The offset and the gain should satisfy the following condition:
4mA ≤ (Gain - Offset) ≤ 32mA
A-32
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 4 Comparison of Performance Specifications
Common Items 4.2 Analog Output
4.2.5 FX2NC-4DA
A
Common Items
FX2NC-4DA
Specifications
Voltage output Current output
Number of output points 4ch
0mA to 20mA DC
B
-10V to +10V DC
FX3UC-4AD
FX3U-4AD
Analog output range 4mA to 20mA DC
(External load: 2k to 1MΩ)
(External load: 500Ω or less)
Offset -5V to +5V*1,*2 -20mA to +20mA*1,*3
Gain -4V to +15V*1,*2 -16mA to +32mA*1,*3
Digital input With sign, 12 bits, binary 10 bits, binary C
FX3U-4AD-ADP
Resolution*1 5mV(20V×1/4000) 20μA(20mA×1/1000)
Ambient temperature: ±0.5%(±100μA) for 20mA full scale
Overall accuracy
FX3G-2AD-BD
Time required for D/A
2.1ms (The number of selected channels will not affect this value.)
conversion
zWhen the output mode is set to "0": zWhen the output mode is "2":
(The dotted line is for mode 1.)
E
FX3U-4DA
+10V
20mA
+2047
0
output
+2000
-2048
1023
4mA
FX3U-4DA-ADP
-10V
0 1000
Digital input
• The photocoupler is used to insulate the analog output area from the PLC.
Insulation method • The DC/DC converter is used to insulate the power supply from the analog output.
• Channels are not insulated from each other. G
FX3G-1DA-BD
Number of I/O points
8 points (Taken from either the input or output points of the PLC.)
occupied
*1. Adjustment of the offset or gain value will not affect the resolution.
*2. The offset and the gain should satisfy the following condition:
1V ≤ (Gain - Offset) ≤ 15V H
*3. The offset and the gain should satisfy the following condition:
FX3U-3A-ADP
I
FX3U-4AD-PT
-ADP
J
FX3U-4AD-PTW
-ADP
A-33
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 4 Comparison of Performance Specifications
Common Items 4.2 Analog Output
4.2.6 FX3G-1DA-BD
FX3G-1DA-BD
Specifications
Voltage output Current output
Number of output points 1ch
0V to 10V DC 4mA to 20mA DC
Analog output range
(External load: 2k to 1MΩ) (External load: 500Ω or less)
Offset
Impossible to change Impossible to change
Gain
Digital input 12 bits, binary 11 bits, binary
Resolution 2.5mV(10V×1/4000) 8μA(16mA×1/2000)
Ambient temperature:
±0.5%(±50mV) for 10V full scale ±0.5%(±80μA) for 16mA full scale
25±5°C
Ambient temperature:
Overall accuracy
±1.0%(±100mV) for 10V full scale ±1.0%(±160μA) for 16mA full scale
0 to 55°C
Shipment adjustment is carried out by external
load resistance 2kΩ.
If external load resistance becomes larger than
Reference -
2kΩ, the output voltage will increase slightly.
When the load is 1MΩ, the output voltage is
about 2% higher than the correct value.
Time required for D/A
60μs (Data updated every scan time.)
conversion
10V 20mA
Analog output
Analog output
Output characteristics
4mA
Caution:
An area of dead band is located in the region of
0V. Therefore the output analog value may not
represent the digital value accurately.
Insulation method • The analog output area is not insulated from the PLC.
Number of I/O points
0 point (This number is not related to the maximum I/O points of the PLC.)
occupied
A-34
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 4 Comparison of Performance Specifications
Common Items 4.3 Mixed Analog Input/Output
Common Items
4.3.1 FX3U-3A-ADP
Specifications
FX3U-3A-ADP
B
Voltage input Current input Voltage output Current output
FX3UC-4AD
FX3U-4AD
Number of input/
2ch 1ch
output points
4mA to 20mA DC
Analog input/ 0V to 10V DC 4mA to 20mA DC 0V to 10V DC
(External load:
output range (Input resistance:198.7kΩ) (Input resistance:250Ω) (External load:5k to 1MΩ)
500Ω or less)
C
Absolute -0.5V, -2mA,
- -
FX3U-4AD-ADP
maximum input +15V +30mA
Digital input/
12 bits, binary
output
Resolution 2.5mV(10V×1/4000) 5μA(16mA×1/3200) 2.5mV(10V×1/4000) 4μA(16mA×1/4000)
Ambient
±0.5%(±50mV) ±0.5%(±80μA) ±0.5%(±50mV) ±0.5%(±80μA) D
temperature:
for 10V full scale for 16mA full scale for 10V full scale for 16mA full scale
FX3G-2AD-BD
25±5°C
Ambient
±1.0%(±100mV) ±1.0%(±160μA) ±1.0%(±100mV) ±1.0%(±160μA)
temperature:
for 10V full scale for 16mA full scale for 10V full scale for 16mA full scale
0 to 55°C
Overall accuracy
FX3U-4DA
than 5kΩ, the accuracy
increases as shown in the
following formula:
Reference - - -
(Increase: 100 mV per
1%)
47×100
-0.9(%)
F
Rs+47
FX3U-4DA-ADP
• FX3U/FX3UC Series PLC :
80μs for each selected input channel + 40μs for each selected output channel
Time required (Operation synchronized with sequence program)
for conversion • FX3G Series PLC :
90μs for each selected input channel + 50μs for each selected output channel
(Operation synchronized with sequence program)
G
FX3G-1DA-BD
4080 3280
4000 3200 10V 20mA
Analog output
Analog output
Digital output
Digital output
I/O
characteristics
H
20.4mA
FX3U-3A-ADP
10.2V
4080
4080
4mA
0 10V 0 4mA 20mA 0 4000 0 4000
Analog input Analog input Digital input Digital input
Insulation
• The photocoupler is used to insulate the analog input and output area from the PLC.
• The DC/DC converter is used to insulate the power supply from the analog input and output.
I
method
FX3U-4AD-PT
J
FX3U-4AD-PTW
-ADP
A-35
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 4 Comparison of Performance Specifications
Common Items 4.3 Mixed Analog Input/Output
4.3.2 FX2N-5A
1. Analog input
FX2N-5A
Specifications
Voltage input Current input
Number of input points 4ch
-10V to +10V DC -20mA to +20mA DC
Analog input range -100mV to +100mV DC 4mA to 20mA DC
(Input resistance: 200kΩ) (Input resistance: 250Ω)
Absolute maximum input ±15V ±30mA
• -10V to +10V DC:
-32V to +5V DC
Offset -32mA to +10mA
• -100mV to +100mV DC:
-320mV to +50mV DC
• -10V to +10V DC:
-5V to +32V, and Gain - Offset > 1V -10mA to +32mA, and
Gain
• -100mV to +100mV DC: Gain - Offset > 1 mA
-50mV to +320mV, and Gain - Offset > 10mA
• -10V to +10V DC:
With sign, 16 bits, binary
Digital input/output With sign, 15 bits, binary
• -100mV to +100mV DC:
With sign, 12 bits, binary
312.5μV(20V×1/64000) 1.25μA(40mA×1/32000)
Resolution
50μV(200mV×1/4000) 10μA(40mA×1/4000)
• -10V to +10V DC:
Ambient temperature: ±0.3% (±60mV) for 20V full scale ±0.3%(±120μA) for 40mA full scale
Overall accuracy
25±5°C • -100mV to +100mV DC: Same accuracy for 4mA to 20mA input
±0.5% (±1mV) for 200mV full scale
• -10V to +10V DC:
Ambient temperature: ±0.5% (±100mV) for 20V full scale ±0.5%(±200μA) for 40mA full scale
0±55°C • -100mV to +100mV DC: Same accuracy for 4mA to 20mA input
±1.0% (±2mV) for 200mV full scale
Time required for
1ms × number of selected channels
conversion
zWhen the input mode is set to "0": zWhen the input mode is set to "2":
+32767 +32767 +20.480mA
+32000
+10.240V
+32000
-10V 0 -20mA 0
+20mA
-20.480mA
+10V
-10.240V
-32000 -32000
I/O characteristics
-32768 -32768
zWhen the input mode is set to "1":
+32767
+32000
20.383mA
2mA
0 4mA 20mA
-4000
A-36
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 4 Comparison of Performance Specifications
Common Items 4.3 Mixed Analog Input/Output
2. Analog output
A
Common Items
FX2N-5A
Specifications
Voltage output Current output
Number of output points 1ch
0mA to 20mA DC
Analog output range
-10V to +10V DC
(External load: 5k to 1MΩ)
4mA to 20mA DC B
(External load: 500Ω or less)
FX3UC-4AD
FX3U-4AD
Offset -10V to +5V 0mA to 10mA
-9V to +10V, and 3 mA to 30 mA or less, and
Gain
Gain - Offset ≥ 1V Gain - Offset ≥ 3mA
Digital input/output With sign, 12 bits, binary 10 bits, binary
Resolution 5mV(10V×1/4000) 20μA(20mA×1/1000) C
FX3U-4AD-ADP
Overall accuracy
FX3G-2AD-BD
zWhen the output mode is set to "0": zWhen the output mode is "4":
(The dotted line is for mode 2.)
+10V
20mA
+32767
Analog output
-32000 0
FX3U-4DA
I/O characteristics
+32000
-32768
32767
-10V 4mA
0
Digital input
32000
F
FX3U-4DA-ADP
3. Other
Specifications FX2N-5A
• The photocoupler is used to insulate the analog input and output area from the G
PLC.
FX3G-1DA-BD
Insulation method • The DC/DC converter is used to insulate the power supply from the analog input
and output.
• Channels are not insulated from each other.
Number of I/O points
8 points (Taken from either the input or output points of the PLC.)
occupied
H
FX3U-3A-ADP
I
FX3U-4AD-PT
-ADP
J
FX3U-4AD-PTW
-ADP
A-37
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 4 Comparison of Performance Specifications
Common Items 4.3 Mixed Analog Input/Output
4.3.3 FX0N-3A
FX0N-3A
Specifications
Voltage input Current input Voltage output Current output
Number of
input/output 2ch 1ch
points
0V to 10V DC 0V to 10V DC
Analog input/ 4mA to 20mA DC 4mA to 20mA DC
0V to 5V DC 0V to 5V DC
output range*1 (Input resistance: 250Ω) (External load: 500Ω)
(Input resistance: 200kΩ) (External load: 1k to 1MΩ)
Absolute
-0.5V, -2mA,
maximum - -
+15V +60mA
input
If the digital value is "0": If the digital value is "0": If the digital value is "0": If the digital value is "0":
Offset*2*3 0V to 1V 0mA to 4mA 0V to 1V 4mA
If the digital value is "250": If the digital value is "250": If the digital value is "250": If the digital value is "250":
Gain*2*3 5V to 10V 20mA 5V to 10V 20mA
Digital input/ 0 to 250 0 to 250
output 8 bits, binary 8 bits, binary
Resolution*3 40mV(10V×1/250) 64μA(16mA×1/250) 40mV(10V×1/250) 64μA(16mA×1/250)
Overall
±0.1V ±0.16mA ±0.1V ±0.16mA
accuracy
Time required TO instruction processing time × 2 + FROM instruction processing time
for conversion (operation synchronized with sequence program)
255 255
250 250 10V 20mA
Analog output
Digital output
Digital output
Analog output
20.320mA
10.200V
I/O
characteristics
255
255
4mA
0 10V 0 4mA 20mA 0 250 0 250
Analog input Analog input Digital input Digital input
A-38
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 4 Comparison of Performance Specifications
Common Items 4.4 Temperature Sensor Input
Common Items
4.4.1 FX3U-4AD-PT-ADP
Specifications
FX3U-4AD-PT-ADP B
FX3UC-4AD
FX3U-4AD
Centigrade(°C) Fahrenheit(°F)
Number of input points 4ch
3-wire platinum resistance thermometer sensor(s)
Input signal
JIS C 1604-1997
Rated temperature range -50°C to +250°C -58°F to +482°F
C
Digital output -500 to +2500 -580 to +4820
FX3U-4AD-ADP
Resolution 0.1°C 0.18°F
• Ambient temperature: 25°C±5°C ±0.5% for full scale
Overall accuracy
• Ambient temperature: 0°C to 55°C ±1.0% for full scale
Time required for • FX3U/FX3UC Series PLC : 200μs (Data updated every scan time.)
conversion • FX3G Series PLC : 250μs (Data updated every scan time.) D
FX3G-2AD-BD
+2550 +4910
+2500 +4820
Digital
output
Digital
output
+491°F
+255°C
Input characteristics
FX3U-4DA
-50°C -58°F
0 0
-67°F
-55°C
+250°C +482°F
-500 Temperature -580 Temperature
-550 -670
Insulation method
• The photocoupler is used to insulate the analog input area from the PLC.
• The DC/DC converter is used to insulate the power supply from the analog inputs.
F
FX3U-4DA-ADP
• Channels are not insulated from each other.
Number of I/O points 0 points
occupied (This number of points is not related to the maximum number of input/output points of the PLC.)
FX3G-1DA-BD
H
FX3U-3A-ADP
I
FX3U-4AD-PT
-ADP
J
FX3U-4AD-PTW
-ADP
A-39
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 4 Comparison of Performance Specifications
Common Items 4.4 Temperature Sensor Input
4.4.2 FX3U-4AD-PTW-ADP
FX3U-4AD-PTW-ADP
Specifications
Centigrade(°C) Fahrenheit(°F)
Number of input points 4ch
3-wire platinum resistance thermometer sensor(s)
Input signal
JIS C 1604-1997
Rated temperature range -100°C to +600°C -148°F to +1112°F
Digital output -1000 to +6000 -1480 to +11120
Resolution 0.2°C to 0.3°C 0.4°F to 0.5°F
• Ambient temperature: 25°C±5°C ±0.5% for full scale
Overall accuracy
• Ambient temperature: 0°C to 55°C ±1.0% for full scale
Time required for • FX3U/FX3UC Series PLC : 200μs (Data updated every scan time.)
conversion • FX3G Series PLC : 250μs (Data updated every scan time.)
+6150 +11390
+6000 +11120
Digital
output
Digital
output
+1139°F
+615°C
Input characteristics
-100°C -148°F
-115°C
-175°F
0 +600°C 0 +1112°F
-1000Temperature -1480Temperature
-1150 -1750
• The photocoupler is used to insulate the analog input area from the PLC.
Insulation method • The DC/DC converter is used to insulate the power supply from the analog inputs.
• Channels are not insulated from each other.
Number of I/O points 0 points
occupied (This number of points is not related to the maximum number of input/output points of the PLC.)
A-40
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 4 Comparison of Performance Specifications
Common Items 4.4 Temperature Sensor Input
4.4.3 FX3U-4AD-PNK-ADP
A
Common Items
FX3U-4AD-PNK-ADP
Specifications
Centigrade(°C) Fahrenheit(°F)
Number of input points 4ch
Platinum resistance thermometer sensor (2-wire or 3-wire) Pt1000
B
FX3UC-4AD
FX3U-4AD
JIS C 1604-1997
Input signal
Nickel resistance thermometer sensor (2-wire or 3-wire) Ni1000
DIN 43760-1987
Pt1000 -50°C to +250°C Pt1000 -58°F to +482°F
Rated temperature range
Ni1000
Pt1000
-40°C to +110°C
-500 to +2500
Ni1000
Pt1000
-40°F to +230°F
-580 to +4820
C
FX3U-4AD-ADP
Digital output
Ni1000 -400 to +1100 Ni1000 -400 to +2300
Pt1000 Pt1000
Resolution 0.1°C 0.2°F
Ni1000 Ni1000
• Ambient temperature : 25°C±5°C ±0.5% for full scale
Overall accuracy
• Ambient temperature : 0°C to 55°C ±1.0% for full scale D
FX3G-2AD-BD
Time required for • FX3U/FX3UC Series PLC : 200μs (Data updated every scan time.)
conversion • FX3G Series PLC : 250μs (Data updated every scan time.)
-Pt1000 -Pt1000
+2560 +4920
+2500 +4820
E
FX3U-4DA
+492.8°F
Approx.
+256°C
Approx.
-50°C 0 -58°F 0
Approx.
Approx.
+250°C +482 °F
-55°C
-67°F
-500
-550
-580
-670
F
FX3U-4DA-ADP
Input characteristics
-Ni1000 -Ni1000
+1150 +2390
+1100 +2300
G
Approx.
Approx.
+115°C
+239°F
FX3G-1DA-BD
-40°C 0 -40°F 0
Approx.
Approx.
+110°C +230°F
-45°C
-49°F
-400 -400
-450 -490
• The photocoupler is used to insulate the analog input area from the PLC.
H
FX3U-3A-ADP
Insulation method • The DC/DC converter is used to insulate the power supply line from the analog input area.
• Channels are not insulated from each other.
Number of I/O points 0 points
occupied (This number of points is not related to the maximum number of input/output points of the PLC.)
I
FX3U-4AD-PT
-ADP
J
FX3U-4AD-PTW
-ADP
A-41
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 4 Comparison of Performance Specifications
Common Items 4.4 Temperature Sensor Input
4.4.4 FX3U-4AD-TC-ADP
FX3U-4AD-TC-ADP
Specifications
Centigrade(°C) Fahrenheit(°F)
Number of input points 4ch
Thermocouple type K or J
Input signal
JIS C 1602-1995
• Type K: -100°C to +1000°C • Type K: -148°F to +1832°F
Rated temperature range
• Type J: -100°C to +600°C • Type J: -148°F to +1112°F
• Type K: -1000 to +10000 • Type K: -1480 to +18320
Digital output
• Type J: -1000 to +6000 • Type J: -1480 to +11120
• Type K: 0.4°C • Type K: 0.72°F
Resolution
• Type J: 0.3°C • Type J: 0.54°F
Overall accuracy ±(0.5% for full scale +1°C)
Time required for • FX3U/FX3UC Series PLC : 200μs (Data updated every scan time.)
conversion • FX3G Series PLC : 250μs (Data updated every scan time.)
• Type K • Type K
+10100 +18500
+10000 +18320
Digital
output
Digital
output
+1010°C
+1850°F
-110°C -148°F
0 -166°F 0
-110°C
+1000°C +1832°F
Temperature Temperature
-1000 -1480
-1100 -1660
Input characteristics
• Type J • Type J
+6100
+6000 +11300
+11120
Digital
output
Digital
output
+1130°F
+610°C
-100°C -148°F
-110°C
0 0
-166°F
+600°C +1112°F
Temperature Temperature
-1000 -1480
-1100 -1660
• The photocoupler is used to insulate the analog input area from the PLC.
Insulation method • The DC/DC converter is used to insulate the power supply from the analog inputs.
• Channels are not insulated from each other.
Number of I/O points 0 points
occupied (This number of points is not related to the maximum number of input/output points of the PLC.)
A-42
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 4 Comparison of Performance Specifications
Common Items 4.4 Temperature Sensor Input
4.4.5 FX2N-4AD-PT
A
Common Items
FX2N-4AD-PT
Specifications
Centigrade(°C) Fahrenheit(°F)
Number of input points 4ch
3-wire platinum resistance thermometer sensor(s)
B
FX3UC-4AD
FX3U-4AD
DIN43760
Input signal
Pt100 JIS C 1604-1997
JPt100 JIS C 1604-1981
Input signal current 1mA(Constant current system)
-148°F to +1112°F
Rated temperature range -100°C to +600°C
C
Digital output -1000 to +6000 -1480 to +11120
FX3U-4AD-ADP
Resolution 0.2°C to 0.3°C 0.36°F to 0.54°F
Overall accuracy ±1.0% for full scale
Time required for
60ms(15ms×4ch)
conversion
D
+6000 +11120
FX3G-2AD-BD
Digital
output
Digital
output
Input characteristics
-100°C -148°F
E
FX3U-4DA
0 +600°C 0 °
+1112 F
Temperature Temperature
-1000 -1480
• The photocoupler is used to insulate the analog input area from the PLC.
Insulation method • The DC/DC converter is used to insulate the power supply from the analog inputs.
• Channels are not insulated from each other.
F
FX3U-4DA-ADP
Number of I/O points
8 points (Count either the input or output points of the PLC.)
occupied
FX3G-1DA-BD
H
FX3U-3A-ADP
I
FX3U-4AD-PT
-ADP
J
FX3U-4AD-PTW
-ADP
A-43
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 4 Comparison of Performance Specifications
Common Items 4.4 Temperature Sensor Input
4.4.6 FX2N-4AD-TC
FX2N-4AD-TC
Specifications
Centigrade(°C) Fahrenheit(°F)
Number of input points 4ch
Thermocouple type K or J
Input signal
JIS C 1602-1995
• Type K: -100°C to +1200°C • Type K: -148°F to +2192°F
Rated temperature range
• Type J: -100°C to +600°C • Type J: -148°F to +1112°F
• Type K: -1000 to +12000 • Type K: -1480 to +21920
Digital output
• Type J: -1000 to +6000 • Type J: -1480 to +11120
• Type K: 0.4°C • Type K: 0.72°F
Resolution
• Type J: 0.3°C • Type J: 0.54°F
Overall accuracy ±(0.5% for full scale +1°C)
Time required for
(240ms±2%)× number of selected channels
conversion
+12000 +21920
(Type K) (Type K)
Digital
Digital
output
output
+6000 +11120
(Type J) (Type J)
Input characteristics
-100°C -148°F
0 +600°C +1200°C 0 +1112°F +2192°F
(Type J) (Type K) (Type J) (Type K)
-1000 -1480
Temperature Temperature
• The photocoupler is used to insulate the analog input area from the PLC.
Insulation method • The DC/DC converter is used to insulate the power supply from the analog inputs.
• Channels are not insulated from each other.
Number of I/O points
8 points (Taken from either the input or output points of the PLC.)
occupied
A-44
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 4 Comparison of Performance Specifications
Common Items 4.4 Temperature Sensor Input
4.4.7 FX2N-8AD
A
Common Items
FX2N-8AD
Specifications
Centigrade(°C) Fahrenheit(°F)
Number of input points 8ch
Input signal
Thermocouple type K, J, and T B
JIS C 1602-1995
FX3UC-4AD
FX3U-4AD
• Type K • Type K
-100°C to +1200°C -148°F to +2192°F
• Type J • Type J
Rated temperature range
-100°C to +600°C -148°F to +1112°F
• Type T
-100°C to +350°C
• Type T
-148°F to +662°F
C
FX3U-4AD-ADP
• Type K • Type K
-1000 to +12000 -1480 to +21920
• Type J • Type J
Digital output
-1000 to +6000 -1480 to +11120
• Type T
-1000 to +3500
• Type T
-1480 to +6620
D
FX3G-2AD-BD
Resolution 0.1°C 0.1°F
• Type K: • Type K:
Overall accuracy
FX3U-4DA
±0.7%(±3.15°C) for full scale ±0.7%(±5.67°F) for full scale
Time required for
40ms × number of selected channels
conversion
+12000 +21920
(Type K) (Type K) F
FX3U-4DA-ADP
Digital
Digital
output
output
+6000 +11120
(Type J) (Type J)
+3500 +6620
Input characteristics (Type T) (Type T)
+600°C +1112°F
-100°C (Type J) -148°F (Type J)
0 +350°C
(Type T)
+1200°C
(Type K)
0 +662°F
(Type T)
+2192°F
(Type K)
G
FX3G-1DA-BD
-1000 -1480
Temperature Temperature
• The photocoupler is used to insulate the analog input area from the PLC.
Insulation method • The DC/DC converter is used to insulate the power supply from the analog inputs.
• Channels are not insulated from each other.
H
Number of I/O points
FX3U-3A-ADP
8 points (Taken from either the input or output points of the PLC.)
occupied
I
FX3U-4AD-PT
-ADP
J
FX3U-4AD-PTW
-ADP
A-45
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 4 Comparison of Performance Specifications
Common Items 4.4 Temperature Sensor Input
4.4.8 FX2N-2LC
FX2N-2LC*1*2
Specifications
Centigrade(°C) Fahrenheit(°F)
Number of input points 2ch
Thermocouple type K, J, R, S, E, T, B, N, PL II, WRe5-26, U, and L
JIS C 1602-1995
Input signal
3-wire platinum resistance thermometer sensor(s)
Pt100 JIS C 1604-1997, JPt100 JIS C 1604-1981
Examples: Examples:
• Type K • Type K
Rated temperature range -100°C to +1300°C -100°F to +2400°F
• Type J • Type J
-100.0°C to +800.0°C -100°F to +2100°F
Examples: Examples:
• Type K • Type K
Digital output -100 to +1300 -100 to +2400
• Type J • Type J
-1000 to +8000 -100 to +2100
Resolution 1°C or 0.1°C 1°F or 0.1°F
Overall accuracy
Ambient temperature:
±0.3°C(±1digit) for full scale
23±5°C
Ambient temperature:
±0.7°C (±1digit) for full scale
0 to 55°C
±1.0°C
Cold junction temperature
±2.0°C if the input value is in the range from -150°C to -100°C
compensation error
±3.0°C if the input value is in the range from -200°C to -150°C
Time required for
500ms(Sampling period)
conversion
Digital
output
Input characteristics
-100°C -100°F
0 +1300°C 0 +2400°F
Temperature Temperature
-100 -100
• The photocoupler is used to insulate the analog input area from the PLC.
Insulation method • The DC/DC converter is used to insulate the power supply from the analog inputs.
• Channels are insulated from each other.
Number of I/O points
8 points (Taken from either the input or output points of the PLC.)
occupied
*1. For FX2N-2LC, the rated temperature range, digital output value, and resolution depend on the selected sensor
and mode.
*2. Accuracy is not guaranteed for the temperature range of 0°C to 399°C(0°F to 799°F) of the thermocouple -B input
and for the temperature range of 0°F to 32°F of the PL II and WRe5-26 inputs.
A-46
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 5 Version Number
Common Items 5.1 PLC Main Unit
Common Items
5. Version Number
FX3UC-4AD
FX3U-4AD
5.1.1 Manufacturer's serial number check method
The year and month of production of the PLC main unit can be checked on the nameplate, and "LOT"
indicated on the front of the product. C
FX3U-4AD-ADP
1. Checking the nameplate
The year and month of production of the PLC main unit can be checked from the manufacturer's serial
number "SERIAL" indicated on the label adhered to the right side of the product.
Example: FX3U-48MR/ES (manufacture's serial number: 930001)
MITSUBISHI PROGRAMMABLE
CONTROLLER
D
FX3G-2AD-BD
Right side MODEL FX3U-48MR/ES
100-240VAC 50/60Hz 40W
OUT:30VDC/240VAC 2A(COSφ=1)
SERIAL 930001
FX3U-4DA
MITSUBISHI ELECTRIC CORPORATION
MADE IN JAPAN
9 3 0 0 0 1
Control number
Month (Example: Mar.): (1 to 9 =January to September, F
FX3U-4DA-ADP
X= October, Y= November, Z= December)
Year (Example: 2009): Last digit of year
FX3G-1DA-BD
Main unit "LOT" indication adoption time
FX3U(C) Series PLC January 2009 and later
FX3G Series PLC October 2008 and later
Example: FX3U-48MR/ES
H
FX3U-3A-ADP
I
FX3U-4AD-PT
-ADP
9 3
A-47
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 5 Version Number
Common Items 5.2 Special adapter
D8001 2 4 1 0 0
PLC type and
version number Version data (Example: Ver. 1.00)
(
PLC type Example: 24 = FX3U and FX3UC series
26 = FX3G series )
5.2 Special adapter
Left side
Control number
Month (Example: June): (1 to 9 =January to September,
X= October, Y= November, Z= December)
Year (Example: 2009): Last digit of year
A-48
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 6 Manual Introduction (Types, Contents, and Obtainment)
Common Items 6.1 How to Use the Manuals
Common Items
6. Manual Introduction (Types, Contents, and Obtainment)
This chapter describes the FX3U/FX3UC/FX3G Series PLC main unit instruction manual and the various
manuals of analog products.
B
FX3UC-4AD
FX3U-4AD
6.1 How to Use the Manuals
Various analog products can be connected to the FX Series PLC to control the analog inputs and outputs.
C
FX3U-4AD-ADP
PLC
FX3G-2AD-BD
For sequence programs:
•Programming manual Supplied separately
FX3U-4DA
Analog products
Depending on the product type, the "Installation Manual" or the "User's Manual" is supplied with the
product.
For a detailed description, refer to the separate manual "User's Manual - Analog Control Edition" as
described below:
F
FX3U-4DA-ADP
For installation and parts identification:
•Installation Manual Supplied
(For a detailed description of the programming method, refer to the
separate manual.)
FX3G-1DA-BD
refer to the separate manual.)
Analog control H
FX3U-3A-ADP
Voltage input Current input Voltage output Current output Temperature input
For each analog product, use this manual for details on wiring/setup details, example
I
programs, and troubleshooting methods.
FX3U-4AD-PT
-ADP
J
FX3U-4AD-PTW
-ADP
A-49
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 6 Manual Introduction (Types, Contents, and Obtainment)
Common Items 6.2 Description of Related Manuals
Supplied with
Document product or
Manual type Description
number supplied
separately
FX3G/FX3U/FX3UC Series PLC
FX3G/FX3U/FX3UC Series Supplied
This manual describes the details of the FX3G/ FX3U/
User’s Manual JY997D16701 separately
FX3UC Series PLC analog products.
- Analog Control Edition (This manual)
Supplied with
Document product or
Manual type Description
number supplied
separately
FX3G Series PLC
This manual describes various items necessary for the
FX3G Series Supplied with
JY997D33401 hardware of the FX3G Series PLC main unit, such as
HARDWARE MANUAL product
specifications, wiring, and installation.
This manual describes various items necessary for the
FX3G Series User’s Manual Supplied FX3G Series PLC main unit and various items for the
JY997D31301
- Hardware Edition separately hardware, such as extension specifications, wiring, and
installation.
FX3U Series PLC
This manual describes various items necessary for the
FX3U Series Supplied with
JY997D18801 hardware of the FX3U Series PLC main unit, such as
HARDWARE MANUAL product
specifications, wiring, and installation.
This manual describes various items necessary for the
FX3U Series User’s Manual Supplied FX3U Series PLC main unit and various items for the
JY997D16501
- Hardware Edition separately hardware, such as extension specifications, wiring, and
installation.
FX3UC Series PLC
The input/output specifications and the wiring and
installation methods for the FX3UC (D, DSS) PLC are
FX3UC (D, DSS) Series Supplied with excerpted from the FX3UC Series User's Manual (for
JY997D28601
HARDWARE MANUAL product Hardware).
For details, refer to the FX3UC Series User's Manual (for
Hardware).
This manual describes various items necessary for the
FX3UC-32MT-LT-2 Supplied with
JY997D31601 hardware of the FX3UC-32MT-LT-2 PLC main unit, such
HARDWARE MANUAL product
as specifications, wiring, and installation.
A-50
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 6 Manual Introduction (Types, Contents, and Obtainment)
Common Items 6.2 Description of Related Manuals
Supplied with
A
Common Items
Document product or
Manual type Description
number supplied
separately
Provides detailed information on the hardware, such as
FX3UC Series User’s Manual Supplied
JY997D28701 the input/output specifications and detailed wiring,
- Hardware Edition separately
installation, and maintenance methods for the FX3UC PLC. B
FX3G, FX3U, FX3UC Series PLC
FX3UC-4AD
FX3U-4AD
FX3G/FX3U/FX3UC Series This manual describes the basic and application
Supplied
Programming Manual - Basic JY997D16601 commands necessary for the FX3G/FX3U/FX3UC Series
separately
& Applied Instruction Edition PLC.
FX3U-4AD-ADP
D
FX3G-2AD-BD
E
FX3U-4DA
F
FX3U-4DA-ADP
G
FX3G-1DA-BD
H
FX3U-3A-ADP
I
FX3U-4AD-PT
-ADP
J
FX3U-4AD-PTW
-ADP
A-51
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 6 Manual Introduction (Types, Contents, and Obtainment)
Common Items 6.2 Description of Related Manuals
Supplied with
Document product or
Manual type Description
number supplied
separately
Analog input unit
This manual describes the FX3G-2AD-BD analog input
FX3G-2AD-BD Supplied with
JY997D33501 expansion board hardware, such as specifications and
INSTALLATION MANUAL product
installation.
This manual describes the FX3U-4AD analog input
FX3U-4AD Supplied with
JY997D20701 special function block hardware, such as specifications
INSTALLATION MANUAL product
and installation, and also describes various programs.
This manual describes the FX3U-4AD-ADP analog input
FX3U-4AD-ADP Supplied with
JY997D13901 special adapter hardware, such as specifications and
USER’S MANUAL product
installation.
This manual describes the FX2NC-4AD analog input
FX2NC-4AD Supplied with
JY997D07801 special function block hardware, such as specifications
USER’S MANUAL product
and installation, and also describes various programs.
This manual describes the FX2N-8AD analog input
FX2N-8AD Supplied with
JY992D86001 special function block hardware, such as specifications
USER’S MANUAL product
and installation, and also describes various programs.
This manual describes the FX2N-4AD analog input
FX2N-4AD Supplied with
JY992D65201 special function block hardware, such as specifications
USER’S GUIDE product
and installation, and also describes various programs.
This manual describes the FX2N-2AD analog input
FX2N-2AD Supplied with
JY992D74701 special function block hardware, such as specifications
USER’S GUIDE product
and installation, and also describes various programs.
Analog output unit
This manual describes the FX3G-1DA-BD analog output
FX3G-1DA-BD Supplied with
JY997D33601 expansion board hardware, such as specifications and
INSTALLATION MANUAL product
installation.
This manual describes the FX3U-4DA analog output
FX3U-4DA Supplied with
JY997D20801 special function block hardware, such as specifications
INSTALLATION MANUAL product
and installation.
This manual describes the FX3U-4DA-ADP analog output
FX3U-4DA-ADP Supplied with
JY997D14001 special adapter hardware, such as specifications and
USER’S MANUAL product
installation.
This manual describes the FX2NC-4DA analog output
FX2NC-4DA Supplied with
JY997D07601 special function block hardware, such as specifications
USER’S MANUAL product
and installation, and also describes various programs.
This manual describes the FX2N-4DA analog output
FX2N-4DA Supplied with
JY992D65901 special function block hardware, such as specifications
USER’S GUIDE product
and installation, and also describes various programs.
This manual describes the FX2N-2DA analog output
FX2N-2DA Supplied with
JY992D74901 special function block hardware, such as specifications
USER’S GUIDE product
and installation, and also describes various programs.
Analog input/output unit
This manual describes the FX3U-3A-ADP analog input/
FX3U-3A-ADP Supplied with
JY997D35601 output special adapter hardware, such as specifications
USER’S MANUAL product
and installation.
This manual describes the FX2N-5A analog input/output
FX2N-5A Supplied with
JY997D11401 special function block hardware, such as specifications
USER’S MANUAL product
and installation, and also describes various programs.
This manual describes the FX0N-3A analog input/output
FX0N-3A Supplied with
JY992D49001 special function block hardware, such as specifications
USER’S GUIDE product
and installation, and also describes various programs.
A-52
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 6 Manual Introduction (Types, Contents, and Obtainment)
Common Items 6.2 Description of Related Manuals
Common Items
Supplied with
Document product or
Manual type Description
number supplied
separately
Temperature sensor unit B
This manual describes the FX3U-4AD-PT-ADP platinum
FX3UC-4AD
FX3U-4AD
FX3U-4AD-PT-ADP Supplied with
JY997D14701 resistance thermometer input special adapter hardware,
USER’S MANUAL product
such as specifications and installation.
This manual describes the FX3U-4AD-PTW-ADP
FX3U-4AD-PTW-ADP Supplied with
JY997D29101 platinum resistance thermometer input special adapter
USER’S MANUAL product
hardware, such as specifications and installation. C
This manual describes the FX3U-4AD-PNK-ADP
FX3U-4AD-ADP
FX3U-4AD-PNK-ADP Supplied with
JY997D29201 resistance thermometer input special adapter hardware,
USER’S MANUAL product
such as specifications and installation.
This manual describes the FX3U-4AD-TC-ADP
FX3U-4AD-TC-ADP Supplied with
JY997D14801 thermocouple input special adapter hardware, such as
USER’S MANUAL product
specifications and installation.
D
This manual describes the FX2N-4AD-PT platinum
FX3G-2AD-BD
FX2N-4AD-PT Supplied with resistance thermometer input special function block
JY992D65601
USER’S GUIDE product hardware, such as specifications and installation, and
also describes various programs.
This manual describes the FX2N-4AD-TC thermocouple
FX2N-4AD-TC
USER’S GUIDE
JY992D65501
Supplied with
product
input special function block hardware, such as
specifications and installation, and also describes various E
programs.
FX3U-4DA
This manual describes the FX2N-2LC temperature
FX2N-2LC Supplied with
JY992D85601 adjustment special function block hardware, such as
USER’S GUIDE product
specifications and installation.
This manual describes the FX2N-2LC temperature
FX2N-2LC
JY992D85801
Supplied adjustment special function block hardware, such as F
USER’S MANUAL separately specifications and installation, and also describes various
FX3U-4DA-ADP
programs.
FX3G-1DA-BD
H
FX3U-3A-ADP
I
FX3U-4AD-PT
-ADP
J
FX3U-4AD-PTW
-ADP
A-53
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 7 Generic Names and Abbreviations in This Manual
Common Items 6.2 Description of Related Manuals
A-54
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 7 Generic Names and Abbreviations in This Manual
Common Items 6.2 Description of Related Manuals
Common Items
Analog special adapter Generic name for analog special adapter.
4AD-ADP FX3U-4AD-ADP
4DA-ADP FX3U-4DA-ADP
3A-ADP FX3U-3A-ADP
PT-ADP FX3U-4AD-PT-ADP B
FX3UC-4AD
FX3U-4AD
PTW-ADP FX3U-4AD-PTW-ADP
PNK-ADP FX3U-4AD-PNK-ADP
TC-ADP FX3U-4AD-TC-ADP
Special adapter connection
conversion adapter or connection
conversion adapter
Generic name for CNVADP
C
FX3U-4AD-ADP
CNVADP FX3G-CNV-ADP
3. Extension unit
D
Abbreviation, generic name Description
FX3G-2AD-BD
Voltage/current input
Generic name for the FX2N Series extension unit, FX2NC Series extension unit,
and FX0N Series extension unit.
Extension unit The number of connectable units, however, depends on the type of the main
unit. To check the number of connectable units, refer to the User’s Manual -
Hardware Edition of the main unit to be used for your system.
E
FX3U-4DA
Generic name for FX2N Series input/output powered extension unit, FX2N Series
FX2N Series extension unit input/output extension block, FX2N Series special function unit, and FX2N Series
special function block.
Generic name for FX2NC Series input/output extension block and FX2NC Series
FX2NC Series extension unit
special function block.
Generic name for FX0N Series input/output extension block and FX0N Series
F
FX0N Series extension unit
FX3U-4DA-ADP
special function block.
Generic name for FX3U Series special function block, FX3UC Series special
function block, FX2N Series special function unit, FX2N Series special function
Special function unit/block
block, FX2NC Series special function block, and FX0N Series special function
block.
FX3U Series special
FX3U-4AD, FX3U-4DA, FX3U-20SSC-H, FX3U-64CCL
G
function block
FX3G-1DA-BD
FX3UC Series special
FX3UC-4AD
function block
FX2N Series special
FX2N-10GM, FX2N-20GM, FX2N-1RM-E-SET, FX2N-1RM-SET
function unit
FX2N-232IF, FX2N-16CCL-M, FX2N-32CCL, FX2N-32ASI-M, FX2N-2AD, H
FX2N-4AD, FX2N-8AD, FX2N-4AD-PT, FX2N-4AD-TC, FX2N-2LC, FX2N-2DA,
FX3U-3A-ADP
J
FX3U-4AD-PTW
-ADP
A-55
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 7 Generic Names and Abbreviations in This Manual
Common Items 6.2 Description of Related Manuals
4. Peripheral unit
Abbreviation, generic name Description
Peripheral unit
Generic name for programming software, handy programming panel,
Peripheral unit
and display units.
Programming tool
Programming tool Generic name for programming software, and handy programming panel.
Programming software Generic name for Programming software.
Generic name for SW D5C-GPPW-J and SW D5C-GPPW-E programming
GX Developer
software packages.
Handy programming panels Generic name for the following models
(HPP) FX-30P, FX-20P, FX-20P-E
5. Manual
Abbreviation, generic name Description
FX3G hardware manual FX3G Series User's Manual - Hardware Edition
FX3U hardware manual FX3U Series User's Manual - Hardware Edition
FX3UC hardware manual FX3UC Series User's Manual - Hardware Edition
FX3G/FX3U/FX3UC Series Programming Manual - Basic and Applied Instruction
Programming manual
Edition
A-56
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition
FX3U-4AD/FX3UC-4AD (4-channel Analog Input)
Common Items
B
FX3UC-4AD
FX3U-4AD
FX3G/FX3U/FX3UC Series Programmable
Controllers C
FX3U-4AD-ADP
User's Manual [Analog Control Edition]
FX3U-4AD (4-channel Analog Input)
D
FX3UC-4AD (4-channel Analog Input)
FX3G-2AD-BD
E
FX3U-4DA
F
FX3U-4DA-ADP
G
FX3G-1DA-BD
H
FX3U-3A-ADP
Foreword
This manual describes the specifications, wiring, and operation methods for the FX3U-4AD/FX3UC-4AD
special extension block (4-channel analog input) and should be read and understood before attempting to
install or use the unit. I
FX3U-4AD-PT
Store this manual in a safe place so that you can take it out and read it whenever necessary. Always forward
it to the end user.
-ADP
This manual confers no industrial property rights or any rights of any other kind, nor does it confer any patent
licenses. Mitsubishi Electric Corporation cannot be held responsible for any problems involving industrial property
rights which may occur as a result of using the contents noted in this manual. J
FX3U-4AD-PTW
B-1
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition
FX3U-4AD/FX3UC-4AD (4-channel Analog Input)
B-2
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 1 Outline
FX3U-4AD/FX3UC-4AD (4-channel Analog Input) 1.1 Outline of Functions
Common Items
1. Outline
This chapter outlines the FX3U-4AD/FX3UC-4AD. B
For common descriptions of the FX3U-4AD and FX3UC-4AD, these model names are referred to as the 4AD.
FX3UC-4AD
FX3U-4AD
1.1 Outline of Functions
The FX3U-4AD is an analog special function block which is connectable with the FX3G, FX3U and FX3UC
Series PLC used to capture 4-ch voltage/current data. The FX3UC-4AD cannot be connected to the FX3G/
C
FX3U-4AD-ADP
FX3U Series PLC.
1) Up to 8*1 units can be connected to the FX3G/FX3U/FX3UC Series PLC.
(including the other special function blocks).
2) Either "voltage input" or "current input" can be specified for each channel.
3) The A/D conversion values will be stored in the 4AD buffer memory (BFM). D
FX3G-2AD-BD
4) Set the digital filter to read out stable A/D conversion values.
5) For each channel, up to 1,700 A/D conversion values can be stored as history data.
FX3U-4DA
Up to 8 units*1 connect to the FX3G/FX3U/FX3UC Series PLC
(including other types of special function blocks)
•••••• Number of connectable units
FX3U-4DA-ADP
•••••••••
FX3G-1DA-BD
For a detailed description of
•••••• analog data reading programs,
refer to Chapter 4, 6, and 7.
••••••
For a detailed description of
the buffer memory, refer to
H
Program Buffer memory
FX3U-3A-ADP
••••••
or to directly specify the BFM,
• BFM direct BFM#6999 refer to Section 5.2.
specification(U\G)*2
Refer to the system configuration shown in the FX3G/FX3U/FX3UC User's Manual - Hardware Edition to check the I
number of connectable units and to configure the entire system.
FX3U-4AD-PT
*2. This function is just available for FX3U and FX3UC PLCs.
J
FX3U-4AD-PTW
-ADP
B-3
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 1 Outline
FX3U-4AD/FX3UC-4AD (4-channel Analog Input) 1.2 Setup Procedure Before Starting Operation
FX3U-4AD/FX3UC-4AD
Refer to Chapter 1.
Wiring Wiring:
• Power supply line
• Analog input line
Refer to Chapter 4.
Refer to Chapter 7.
B-4
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 1 Outline
FX3U-4AD/FX3UC-4AD (4-channel Analog Input) 1.3 Connectable PLC and Version Numbers
A
1.3 Connectable PLC and Version Numbers
Common Items
FX3U-4AD is compatible with the following PLC.
FX3UC-4AD
FX3U-4AD
FX3UC Series PLC Ver. 1.30 or later August 2004 and later
FX3G Series PLC Ver. 1.00 or later from first product
FX3U-4AD-ADP
FX3UC Series PLC Ver. 1.30 or later August 2004 and later
1. Version check
Special data register D8001 contains information for determining the PLC version number. D
→ For a detailed description of the version check, refer to A. Common Items Subsection 5.1.2.
FX3G-2AD-BD
2. How to look at the manufacturer's serial number
The year and month of production of the product can be checked on the nameplate, and on the front of the
product.
→ For a detailed description of the How to look at the manufacturer's serial number,
refer to A. Common Items Subsection 5.1.1. E
FX3U-4DA
1.4 Compatible Programming Tool Version Number
Use a programming tool with the following version number to create 4AD programs for the FX3G/FX3U/FX3UC
Series PLC.
F
1. GX Developer
FX3U-4DA-ADP
1) FX3U-4AD
Software Version number Remarks
GX Developer Ver. SW8 P or later
• SW D5C-GPPW-J (Ver. 8.13P) When selecting the model, select FX3U(C)*1. G
FX3G-1DA-BD
• SW D5C-GPPW-E Ver. 8.72A or later When selecting the model, select FX3G.
2) FX3UC-4AD
Software Version number Remarks
GX Developer
H
Ver. SW8 P or later
FX3U-3A-ADP
• SW D5C-GPPW-J
(Ver. 8.13P) When selecting the model, select FX3U(C)*1.
• SW D5C-GPPW-E
If a programming tool with the wrong version number is used, some instructions and devices cannot be used.
*1. For Ver. 8.13P to 8.24A of GX Developer, select FX3UC for the PLC type. I
FX3U-4AD-PT
2. FX-30P
Model name Version number Remarks
-ADP
J
FX3U-4AD-PTW
-ADP
B-5
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 2 Specifications
FX3U-4AD/FX3UC-4AD (4-channel Analog Input) 2.1 Generic Specifications
2. Specifications
This chapter describes the general, power supply, and performance specifications for the 4AD.
Item Specifications
Ambient 0 to 55°C (32 to 131°F) when operating
temperature -25 to 75°C (-13 to 167°F) when stored
Relative
5 to 95%RH (no condensation) when operating
humidity
Frequency Acceleration Half amplitude
(Hz) (m/s2) (mm)
10 times of testing in
Vibration 10 - 57 - 0.035 each direction (X-, Y-,
DIN Rail Mounting
resistance*1 57 - 150 4.9 - and Z-axis directions)
(Total: 80 min, each)
10 - 57 - 0.075
Direct Mounting*2
57 - 150 9.8 -
Shock
147 m/s2 Acceleration, Action time: 11ms, 3 times by half-sine pulse in each direction X, Y, and Z
resistance*1
Noise Using noise simulator of:
resistance Noise voltage: 1,000Vp-p / Noise width: 1μs / Rise: 1ns / Cycle: 30 to 100Hz
Dielectric
withstand 500 V AC, for 1 min
voltage Between all terminals and ground terminal
Insulation 5MΩ or more using 500V DC
resistance insulation resistance meter
Class D grounding (grounding resistance: 100 Ω or less)
Grounding
<Common grounding with a heavy electrical system is not allowed.>*3
Working
Free from corrosive or flammable gas and excessive conductive dust
atmosphere
Working
altitude < 2000m*4
B-6
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 2 Specifications
FX3U-4AD/FX3UC-4AD (4-channel Analog Input) 2.2 Power Supply Specifications
A
2.2 Power Supply Specifications
Common Items
FX3U-4AD
Item Specifications
B
A/D conversion 24V DC ±10%, 90mA
FX3UC-4AD
FX3U-4AD
circuit drive power (It is necessary to supply 24V DC from the terminal block.)
5V DC, 110mA
CPU drive power (Since the internal power is supplied from the main unit, it is not necessary to supply power
externally.)
C
FX3UC-4AD
FX3U-4AD-ADP
Item Specifications
A/D conversion 24V DC ±10%, 80mA
circuit drive power (It is necessary to supply 24V DC from the power connector.)
FX3G-2AD-BD
2.3 Performance Specifications
Item
Specifications E
FX3U-4DA
Voltage input Current input
-10V to +10V DC -20mA to +20mA DC, 4mA to 20mA DC
Analog input range
(Input resistance: 200kΩ) (Input resistance: 250Ω)
Offset*1 -10V to +9V*2 -20mA to +17mA*3
Gain*1 -9V to +10V*2 -17mA to +30mA*3 F
FX3U-4DA-ADP
Absolute maximum
±15V ±30mA
input
Digital output With sign, 16bits, binary With sign, 15bits, binary
0.32mV (20V × 1/ 64,000) 1.25μA (40mA × 1/ 32,000)
Resolution*4 2.5mV (20V × 1/8000) 5.00μA (40mA × 1/8000)
• Ambient temperature: 25°C±5°C
G
FX3G-1DA-BD
• Ambient temperature: 25°C±5°C ±0.5% (±200μA) for 40mA full scale
±0.3% (±60mV) for 20V full scale Same accuracy (±200μA) for 4mA to 20mA input
Overall accuracy
• Ambient temperature: 0°C to 55°C • Ambient temperature: 0°C to 55°C
±0.5% (±100mV) for 20V full scale ±1% (±400μA) for 40mV full scale
Same accuracy (±400μA) for 4mA to 20mA input
Time required for 500μs × number of selected channels H
A/D conversion (If 1 or more channels use the digital filter(s): 5ms × number of selected channels)
FX3U-3A-ADP
• The photocoupler is used to insulate the analog input area from the PLC.
Insulation method • The DC/DC converter is used to insulate the analog input area from the power supply unit.
• Channels are not insulated from each other.
Number of I/O
points occupied
8 points (Taken from either the input or output points of the PLC.)
I
FX3U-4AD-PT
*1. Adjustment of the offset or gain value will not affect the resolution. In the direct indication mode,
however, the offset/gain cannot be adjusted.
*2. The offset and the gain should satisfy the following condition:
-ADP
1V ≤ (Gain - Offset)
*3. The offset and the gain should satisfy the following condition: J
3 mA ≤ (Gain - Offset) ≤ 30 mA
FX3U-4AD-PTW
*4. If 1 or more channels use the digital filter(s), the time required for A/D conversion will be
"5 ms × number of selected channels."
-ADP
B-7
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 2 Specifications
FX3U-4AD/FX3UC-4AD (4-channel Analog Input) 2.4 Input Mode (Characteristics) BFM #0
+10.2V
+10.2V
Input Input Input
voltage -10V 0 voltage -10V 0 voltage -10V 0
+10V +10V +10V
-10.2V
-10.2V
-10.2V
20.4 mA
20.4 mA
4000
B-8
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 2 Specifications
FX3U-4AD/FX3UC-4AD (4-channel Analog Input) 2.4 Input Mode (Characteristics) BFM #0
A
3. Current input characteristics [-20 to +20mA] (Input mode: 6 to 8)
Common Items
Set input mode: 8
Set input mode: 6 Set input mode: 7
Input type: Current input
Input type: Current input Input type: Current input
(analog value direct indication)
Analog input range: -20 to +20mA Analog input range: -20 to +20mA
Analog input range: -20 to +20mA
Digital output range: -16000 to +16000 Digital output range: -4000 to +4000
Offset/gain adjustment: Possible Offset/gain adjustment: Possible
Digital output range: -20000 to +20000
Offset/gain adjustment: Impossible B
FX3UC-4AD
FX3U-4AD
Digital value Digital value Digital value
+16320 +4080 +20400
+16000 +4000 +20000
+20.4mA
+20.4mA
+20.4mA
Current
Input -20mA 0
Current
Input -20mA 0
Current
Input -20mA 0 C
+20mA +20mA +20mA
FX3U-4AD-ADP
-20.4mA
-20.4mA
-20.4mA
FX3G-2AD-BD
E
FX3U-4DA
F
FX3U-4DA-ADP
G
FX3G-1DA-BD
H
FX3U-3A-ADP
I
FX3U-4AD-PT
-ADP
J
FX3U-4AD-PTW
-ADP
B-9
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 3 Wiring
FX3U-4AD/FX3UC-4AD (4-channel Analog Input) 2.4 Input Mode (Characteristics) BFM #0
3. Wiring
This chapter describes the 4AD wiring.
Observe the following cautions when wiring the 4AD.
WIRING PRECAUTIONS
• Make sure to cut off all phases of the power supply externally before attempting wiring work.
Failure to do so may cause electric shock or damages to the product.
WIRING PRECAUTIONS
• Connect the DC power supply wiring to the dedicated terminals described in this manual.
If an AC power supply is connected to a DC input/output terminal or DC power supply terminal, the PLC will be
burnt out.
• Do not wire vacant terminals externally.
Doing so may damage the product.
• Perform class D grounding (grounding resistance: 100Ω or less) to the grounding terminal on the main unit.
Do not use common grounding with heavy electrical systems.
• When drilling screw holes or wiring, make sure cutting or wire debris does not enter the ventilation slits.
Failure to do so may cause fire, equipment failures or malfunctions.
• Make sure to observe the following precautions in order to prevent malfunctions under the influence of noise:
- Do not bundle the power line or twisted shielded cable together with or lay it close to the main circuit, high-
voltage line, or load line.
Otherwise, noise disturbance and/or surge induction are likely to take place. As a guideline, lay the control line
at least 100mm (3.94") or more away from the main circuit, high-voltage line, or load line.
- Ground the shield of the analog input/output cable at one point on the signal receiving side.
However, do not use common grounding with heavy electrical systems.
• Make sure to properly wire to the European terminal board in accordance with the following precautions.
Failure to do so may cause electric shock, a short-circuit, wire breakage, or damage to the product.
- The disposal size of the cable end should be 9 mm (0.35").
- Tightening torque should be between 0.22 to 0.25 N•m.
- Twist the end of strand wire and make sure there are no loose wires.
- Do not solder-plate the electric wire ends.
- Do not connect more than the specified number of wires or electric wires of unspecified size.
- Affix the electric wires so that neither the terminal block nor the connected parts are directly stressed.
• Make sure to properly wire the terminal block in accordance with the following precautions.
Failure to do so may cause electric shock, a short-circuit, wire breakage, or damage to the product.
- The disposal size of the cable end should follow the dimensions described in this manual.
- Tightening torque should be between 0.5 and 0.8 N•m.
B-10
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 3 Wiring
FX3U-4AD/FX3UC-4AD (4-channel Analog Input) 3.1 Terminal Layout
A
3.1 Terminal Layout
Common Items
FX3U-4AD
Signal Application
24+
24V DC power supply
B
24-
FX3UC-4AD
FX3U-4AD
Ground terminal
V+
VI- Channel-1 analog input
I+
FG
V+
C
Channel-2 analog input
FX3U-4AD-ADP
VI-
I+
FG
V+ Channel-3 analog input
VI-
I+ D
FG
FX3G-2AD-BD
V+ Channel-4 analog input
VI-
I+
FX3U-4DA
FX3UC-4AD
F
PW
I1+
I1+
FX3U-4DA-ADP
SLD
SLD
A/D
V2+
V2+
I2+
I2+
COM2
SLD
• G
•
FX3G-1DA-BD
•
V3+
V3+
I3+
I3+
SLD
SLD
V4+ H
V4+
I4+
I4+
COM4
COM4
SLD
SLD
Ground terminal
I
FX3U-4AD-PT
-ADP
J
FX3U-4AD-PTW
-ADP
B-11
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 3 Wiring
FX3U-4AD/FX3UC-4AD (4-channel Analog Input) 3.2 Cable and Terminal Tightening Torque
The crossover cable (type "C") can skip up to 4 16-point output blocks to connect units.
If more blocks should be skipped to supply power to an input block, use cable type "B".
Supply the 24V DC power to FX3UC-4AD via the power supply connector.
3.2(0.13")
6.2mm(0.24") Terminal
or less 6.3mm(0.25")
or more
B-12
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 3 Wiring
FX3U-4AD/FX3UC-4AD (4-channel Analog Input) 3.2 Cable and Terminal Tightening Torque
A
3.2.3 Cable (FX3UC-4AD)
Common Items
Use the following cables to connect with counterpart equipment. Terminate the cable end as shown below.
1. Cable
Applicable cable and tightening torque B
Wire size (stranded/ Tightening
FX3UC-4AD
FX3U-4AD
Termination
single-wire) torque
0.3mm2 to 0.5mm2 • To connect a stranded cable, peel the cover off the cable
Single wire and then twist the core before connection.
(AWG22 to 20)
• To connect a single-wire cable, peel the cover off the
Double wire 0.3mm2(AWG22) cable before connection. C
0.3mm2 to 0.5mm2 0.22N•m to • Rod terminal with insulation sleeve
FX3U-4AD-ADP
Rod terminal (AWG22 to 20) 0.25N•m (recommended terminal)
with (Refer to the external AI 0.5-8WH : Manufactured by Phoenix Contact
insulation view of rod terminal • Caulking tool
sleeve shown in the following CRIMPFOX ZA 3 : Manufactured by Phoenix Contact
figure.) (or CRIMPFOX UD 6 : Manufactured by Phoenix Contact)
D
2. Termination of cable end
FX3G-2AD-BD
To terminate the cable, treat the stranded/single-wire directly or use the rod terminal with insulation sleeve.
• To directly terminate end of stranded/single-wire cable: Termination of cable end
- Terminate the end of the stranded cable so that the "barbed wires"
cannot protrude.
- Do not solder-plate the end of the cable.
E
FX3U-4DA
9mm
• To terminate cable end using rod terminal with insulation sleeve:
(0.35")
If the cable sheath is too thick, it may be difficult to insert the cable
Insulation sleeve Contact area
into the insulation sleeve. For this reason, select an appropriate cable (Crimp area)
while referring to the external view.
Manufacturer Model Caulking tool 8mm (0.31") F
CRIMPFOX ZA 3 2.6mm
FX3U-4DA-ADP
Phoenix Contact AI 0.5-8WH 14mm
(or CRIMPFOX UD 6) (0.1")
(0.55")
3. Tool
• To tighten terminals, use a purchased small-sized screwdriver whose head is straight and is not widened
as shown in the right figure. G
FX3G-1DA-BD
Note:
If the diameter of screwdriver grip is too small, tightening torque will not
The head
be able to be achieved. Use the following recommended screwdriver or should be
an appropriate replacement (grip diameter: approximately 25mm). straight.
Manufacturer
Phoenix Contact
Model
SZS 0.4×2.5
H
0.4mm 2.5mm
FX3U-3A-ADP
(0.01") (0.09")
I
FX3U-4AD-PT
-ADP
J
FX3U-4AD-PTW
-ADP
B-13
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 3 Wiring
FX3U-4AD/FX3UC-4AD (4-channel Analog Input) 3.3 Examples of Power Supply Circuit
3.3.1 FX3U-4AD
Below are shown examples of circuits for using the 24V DC service power supply of the FX3G/FX3U Series
PLC.
1) Sink input [- common] wiring
AC power
100 to 240 V
Class-D
grounding
L N S/S 0V 24V 24+ 24-
+15V
Connect the "S/S" terminal of the main unit to the "24V" terminal.
AC power
100 to 240 V
Class-D
grounding
L N S/S 0V 24V 24+ 24-
+15V
Connect the "S/S" terminal of the main unit to the "0V" terminal.
B-14
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 3 Wiring
FX3U-4AD/FX3UC-4AD (4-channel Analog Input) 3.3 Examples of Power Supply Circuit
A
3.3.2 FX3UC-4AD
Common Items
Terminal block Terminal block
FX3UC-4AD
FX3U-4AD
+15V +15V
-15V -15V
Power
Power
crossover
connector
Power crossover
connector connector
Power
crossover C
connector
FX3U-4AD-ADP
Power connector
24- 24+ 24- 24+ 24- 24+ 24- 24+ 24- 24+ 24- 24+ 24- 24+
Power Power
Black Red Green connector Black Red Black Red connector
Black Black Red Black Red
D
Red
FX3G-2AD-BD
Class-D FX2NC-10BPCB1 FX2NC-10BPCB1
grounding Power crossover cable Power crossover cable
24V DC
FX2NC-100BPCB
Power cable*1
E
FX3U-4DA
*1. The FX3UC- MT/D and FX3UC-32MT-LT(-2) are supplied together with power cable.
*2. The FX2NC- EX-DS and FX2NC-16EX-T-DS do not have a power connector, and receive power
from the input connector.
FX3U-4DA-ADP
• Ground the " " terminal and " " terminal to the Class - D grounding line (100 Ω or less) together
with the ground terminal of the main unit.
• To perform crossover wiring to connect the power line from FX3UC-4AD to a succeeding extension block,
remove the resin cover from the power crossover connector using nippers.
• For the timing of power-on/off when using an external power supply, see the following manual of the G
connected PLC.
FX3G-1DA-BD
→ Refer to the FX3G Series User’s Manual - Hardware Edition.
→ Refer to the FX3U Series User’s Manual - Hardware Edition.
→ Refer to the FX3UC Series User’s Manual - Hardware Edition.
H
FX3U-3A-ADP
I
FX3U-4AD-PT
-ADP
J
FX3U-4AD-PTW
-ADP
B-15
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 3 Wiring
FX3U-4AD/FX3UC-4AD (4-channel Analog Input) 3.4 Analog Input Line
3.4.1 FX3U-4AD
Class-D grounding
*2
If current input is
selected
ch 6.8kΩ
*3 ch
V+
*4 250Ω
I+
VI-
FG 200kΩ
If voltage input is *2
selected
ch
*3 6.8kΩ ch
V+
*5 250Ω
I+
VI-
200kΩ
FG
*2
*1. For FX3G/FX3U Series PLC (AC power type), the 24V DC service power supply is also available.
*2. The [FG] terminal and the [ ] terminal are connected internally.
There is no “FG” terminal for ch1. When using ch1, connect directly to the [ ] terminal.
*3. Use a 2-core twisted shield wire for analog input line, and separate it from other power lines or
inductive lines.
*4. For the current input, short-circuit the [V+] terminal and the [I+] terminal.
*5. If there is voltage ripple in the input voltage or there is noise in the external wiring, connect a capacitor
of approximately 0.1 to 0.47μF 25 V.
B-16
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 3 Wiring
FX3U-4AD/FX3UC-4AD (4-channel Analog Input) 3.5 Grounding
A
3.4.2 FX3UC-4AD
Common Items
If current input is FX3UC-4AD
selected Terminal
*1 block
V +
6.8kΩ ch B
*2 250Ω
FX3UC-4AD
FX3U-4AD
I +
200kΩ
COM
SLD *3
If voltage input is
selected
*1 6.8kΩ ch
C
V +
FX3U-4AD-ADP
250Ω
I +
200kΩ
COM
SLD
D
*4 •
FX3G-2AD-BD
Class-D
grounding
E
V +, I +, ch : represents the channel number.
FX3U-4DA
*1. Use the 2-core shielded twisted pair cable for the analog input lines, and separate the analog input
lines from the other motive power lines or inductive lines.
*2. To use the current input, be sure to short circuit the line between the V
+ terminal ( : channel number).
+ terminal and the I F
FX3U-4DA-ADP
*3. The SLD and " " terminals are connected to each other inside.
*4. Do not connect any lines to the "•" terminal.
G
3.5 Grounding
FX3G-1DA-BD
Grounding should be performed as stated below.
• The grounding resistance should be 100Ω or less.
• Independent grounding should be performed for best results.
When independent grounding is not performed, perform "shared grounding" as shown in the following H
figure.
FX3U-3A-ADP
→ For details, refer to the User’s Manual - Hardware Edition of each Series.
• The PLC grounding point should be close, and all grounding wires should be as short as possible.
-ADP
B-17
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 4 Analog Input
FX3U-4AD/FX3UC-4AD (4-channel Analog Input) 4.1 Analog Input Procedures
4. Analog Input
This chapter describes the minimum programming necessary to readout the 4AD analog data.
Follow the procedure below to confirm that the analog data can be properly read out.
H
ch4 ch1
ch3 ch2
B-18
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 4 Analog Input
FX3U-4AD/FX3UC-4AD (4-channel Analog Input) 4.1 Analog Input Procedures
A
3
Common Items
Creation of sequence program
Create the program as follows to read analog signals.
• While referring to step 2, set the input mode "H****".
• While referring to step 1, set the unit number in B
- Program Example (For FX3U, FX3UC Series PLCs)*1
FX3UC-4AD
FX3U-4AD
Input mode (step 2)
Unit number (step 1)
Initial pulse
M8002
FNC 12 H**** U \GO Specify the input mode (BFM #0) for channels C
MOV P 1 to 4.
FX3U-4AD-ADP
RUN monitor
M8000
T0 K50
T0
FNC 15 U \G10 D0 K4
5 seconds after starting the PLC, the digital
values of channels 1 to 4 (BFM #10 to #13) will D
BMOV be read out to D0 to D3.
FX3G-2AD-BD
Unit number (step 1)
FX3U-4DA
1) Transfer the sequence program, and start the PLC.
2) The 4AD analog data input mode will be stored in data registers (D0 to D3) of the PLC.
3) Check that the data is stored in D0 to D3.
→ If the data is not properly stored, refer to Chapter 8 "Troubleshooting." F
FX3U-4DA-ADP
G
FX3G-1DA-BD
H
FX3U-3A-ADP
I
FX3U-4AD-PT
-ADP
J
FX3U-4AD-PTW
-ADP
B-19
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 5 Buffer Memory (BFM)
FX3U-4AD/FX3UC-4AD (4-channel Analog Input) 5.1 Assignment of Unit Numbers and Outline of Buffer Memory
B-20
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 5 Buffer Memory (BFM)
FX3U-4AD/FX3UC-4AD (4-channel Analog Input) 5.1 Assignment of Unit Numbers and Outline of Buffer Memory
A
2. Outline of buffer memory
Common Items
The analog signals input into the 4AD will be converted into digital values and then stored in the 4AD buffer
memory.
To switch the input mode between voltage input and current input, or to adjust the offset or gain, numeric data
will be sent from the main unit and written/set in the 4AD buffer memory.
To read/write data from/to the 4AD buffer memory, the buffer memory can be directly specified using the
FROM/TO instruction or an applied instruction. Using this function, sequence programs can be easily created.
B
FX3UC-4AD
FX3U-4AD
Main unit 4AD • BFM direct 4AD
specification*1
• TO instruction
Buffer
• BFM direct
memory
C
• BFM direct
FX3U-4AD-ADP
specification*1
specification*1
• TO instruction
Sequence Buffer • FROM instruction
program memory
Digital
• BFM direct Digital value
specification*1
• FROM
value
D
A/D A/D
FX3G-2AD-BD
instruction conversion conversion
FX3U-4DA
Flowmeter, pressure sensor, etc.
*1. Since buffer memory direct specification (U\G) can directly specify the buffer memory in the source or
destination area of an applied instruction, programs can be created efficiently. (This function is supported
only in FX3U/FX3UC PLCs.)
→ For a detailed description of buffer memory reading/writing, refer to Section 5.2.
F
FX3U-4DA-ADP
→ For a detailed description of the buffer memory, refer to Section 5.4.
FX3G-1DA-BD
H
FX3U-3A-ADP
I
FX3U-4AD-PT
-ADP
J
FX3U-4AD-PTW
-ADP
B-21
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 5 Buffer Memory (BFM)
FX3U-4AD/FX3UC-4AD (4-channel Analog Input) 5.2 Buffer Memory Reading/Writing Method
1. Example 1
If the following program is created, data in buffer memory (BFM #10) of unit 1 will be multiplied by the data
(K10), and then the multiplication result will be output to data registers (D10, D11).
READ command
FNC 22 U1\G10 K10 D10
MUL
Multiplication result
Unit number
Buffer memory number Multiplier
2. Example 2
If the following program is created, the value in data register (D20) is added to K10 and written to buffer
memory (BFM #6) of unit 1.
WRITE command
FNC 20 D20 K10 U1\G6
ADD
(
Addition Unit number
result Buffer memory number )
Augend Addend
B-22
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 5 Buffer Memory (BFM)
FX3U-4AD/FX3UC-4AD (4-channel Analog Input) 5.3 Buffer Memory List (BFM)
A
5.3 Buffer Memory List (BFM)
Common Items
4AD incorporates the following buffer memories.
→ For a detailed description of the buffer memory, refer to Section 5.4 and subsequent sections.
BFM number Description Setting range Initial value Data type Reference B
FX3UC-4AD
FX3U-4AD
Hexadeci- Subsection
#0*1 Input mode setting for channels 1 to 4 *2 H0000 at delivery
mal 5.4.1
#1 Not used - - - -
#2 Averaging time units for channel 1 1 to 4095 K1 Decimal
#3 Averaging time units for channel 2 1 to 4095 K1 Decimal
#4 Averaging time units for channel 3 1 to 4095 K1 Decimal
Subsection
5.4.2 C
FX3U-4AD-ADP
#5 Averaging time units for channel 4 1 to 4095 K1 Decimal
#6 Channel-1 digital filter setting 0 to 1600 K0 Decimal
#7 Channel-2 digital filter setting 0 to 1600 K0 Decimal Subsection
#8 Channel-3 digital filter setting 0 to 1600 K0 Decimal 5.4.3
FX3G-2AD-BD
#10 Channel-1 data (current data or average data) - - Decimal
#11 Channel-2 data (current data or average data) - - Decimal Subsection
#12 Channel-3 data (current data or average data) - - Decimal 5.4.4
FX3U-4DA
Disables adjustment of the following buffer
memory locations:
• Input mode specification (BFM #0)
To enable data
• Initialization function (BFM #20)
change: K2080
• Input characteristics writing (BFM #21) Subsection
#19*1 To disable data K2080 at delivery Decimal
• Convenient functions (BFM #22)
• Offset data (BFM #41 to #44)
change: Value
5.4.5
F
other than K2080
FX3U-4DA-ADP
• Gain data (BFM #51 to #54)
• Automatic transfer-to data register
specification (BFM #125 to #129)
• Data history sampling time setting (BFM #198)
Initialization function:
#20
Set "K1" in this buffer memory to perform
initialization. At the completion of initialization, K0 or K1 K0 Decimal
Subsection G
5.4.6
FX3G-1DA-BD
buffer memory will be automatically reset to
"K0".
Input characteristics writing:
Write the input characteristics offset/gain value.
Hexadeci- Subsection
#21 At the completion of writing, buffer memory will *3 H0000
mal 5.4.7
be automatically reset to "H0000" (b0 to b3:
OFF). H
FX3U-3A-ADP
*1. If power failure occurs, the EEPROM will retain its data.
*2. To specify the input mode of each channel, set each digit using hexadecimal numbers 0 to 8 and F.
*3. Use b0 to b3.
I
FX3U-4AD-PT
-ADP
J
FX3U-4AD-PTW
-ADP
B-23
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 5 Buffer Memory (BFM)
FX3U-4AD/FX3UC-4AD (4-channel Analog Input) 5.3 Buffer Memory List (BFM)
BFM number Description Setting range Initial value Data type Reference
Convenient function setting:
Convenient functions:Automatic send
Hexadeci- Subsection
#22*1 function, data addition, upper/lower limit *2 H0000 at delivery
mal 5.4.8
detection, abrupt change detection, peak
value holding
#23 to #25 Not used - - - -
Upper/lower limit value error status (Valid if b1 Hexadeci- Subsection
#26 - H0000
of BFM #22 is set to ON) mal 5.4.9
Abrupt change detection status (Valid if b2 of Hexadeci- Subsection
#27 - H0000
BFM #22 is set to ON) mal 5.4.10
Hexadeci- Subsection
#28 Over-scale status - H0000
mal 5.4.11
Hexadeci- Subsection
#29 Error status - H0000
mal 5.4.12
Subsection
#30 Model code K2080 - K2080 Decimal
5.4.13
#31 to #40 Not used - - - -
#41*1 Channel-1 offset data (Unit: mV or μA) • Voltage input: K0 at delivery Decimal
BFM #21 -10000 to
#42 *1 Channel-2 offset data (Unit: mV or μA) will be K0 at delivery Decimal
+9000*3 Subsection
used for
#43 *1 Channel-3 offset data (Unit: mV or μA) • Current input: K0 at delivery Decimal 5.4.14
writing
-20000 to
data.
#44*1 Channel-4 offset data (Unit: mV or μA) +17000*4 K0 at delivery Decimal
#51 *1 Channel-1 gain data (Unit: mV or μA) • Voltage input: K5000 at delivery Decimal
BFM #21 -9000 to
#52*1 Channel-2 gain data (Unit: mV or μA) will be K5000 at delivery Decimal
+10000*3 Subsection
used for
#53*1 Channel-3 gain data (Unit: mV or μA) • Current input: K5000 at delivery Decimal 5.4.14
writing
-17000 to
data.
#54*1 Channel-4 gain data (Unit: mV or μA) +30000*4 K5000 at delivery Decimal
*1. If power failure occurs, the EEPROM will retain its data.
*2. Use b0 to b7.
*3. The offset and gain values should satisfy the following conditions: Gain value - Offset value ≥ 1000
*4. The offset and gain values should satisfy the following conditions: 30000 ≥ Gain value - Offset value ≥ 3000
B-24
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 5 Buffer Memory (BFM)
FX3U-4AD/FX3UC-4AD (4-channel Analog Input) 5.3 Buffer Memory List (BFM)
Common Items
BFM number Description Setting range Initial value Data type Reference
Channel-1 upper limit value error setting Maximum digital
#81 Decimal
(Valid if b1 of BFM #22 is set to ON) value in input range
#82
Channel-2 upper limit value error setting From lower limit Maximum digital
value error setting value in input range Decimal B
(Valid if b1 of BFM #22 is set to ON) Subsection
FX3UC-4AD
FX3U-4AD
value to maximum
Channel-3 upper limit value error setting Maximum digital 5.4.16
#83 digital value in Decimal
(Valid if b1 of BFM #22 is set to ON) input range value in input range
Channel-4 upper limit value error setting Maximum digital
#84 Decimal
(Valid if b1 of BFM #22 is set to ON) value in input range
#85 to #90 Not used - - - -
C
Channel-1 abrupt change detection value From 1 to 50% of
FX3U-4AD-ADP
#91 5% of full scale Decimal
(Valid if b2 of BFM #22 is set to ON) full scale
Channel-2 abrupt change detection value From 1 to 50% of
#92 5% of full scale Decimal
(Valid if b2 of BFM #22 is set to ON) full scale Subsection
Channel-3 abrupt change detection value From 1 to 50% of 5.4.17
#93 5% of full scale Decimal
(Valid if b2 of BFM #22 is set to ON)
Channel-4 abrupt change detection value
full scale
From 1 to 50% of
D
#94 5% of full scale Decimal
FX3G-2AD-BD
(Valid if b2 of BFM #22 is set to ON) full scale
#95 to #98 Not used - - - -
Clear of upper/lower limit error data or abrupt Subsection
#99 *1 H0000 -
change error data 5.4.18
#100 Not used
Channel-1 minimum peak value (Valid if b3 of
- - - -
E
#101 - - Decimal
FX3U-4DA
BFM #22 is set to ON)
Channel-2 minimum peak value (Valid if b3 of
#102 - - Decimal
BFM #22 is set to ON) Subsection
Channel-3 minimum peak value (Valid if b3 of 5.4.19
#103 - - Decimal
BFM #22 is set to ON)
Channel-4 minimum peak value (Valid if b3 of
F
#104 - - Decimal
FX3U-4DA-ADP
BFM #22 is set to ON)
#105 to #108 Not used - - - -
Hexadeci- Subsection
#109 Minimum peak value resetting *3 H0000
mal 5.4.20
#110 Not used
Channel-1 maximum peak value (Valid if b3
- - - -
G
#111 - - Decimal
FX3G-1DA-BD
of BFM #22 is set to ON)
Channel-2 maximum peak value (Valid if b3
#112 - - Decimal
of BFM #22 is set to ON) Subsection
Channel-3 maximum peak value (Valid if b3 5.4.19
#113 - - Decimal
of BFM #22 is set to ON)
Channel-4 maximum peak value (Valid if b3 H
#114 - - Decimal
FX3U-3A-ADP
B-25
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 5 Buffer Memory (BFM)
FX3U-4AD/FX3UC-4AD (4-channel Analog Input) 5.3 Buffer Memory List (BFM)
BFM number Description Setting range Initial value Data type Reference
Upper/lower limit error status data (BFM #26)
Subsection
#126*1 automatic transfer-to data register specification 0 to 7999 K208 at delivery Decimal
5.4.22
(Valid if b5 of BFM #22 is set to ON)
Abrupt change detection status data (BFM #27)
Subsection
#127*1 automatic transfer-to data register specification 0 to 7999 K209 at delivery Decimal
5.4.23
(Valid if b6 of BFM #22 is set to ON)
Over-scale status data (BFM #28) automatic
Subsection
#128*1 transfer-to data register specification (Valid if b7 0 to 7999 K210 at delivery Decimal
5.4.24
of BFM #22 is set to ON)
Error status data (BFM #29) automatic transfer-
Subsection
#129*1 to data register specification (Valid if b8 of BFM 0 to 7999 K211 at delivery Decimal
5.4.25
#22 is set to ON)
#130 to #196 Not used - - - -
Selection of cyclic data update function (function Hexadeci- Subsection
#197 *2 H0000
for data history) mal 5.4.26
Subsection
#198*1 Data history sampling time setting (Unit: ms) 0 to 30000 K15000 Decimal
5.4.27
Hexadeci- Subsection
#199 Data history resetting/stoppage *3 H0000
mal 5.4.28
#200 Channel-1 data history (initial value) - K0 Decimal
Decimal
~
~
#1899 Channel-1 data history (1,700th value) - K0 Decimal
#1900 Channel-2 data history (initial value) - K0 Decimal
Decimal
~
~
#3599 Channel-2 data history (1,700th value) - K0 Decimal Subsection
#3600 Channel-3 data history (initial value) - K0 Decimal 5.4.29
Decimal
~
*1. If power failure occurs, the EEPROM will retain its data.
*2. Use b0 to b3.
*3. Use b0 to b3 and b8 to b11.
B-26
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 5 Buffer Memory (BFM)
FX3U-4AD/FX3UC-4AD (4-channel Analog Input) 5.4 Buffer Memory Details
A
5.4 Buffer Memory Details
Common Items
5.4.1 BFM #0: Input mode specification
FX3UC-4AD
FX3U-4AD
Specify the input modes of channel 1 to 4.
4 hexadecimal digits are assigned to specify the input modes of the 4 channels.
Change the value of each digit to change the input mode of each channel. 0 to 8 or F can be set for each digit.
C
H
FX3U-4AD-ADP
ch4 ch1
ch3 ch2
The different types of input modes are shown in the following table:
→ For a detailed description of input characteristics, refer to Section 2.4. D
FX3G-2AD-BD
Set value Analog input Digital output
Input mode
[HEX] range range
0 Voltage input mode -10V to +10V -32000 to +32000
1 Voltage input mode -10V to +10V -4000 to +4000
Voltage input
E
2*1 -10V to +10V -10000 to +10000
FX3U-4DA
Analog value direct indication mode
3 Current input mode 4mA to 20mA 0 to 16000
4 Current input mode 4mA to 20mA 0 to 4000
Current input
5*1 4mA to 20mA 4000 to 20000
Analog value direct indication mode F
6 Current input mode -20mA to +20mA -16000 to +16000
FX3U-4DA-ADP
7 Current input mode -20mA to +20mA -4000 to +4000
Current input
8*1 Analog value direct indication mode
-20mA to +20mA -20000 to +20000
FX3G-1DA-BD
*1. The offset/gain values cannot be changed.
1. Cautions regarding input mode setting
• If the input mode is set (changed), the analog input characteristics will be changed automatically.
Furthermore, when the offset/gain value is changed, the characteristics can be set to the desired values.
(The resolution cannot be changed.) H
FX3U-3A-ADP
• If the analog value direct indication (*1) is specified, the offset/gain value cannot be changed.
• It takes approximately 5 seconds to determine the input mode. For this reason, after changing the input
mode, be sure to wait for 5 seconds or more before writing other data.
• HFFFF (no channels used) cannot be set.
2. Caution regarding EEPROM writing I
If data is written to BFM #0, #19, #21, #22, #125 to #129, or #198, the data will also be written to the 4AD
FX3U-4AD-PT
EEPROM.
The maximum number of EEPROM rewrites is 10,000 times. Therefore, when creating a program, do not
frequently write data to the above buffer memories (BFM).
-ADP
J
FX3U-4AD-PTW
-ADP
B-27
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 5 Buffer Memory (BFM)
FX3U-4AD/FX3UC-4AD (4-channel Analog Input) 5.4 Buffer Memory Details
To change the channel data type from the immediate data (channels 1 to 4: BFM #10 to #13) to the average
data, set the desired averaging time (channels 1 to 4 : BFM #2 to 5).
The relation between the set averaging time and the corresponding operation is shown in the following table.
→ For a detailed description of channel data update timing, refer to Subsection 5.4.4.
Averaging
time (BFM Channel data (BFM #10 to #13) type Error descriptions
#2 to #5)
Immediate data K0 will be set, and the averaging time
0 or less (Each time the A/D conversion is performed, the channel setting error (b10 of BFM #29) will
data will be updated.) occur.
Immediate data
1 (initial
(Each time the A/D conversion is performed, the channel -
value)
data will be updated.)
Average data
(Each time the A/D conversion is performed, the average
2 to 400 -
value will be calculated and the channel data will be
updated.)
Average data
(Each time the A/D conversion data reaches the averaging
401 to 4095 -
time, the average data will be calculated and the channel
data will be updated.)
Average data 4096 will be set, and the averaging
4096 or more (Each time the A/D conversion is performed, the channel time setting error (b10 of BFM #29) will
data will be updated.) occur.
1. Application
If the measurement signal contains comparatively reduced ripple noise, such as supply voltage frequency,
averaging will result in obtaining of stable data.
B-28
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 5 Buffer Memory (BFM)
FX3U-4AD/FX3UC-4AD (4-channel Analog Input) 5.4 Buffer Memory Details
A
5.4.3 BFM #6 to #9: Digital filter setting
Common Items
Setting range: 0 to 1600
Initial value: K0
Numeric data type: Decimal (K)
B
To use the digital filter for channel data (BFM #10 to #13 for channels 1 to 4), set the digital filter value in the
FX3UC-4AD
FX3U-4AD
corresponding buffer memory (BFM #6 to #9 for channels 1 to 4).
→ For a detailed description of channel data update timing, refer to Subsection 5.4.4.
If the digital filter function is used, the relation between the analog input value and the set digital filter value or
the digital output value (channel data) will be as follows:
• Digital filter value (BFM #6 to #9 for channels 1 to 4) > Fluctuation of analog signal (fluctuation C
width: less than 10 times of sampling)
FX3U-4AD-ADP
If the fluctuation of the analog signal (input value) is less than the set digital filter value, the analog input
value will be converted into a stabilized digital output value and stored in the corresponding buffer memory
(BFM #10 to #13 for channels 1 to 4).
• Digital filter value (BFM #6 to #9 for channels 1 to 4) < Fluctuation of analog signal
If the fluctuation of the analog signal (input value) is more than the set digital filter value, the digital output D
value will follow the analog input value, and the digital output value equal to the analog input value will be
FX3G-2AD-BD
stored in the corresponding buffer memory (BFM #10 to #13 for channels 1 to 4).
E
Set digital filter value
FX3U-4DA
Set digital filter value
FX3U-4DA-ADP
The relation between the set value and the corresponding operation is shown in the following table:
FX3G-1DA-BD
1601 or more Disables the digital filter function. A setting error will occur (b11 of BFM #29 will be set to ON).
1. Application
If the measurement signal contains steep spike noise, use the digital filter instead of the averaging function. H
The digital filter produces more stabilized data results.
FX3U-3A-ADP
• If the digital filter set value is not in the range from 0 to 1600, the digital filter setting error (b11 of BFM #29)
will occur.
-ADP
J
FX3U-4AD-PTW
-ADP
B-29
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 5 Buffer Memory (BFM)
FX3U-4AD/FX3UC-4AD (4-channel Analog Input) 5.4 Buffer Memory Details
Use these buffer memories to store the A/D converted digital values.
The channel data (BFM #10 to #13 for channels 1 to 4) and the data update timing will depend on the set
averaging time (BFM #2 to #5 for channels 1 to 4) or the digital filter setting condition (BFM #6 to #9 for
channels 1 to 4) as shown in the following table.
→ For a detailed description of the averaging time, refer to Subsection 5.4.2.
→ For a detailed description of digital filter functions, refer to Subsection 5.4.3.
Averaging Digital filter Channel data (BFM #10 to #13) update timing
time function
(BFM #2 to #5) (BFM #6 to #9) Channel data type Update timing
B-30
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 5 Buffer Memory (BFM)
FX3U-4AD/FX3UC-4AD (4-channel Analog Input) 5.4 Buffer Memory Details
A
5.4.5 BFM #19: Data change disable
Common Items
Setting range: K2080, or value other than K2080
Initial value (at delivery): K2080
Numeric data type: Decimal (K)
Disables adjustment of the following BFMs: B
• Input mode specification (BFM #0) • Initialization function (BFM #20)
FX3UC-4AD
FX3U-4AD
• Input characteristics writing (BFM #21) • Convenient functions (BFM #22)
• Offset data (BFM #41 to #44) • Gain data (BFM #51 to #54)
• Automatic transfer-to data register specification (BFM #125 to #129)
• Data history sampling time setting (BFM #198)
Set the value of BFM #19 (Data change disable) as follows:
C
FX3U-4AD-ADP
Set value Description
K2080 Data change enabled.
Value other than K2080 Data change disabled.
FX3G-2AD-BD
EEPROM.
→ For a detailed description of caution regarding EEPROM writing, refer to Subsection 5.4.1.
FX3U-4DA
Initial value: K0
Numeric data type: Decimal (K)
Use this function to initialize all data in BFM #0 to #6999, to the factory default status.
Set value Description F
K0 Normal
FX3U-4DA-ADP
K1 Initializes all data
Set "K1" to initialize all data. When initialization is complete, "K0" will be set automatically.
FX3G-1DA-BD
• Priority is given to BFM #19 which prevents a data from being changed. To initialize, set K2080 in BFM #19.
Channel numbers are assigned to the 4 lower bits of BFM #21. If any of these bits are turned on, the offset
data (BFM #41 to #44) and gain data (BFM #51 to #54) of the corresponding channel will be written to the
internal memory (EEPROM). When written to the internal memory, the data will become valid.
b2 Channel-3 offset data (BFM #43) and gain data (BFM #53) writing
b3 Channel-4 offset data (BFM #44) and gain data (BFM #54) writing J
FX3U-4AD-PTW
B-31
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 5 Buffer Memory (BFM)
FX3U-4AD/FX3UC-4AD (4-channel Analog Input) 5.4 Buffer Memory Details
Turn on each bit (b0 to b8) of BFM #22 to enable the function assigned to each bit (refer to the following
table). Turn off each bit to disable the function of each bit.
B-32
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 5 Buffer Memory (BFM)
FX3U-4AD/FX3UC-4AD (4-channel Analog Input) 5.4 Buffer Memory Details
A
2. Caution regarding convenient function setting
Common Items
• Even if the data addition function is used, the value before adding the addition data (BFM #61 to #64) will
be checked to detect the over-scale error.
• To use the peak value automatic transfer function (b4 of BFM #22), be sure to enable the peak value
holding function (b3 of BFM #22).
• To use the upper/lower limit error status data automatic transfer function (b5 of BFM #22), be sure to
B
FX3UC-4AD
FX3U-4AD
enable the upper/lower limit value detection function (b1 of BFM #22).
• To use the abrupt change detection status data automatic transfer function (b6 of BFM #22), be sure to
enable the abrupt change detection function (b2 of BFM #22).
FX3U-4AD-ADP
EEPROM.
→ For a detailed description of caution regarding EEPROM writing, refer to Subsection 5.4.1.
FX3G-2AD-BD
E
FX3U-4DA
F
FX3U-4DA-ADP
G
FX3G-1DA-BD
H
FX3U-3A-ADP
I
FX3U-4AD-PT
-ADP
J
FX3U-4AD-PTW
-ADP
B-33
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 5 Buffer Memory (BFM)
FX3U-4AD/FX3UC-4AD (4-channel Analog Input) 5.4 Buffer Memory Details
3. Upper/lower limit error status data automatic transfer function (b5 of BFM #22)
If the upper/lower limit error status data automatic transfer-to data register is specified in BFM #126, the data
in BFM #26 can be transferred to the specified data register.
When the upper/lower error is detected, data will be automatically transferred from the 4AD to the PLC. For
this reason, the PLC does not need the program for reading data, and the scanning time of the PLC can be
shortened.
: Represents a numeric value.
Convenient function
Automatic data transfer function
setting
Transfer-to data register specification
ON = Valid Transfer-from buffer memory
(BFM #126: K )
BFM #22 b1:ON
BFM #26 → D
BFM #22 b5:ON
B-34
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 5 Buffer Memory (BFM)
FX3U-4AD/FX3UC-4AD (4-channel Analog Input) 5.4 Buffer Memory Details
A
5.4.10 BFM #27: Abrupt change detection status
Common Items
Initial value: H0000
Numeric data type: Hexadecimal (H)
When channel data (BFM #10 to #13) is updated, if the difference between the previous value and the new
value is larger than the set abrupt change detection value (value set in BFM #91 to #94), the following
operation will be performed:
B
FX3UC-4AD
FX3U-4AD
• If "(new value) - (previous value) > (abrupt change detection value)":
The "+" direction bit will turn on.
• If "(previous value) - (new value) > (abrupt change detection value)":
The "-" direction bit will turn on.
→ For a detailed description of abrupt change detection status data resetting,
refer to Subsection 5.4.18.
C
FX3U-4AD-ADP
1. Assignment of each bit of BFM #27
For the abrupt change detection function of each channel, the "+" and "-" directions are assigned as shown in
the following table:
FX3G-2AD-BD
ch1
b1 "+" direction for abrupt change detection
b2 "-" direction for abrupt change detection
ch2
b3 "+" direction for abrupt change detection
b4
ch3
"-" direction for abrupt change detection E
b5 "+" direction for abrupt change detection
FX3U-4DA
b6 "-" direction for abrupt change detection
ch4
b7 "+" direction for abrupt change detection
b8 to b15 Not used.
FX3U-4DA-ADP
• To use the abrupt change status data, be sure to turn on the abrupt change detection function (b2 of BFM
#22).
• Perform one of the following operations to turn off the previously turned on bit:
- Turn the power off and on.
- Turn on b2 of BFM #99 to reset the abrupt change detection error status.
- Write "H0000" in BFM #27 as the abrupt change detection status data.
G
FX3G-1DA-BD
• Even if abrupt change is detected, channel data (BFM #10 to #13) will be continuously updated.
3. Abrupt change detection status data automatic transfer function (b6 of BFM #22)
If the abrupt change detection status data automatic transfer-to data register is specified in BFM #127, the
data in BFM #27 can be transferred to the specified data register.
When abrupt change is detected, data will be automatically transferred from the 4AD to the PLC. For this H
reason, the PLC does not need any program for reading the data, and the scan time of the PLC can be
FX3U-3A-ADP
shortened.
: Represents a numeric value.
Convenient function
Automatic data transfer function
setting
J
FX3U-4AD-PTW
-ADP
B-35
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 5 Buffer Memory (BFM)
FX3U-4AD/FX3UC-4AD (4-channel Analog Input) 5.4 Buffer Memory Details
B-36
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 5 Buffer Memory (BFM)
FX3U-4AD/FX3UC-4AD (4-channel Analog Input) 5.4 Buffer Memory Details
A
5.4.12 BFM #29: Error status
Common Items
Initial value: H0000
Numeric data type: Hexadecimal (H)
Error data is assigned to the bits of BFM #29.
B
1. BFM #29 Bit Assignment
FX3UC-4AD
FX3U-4AD
Bit No. Item Description
b0 Error detection If any bits between b2 and b4 are turned on, b0 will turn on.
b1 - -
FX3U-4AD-ADP
FX3U-4AD/FX3UC-4AD may be defective. Please contact the nearest
b3 Hardware error
Mitsubishi Electric distributor office.
The A/D conversion value is abnormal.
b4 A/D conversion error Check the over-scale status data (BFM #28) to localize the error
b5 -
channel.
-
D
FX3G-2AD-BD
BFM reading/writing If change in the input characteristics is started, this bit will turn on. If
b6
impossible this bit (b6) is on, A/D conversion data cannot be read out correctly.
b7 - -
b8 Data setting error detection If any bits between b10 and b15 are turned on, b8 will turn on.
b9 - - E
FX3U-4DA
The averaging time (BFM #2 to #5) is not set correctly.
b10 Averaging time setting error
Set the averaging time again in the range from 1 to 4095.
The digital filter value (BFM #6 to #9) is not set correctly.
b11 Digital filter setting error
Set the digital filter value again in the range from 0 to 1600.
b12
Abrupt change detection
The abrupt change detection value (BFM #91 to #94) is not set
correctly.
F
value setting error
FX3U-4DA-ADP
Correctly set the value again.
The lower limit error detection value (BFM #71 to #74) or the upper
Upper/lower limit error
b13 limit error detection value (BFM #81 to #84) is not set correctly.
detection value setting error
Correctly set the value again.
b14 - -
The addition data (BFM #61 to #64) is not set correctly.
G
b15 Addition data setting error
FX3G-1DA-BD
Set the addition data again in the range from -16000 to +16000.
If the error status data automatic transfer-to data register is specified in BFM #129, the data in BFM #29 can
be transferred to the specified data register.
When an error is detected, data will be automatically transferred from 4AD to the PLC. For this reason, the
PLC does not need any program for reading the data, and the scan time of the PLC can be shortened.
: Represents a numeric value. I
Convenient function
FX3U-4AD-PT
B-37
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 5 Buffer Memory (BFM)
FX3U-4AD/FX3UC-4AD (4-channel Analog Input) 5.4 Buffer Memory Details
5.4.14 BFM #41 to #44: Offset data / BFM #51 to #54: Gain data
If the input mode is specified in BFM #0, the offset data and the gain data of each channel will be
automatically stored. The initial offset data and gain data are set for each mode as shown in the following
table:
• Offset data: Analog input value when the digital value is "0" (reference offset value)
• Gain data: Analog input value when the digital value is equal to the reference gain value (The
reference gain value depends on the set input mode.)
B-38
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 5 Buffer Memory (BFM)
FX3U-4AD/FX3UC-4AD (4-channel Analog Input) 5.4 Buffer Memory Details
A
2. Offset/gain data change
Common Items
Set offset data and gain data to change the input characteristics.
The offset and gain data can be set for each channel. If the voltage input mode is set, write the offset and gain
data in mV. If the current input mode is set, write the offset and gain data in μA.
To change the offset data or gain data, turn on the corresponding bit of BFM #21 (buffer memory for input
characteristics writing).
The data setting range is shown in the following table:
B
FX3UC-4AD
FX3U-4AD
Voltage input (mV) Current input (μA)
Offset data -10000 to +9000*1 -20000 to +17000*2
Gain data -9000 to +10000*1 -17000 to +30000*2
*1. The offset and gain values should meet the following condition:
C
FX3U-4AD-ADP
Gain value - Offset value ≥ 1000
*2. The offset and gain values should meet the following condition:
30000 ≥ Gain value - Offset value ≥ 3000
FX3G-2AD-BD
• If the analog value direct indication mode is used, the input characteristics cannot be changed.
• Even if the input characteristics are changed, the actual valid input range will not be changed:
from -10V to +10V for the voltage input mode, and from -20mA to +20mA for the current input mode.
• Even if the input characteristics are changed, the resolution will not increase.
→ For a detailed description of input characteristics change, refer to Chapter 6. E
FX3U-4DA
5.4.15 BFM #61 to #64: Addition data
FX3U-4DA-ADP
If the addition data (BFM #61 to #64) is set, the set data will be added before storing the channel data (BFM
#10 to #13), peak data (BFM #101 to #104, BFM #111 to #114), or data history (BFM #200 to #6999).
FX3G-1DA-BD
add the addition data (BFM #61 to #64) to the error data to be set.
H
FX3U-3A-ADP
I
FX3U-4AD-PT
-ADP
J
FX3U-4AD-PTW
-ADP
B-39
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 5 Buffer Memory (BFM)
FX3U-4AD/FX3UC-4AD (4-channel Analog Input) 5.4 Buffer Memory Details
5.4.16 BFM #71 to #74: Lower limit error setting / BFM #81 to #84: Upper limit error setting
Set the upper/lower limit error data so that the upper/lower limit error status (BFM #26) can be detected.
The data setting range depends on the input mode set in BFM #0.
The following table shows the data setting range for each input mode:
B-40
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 5 Buffer Memory (BFM)
FX3U-4AD/FX3UC-4AD (4-channel Analog Input) 5.4 Buffer Memory Details
A
5.4.17 BFM #91 to #94: Abrupt change detection value setting
Common Items
Setting range: See below.
Initial value: See below.
Numeric data type: Decimal (K)
When channel data (BFM #10 to #13) is updated, if the difference between the previous value and the new
B
FX3UC-4AD
FX3U-4AD
value is larger than the set abrupt change detection value (value set in BFM #91 to #94), the system will judge
that the channel data is changed abruptly.
The result of abrupt change detection will be written to BFM #27 as the abrupt change detection status data.
The abrupt change detection value setting range depends on the set input mode (BFM #0) as shown in the
following table:
Input mode (BFM #0)
C
FX3U-4AD-ADP
Set Setting range Initial value
Description
value
Voltage input
0 1 to 32767 3200
(-10V to +10V:-32000 to +32000)
1
Voltage input
(-10V to +10V:-4000 to +4000)
1 to 4095 400 D
FX3G-2AD-BD
Voltage input
2 Analog value direct indication mode 1 to 10000 1000
(-10V to +10V:-10000 to +10000)
3 Current input (4mA to 20mA:0 to 16000) 1 to 8191 800
4 Current input (4mA to 20mA:0 to 4000) 1 to 2047 200 E
FX3U-4DA
Current input
5 Analog value direct indication mode 1 to 8191 800
(4mA to 20mA:4000 to 20000)
Current input
6 1 to 16383 1600
(-20mA to +20mA:-16000 to +16000)
Current input
F
7 1 to 4095 400
FX3U-4DA-ADP
(-20mA to +20mA:-4000 to +4000)
Current input
8 Analog value direct indication mode 1 to 20000 2000
(-20mA to +20mA:-20000 to +20000)
FX3G-1DA-BD
To use the abrupt change detection value, be sure to turn on the abrupt change detection function (b2 of BFM
#22).
H
FX3U-3A-ADP
I
FX3U-4AD-PT
-ADP
J
FX3U-4AD-PTW
-ADP
B-41
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 5 Buffer Memory (BFM)
FX3U-4AD/FX3UC-4AD (4-channel Analog Input) 5.4 Buffer Memory Details
5.4.18 BFM #99: Clearance of upper/lower limit error data and abrupt change detection data
5.4.19 BFM #101 to #104: Minimum peak value / BFM #111 to #114: Maximum peak value
The minimum channel data (channels 1 to 4) value written to BFM #10 to #13 will be written to BFM #101 to
#104 as the minimum peak value, and the maximum channel data value will be written to BFM #111 to #114
as the maximum peak value.
• If the data addition function (b0 of BFM #22) is used together with this function, the addition data will be
added to the measurement data.
• If the value holding function is not used, the peak value will be "K0".
B-42
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 5 Buffer Memory (BFM)
FX3U-4AD/FX3UC-4AD (4-channel Analog Input) 5.4 Buffer Memory Details
A
5.4.20 BFM #109: Minimum peak value resetting / BFM #119: Maximum peak value
Common Items
resetting
FX3UC-4AD
FX3U-4AD
Channel numbers are assigned to the bits of BFM #109 and #119 to specify the channel to be subject to peak
value resetting.
Turn on each bit to reset the peak value of the corresponding channel.
FX3U-4AD-ADP
Description
Bit No.
BFM #109 BFM #119
b0 Channel-1 minimum peak value (BFM #101) resetting Channel-1 maximum peak value (BFM #111) resetting
b1 Channel-2 minimum peak value (BFM #102) resetting Channel-2 maximum peak value (BFM #112) resetting
b2 Channel-3 minimum peak value (BFM #103) resetting Channel-3 maximum peak value (BFM #113) resetting D
FX3G-2AD-BD
b3 Channel-4 minimum peak value (BFM #104) resetting Channel-4 maximum peak value (BFM #114) resetting
b4 to b15 Not used.
Two or more bits can be turned on at a time.
E
5.4.21 BFM #125: Peak value automatic transfer to first data register specification
FX3U-4DA
Setting range: 0 to 7992
Initial value (at delivery) : K200
Numeric data type: Decimal (K)
If the automatic transfer to first data register is specified in BFM #125, the minimum peak value (BFM #101 to F
FX3U-4DA-ADP
#104) and the maximum peak value (BFM #111 to #114) will be automatically transferred to the specified
data registers (8 points (registers) starting from the first data register specified).
When the peak value is updated, data will be automatically transferred from the 4AD to the PLC. For this
reason, the PLC does not need any program for reading the data, and the scan time of the PLC can be
shortened.
→ For a detailed description of the minimum peak value (BFM #101 to #104) and the maximum peak G
value (BFM #111 to #114), refer to Subsection 5.4.19.
FX3G-1DA-BD
1. If "BFM #125 = K200 (initial value)"
Data will be transferred to D200 to D207 (8 points).
Specified data register Description
D200 Channel-1 minimum peak value (BFM #101) H
FX3U-3A-ADP
2. Caution regarding peak value automatic transfer-to first data register specification
• If data registers are already specified for the other automatic transfer functions, do not specify the same
data registers.
J
FX3U-4AD-PTW
• Be sure to turn on the peak value automatic transfer function (b4 of BFM #22) and the peak value holding
function (b3 of BFM #22).
• The data written to BFM #125 will be retained in the EEPROM.
-ADP
B-43
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 5 Buffer Memory (BFM)
FX3U-4AD/FX3UC-4AD (4-channel Analog Input) 5.4 Buffer Memory Details
5.4.22 BFM #126: Upper/lower error status data automatic transfer-to data register
specification
Use this function to automatically transfer the upper/lower limit error status data (BFM #26) to the data
register specified in BFM #126.
When the upper/lower limit error is detected, data will be automatically transferred from the 4AD to the PLC.
For this reason, the PLC does not need any program for reading the data, and the scanning time of the PLC
can be shortened.
→ For a detailed description of the upper/lower limit error status data (BFM #26),
refer to Subsection 5.4.9.
2. Cautions regarding upper/lower limit error status data automatic transfer-to data register
specification
• If a data register is already specified for the other automatic transfer functions, do not specify the same
data register.
• Be sure to turn on the upper/lower limit error status data automatic transfer function (b5 of BFM #22) and
the upper/lower limit detection function (b1 of BFM #22).
• The data written to BFM #126 will be retained in the EEPROM.
B-44
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 5 Buffer Memory (BFM)
FX3U-4AD/FX3UC-4AD (4-channel Analog Input) 5.4 Buffer Memory Details
A
5.4.23 BFM #127: Abrupt change detection status data automatic transfer-to data register
Common Items
specification
FX3UC-4AD
FX3U-4AD
Use this function to automatically transfer the abrupt change detection status data (BFM #27) to the data
register specified in BFM #127.
When abrupt change is detected, data will be automatically transferred from the 4AD to the PLC. For this
reason, the PLC does not need any program for reading the data, and the scan time of the PLC can be
shortened.
→ For a detailed description of the abrupt change detection status data (BFM #27), C
FX3U-4AD-ADP
refer to Subsection 5.4.10.
FX3G-2AD-BD
specification
• If a data register is already specified for the other automatic transfer functions, do not specify the same
data register.
• Be sure to turn on the abrupt change detection status data automatic transfer function (b6 of BFM #22) and
the abrupt change detection function (b2 of BFM #22).
E
FX3U-4DA
• The data written to BFM #127 will be retained in the EEPROM.
FX3U-4DA-ADP
G
FX3G-1DA-BD
H
FX3U-3A-ADP
I
FX3U-4AD-PT
-ADP
J
FX3U-4AD-PTW
-ADP
B-45
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 5 Buffer Memory (BFM)
FX3U-4AD/FX3UC-4AD (4-channel Analog Input) 5.4 Buffer Memory Details
5.4.24 BFM #128: Over-scale status data automatic transfer-to data register specification
Use this function to automatically transfer the over-scale status data (BFM #28) to the data register specified
in BFM #128.
When over-scale is detected, data will be automatically transferred from the 4AD to the PLC. For this reason,
the PLC does not need any program for reading the data, and the scan time of the PLC can be shortened.
→ For a detailed description of the over-scale status data (BFM #28), refer to Subsection 5.4.11.
2. Cautions regarding over-scale status data automatic transfer-to data register specification
• If a data register is already specified for the other automatic transfer functions, do not specify the same
data register.
• Be sure to turn on the over-scale status data automatic transfer function (b7 of BFM #22).
• The data written to BFM #128 will be retained in the EEPROM.
5.4.25 BFM #129: Error status data automatic transfer-to data register specification
Use this function to automatically transfer the error status data (BFM #29) to the data register specified in
BFM #129.
When an error is detected, data will be automatically transferred from the 4AD to the PLC. For this reason,
the PLC does not need any program for reading the data, and the scan time of the PLC can be shortened.
→ For a detailed description of the error status data (BFM #29), refer to Subsection 5.4.12.
2. Cautions regarding error status data automatic transfer-to data register specification
• If a data register is already specified for the other automatic transfer functions, do not specify the same
data register.
• Be sure to turn on the error status data automatic transfer function (b8 of BFM #22).
• The data written to BFM #129 will be retained in the EEPROM.
B-46
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 5 Buffer Memory (BFM)
FX3U-4AD/FX3UC-4AD (4-channel Analog Input) 5.4 Buffer Memory Details
A
5.4.26 BFM #197: Selection of cyclic data update function (function for data history)
Common Items
Initial value: H0000
Numeric data type: Hexadecimal (H)
Use this function to update the data history in BFM #200 to #6999.
Channel numbers are respectively assigned to the 4 lower bits of BFM #197. Turn each bit on or off to select B
the data history update function.
FX3UC-4AD
FX3U-4AD
ON: If a bit is turned on, the corresponding data will be stored in the buffer memories in the order of the
smallest BFM number to the largest BFM number, but when 1,700 points of data are stored, data will be
then overwritten in the buffer memories starting from the smallest BFM numbers.
OFF: If a bit is turned off, the corresponding data will be stored in the buffer memories in the order of the
smallest BFM number to the largest BFM number, but when 1,700 points of data are stored, data C
storage will stop.
FX3U-4AD-ADP
1. Channel number assignment to each bit of BFM #197
Bit No. Description History data stored in
b0 Selection of channel-1 data update function BFM #200 to #1899, 1,700 points
b1 Selection of channel-2 data update function BFM #1900 to #3599, 1,700 points D
FX3G-2AD-BD
b2 Selection of channel-3 data update function BFM #3600 to #5299, 1,700 points
b3 Selection of channel-4 data update function BFM #5300 to #6999, 1,700 points
b4 to b15 Not used. -
FX3U-4DA
Setting range: 0 to 30000
Initial value (at delivery) : K15000
Numeric data type: Decimal (K)
FX3U-4DA-ADP
1. Sampling cycle
As shown in the following table, the sampling cycle depends on whether the digital filter function is used.
Value set in
Whether digital filter function is used Sampling cycle
BFM #198 G
0.5 ms × number of selected channels (number of
FX3G-1DA-BD
0
channels using the digital filter function)
None of the channels use the digital filter
function. Set value (ms) in BFM #198 × number of selected
1 or more channels (number of channels using the digital filter
function)
9 or less
5 ms × number of selected channels (number of H
channels using the digital filter function)
FX3U-3A-ADP
If the averaging time is set, the data history function cannot be used.
EEPROM.
→ For a detailed description of cautions regarding EEPROM writing, refer to Subsection 5.4.1.
-ADP
B-47
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 5 Buffer Memory (BFM)
FX3U-4AD/FX3UC-4AD (4-channel Analog Input) 5.4 Buffer Memory Details
B-48
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 5 Buffer Memory (BFM)
FX3U-4AD/FX3UC-4AD (4-channel Analog Input) 5.4 Buffer Memory Details
A
5.4.29 BFM #200 to #6999: Data history
Common Items
Initial value: K0
Numeric data type: Decimal (K)
Use this function to sample the A/D conversion data of each channel and to write the sampled data to the
buffer memories.
The 4AD can sample up to 1,700 points of A/D conversion data of each channel at the sampling cycle
B
FX3UC-4AD
FX3U-4AD
specified in BFM #198, and can store the sampled data as history data in the buffer memories as shown in
the following table. Buffer memories are assigned to the 4 channels as shown in the following table, and data
is stored in the buffer memories in the order of the smallest BFM number to the largest BFM number.
Use BFM #199 to stop or reset the data history.
Number of data
samples
BFM number C
ch1 ch2 ch3 ch4
FX3U-4AD-ADP
1st #200 #1900 #3600 #5300
2nd #201 #1901 #3601 #5301
3rd #202 #1902 #3602 #5302
D
…
…
1,700th #1899 #3599 #5299 #6999
FX3G-2AD-BD
1. Caution regarding data history reading
If a large amount of history data is collectively read out to the PLC main unit using the FROM instruction, the
watchdog timer error may occur in the PLC main unit. Therefore, when programming, separate the history
data and then read it out using the FROM instruction. Set WDT (watchdog timer refresh) instruction between
the separated data. E
FX3U-4DA
F
FX3U-4DA-ADP
G
FX3G-1DA-BD
H
FX3U-3A-ADP
I
FX3U-4AD-PT
-ADP
J
FX3U-4AD-PTW
-ADP
B-49
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 6 Changing Input Characteristics
FX3U-4AD/FX3UC-4AD (4-channel Analog Input) 6.1 Procedure for Changing Input Characteristics
Set value
Input mode Analog input range Digital output range
(HEX)
0 Voltage input mode -10V to +10V -32000 to +32000
1 Voltage input mode -10V to +10V -4000 to +4000
Voltage input analog value direct indication
2 The offset and the gain cannot be adjusted.
mode
3 Current input mode 4mA to 20mA 0 to 16000
4 Current input mode 4mA to 20mA 0 to 4000
Current input analog value direct indication
5 The offset and the gain cannot be adjusted.
mode
6 Current input mode -20mA to +20mA -16000 to +16000
7 Current input mode -20mA to +20mA -4000 to +4000
Current input analog value direct indication
8 The offset and the gain cannot be adjusted.
mode
9 to E Not used. - -
F Channel not used - -
Example: Enter "HFF00" in BFM #0 to set input mode 0 for channels 1 and 2 and prevent use channels 3 and
4.
B-50
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 6 Changing Input Characteristics
FX3U-4AD/FX3UC-4AD (4-channel Analog Input) 6.1 Procedure for Changing Input Characteristics
A
2
Common Items
Determine the input characteristics to be changed.
Determine the digital value to be output according to the input voltage/current.
Example: To output digital values in the range from 0 to 32000 by inputting the voltage in the range
from 1V DC to 5V DC: B
FX3UC-4AD
FX3U-4AD
Input mode 0 Input characteristics provided at the time Input characteristics newly provided
of factory shipment
Digital value Digital value
+32640 +32000
+32000
C
Gain reference value
FX3U-4AD-ADP
Gain reference value (+16000)
(+16000)
FX3G-2AD-BD
-32000
-32640
FX3U-4DA
3 Determine the offset data.
Determine the analog input value (offset data) for digital output value of "0".
Set the analog input value in mV for the voltage input mode, and set the analog input value in μA F
for the current input mode.
FX3U-4DA-ADP
Example: To set the offset value of 1 V, set 1,000 mV.
→ For a detailed description of offset data, refer to Subsection 5.4.14.
FX3G-1DA-BD
value of each input mode.
The following table shows the gain reference value of each input mode:
Numeric
value
Input mode Analog input range Gain standard value Initial value H
FX3U-3A-ADP
Set the analog input value in mV for the voltage input mode, and set the analog input value in μA
-ADP
B-51
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 6 Changing Input Characteristics
FX3U-4AD/FX3UC-4AD (4-channel Analog Input) 6.1 Procedure for Changing Input Characteristics
T0 K50 *1
T0
FNC 16 Offset value of
K1000 U0\G41 K2 channels 1 and 2
FMOV P
RST M0
*1. It takes approximately 5 seconds to change the input mode (BFM #0). This is because all the set
values should be changed.
After changing the input mode, be sure to wait for 5 seconds or more before setting other data.
The input characteristics of each channel can be written in BFM #21. It is also possible to perform
batch writing of input characteristics for two or more channels.
RUN monitor
M8000 The digital values set for
FNC 16 channels 1 to 4 will be read
U0\G10 D0 K4 out to D0 to D3.
BMOV
B-52
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 7 Examples of Practical Programs
FX3U-4AD/FX3UC-4AD (4-channel Analog Input) 7.1 Program That Uses Averaging Time
Common Items
7. Examples of Practical Programs
Use the functions incorporated in the 4AD to create practical programs. This chapter describes the examples B
of practical programs.
FX3UC-4AD
FX3U-4AD
• Program that uses the averaging time
• Program that uses convenient functions
• Program that uses the data history function
• Program that initializes 4AD (to the factory default status)
C
FX3U-4AD-ADP
7.1 Program That Uses Averaging Time
This section describes a program that uses the analog data averaging time input to the 4AD or the digital filter
function of the 4AD.
1. Conditions D
FX3G-2AD-BD
The sequence program described in this section is created under the following conditions.
1) System configuration
The FX3U-4AD (unit No.0) should be connected to the FX3U Series PLC.
2) Input mode
Channels 1 and 2 should be set to mode 0 (voltage input, -10V to +10V → -32000 to +32000).
Channels 3 and 4 should be set to mode 3 (current input, 4mA to 20mA → 0 to 16000).
E
FX3U-4DA
3) Averaging time
For channels 1 to 4, the averaging time should be set to "10".
4) Digital filter function
For channels 1 to 4, the digital filter function should be disabled (default).
5) Device assignment F
FX3U-4DA-ADP
Device Description
D0 A/D converted digital value for channel 1
D1 A/D converted digital value for channel 2
D2 A/D converted digital value for channel 3
D3 A/D converted digital value for channel 4 G
FX3G-1DA-BD
2. Example of sequence program
• For FX3U, FX3UC Series PLCs
Initial pulse
M8002
Input modes of channels 1
RUN monitor
FNC 12
MOV P
H3300 U0\G0 to 4 will be specified.*1 H
FX3U-3A-ADP
M8000
T0 K50 *1
T0
FNC 16 For channels 1 and 2, the averaging time
K10 U0\G2 K4 will be set to "10".
FMOV P
FNC 16 K0 U0\G6 K4
The digital filter function of channels 1 I
FMOV P and 2 will be disabled. *2
FX3U-4AD-PT
*1. After setting the input mode, set the data writing time (waiting time) to 5 seconds or more for each
setting. J
The specified input mode will be retained even if power failure occurs. After specifying the input mode,
FX3U-4AD-PTW
if the same input mode is used, it is not necessary to set the input mode and waiting time (T0 K50).
*2. To use the default value set for the digital filter function, it is not necessary to set the digital filter
-ADP
B-53
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 7 Examples of Practical Programs
FX3U-4AD/FX3UC-4AD (4-channel Analog Input) 7.1 Program That Uses Averaging Time
T0
FNC 79 For channels 1 and 2, the averaging time
K0 K2 K10 K4 will be set to "10".
TO P
*1. After setting the input mode, set the data writing time (waiting time) to 5 seconds or more for each
setting.
The specified input mode will be retained even if power failure occurs. After specifying the input mode,
if the same input mode is used, it is not necessary to set the input mode and waiting time (T0 K50).
*2. To use the default value set for the digital filter function, it is not necessary to set the digital filter
function in the sequence program.
B-54
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 7 Examples of Practical Programs
FX3U-4AD/FX3UC-4AD (4-channel Analog Input) 7.2 Program That Uses Convenient Functions
A
7.2 Program That Uses Convenient Functions
Common Items
This section describes a program that uses the 4AD convenient functions (BFM #22).
1. Conditions
The sequence program described in this section is created under the following conditions. B
1) System configuration
FX3UC-4AD
FX3U-4AD
The FX3U-4AD (unit No.0) should be connected to the FX3U Series PLC.
2) Input mode
Channels 1 and 2 should be set to mode 0 (voltage input, -10V to +10V → -32000 to +32000).
Channels 3 and 4 should be set to mode 3 (current input, 4mA to 20mA → 0 to 16000).
3) Averaging time C
FX3U-4AD-ADP
For all the channels, the averaging time should be set to "1" (default).
(To use the default value, it is not necessary to set the averaging time in the sequence program.)
4) Digital filter function
For all channels, the digital filter function should be disabled (default).
(To use the default value, it is not necessary to set the digital filter function in the sequence program.)
5) Convenient functions
D
FX3G-2AD-BD
The upper/lower limit detection function, upper/lower limit error status data automatic transfer function,
over-scale status data automatic transfer function, and error status data automatic transfer function
should be used.
6) Device assignment
Device Description E
X000 Clearance of upper/lower limit error data
FX3U-4DA
Input
X001 Clearance of over-scale data
Y000 Output of channel-1 lower limit error data
Y001 Output of channel-1 upper limit error data
Y002 Output of channel-2 lower limit error data
Y003 Output of channel-2 upper limit error data
F
FX3U-4DA-ADP
Y004 Output of channel-3 lower limit error data
Y005 Output of channel-3 upper limit error data
Y006 Output of channel-4 lower limit error data
Y007 Output of channel-4 upper limit error data
Y010 Output of channel-1 over-scale (lower limit) data G
FX3G-1DA-BD
Y011 Output of channel-1 over-scale (upper limit) data
Y012 Output of channel-2 over-scale (lower limit) data
Y013 Output of channel-2 over-scale (upper limit) data
Output Y014 Output of channel-3 over-scale (lower limit) data
Y015 Output of channel-3 over-scale (upper limit) data H
Y016 Output of channel-4 over-scale (lower limit) data
FX3U-3A-ADP
D100 Upper/lower limit error status data automatic transfer-to data register
D101 Over-scale status data automatic transfer-to data register
D102 Error status data automatic transfer-to data register J
FX3U-4AD-PTW
-ADP
B-55
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 7 Examples of Practical Programs
FX3U-4AD/FX3UC-4AD (4-channel Analog Input) 7.2 Program That Uses Convenient Functions
Initial pulse
M8002
FNC 12 Input modes of channels 1 to 4 will be
H3300 U0\G0 specified. *2
RUN monitor MOV P
M8000
T0 K50 *1
T0
FNC 12 H01A2 U0\G22 The convenient functions will be set. *2
MOV P
RUN monitor
M8000
FNC 12 The upper/lower limit error status data of each channel
D100 K2Y000 will be output to Y000 to Y007.
MOV
*1. After setting the input mode, set the data writing time (waiting time) to 5 seconds or more for each
setting.
After this, if the same input mode is used, it is not necessary to set the input mode and waiting time
(T0 K50) again.
*2. The set input mode, convenient functions, upper/lower limit error status data automatic transfer-to
data register number, over-scale status data automatic transfer-to data register number, and error
status data automatic transfer-to data register number are retained in the 4AD EEPROM. For this
reason, even if the sequence program is deleted, the previously set functions will still be valid.
B-56
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 7 Examples of Practical Programs
FX3U-4AD/FX3UC-4AD (4-channel Analog Input) 7.2 Program That Uses Convenient Functions
A
• For FX3G, FX3U, FX3UC Series PLCs
Common Items
Initial pulse
M8002
FNC 79 Input modes of channels 1 to 4 will be
K0 K0 H3300 K1 specified. *2
RUN monitor TO P
M8000
T0 K50 *1 B
FX3UC-4AD
FX3U-4AD
T0
FNC 79 K0 K22 H01A2 K1 The convenient functions will be set. *2
TO P
FX3U-4AD-ADP
K0 K128 K101 K1 register will be set to D101. *2
TO P
FNC 78
FROM P
K0 K10 D0 K4 Reads the digital values of channels 1 to 4 from
BFM#10 to #13 into D0 to D3. D
FX3G-2AD-BD
Clearance of upper/
lower limit error data
X000
FNC 79 K0 K99 H0003 K1 Clearance of upper/lower limit error data
TO P
Clearance of over-scale
data
X001
FNC 79
E
K0 K28 K0 K1 Clearance of over-scale data
FX3U-4DA
TO
RUN monitor
M8000
FNC 12 The upper/lower limit error status data of each channel
D100 K2Y000 will be output to Y000 to Y007.
MOV
FX3U-4DA-ADP
MOV output to Y010 to Y017.
FX3G-1DA-BD
M8
Y021 The setting error detection signal will be output to Y021.
*1. After setting the input mode, set the data writing time (waiting time) to 5 seconds or more for each
setting. H
After this, if the same input mode is used, it is not necessary to set the input mode and waiting time
FX3U-3A-ADP
J
FX3U-4AD-PTW
-ADP
B-57
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 7 Examples of Practical Programs
FX3U-4AD/FX3UC-4AD (4-channel Analog Input) 7.3 Program That Uses Data History Function
1. Conditions
The sequence program described in this section is created under the following functions.
1) System configuration
The FX3U-4AD (unit No.0) should be connected to the FX3U Series PLC.
2) Input mode
Channels 1 and 2 should be set to mode 0 (voltage input, -10V to +10V → -32000 to +32000).
Channels 3 and 4 should be set to mode 3 (current input, 4mA to 20mA → 0 to 16000).
3) Averaging time
For all the channels, the averaging time should be set to "1" (default).
(To use the default value, it is not necessary to set the averaging time in the sequence program.)
4) Digital filter function
For all channels, the digital filter function should be disabled (default).
(To use the default value, it is not necessary to set the digital filter function in the sequence program.)
5) Data history function
For all channels, the data sampling time should be set to 100 ms.
The sampling cycle should be 100 ms × 4 (number of selected channels) = 400 ms.
For all channels, data will be sampled 100 times, and the sampled data will be stored as data history in
the data registers.
6) Device assignment
Device Description
X000 Clearance of data history
Input
X001 Temporarily stoppage of data history
D0 A/D converted digital value of channel 1
D1 A/D converted digital value of channel 2
D2 A/D converted digital value of channel 3
D3 A/D converted digital value of channel 4
Data register
D100 to D199 Channel-1 data history(100 data samples)
D200 to D299 Channel-2 data history(100 data samples)
D300 to D399 Channel-3 data history(100 data samples)
D400 to D499 Channel-4 data history(100 data samples)
B-58
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 7 Examples of Practical Programs
FX3U-4AD/FX3UC-4AD (4-channel Analog Input) 7.3 Program That Uses Data History Function
A
2. Example of sequence program
Common Items
• For FX3U, FX3UC Series PLCs
Initial pulse
M8002
FNC 12 Input modes of channels 1 to 4 will be
B
H3300 U0\G0 specified. *2
RUN monitor MOV P
M8000
FX3UC-4AD
FX3U-4AD
T0 K50 *1
T0
FNC 12 K100 U0\G198 The sampling time will be set to 100 ms.
*2
MOV P
FNC 15
BMOV
U0\G10 D0 K4
The digital values set for channels 1
to 4 will be read out to D0 to D3. C
Clear data
FX3U-4AD-ADP
history
X000
FNC 12 Data history of all the channels will be
H000F U0\G199 erased.
MOV P
Temporarily stop
data history
X001
FNC 12 H0F00 U0\G199
Data history of all the channels will be
temporarily stopped.
D
MOV P
FX3G-2AD-BD
Temporarily stop
data history
X001
FNC 12 Temporary stoppage of data history will be
H0000 U0\G199 canceled for all the channels.
MOV P
T0 E
FNC 15 Channel-1 history data (100 data samples)
FX3U-4DA
U0\G200 D100 K100 will be read out to D100 to D199.
BMOV
FNC 15
BMOV
U0\G1900 D200 K100
Channel-2 history data (100 data samples)
will be read out to D200 to D299. F
FX3U-4DA-ADP
FNC 07 The watchdog timer will be refreshed.*3
WDT
FNC 07
G
The watchdog timer will be refreshed.*3
FX3G-1DA-BD
WDT
FNC 07
WDT
The watchdog timer will be refreshed.*3 H
FX3U-3A-ADP
*1. After setting the input mode, set the data writing time (waiting time) to 5 seconds or more for each
setting.
After this, if the same input mode is used, it is not necessary to set the input mode and waiting time
(T0 K50) again.
*2. The set input mode and the sampling time are retained in the 4AD EEPROM. Therefore, even if the I
sequence program is deleted, the previously set functions will still be valid.
FX3U-4AD-PT
*3. If a large amount of history data is read out, the scan time of the PLC will be become longer. If the
scan time exceeds 200 ms, the CPU error indicator lamp will illuminate, and the PLC will stop.
-ADP
J
FX3U-4AD-PTW
-ADP
B-59
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 7 Examples of Practical Programs
FX3U-4AD/FX3UC-4AD (4-channel Analog Input) 7.3 Program That Uses Data History Function
Initial pulse
M8002
FNC 79 K0 K0 H3300 K1 Input modes of channels 1 to 4 will be
TO P specified. *2
RUN monitor
M8000
T0 K50 *1
T0
FNC 79 K0 K198 K100 K1 The sampling time will be set to 100 ms.
*2
TO P
T0
FNC 79 K0 K200 D100 K100 Channel-1 history data (100 data samples)
TO will be read out to D100 to D199.
FNC 79 K0 K4300 D400 K100 Channel-4 history data (100 data samples)
TO will be read out to D400 to D499.
*1. After setting the input mode, set the data writing time (waiting time) to 5 seconds or more for each
setting.
After this, if the same input mode is used, it is not necessary to set the input mode and waiting time
(T0 K50) again.
*2. The set input mode and the sampling time are retained in the 4AD EEPROM. Therefore, even if the
sequence program is deleted, the previously set functions will still be valid.
*3. If a large amount of history data is read out, the scan time of the PLC will be become longer. If the
scan time exceeds 200 ms, the CPU error indicator lamp will illuminate, and the PLC will stop.
Insert WDT instruction (watchdog timer refresh) between BMOV instructions.
B-60
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 7 Examples of Practical Programs
FX3U-4AD/FX3UC-4AD (4-channel Analog Input) 7.4 Initialization Program for 4AD (Factory Default)
A
7.4 Initialization Program for 4AD (Factory Default)
Common Items
Execution of the following program will reset the input mode (BFM #0), offset data (BFM #41 to #44), gain
data (BFM #51 to #54), etc. to the factory default status.
1. Conditions B
The sequence program described in this section runs under the following conditions.
FX3UC-4AD
FX3U-4AD
1) System configuration
The FX3U-4AD (unit No.0) should be connected to the FX3U Series PLC.
2) Device assignment
Device Description
X000 4AD initialization command
C
FX3U-4AD-ADP
2. Example of sequence program
• For FX3U, FX3UC Series PLCs
FX3G-2AD-BD
MOV P (BFM #0 to #6999 will be cleared.)
FX3U-4DA
TO P (BFM #0 to #6999 will be cleared.)
3. Cautions
• It takes approximately 5 seconds to complete initialization.
Do not write any data to the buffer memory in this time. F
FX3U-4DA-ADP
• When initialization is complete, the value of BFM #20 will be reset to "K0".
• Priority is given to the data change disable (BFM #19). To initialize, write K2080 to BFM #19.
FX3G-1DA-BD
H
FX3U-3A-ADP
I
FX3U-4AD-PT
-ADP
J
FX3U-4AD-PTW
-ADP
B-61
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 8 Troubleshooting
FX3U-4AD/FX3UC-4AD (4-channel Analog Input) 8.1 PLC Version Number Check
8. Troubleshooting
This chapter describes troubleshooting methods and error codes.
If the A/D conversion data is not input, or if the proper digital value is not input, check the following items:
• PLC version number
• Wiring
• Program
• Error status
FX3U-4AD
Compatible PLC Version number
FX3U Series PLC Ver. 2.20 or later
FX3UC Series PLC Ver. 1.30 or later
FX3G Series PLC Ver. 1.00 or later
FX3UC-4AD
Compatible PLC Version number
FX3UC Series PLC Ver. 1.30 or later
→ For a detailed description of version number check method, refer to Section 1.3.
1. Power
The 4AD needs driving power. Verify that the power supply line is properly connected. Also check that the 24
V indicator lamp of the 4AD is on.
1. Storage devices
Check whether the device holding digital values contains any values written by other programs.
B-62
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 8 Troubleshooting
FX3U-4AD/FX3UC-4AD (4-channel Analog Input) 8.4 Error Status Check
A
8.4 Error Status Check
Common Items
If an error occurs in the 4AD, the corresponding bit of BFM #29 (error status buffer memory) will turn on. To
solve the problem, refer to the troubleshooting method described below:
FX3UC-4AD
FX3U-4AD
b1 - b9 -
b2 Power supply error b10 Averaging time setting error
b3 Hardware error b11 Digital filter setting error
b4 A/D conversion error b12 Abrupt change detection value setting error C
b5 - b13 Upper/lower limit detection setting error
FX3U-4AD-ADP
b6 BFM reading/writing impossible b14 -
b7 - b15 Addition data setting error
FX3G-2AD-BD
If any bits from b2 to b4 are turned on, this bit (b0) will turn on.
FX3U-4DA
Check the wiring condition or the supplied voltage.
FX3U-4DA-ADP
Please contact the nearest Mitsubishi Electric distributor office.
FX3G-1DA-BD
Check the over-scale status data (BFM #28) to localize the error channel. After that, check to make sure
the input analog data is in the specified range.
2) Remedy
Check the sequence program and confirm that the input characteristics (BFM #21 b0 to b3) are not being
written continuously.
If any bits from b10 to b15 are turned on, this bit (b8) will turn on.
1) Description of error
The averaging time (BFM #2 to #5) is not set correctly. J
2) Remedy
FX3U-4AD-PTW
B-63
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 8 Troubleshooting
FX3U-4AD/FX3UC-4AD (4-channel Analog Input) 8.5 4AD Initialization and Test Program
B-64
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition
FX3U-4AD-ADP (4-channel analog Input)
Common Items
B
FX3UC-4AD
FX3U-4AD
FX3G/FX3U/FX3UC Series Programmable
Controllers C
FX3U-4AD-ADP
User's Manual [Analog Control Edition]
FX3U-4AD-ADP (4-channel analog Input)
D
FX3G-2AD-BD
E
FX3U-4DA
F
FX3U-4DA-ADP
G
FX3G-1DA-BD
H
FX3U-3A-ADP
Foreword
This manual describes the specifications, wiring, and operation methods for the FX3U-4AD-ADP special
adapter (4-channel analog input) and should be read and understood before attempting to install or use the
unit. I
Store this manual in a safe place so that you can take it out and read it whenever necessary. Always forward
FX3U-4AD-PT
This manual confers no industrial property rights or any rights of any other kind, nor does it confer any patent
licenses. Mitsubishi Electric Corporation cannot be held responsible for any problems involving industrial property
rights which may occur as a result of using the contents noted in this manual. J
FX3U-4AD-PTW
C-1
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition
FX3U-4AD-ADP (4-channel analog Input)
C-2
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 1 Outline
FX3U-4AD-ADP (4-channel analog Input) 1.1 Outline of Functions
Common Items
1. Outline
This chapter outlines the FX3U-4AD-ADP (referred to as the 4AD-ADP). B
FX3UC-4AD
FX3U-4AD
1.1 Outline of Functions
The FX3U-4AD-ADP is an analog special adapter. Connect the FX3U-4AD-ADP to the FX3U/FX3UC/FX3G
Series PLC to read 4 channels of voltage/current data.
C
FX3U-4AD-ADP
1) Up to 4 4AD-ADP units can be connected to the FX3U/FX3UC Series PLC.
Up to 2*1 4AD-ADP units can be connected to the FX3G Series PLC.
(including the other analog special adapters).
2) Either "voltage input" or "current input" can be specified for each channel.
3) A/D conversion data of each channel will be automatically written to the special data register of the FX3U/ D
FX3UC/FX3G Series PLC.
FX3G-2AD-BD
System Point and section to be
referred to
FX3U-4DA
units
FX3U/FX3UC/FX3G Series PLC
FX3U-4DA-ADP
*2
4th 3rd 2nd 1st Expansion board
adapter adapter adapter adapter
Refer to the system configuration shown in the User's Manual - Hardware Edition to check the number of connectable units I
and to configure the entire system.
FX3U-4AD-PT
*1.Only 1 analog special adapter can be connected to the 14-point and 24-point type main unit.
-ADP
*2.The expansion board is not required when connecting with the FX3UC (D, DSS) PLC.
For the FX3G Series PLC a connector conversion adapter is used.
J
FX3U-4AD-PTW
-ADP
C-3
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 1 Outline
FX3U-4AD-ADP (4-channel analog Input) 1.2 Setup Procedure Before Starting Operation
FX3U-4AD-ADP
Refer to Chapter 1.
Wiring Wiring:
• Selection of sensor cable
• Power supply line
Refer to Chapter 4. • Analog input line
Programming Programming:
• Details of special devices
• Examples of basic programs
Refer to Chapter 5.
C-4
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 1 Outline
FX3U-4AD-ADP (4-channel analog Input) 1.3 Connectable PLCs and Version Number
A
1.3 Connectable PLCs and Version Number
Common Items
The 4AD-ADP is compatible with the following PLCs.
FX3UC-4AD
FX3U-4AD
FX3UC Series PLC Ver.1.20 or later After April 2004
FX3G Series PLC Ver.1.00 or later After June 2008 (initial production)
1. Version check
Special data register D8001 contains information for determining the PLC version number.
C
FX3U-4AD-ADP
→ For a detailed description of the version check, refer to A. Common Items Subsection 5.1.2.
FX3G-2AD-BD
1.4 Compatible Programming Tool Version Number
Use the programming tool with following version numbers to create programs for the 4AD-ADP:
E
1. GX Developer
FX3U-4DA
Software Version number Remarks
GX Developer Ver.SW8 P or later
(Ver.8.13P) When selecting a model, select FX3U(C)*1.
• SW D5C-GPPW-J
• SW D5C-GPPW-E Ver. 8.72A or later When selecting a model, select FX3G. F
FX3U-4DA-ADP
If a programming tool with the wrong version number is used, programming will not be possible.
*1. For Ver. 8.13P to 8.24A of GX Developer, select FX3UC for the PLC type.
2. FX-30P
Model name Version number Remarks
G
FX3G-1DA-BD
FX-30P Ver.1.00 or later
H
FX3U-3A-ADP
I
FX3U-4AD-PT
-ADP
J
FX3U-4AD-PTW
-ADP
C-5
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 2 Specifications
FX3U-4AD-ADP (4-channel analog Input) 2.1 Generic Specifications
2. Specifications
This chapter describes the general, power supply, and performance specifications for the 4AD-ADP.
Item Specifications
Ambient 0 to 55°C (32 to 131°F) when operating
temperature -25 to 75°C (-13 to 167°F) when stored
Relative
5 to 95%RH (no condensation) when operating
humidity
Frequency Acceleration Half amplitude
(Hz) (m/s2) (mm)
Tests 10 times in each
Vibration 10 - 57 - 0.035 direction (X-, Y-, and Z-
DIN Rail Mounting
resistance*1 57 - 150 4.9 - axis directions) (Total:
80 min, each)
10 to 57 − 0.075
Direct Mounting*2
57 to 150 9.8 −
Shock
147 m/s2 Acceleration, Action time: 11ms, 3 times by half-sine pulse in each direction X, Y, and Z
resistance*1
Noise Using noise simulator of:
resistance Noise voltage: 1,000Vp-p / Noise width: 1μs / Rise: 1ns / Cycle: 30 to 100Hz
Dielectric
withstand 500 V AC, for 1 min
voltage Between all terminals and ground terminal
Insulation 5MΩ or more using 500V DC
resistance insulation resistance meter
Class D grounding (grounding resistance: 100 Ω or less)
Grounding
<Common grounding with a heavy electrical system is not allowed.>*3
Working
Free from corrosive or flammable gas and excessive conductive dusts
environment
Working
altitude < 2000m*4
C-6
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 2 Specifications
FX3U-4AD-ADP (4-channel analog Input) 2.2 Power Supply Specifications
A
2.2 Power Supply Specifications
Common Items
Item Specifications
A/D conversion circuit 24V DC +20%-15%, 40mA B
driving power (It is necessary to connect a 24V DC power supply to the terminal block.)
FX3UC-4AD
FX3U-4AD
5V DC, 15mA
Interface driving power (Since the internal power is supplied from the FX Series main unit, it is not
necessary to supply the power.)
FX3U-4AD-ADP
Specifications
Item
Voltage input Current input
D
Analog input 0V to 10V DC 4mA to 20mA DC
FX3G-2AD-BD
range (Input resistance: 194 kΩ) (Input resistance: 250 Ω)
Absolute input
-0.5V, +15V -2mA, +30mA
maximum
Digital output 12 bits, binary 11 bits, binary
Resolution 2.5mV (10V/4000) 10μA (16mA/1600) E
• ±0.5% (±50mV) for 10V full scale • ±0.5% (±80μA) for 16mA full scale
FX3U-4DA
(when ambient temperature is 25°C ± 5°C) (when ambient temperature is 25°C ± 5°C)
Total accuracy
• ±1.0% (±100mV) for 10V full scale • ±1.0% (±160μA) for 16mA full scale
(when ambient temperature is 0°C to 55°C) (when ambient temperature is 0°C to 55°C)
• FX3U/ FX3UC Series PLC : 200 μs (The data will be updated at every scan time.)
A/D conversion
time
• FX3G Series PLC : 250 μs (The data will be updated at every scan time.) F
→ For a detailed description of data update, refer to Section 2.4.
FX3U-4DA-ADP
4080 1640
4000 1600
G
FX3G-1DA-BD
Input
Digital output
Digital output
characteristics
• The photocoupler is used to insulate the analog input area from the PLC.
Insulation method • The DC/DC converter is used to insulate the power supply line from the analog input area.
• Channels are not insulated from each other.
Number of I/O
points occupied
0 point (This number is not related to the maximum number of input/output points of the PLC.) I
FX3U-4AD-PT
-ADP
J
FX3U-4AD-PTW
-ADP
C-7
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 2 Specifications
FX3U-4AD-ADP (4-channel analog Input) 2.4 A/D Conversion Time
Sequence
program
A/D conversion start
A/D command
conversion
Digital value reading
200μs/4ch
A/D conversion start END instruction
A/D command
conversion
Digital value reading
200μs/4ch
C-8
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 2 Specifications
FX3U-4AD-ADP (4-channel analog Input) 2.4 A/D Conversion Time
A
2.4.2 When connected to a FX3G PLC
Common Items
1. A/D conversion and special data register update timing
A/D conversion is performed at every scan time of the PLC.
During execution of END instruction, the PLC performs A/D conversion, reads out the A/D converted data,
and then writes the data in the special data registers. B
FX3UC-4AD
FX3U-4AD
FX3U-4AD-ADP FX3U-4AD-ADP
2nd 1st FX3G Series PLC
C
Sequence
program
A/D conversion start
FX3U-4AD-ADP
A/D command
conversion
Digital value reading
250μs/4ch
A/D conversion start END instruction
A/D
conversion
command
D
FX3G-2AD-BD
Digital value reading
250μs/4ch
FX3U-4DA
3. If two analog special adapters are connected
During execution of the END instruction, data will be read out from all the connected adapters (in the order of
1st adapter → 2nd adapter).
FX3U-4DA-ADP
the data read out will be written to the special data registers.
END instruction execution time will be "250μs × number of connected analog adapters."
FX3G-1DA-BD
H
FX3U-3A-ADP
I
FX3U-4AD-PT
-ADP
J
FX3U-4AD-PTW
-ADP
C-9
FX3U/FX3UC Series PLC User's Manual - Analog Control Edition 3 Wiring
FX3U-4AD-ADP (4-channel analog Input)
3. Wiring
This chapter describes the 4AD-ADP wiring.
Observe the following caution to wire the 4AD-ADP.
WIRING PRECAUTIONS
• Make sure to cut off all phases of the power supply externally before attempting wiring work.
Failure to do so may cause electric shock or damages to the product.
WIRING PRECAUTIONS
• Connect the DC power supply wiring to the dedicated terminals described in this manual.
If an AC power supply is connected to a DC input/output terminal or DC power supply terminal, the PLC will be
burnt out.
• Do not wire vacant terminals externally.
Doing so may damage the product.
• Perform class D grounding (grounding resistance: 100Ω or less) to the grounding terminal on the main unit.
Do not use common grounding with heavy electrical systems.
• When drilling screw holes or wiring, make sure cutting or wire debris does not enter the ventilation slits.
Failure to do so may cause fire, equipment failures or malfunctions.
• Make sure to observe the following precautions in order to prevent malfunctions under the influence of noise:
- Do not bundle the power line or twisted shielded cable together with or lay it close to the main circuit, high-
voltage line, or load line.
Otherwise, noise disturbance and/or surge induction are likely to take place. As a guideline, lay the control line
at least 100mm (3.94") or more away from the main circuit, high-voltage line, or load line.
- Ground the shield of the analog input/output cable at one point on the signal receiving side.
However, do not use common grounding with heavy electrical systems.
• Make sure to properly wire to the European terminal board in accordance with the following precautions.
Failure to do so may cause electric shock, a short-circuit, wire breakage, or damage to the product.
- The disposal size of the cable end should be 9 mm (0.35").
- Tightening torque should be between 0.22 to 0.25 N•m.
- Twist the end of strand wire and make sure there are no loose wires.
- Do not solder-plate the electric wire ends.
- Do not connect more than the specified number of wires or electric wires of unspecified size.
- Affix the electric wires so that neither the terminal block nor the connected parts are directly stressed.
C-10
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 3 Wiring
FX3U-4AD-ADP (4-channel analog Input) 3.1 Terminal Layout
A
3.1 Terminal Layout
Common Items
The terminals of the 4AD-ADP are arranged as follows:
B
FX3U-4AD-ADP
FX3UC-4AD
FX3U-4AD
POWER
Signal Application
24+
C
24+
External power
24-
24-
Grounding terminal
FX3U-4AD-ADP
VI+
V1+
I1+
COM1
V2+
V2+
Channel 2 analog input D
I2+
I2+
COM2
COM2
FX3G-2AD-BD
V3+
V3+
I3+ Channel 3 analog input
I3+
COM3
COM3
V4+
V4+
Channel 4 analog input
I4+
I4+
E
COM4
COM4
FX3U-4DA
F
FX3U-4DA-ADP
G
FX3G-1DA-BD
H
FX3U-3A-ADP
I
FX3U-4AD-PT
-ADP
J
FX3U-4AD-PTW
-ADP
C-11
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 3 Wiring
FX3U-4AD-ADP (4-channel analog Input) 3.2 Applicable Cables and Terminal Tightening Torque
1. Cables
Applicable cable and tightening torque
Wire size (stranded/ Tightening
Termination
single-wire) torque
0.3mm2 to 0.5mm2 • To connect a stranded cable, peel the cover off the cable
Single-wire and then twist the core before connection.
(AWG22 to 20)
• To connect a single-wire cable, just strip the cover off the
2-wire 0.3mm2(AWG22) cable before connection.
0.22N•m to • Rod terminal with insulation sleeve
Rod terminal 0.3mm2 to 0.5mm2 0.25N•m (recommended terminal)
with (AWG22 to 20) AI 0.5-8WH : Manufactured by Phoenix Contact
insulation (Refer to the rod terminal
• Caulking tool
sleeve external view shown in the
CRIMPFOX ZA 3 : Manufactured by Phoenix Contact
following figure.)
(or CRIMPFOX UD 6 : Manufactured by Phoenix Contact)
3. Tool
• To tighten terminals, use a small-sized screwdriver whose head is straight and is not widened as shown in
the figure to the right.
Note:
If the diameter of screwdriver grip is too small, tightening torque will not
The head
be able to be achieved. Use the following recommended screwdriver or should be
an appropriate replacement (grip diameter: approximately 25mm). straight.
Manufacturer Model
Phoenix Contact SZS 0.4×2.5 0.4mm 2.5mm
(0.01") (0.09")
C-12
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 3 Wiring
FX3U-4AD-ADP (4-channel analog Input) 3.3 Power Supply Line
A
3.3 Power Supply Line
Common Items
Connect the 24V DC power supply line of the 4AD-ADP to the 24+ and 24- terminals of the terminal block.
FX3UC-4AD
FX3U-4AD
1. To use an External power supply 2. To use the 24V DC power of the PLC
FX3U-4AD-ADP
24- 24+ 24- 24+ 0V 24V D
FX3G-2AD-BD
Terminal
block Terminal
block
Class-D Class-D
24V DC grounding grounding
E
FX3U-4DA
Caution regarding connection of the power supply line:
• Ground the " " terminal to a class-D grounded power supply line (100Ω or less) together with the
grounding terminal of the PLC main unit.
• For the timing of power-on/off when using an external power supply, see the following manual of the PLC
to be connected. F
→ Refer to the FX3G Series User's Manual - Hardware Edition.
FX3U-4DA-ADP
→ Refer to the FX3U Series User's Manual - Hardware Edition.
FX3G-1DA-BD
15V block)
Power
H
FX3U-3A-ADP
Class-D
grounding
-ADP
24V DC
• Ground the " " terminal to a class-D grounded power supply line (100Ω or less) together with the
grounding terminal of the PLC main unit.
-ADP
C-13
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 3 Wiring
FX3U-4AD-ADP (4-channel analog Input) 3.4 Analog Input Line
*1 147kΩ ch
V +
250Ω
I +
47kΩ
COM
Class-D
grounding
*1. Use the 2-core shielded twisted pair cable for the analog input lines, and separate the analog input
lines from other power lines or inductive lines.
*2. If "current input" is selected, be sure to short the line between the V + terminal and the I + terminal.
( : Channel number).
3.5 Grounding
Grounding should be performed as stated below.
• The grounding resistance should be 100Ω or less.
• Independent grounding should be performed for best results.
When independent grounding is not performed, perform "shared grounding" as shown in the following
figure.
→ For details, refer to the User’s Manual - Hardware Edition of the PLC Series.
C-14
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 4 Programming
FX3U-4AD-ADP (4-channel analog Input) 4.1 Loading of A/D Conversion Data
Common Items
4. Programming
This chapter describes how to create programs that can read analog data using the 4AD-ADP. B
FX3UC-4AD
FX3U-4AD
4.1 Loading of A/D Conversion Data
1) The input analog data will be converted into digital data and then stored in the special devices of the
FX3U/FX3UC/FX3G Series PLC.
C
2) If the data is stored in the special devices, the averaging time can be set, and the input mode can be
FX3U-4AD-ADP
specified.
3) Special auxiliary relays (10 points) and special data registers (10 points) are assigned automatically
starting from the adapter nearest to the main unit.
→ For a detailed description of special device assignment, refer to Section 4.2.
• FX3U, FX3UC Series PLC D
FX3G-2AD-BD
Communic High-speed
FX3U-4AD FX3U-4AD FX3U-4AD -ation FX3U-4AD input/output
-ADP -ADP -ADP special -ADP special
adapter adapter FX3U/FX3UC Series PLC
FX3U-4DA
A/D Special data registers:
D8260 to D8269
FX3U-4DA-ADP
Special auxiliary relays:
M8280 to M8289
A/D Special data registers:
D8280 to D8289.
FX3G-1DA-BD
The analog special adapter nearest to the main unit is counted as the 1st analog special adapter, and the
next adapter as the 2nd analog special adapter, and so on. However, in this case, do not include the high-
speed input/output special adapter, communication special adapter, and the CF card special adapter. H
FX3U-3A-ADP
I
FX3U-4AD-PT
-ADP
J
FX3U-4AD-PTW
-ADP
C-15
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 4 Programming
FX3U-4AD-ADP (4-channel analog Input) 4.1 Loading of A/D Conversion Data
The analog special adapter nearest to the main unit is counted as the 1st analog special adapter, and the
next adapter as the 2nd analog special adapter. However, in this case, do not include the connector
conversion adapter and the communication special adapter.
*1. The second special adapter is not available in the FX3G Series PLC(14-point and 24-point type).
C-16
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 4 Programming
FX3U-4AD-ADP (4-channel analog Input) 4.2 List of Special Devices
A
4.2 List of Special Devices
Common Items
If the 4AD-ADP is connected, special devices will be assigned automatically as shown in the following table:
• FX3U, FX3UC Series PLC
R: Read / W: Write
Special Device number Refer-
B
Description Attribute
FX3UC-4AD
FX3U-4AD
device 1st 2nd 3rd 4th ence
M8260 M8270 M8280 M8290 Switches the input mode of channel 1 R/W
M8261 M8271 M8281 M8291 Switches the input mode of channel 2 R/W Section
Special 4.3
M8262 M8272 M8282 M8292 Switches the input mode of channel 3 R/W
auxiliary
relay M8263 M8273 M8283 M8293 Switches the input mode of channel 4 R/W C
FX3U-4AD-ADP
M8264 to M8274 to M8284 to M8294 to
Unused (Do not use.) - -
M8269 M8279 M8289 M8299
D8260 D8270 D8280 D8290 Channel-1 input data R
D8261 D8271 D8281 D8291 Channel-2 input data R Section
4.4
D8262
D8263
D8272
D8273
D8282
D8283
D8292
D8293
Channel-3 input data
Channel-4 input data
R
R
D
FX3G-2AD-BD
Averaging time for channel-1 (Setting
D8264 D8274 D8284 D8294 R/W
range: 1 to 4095)
FX3U-4DA
Averaging time for channel-4 (Setting
D8267 D8277 D8287 D8297 R/W
range: 1 to 4095)
Section
D8268 D8278 D8288 D8298 Error status R/W
4.6
FX3U-4DA-ADP
G
FX3G-1DA-BD
H
FX3U-3A-ADP
I
FX3U-4AD-PT
-ADP
J
FX3U-4AD-PTW
-ADP
C-17
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 4 Programming
FX3U-4AD-ADP (4-channel analog Input) 4.3 Switching of Input Mode
C-18
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 4 Programming
FX3U-4AD-ADP (4-channel analog Input) 4.4 Input Data
A
4.4 Input Data
Common Items
Numeric data type: Decimal (K)
The data converted by the 4AD-ADP will be stored in the special data registers.
The special data registers that store the input data are shown in the following table:
B
• FX3U, FX3UC Series PLC
FX3UC-4AD
FX3U-4AD
Special data register
Description
1st 2nd 3rd 4th
D8260 D8270 D8280 D8290 Stores the channel-1 input data
D8261 D8271 D8281 D8291 Stores the channel-2 input data C
FX3U-4AD-ADP
D8262 D8272 D8282 D8292 Stores the channel-3 input data
D8263 D8273 D8283 D8293 Stores the channel-4 input data
FX3G-2AD-BD
Description
1st 2nd
D8280 D8290 Stores the channel-1 input data
D8281 D8291 Stores the channel-2 input data
D8282 D8292 Stores the channel-3 input data
E
D8283 D8293 Stores the channel-4 input data
FX3U-4DA
The converted A/D immediate data or averaged data (data average conforming to the specified averaging
time) will be stored in the above data registers as the input data.
→ For a detailed description of the averaging time, refer to Section 4.5.
FX3U-4DA-ADP
Input data is for reading only.
Do not change (rewrite) the input data using sequence program, indicator, or device monitor of the
programming tool.
FX3G-1DA-BD
M8000 Stores the channel-1 input data
FNC 12 D8260 D100
MOV of the 1st analog special
Normally adapter in the D100.
ON
Even if the input data is not stored in D100 or D101, data registers D8260 or D8261 can be directly used in
the timer/counter set value or in a PID instruction.
I
FX3U-4AD-PT
-ADP
J
FX3U-4AD-PTW
-ADP
C-19
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 4 Programming
FX3U-4AD-ADP (4-channel analog Input) 4.5 Averaging Time
C-20
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 4 Programming
FX3U-4AD-ADP (4-channel analog Input) 4.6 Error Status
A
4.6 Error Status
Common Items
If an error is detected in the 4AD-ADP, the error status data will be stored in the corresponding special data
register.
The following table shows the special data registers that store the error status data:
• FX3U, FX3UC Series PLC B
FX3UC-4AD
FX3U-4AD
Special data register
Description
1st 2nd 3rd 4th
D8268 D8278 D8288 D8298 Stores the error status data.
C
• FX3G Series PLC
FX3U-4AD-ADP
Special data register
Description
1st 2nd
D8288 D8298 Stores the error status data.
D
FX3G-2AD-BD
Check the ON/OFF status of each bit of the error status data register to check the description of the error.
Errors are assigned to the bits as shown in the following table. Create a program to detect errors.
→ For a detailed description of the error status, refer to Section 6.5.
FX3U-4DA
4AD-ADP hardware error
b1 Channel-2 over-scale detection b6
(Power supply error included)
b2 Channel-3 over-scale detection b7 4AD-ADP communication data error
b3 Channel-4 over-scale detection b8 to b15 Unused
b4 EEPROM error - - F
FX3U-4DA-ADP
1. Caution regarding use of error status data
If a 4AD-ADP hardware error (b6) or 4AD-ADP communication data error (b7) is detected, it is necessary to
clear the error status with a program at the next power-on of the PLC.
For this reason, be sure to create the following program:
• For FX3G, FX3U, FX3UC Series PLC G
FX3G-1DA-BD
M8000
MOV D8288 K4M0
Normally ON
M8002 *1
Error status of 3rd analog special adapter
RST M6 b6 = OFF (hardware error)
Initial pulse
*1
H
FX3U-3A-ADP
C-21
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 4 Programming
FX3U-4AD-ADP (4-channel analog Input) 4.6 Error Status
M8000
MOV D8288 K4M0
M0
Y000 Detects over-scale in channel 1 of
the 3rd *1 adapter.
M1
Y001 Detects over-scale in channel 2 of
the 3rd *1 adapter.
M2
Y002 Detects over-scale in channel 3 of
the 3rd *1 adapter.
M3
Y003 Detects over-scale in channel 4 of
the 3rd *1 adapter.
M4
Y004 EEPROM error in 3rd *1 adapter
M5
Y005 Averaging time setting error in
3rd *1 adapter
M6
Y006 Hardware error in 3rd *1 4AD-ADP
M7
Y007 Communication data error in 3rd *1
4AD-ADP
D8268.2
Y002 Detects over-scale in channel 3 of
the 1st adapter.
D8268.3
Y003 Detects over-scale in channel 4 of
the 1st adapter.
D8268.4
Y004 EEPROM error in 1st adapter
D8268.5
Y005 Averaging time setting error in
1st adapter
D8268.6
Y006 Hardware error in 1st 4AD-ADP
D8268.7
Y007 Communication data error in 1st
4AD-ADP
C-22
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 4 Programming
FX3U-4AD-ADP (4-channel analog Input) 4.7 Model Code
A
4.7 Model Code
Common Items
Initial value: K1
Numeric data type: Decimal (K)
When the 4AD-ADP is connected, model code "1" is stored in the corresponding special data register.
The following table shows the special data registers that store the model code: B
FX3UC-4AD
FX3U-4AD
• FX3U, FX3UC Series PLC
Special data register
Description
1st 2nd 3rd 4th
D8269 D8279 D8289 D8299 Model code
C
FX3U-4AD-ADP
• FX3G Series PLC
Special data register
Description
1st 2nd
D8289 D8299 Model code D
Use the special data registers above to check whether a 4AD-ADP is connected or not.
FX3G-2AD-BD
1. Program Example (For FX3U, FX3UC Series PLC)
FNC224
LD =
D8269 K1 Y007 Checks the model code of the 1st
analog special adapter
E
FX3U-4DA
F
FX3U-4DA-ADP
G
FX3G-1DA-BD
H
FX3U-3A-ADP
I
FX3U-4AD-PT
-ADP
J
FX3U-4AD-PTW
-ADP
C-23
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 4 Programming
FX3U-4AD-ADP (4-channel analog Input) 4.8 Basic Program Example
M8002
RST M6 Error status: b6 = OFF
Initial
pulse
RST M7 Error status: b7 = OFF
M8000
FNC 12 Sets the averaging time to "5"
K5 D8284 for channel-1 data.
MOV
Even if the input data is not stored into D100 or D101, the data registers D8280 or D8281 can be directly used
in the timer/counter setting value or in a PID instruction.
*1. "1st" for the FX3G PLC.
C-24
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 4 Programming
FX3U-4AD-ADP (4-channel analog Input) 4.8 Basic Program Example
A
• For FX3U, FX3UC Series PLC
Common Items
The following program will set channel 1 of the 1st adapter to voltage input mode and channel 2 to current
input mode, and will store the converted A/D value of channel-1 data into D100 and that of channel-2 data
into D101.
M8001 Sets the input mode of channel
M8260 1 to the voltage input mode
(0 V to 10 V).
B
FX3UC-4AD
FX3U-4AD
M8000 Sets the input mode of channel
M8261 2 to the current input mode
(4 mA to 20 mA).
M8002
RST D8268.6 Error status: b6 = OFF
C
RST D8268.7 Error status: b7 = OFF
FX3U-4AD-ADP
M8000
FNC 12 Sets the averaging time to "5"
K5 D8264 for channel-1 data.
MOV
FX3G-2AD-BD
FNC 12 D8260 D100 Stores the A/D converted
MOV channel-1 digital data into D100.
Even if the input data is not stored into D100 or D101, the data registers D8260 or D8261 can be directly used E
in the timer/counter setting value or in a PID instruction.
FX3U-4DA
F
FX3U-4DA-ADP
G
FX3G-1DA-BD
H
FX3U-3A-ADP
I
FX3U-4AD-PT
-ADP
J
FX3U-4AD-PTW
-ADP
C-25
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 5 Changing of Input Characteristics
FX3U-4AD-ADP (4-channel analog Input) 5.1 Example: Changing of Voltage Input Characteristics
1. Input characteristics
Voltage input characteristics Digital output value to be changed
(product specifications) Y-axis
Digital output
4000 10000
Digital output to
be calculated
(D110)
2000
400
0 X-axis
1V 5V 10V 0 400(1V) 2000(5V)
Analog input
Digital value actually obtained
by A/D conversion
C-26
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 5 Changing of Input Characteristics
FX3U-4AD-ADP (4-channel analog Input) 5.1 Example: Changing of Voltage Input Characteristics
A
2. Example of program 1 (For FX3U, FX3UC Series PLC)
Common Items
• For example, create the following program to change the digital input data of the 1st analog special
adapter:
M8001
M8260 Sets the input mode of channel 1 to the voltage input mode
M8002
(0 V to 10 V)
B
FX3UC-4AD
FX3U-4AD
RST D8268.6 Error status: b6 = OFF
M8000
FNC 12 K1 D8264 Sets the averaging time to "1" for the channel-1 data C
MOV
FX3U-4AD-ADP
M8002 FNC 12 K2 D50 Program for setting scaling instruction data table
MOV
Item Description Value Device
FNC 12 K400 D51 Number of points Sets the number of points 2 D50
MOV X-
Start coordinate
A/D converted digital value
start point data
400 D51 D
FNC 12 K0 D52 point
FX3G-2AD-BD
Y- Digital output value of changed
MOV coordinate X-axis value start point 0 D52
FX3U-4DA
M8000 FNC 259
D8260 D50 D100 The scaling instruction operation results will be stored in D100.
SCL
FX3U-4DA-ADP
G
FX3G-1DA-BD
H
FX3U-3A-ADP
I
FX3U-4AD-PT
-ADP
J
FX3U-4AD-PTW
-ADP
C-27
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 5 Changing of Input Characteristics
FX3U-4AD-ADP (4-channel analog Input) 5.1 Example: Changing of Voltage Input Characteristics
C-28
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 6 Troubleshooting
FX3U-4AD-ADP (4-channel analog Input) 6.1 PLC Version Number Check
Common Items
6. Troubleshooting
This chapter describes troubleshooting methods and error statuses. B
If the A/D conversion data is not input, or if the proper digital value is not input, check the following items:
FX3UC-4AD
FX3U-4AD
• PLC version number
• Wiring
• Special devices
• Programs C
• Error status
FX3U-4AD-ADP
6.1 PLC Version Number Check
• Any versions (from Ver.2.20 (initial version) to the latest version) of the FX3U Series are compatible. D
• Check the version number of the FX3UC Series PLC. The version number should be 1.20 or later.
FX3G-2AD-BD
• Any versions (from Ver.1.00 (initial version) to the latest version) of the FX3G Series are compatible.
→ For a detailed description of the version number check method, refer to Section 1.3.
FX3U-4DA
Check the following items for wiring:
1. Power
The 4AD-ADP needs driving power. Verify that the power supply line is properly connected. Also check that
the POWER indicator lamp of the 4AD-ADP is on.
F
2. Analog input line
FX3U-4DA-ADP
Use 2-core twisted shielded pair cable for the analog input line. In addition, be sure to separate the analog
input line from other power lines or inductive lines.
FX3G-1DA-BD
into correct digital data.
→ For a detailed description of wiring, refer to Chapter 3.
H
FX3U-3A-ADP
I
FX3U-4AD-PT
-ADP
J
FX3U-4AD-PTW
-ADP
C-29
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 6 Troubleshooting
FX3U-4AD-ADP (4-channel analog Input) 6.3 Special Device Check
2. Input data
Verify that the special device of the selected channel is correctly selected. This special device should be
selected depending on the connecting position and the channel.
3. Averaging time
Check that the set averaging time is within the specified range. The averaging time should be set in the range
from 1 to 4095. If the set averaging time is outside the specified range, an error occurs.
4. Error status
Check that no error is detected in the 4AD-ADP.
If an error is detected, check the details of the error, and then check the wiring and programs.
→ For a detailed description of special devices, refer to Chapter 4.
C-30
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 6 Troubleshooting
FX3U-4AD-ADP (4-channel analog Input) 6.5 Error Status Check
A
6.5 Error Status Check
Common Items
If an error occurs in the 4AD-ADP, the corresponding bit will turn on.
FX3UC-4AD
FX3U-4AD
4AD-ADP hardware error
b1 Channel-2 over-scale detection b6
(Power supply error included)
b2 Channel-3 over-scale detection b7 4AD-ADP communication data error
b3 Channel-4 over-scale detection b8 to b15 Unused
b4 EEPROM error - - C
To solve the problem, refer to the troubleshooting method described below:
FX3U-4AD-ADP
1. Over-scale detection (b0 to b3)
1) Description of error
The input analog value (voltage or current value) is outside the specified range.
The digital value is out of the range specified for the voltage input mode (0 to 4080) or outside the range D
specified for the current input mode (0 to 1640).
FX3G-2AD-BD
2) Remedy
Check that the input analog value is within the specified range. Also check the wiring.
FX3U-4DA
properly or has been destroyed.
2) Remedy
Please contact the nearest Mitsubishi Electric distributor office.
FX3U-4DA-ADP
The averaging time set for one of the channels (channels 1 to 4) is outside the specified range: 1 to 4095.
2) Remedy
Check that the averaging time is set correctly for each channel.
FX3G-1DA-BD
The 4AD-ADP is not operating properly.
2) Remedy
Check that the 24V DC power is properly supplied to the 4AD-ADP. Also check that the 4AD-ADP is
correctly connected to the PLC.
If the problem cannot be solved even after the above check, please contact the nearest Mitsubishi
Electric distributor office.
H
FX3U-3A-ADP
If the problem cannot be solved even after the above check, please contact the nearest Mitsubishi
Electric distributor office.
-ADP
J
FX3U-4AD-PTW
-ADP
C-31
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 6 Troubleshooting
FX3U-4AD-ADP (4-channel analog Input) 6.5 Error Status Check
MEMO
C-32
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition
FX3G-2AD-BD (2-channel analog Input)
Common Items
B
FX3UC-4AD
FX3U-4AD
FX3G/FX3U/FX3UC Series Programmable
Controllers C
FX3U-4AD-ADP
User's Manual [Analog Control Edition]
FX3G-2AD-BD (2-channel analog Input)
D
FX3G-2AD-BD
E
FX3U-4DA
F
FX3U-4DA-ADP
G
FX3G-1DA-BD
H
FX3U-3A-ADP
Foreword
This manual describes the specifications, wiring, and operation methods for the FX3G-2AD-BD analog input
expansion board (2-channel analog input) and should be read and understood before attempting to install or
use the unit. I
FX3U-4AD-PT
Store this manual in a safe place so that you can take it out and read it whenever necessary. Always forward
it to the end user.
-ADP
This manual confers no industrial property rights or any rights of any other kind, nor does it confer any patent
licenses. Mitsubishi Electric Corporation cannot be held responsible for any problems involving industrial property
rights which may occur as a result of using the contents noted in this manual. J
FX3U-4AD-PTW
D-1
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition
FX3G-2AD-BD (2-channel analog Input)
D-2
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 1 Outline
FX3G-2AD-BD (2-channel analog Input) 1.1 Outline of Functions
Common Items
1. Outline
This chapter outlines the FX3G-2AD-BD (referred to as the 2AD-BD). B
FX3UC-4AD
FX3U-4AD
1.1 Outline of Functions
The FX3G-2AD-BD is an analog expansion board. Connect the FX3G-2AD-BD to the FX3G Series PLC to read
2 channels of voltage/current data.
C
FX3U-4AD-ADP
1) Up to 2*1 2AD-BD units can be connected to the FX3G Series PLC.
(including the other analog expansion board, analog special adapters).
2) Either "voltage input" or "current input" can be specified for each channel.
3) A/D conversion data of each channel will be automatically written to the special data register of the FX3G
Series PLC. D
FX3G-2AD-BD
System Point and section to be
referred to
2*1 maximum
FX3U-4DA
board board
To check the connectable
…… PLC model number, refer
to Section 1.3.
FX3U-4DA-ADP
Connected to the option connector 2
Analog data
…… For a detailed
description of wiring,
refer to Chapter 3.
G
Flowmeter, pressure sensor, etc.
•Switching of input mode 2nd board M/D8270 to M/D8279 For a detailed description
•Setting of averaging of a basic program, refer to
time Section 4.8.
Refer to the system configuration shown in the User's Manual - Hardware Edition to check the number of connectable units
and to configure the entire system.
I
FX3U-4AD-PT
*1.Only 1 analog board can be connected to the FX3G Series PLC(14-point and 24-point type).
-ADP
J
FX3U-4AD-PTW
-ADP
D-3
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 1 Outline
FX3G-2AD-BD (2-channel analog Input) 1.2 Setup Procedure Before Starting Operation
FX3G-2AD-BD
Refer to Chapter 1.
Wiring Wiring:
• Selection of sensor cable
• Analog input line
Refer to Chapter 4.
Programming Programming:
• Details of special devices
• Examples of basic programs
Refer to Chapter 5.
D-4
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 1 Outline
FX3G-2AD-BD (2-channel analog Input) 1.3 Connectable PLCs and Version Number
A
1.3 Connectable PLCs and Version Number
Common Items
The 2AD-BD is compatible with the following PLC.
FX3UC-4AD
FX3U-4AD
1. Version check
Special data register D8001 contains information for determining the PLC version number.
→ For a detailed description of the version check, refer to A. Common Items Subsection 5.1.2.
C
2. How to look at the manufacturer's serial number
FX3U-4AD-ADP
The year and month of production of the product can be checked on the nameplate, and on the front of the
product.
→ For a detailed description of the How to look at the manufacturer's serial number,
refer to A. Common Items Subsection 5.1.1.
D
1.4 Compatible Programming Tool Version Number
FX3G-2AD-BD
Use the programming tool with following version numbers to create programs for the 2AD-BD:
1. GX Developer
Software Version number Remarks E
FX3U-4DA
GX Developer
• SW D5C-GPPW-J Ver. 8.72A or later When selecting a model, select FX3G.
• SW D5C-GPPW-E
If a programming tool with the wrong version number is used, programming will not be possible. F
FX3U-4DA-ADP
2. FX-30P
Model name Version number Remarks
FX-30P Ver.1.00 or later
FX3G-1DA-BD
H
FX3U-3A-ADP
I
FX3U-4AD-PT
-ADP
J
FX3U-4AD-PTW
-ADP
D-5
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 2 Specifications
FX3G-2AD-BD (2-channel analog Input) 2.1 Generic Specifications
2. Specifications
This chapter describes the general and performance specifications for the 2AD-BD.
Item Specifications
Ambient 0 to 55°C (32 to 131°F) when operating
temperature -25 to 75°C (-13 to 167°F) when stored
Relative
5 to 95%RH (no condensation) when operating
humidity
Frequency Acceleration Half amplitude
(Hz) (m/s2) (mm)
Tests 10 times in each
Vibration 10 - 57 - 0.035 direction (X-, Y-, and Z-
DIN Rail Mounting
resistance*1 57 - 150 4.9 - axis directions) (Total:
80 min, each)
10 to 57 − 0.075
Direct Mounting
57 to 150 9.8 −
*1
Shock
147 m/s2 Acceleration, Action time: 11ms, 3 times by half-sine pulse in each direction X, Y, and Z
resistance
Noise Using noise simulator of:
resistance Noise voltage: 1,000Vp-p / Noise width: 1μs / Rise: 1ns / Cycle: 30 to 100Hz
Class D grounding (grounding resistance: 100 Ω or less)
Grounding
<Common grounding with a heavy electrical system is not allowed.>*2
Working
Free from corrosive or flammable gas and excessive conductive dusts
environment
Working
altitude < 2000m*3
D-6
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 2 Specifications
FX3G-2AD-BD (2-channel analog Input) 2.2 Performance Specifications
A
2.2 Performance Specifications
Common Items
Specifications
Item
Voltage input Current input B
FX3UC-4AD
FX3U-4AD
Analog input 0V to 10V DC 4mA to 20mA DC
range (Input resistance: 198.7 kΩ) (Input resistance: 250 Ω)
Absolute input
-0.5V, +15V -2mA, +30mA
maximum
Digital output 12 bits, binary 11 bits, binary
Resolution 2.5mV (10V/4000) 8μA (16mA/2000)
C
FX3U-4AD-ADP
• ±0.5% (±50mV) for 10V full scale • ±0.5% (±80μA) for 16mA full scale
(when ambient temperature is 25°C ± 5°C) (when ambient temperature is 25°C ± 5°C)
Total accuracy
• ±1.0% (±100mV) for 10V full scale • ±1.0% (±160μA) for 16mA full scale
(when ambient temperature is 0°C to 55°C) (when ambient temperature is 0°C to 55°C)
A/D conversion
time
180 μs (The data will be updated at every scan time.)
→ For a detailed description of data update, refer to Section 2.4.
D
FX3G-2AD-BD
4080 2040
4000 2000
E
Input Digital output
FX3U-4DA
Digital output
characteristics
0
Analog input
10V 10.2V 0 4mA
Analog input
20mA 20.32mA
F
FX3U-4DA-ADP
• The analog input area is not insulated from the PLC.
Insulation method
• Channels are not insulated from each other.
Number of I/O
0 point (This number is not related to the maximum number of input/output points of the PLC.)
points occupied
G
FX3G-1DA-BD
H
FX3U-3A-ADP
I
FX3U-4AD-PT
-ADP
J
FX3U-4AD-PTW
-ADP
D-7
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 2 Specifications
FX3G-2AD-BD (2-channel analog Input) 2.3 A/D Conversion Time
Sequence Program
END instruction
A/D A/D
conversion conversion
180μs 180μs
/2ch /2ch
FX3G-2AD-BD FX3G-2AD-BD
1st 2nd
D-8
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 3 Wiring
FX3G-2AD-BD (2-channel analog Input)
Common Items
3. Wiring
This chapter describes the 2AD-BD wiring. B
Observe the following caution to wire the 2AD-BD.
FX3UC-4AD
FX3U-4AD
WIRING PRECAUTIONS
• Make sure to cut off all phases of the power supply externally before attempting wiring work.
Failure to do so may cause electric shock or damages to the product. C
FX3U-4AD-ADP
WIRING PRECAUTIONS
• Connect the DC power supply wiring to the dedicated terminals described in this manual.
If an AC power supply is connected to a DC input/output terminal or DC power supply terminal, the PLC will be
burnt out.
D
FX3G-2AD-BD
• Do not wire vacant terminals externally.
Doing so may damage the product.
• Perform class D grounding (grounding resistance: 100Ω or less) to the grounding terminal on the main unit.
Do not use common grounding with heavy electrical systems.
• When drilling screw holes or wiring, make sure cutting or wire debris does not enter the ventilation slits.
Failure to do so may cause fire, equipment failures or malfunctions. E
• Make sure to observe the following precautions in order to prevent malfunctions under the influence of noise:
FX3U-4DA
- Do not bundle the power line or twisted shielded cable together with or lay it close to the main circuit, high-
voltage line, or load line.
Otherwise, noise disturbance and/or surge induction are likely to take place. As a guideline, lay the control line
at least 100mm (3.94") or more away from the main circuit, high-voltage line, or load line.
- Ground the shield of the analog input/output cable at one point on the signal receiving side.
However, do not use common grounding with heavy electrical systems. F
• Make sure to properly wire to the European terminal board in accordance with the following precautions.
FX3U-4DA-ADP
Failure to do so may cause electric shock, a short-circuit, wire breakage, or damage to the product.
- The disposal size of the cable end should be 9 mm (0.35").
- Tightening torque should be between 0.22 to 0.25 N•m.
- Twist the end of strand wire and make sure there are no loose wires.
- Do not solder-plate the electric wire ends.
- Do not connect more than the specified number of wires or electric wires of unspecified size. G
- Affix the electric wires so that neither the terminal block nor the connected parts are directly stressed.
FX3G-1DA-BD
H
FX3U-3A-ADP
I
FX3U-4AD-PT
-ADP
J
FX3U-4AD-PTW
-ADP
D-9
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 3 Wiring
FX3G-2AD-BD (2-channel analog Input) 3.1 Terminal Layout
D-10
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 3 Wiring
FX3G-2AD-BD (2-channel analog Input) 3.2 Applicable Cables and Terminal Tightening Torque
A
3.2 Applicable Cables and Terminal Tightening Torque
Common Items
Use the following cables to connect with the counterpart equipment. Terminate the cable ends as shown
below.
1. Cables B
FX3UC-4AD
FX3U-4AD
Applicable cable and tightening torque
Wire size (stranded/ Tightening
Termination
single-wire) torque
0.3mm2 to 0.5mm2 • To connect a stranded cable, peel the cover off the cable
Single-wire
(AWG22 to 20) and then twist the core before connection.
• To connect a single-wire cable, just strip the cover off the
C
2-wire 2
0.3mm (AWG22)
FX3U-4AD-ADP
cable before connection.
0.22N•m to • Rod terminal with insulation sleeve
Rod terminal 0.3mm2 to 0.5mm2 0.25N•m (recommended terminal)
with (AWG22 to 20) AI 0.5-8WH : Manufactured by Phoenix Contact
insulation (Refer to the rod terminal
• Caulking tool
sleeve external view shown in the
following figure.)
CRIMPFOX ZA 3 : Manufactured by Phoenix Contact D
(or CRIMPFOX UD 6 : Manufactured by Phoenix Contact)
FX3G-2AD-BD
2. Termination of cable end
To terminate the cable, treat the stranded/single-wire directly or use a rod terminal with insulation sleeve.
• To directly terminate the end of a stranded/single-wire cable:
- Twist the end of the stranded cable so that the "barbed wires"
Termination of cable end
E
cannot protrude.
FX3U-4DA
- Do not solder-plate the end of the cable.
9mm
(0.35")
• To terminate cable end using a rod terminal with insulation sleeve: Insulation sleeve Contact area
If the cable cover is too thick, it may be difficult to insert the cable into
the insulation sleeve. For this reason, select an appropriate cable while
(Crimp area) F
FX3U-4DA-ADP
referring to the external view. 8mm (0.31")
Manufacturer Model Caulking tool 2.6mm 14mm
(0.1")
CRIMPFOX ZA 3 (0.55")
Phoenix Contact AI 0.5-8WH
(or CRIMPFOX UD 6)
3. Tool
G
FX3G-1DA-BD
• To tighten terminals, use a small-sized screwdriver whose head is straight and is not widened as shown in
the figure to the right.
Note:
If the diameter of screwdriver grip is too small, tightening torque will not
be able to be achieved. Use the following recommended screwdriver or
The head
should be
H
an appropriate replacement (grip diameter: approximately 25mm).
FX3U-3A-ADP
straight.
Manufacturer Model
Phoenix Contact SZS 0.4×2.5 0.4mm 2.5mm
(0.01") (0.09")
I
FX3U-4AD-PT
-ADP
J
FX3U-4AD-PTW
-ADP
D-11
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 3 Wiring
FX3G-2AD-BD (2-channel analog Input) 3.3 Analog Input Line
*1 110kΩ ch
V +
250Ω
I + 88.7kΩ
Class-D
grounding
VI-
*3
*1. Use the 2-core shielded twisted pair cable for the analog input lines, and separate the analog input
lines from other power lines or inductive lines.
*2. If "current input" is selected, be sure to short the line between the V + terminal and the I + terminal.
( : Channel number).
*3. Make sure to short-circuit the "V +" and "VI-" terminals when ch is not used.
3.4 Grounding
Grounding should be performed as stated below.
• The grounding resistance should be 100Ω or less.
• Independent grounding should be performed for best results.
When independent grounding is not performed, perform "shared grounding" as shown in the following
figure.
→ For details, refer to the User’s Manual - Hardware Edition of the PLC Series.
D-12
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 4 Programming
FX3G-2AD-BD (2-channel analog Input) 4.1 Loading of A/D Conversion Data
Common Items
4. Programming
This chapter describes how to create programs that can read analog data using the 2AD-BD. B
FX3UC-4AD
FX3U-4AD
4.1 Loading of A/D Conversion Data
1) The input analog data will be converted into digital data and then stored in the special devices of the FX3G
Series PLC.
C
2) If the data is stored in the special devices, the averaging time can be set, and the input mode can be
FX3U-4AD-ADP
specified.
3) Special auxiliary relays (10 points) and special data registers (10 points) are assigned respectively to the
analog expansion board connected to the option connector 1 and the analog expansion board connected
to the option connector 2 in this order.
→ For a detailed description of special device assignment, refer to Section 4.2. D
• FX3G Series PLC
FX3G-2AD-BD
FX3G Series PLC
Sequence Program
FX3U-4DA
Special auxiliary relays: Special auxiliary relays:
M8260 to M8269 M8270 to M8279
Special data register: Special data register:
D8260 to D8269 D8270 to D8279
A/D A/D
F
FX3U-4DA-ADP
FX3G-2AD-BD FX3G-2AD-BD
1st 2nd*1
The analog expansion board connected to the option connector 1 is regarded as the 1st unit, and the
analog expansion board connected to the option connector 2 is regarded as the 2nd unit.
*1. The second analog expansion board is not available in the FX3G Series PLC(14-point and 24-point G
FX3G-1DA-BD
type).
H
FX3U-3A-ADP
I
FX3U-4AD-PT
-ADP
J
FX3U-4AD-PTW
-ADP
D-13
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 4 Programming
FX3G-2AD-BD (2-channel analog Input) 4.2 List of Special Devices
1. Program Example
To switch the channel input mode, create a sequence program as follows:
1) To switch the input mode of channel 2) To switch the input mode of channel 2
1 of the 1st analog board to the voltage of the 1st analog board to the current
input mode: input mode:
M8001 M8000
M8260 M8261
Normally OFF Normally ON
D-14
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 4 Programming
FX3G-2AD-BD (2-channel analog Input) 4.4 Input Data
A
4.4 Input Data
Common Items
Numeric data type: Decimal (K)
The data converted by the 2AD-BD will be stored in the special data registers.
The special data registers that store the input data are shown in the following table:
B
FX3UC-4AD
FX3U-4AD
Special data register
Description
1st board 2nd board
D8260 D8270 Stores the channel-1 input data
D8261 D8271 Stores the channel-2 input data
C
The converted A/D immediate data or averaged data (data average conforming to the specified averaging
FX3U-4AD-ADP
time) will be stored in the above data registers as the input data.
→ For a detailed description of the averaging time, refer to Section 4.5.
FX3G-2AD-BD
programming tool.
2. Program Example
M8000
FNC 12 D8260 D100 Stores the channel-1 input data
of the 1st analog board in the D100.
E
MOV
FX3U-4DA
Normally
ON
Even if the input data is not stored in D100 or D101, data registers D8260 or D8261 can be directly used in
the timer/counter set value or in a PID instruction. F
FX3U-4DA-ADP
G
FX3G-1DA-BD
H
FX3U-3A-ADP
I
FX3U-4AD-PT
-ADP
J
FX3U-4AD-PTW
-ADP
D-15
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 4 Programming
FX3G-2AD-BD (2-channel analog Input) 4.5 Averaging Time
2. Program Example
M8000 Sets the averaging time for
FNC 12 K1 D8264 channel-1 of the 1st analog
MOV board to 1.
Normally
ON
Sets the averaging time for
FNC 12 K5 D8265 channel-2 of the 1st analog
MOV board to 5.
D-16
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 4 Programming
FX3G-2AD-BD (2-channel analog Input) 4.6 Error Status
A
4.6 Error Status
Common Items
If an error is detected in the 2AD-BD, the error status data will be stored in the corresponding special data
register.
The following table shows the special data registers that store the error status data:
B
Special data register
FX3UC-4AD
FX3U-4AD
Description
1st board 2nd board
D8268 D8278 Stores the error status data.
Check the ON/OFF status of each bit of the error status data register to check the description of the error.
Errors are assigned to the bits as shown in the following table. Create a program to detect errors. C
→ For a detailed description of the error status, refer to Section 6.5.
FX3U-4AD-ADP
Bit Description Bit Description
b0 Channel-1 over-scale detection b5 Averaging time setting error
b1 Channel-2 over-scale detection b6 2AD-BD hardware error
b2 Unused b7 2AD-BD communication data error
D
FX3G-2AD-BD
b3 Unused b8 to b15 Unused
b4 EEPROM error - -
FX3U-4DA
For this reason, be sure to create the following program:
M8000
FNC 12 D8268 K4M0
MOV
Normally ON
M8002
F
Error status of 1st analog board
FX3U-4DA-ADP
RST M6 b6 = OFF (hardware error)
Initial pulse
FNC 12
MOV
K4M0 D8268 G
FX3G-1DA-BD
H
FX3U-3A-ADP
I
FX3U-4AD-PT
-ADP
J
FX3U-4AD-PTW
-ADP
D-17
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 4 Programming
FX3G-2AD-BD (2-channel analog Input) 4.6 Error Status
2. Program Example
M8000
MOV D8268 K4M0
Normally
ON
M0
Y000 Detects over-scale in channel 1 of
the 1st board.
M1
Y001 Detects over-scale in channel 2 of
the 1st board.
M4
Y004 EEPROM error in 1st board
M5
Y005 Averaging time setting error in
1st board
M6
Y006 Hardware error in 1st 2AD-BD
M7
Y007 Communication data error in 1st
2AD-BD
D-18
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 4 Programming
FX3G-2AD-BD (2-channel analog Input) 4.7 Model Code
A
4.7 Model Code
Common Items
Initial value: K3
Numeric data type: Decimal (K)
When the 2AD-BD is connected, model code "3" is stored in the corresponding special data register.
The following table shows the special data registers that store the model code: B
FX3UC-4AD
FX3U-4AD
Special data register
Description
1st board 2nd board
D8269 D8279 Model code
Use the special data registers above to check whether a 2AD-BD is connected or not.
C
FX3U-4AD-ADP
1. Program Example
FX3G-2AD-BD
4.8 Basic Program Example
Create the following basic program example to read out analog conversion (A/D conversion) data.
The following program will set the 1st board to voltage input mode and channel 2 to current input mode, and
will store the converted A/D value of channel-1 data into D100 and that of channel-2 data into D101.
E
FX3U-4DA
M8001 Sets the input mode of the 1st board
M8260 to the voltage input mode
Normally (0 V to 10 V).
OFF
M8000 Sets the input mode of the 2nd board
F
FX3U-4DA-ADP
M8261 to the current input mode
Normally (4 mA to 20 mA).
ON
M8000
FNC 12 D8268 K4M0
M8002
MOV
G
FX3G-1DA-BD
RST M6 Error status: b6 = OFF
Initial
pulse
RST M7 Error status: b7 = OFF
FNC 12
MOV
K4M0 D8268 H
FX3U-3A-ADP
M8000
FNC 12 Sets the averaging time to "5"
K5 D8264 for channel-1 data.
MOV
Even if the input data is not stored into D100 or D101, the data registers D8260 or D8261 can be directly used
in the timer/counter setting value or in a PID instruction.
J
FX3U-4AD-PTW
-ADP
D-19
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 5 Changing of Input Characteristics
FX3G-2AD-BD (2-channel analog Input) 5.1 Example: Changing of Voltage Input Characteristics
1. Input characteristics
Voltage input characteristics Digital output value to be changed
(product specifications) Y-axis
Digital output
4000 10000
Digital output to
be calculated
(D110)
2000
400
0 X-axis
1V 5V 10V 0 400(1V) 2000(5V)
Analog input
Digital value actually obtained
by A/D conversion
2. Example of program
For example, create the following program to change the digital input data of the 1st analog board:
M8001
M8260 Sets the input mode of channel 1 to the
Normally OFF voltage input mode (0V to 10V).
M8000 FNC 12 D8268 K4M0
Normally ON MOV
M8002
RST M6 Error status : b6=OFF
Initial pulse
FNC 230 FNC 237 D110 K2000 Check to make sure the digital
D110 K400 M10
LD>= AND<= value (D110) is in range.
M10 FNC 21
D110 K400 D111
SUB
D-20
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 6 Troubleshooting
FX3G-2AD-BD (2-channel analog Input) 6.1 PLC Version Number Check
Common Items
6. Troubleshooting
This chapter describes troubleshooting methods and error statuses. B
If the A/D conversion data is not input, or if the proper digital value is not input, check the following items:
FX3UC-4AD
FX3U-4AD
• PLC version number
• Installation
• Wiring
• Special devices C
• Programs
FX3U-4AD-ADP
• Error status
FX3G-2AD-BD
→ For a detailed description of the version number check method, refer to Section 1.3.
FX3U-4DA
of the 2AD-BD is lit correctly.
→ For a detailed description of installing, refer to FX3G Series User’s Manual - Hardware Edition.
FX3U-4DA-ADP
1. Analog input line
Use 2-core twisted shielded pair cable for the analog input line. In addition, be sure to separate the analog
input line from other power lines or inductive lines.
FX3G-1DA-BD
To use the current input mode for a channel, be sure to shortcircuit the line between the V + terminal and the
I +terminal ( : channel number) of the channel. If the line is not shortcircuited, data will not be converted
into correct digital data.
→ For a detailed description of wiring, refer to Chapter 3.
Check whether the special devices for the 2AD-BD are being used correctly:
2. Input data
Verify that the special device of the selected channel is correctly selected. This special device should be
-ADP
3. Averaging time J
FX3U-4AD-PTW
Check that the set averaging time is within the specified range. The averaging time should be set in the range
from 1 to 4095. If the set averaging time is outside the specified range, an error occurs.
-ADP
D-21
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 6 Troubleshooting
FX3G-2AD-BD (2-channel analog Input) 6.5 Program Check
4. Error status
Check that no error is detected in the 2AD-BD.
If an error is detected, check the details of the error, and then check the wiring and programs.
→ For a detailed description of special devices, refer to Chapter 4.
D-22
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 6 Troubleshooting
FX3G-2AD-BD (2-channel analog Input) 6.6 Error Status Check
A
5. 2AD-BD communication data error (b7)
Common Items
1) Description of error
A communication error is detected between the 2AD-BD and the PLC.
2) Remedy
Check that the 2AD-BD is correctly connected to the PLC.
If the problem cannot be solved even after the above check, please contact the nearest Mitsubishi B
Electric distributor office.
FX3UC-4AD
FX3U-4AD
C
FX3U-4AD-ADP
D
FX3G-2AD-BD
E
FX3U-4DA
F
FX3U-4DA-ADP
G
FX3G-1DA-BD
H
FX3U-3A-ADP
I
FX3U-4AD-PT
-ADP
J
FX3U-4AD-PTW
-ADP
D-23
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 6 Troubleshooting
FX3G-2AD-BD (2-channel analog Input) 6.6 Error Status Check
MEMO
D-24
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition
FX3U-4DA (4-channel Analog Output)
Common Items
B
FX3UC-4AD
FX3U-4AD
FX3G/FX3U/FX3UC Series Programmable
Controllers C
FX3U-4AD-ADP
User's Manual [Analog Control Edition]
FX3U-4DA (4-channel Analog Output)
D
FX3G-2AD-BD
E
FX3U-4DA
F
FX3U-4DA-ADP
G
FX3G-1DA-BD
H
FX3U-3A-ADP
Foreword
This manual describes the specifications, wiring, and operation methods for the FX3U-4DA special extension
block (4-channel analog output) and should be read and understood before attempting to install or use the
unit.
I
FX3U-4AD-PT
Store this manual in a safe place so that you can take it out and read it whenever necessary. Always forward
it to the end user.
-ADP
This manual confers no industrial property rights or any rights of any other kind, nor does it confer any patent
licenses. Mitsubishi Electric Corporation cannot be held responsible for any problems involving industrial property
rights which may occur as a result of using the contents noted in this manual. J
FX3U-4AD-PTW
E-1
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition
FX3U-4DA (4-channel Analog Output)
E-2
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 1 Outline
FX3U-4DA (4-channel Analog Output) 1.1 Outline of Functions
Common Items
1. Outline
This chapter outlines the FX3U-4DA. B
FX3UC-4AD
FX3U-4AD
1.1 Outline of Functions
FX3U-4DA is an analog special function block which is connectable to the FX3G, FX3U or FX3UC Series PLC to
convert 4-channel digital signal from the PLC to analog signal (voltage/current).
C
1) Up to 8*1 units can be connected to the FX3G/FX3U/FX3UC Series PLC.
FX3U-4AD-ADP
(including the other special function blocks).
2) Each channel has either Voltage Output or Current Output specification.
3) The block converts the digital values stored in the FX3U-4DA buffer memory (BFM) in FX3U-4DA to
analog signals (voltage/current).
4) A predetermined output pattern is set as data table, and analog signal can be output according to the
D
FX3G-2AD-BD
data table.
FX3U-4DA
(including other types of special function blocks) •••••• Number of connectable units
•••••••••
Section 1.3.
F
FX3U-4DA-ADP
FX3U -4DA FX3U -4DA
24V 24V
D/A D/A
FX3G-1DA-BD
For a detailed description of
•••••• analog data output programs,
refer to Chapter 4, 7, and 8.
For a detailed description of
H
•••••• the buffer memory, refer to
Program Buffer memory
Transmission direction Section 5.3, and Section 5.4.
• FROM(FNC 78) BFM#0
• TO(FNC 79)
FX3U-3A-ADP
••••••
or to directly specify the BFM,
• BFM direct BFM#3098 refer to Section 5.2.
specification(U\G)*2
Refer to the system configuration shown in the FX3G/FX3U/FX3UC User's Manual - Hardware Edition to check the
number of connectable units and to configure the entire system.
I
FX3U-4AD-PT
J
FX3U-4AD-PTW
-ADP
E-3
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 1 Outline
FX3U-4DA (4-channel Analog Output) 1.2 Setup Procedure Before Starting Operation
FX3U-4DA
Refer to Chapter 1.
Wiring Wiring:
• Power supply line
• Analog output line
Refer to Chapter 4.
Refer to Chapter 8.
E-4
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 1 Outline
FX3U-4DA (4-channel Analog Output) 1.3 Connectable PLCs and Version Numbers
A
1.3 Connectable PLCs and Version Numbers
Common Items
FX3U-4DA is compatible with the following PLC.
FX3UC-4AD
FX3U-4AD
FX3UC Series PLC Ver. 1.30 or later August 2004 and later
FX3G Series PLC Ver. 1.00 or later from the first product
1. Version check
Special data register D8001 contains information for determining the PLC version.
C
FX3U-4AD-ADP
→ For a detailed description of the version check, refer to A. Common Items Subsection 5.1.2.
FX3G-2AD-BD
1.4 Compatible Programming Tool Version Number
Use a programming tool with the following version number to create FX3U-4DA programs for the FX3G/FX3U/
FX3UC Series PLC. E
FX3U-4DA
1. GX Developer
Software Version number Remarks
GX Developer Ver. SW8 P or later
When selecting the model, select FX3U(C)*1.
• SW D5C-GPPW-J
• SW D5C-GPPW-E
(Ver. 8.13P)
F
Ver. 8.72A or later When selecting the model, select FX3G.
FX3U-4DA-ADP
If a programming tool with the wrong version number is used, some instructions and devices cannot be used.
*1. For Ver. 8.13P to 8.24A of GX Developer, select FX3UC for the PLC type.
2. FX-30P G
FX3G-1DA-BD
Model name Version number Remarks
FX-30P Ver.1.00 or later
H
FX3U-3A-ADP
I
FX3U-4AD-PT
-ADP
J
FX3U-4AD-PTW
-ADP
E-5
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 2 Specifications
FX3U-4DA (4-channel Analog Output) 2.1 Generic Specifications
2. Specifications
This chapter describes the general, power supply, and performance specifications for the FX3U-4DA.
Item Specifications
Ambient 0 to 55°C (32 to 131°F) when operating
temperature -25 to 75°C (-13 to 167°F) when stored
Relative
5 to 95%RH (no condensation) when operating
humidity
Frequency Acceleration Half amplitude
(Hz) (m/s2) (mm)
Tests 10 times in each
Vibration 10 - 57 - 0.035 direction (X-, Y-, and Z-
DIN Rail Mounting
resistance*1 57 - 150 4.9 - axis directions) (Total:
80 min, each)
10 - 57 - 0.075
Direct Mounting*2
57 - 150 9.8 -
Shock
147 m/s2 Acceleration, Action time: 11ms, 3 times by half-sine pulse in each direction X, Y, and Z
resistance*1
Noise Using noise simulator of:
resistance Noise voltage: 1,000Vp-p / Noise width: 1μs / Rise: 1ns / Cycle: 30 to 100Hz
Dielectric
withstand 500 V AC, for 1 min
voltage Between batch of all terminals and ground terminal
Insulation 5MΩ or more using 500V DC
resistance insulation resistance meter
Class D grounding (grounding resistance: 100 Ω or less)
Grounding
<Common grounding with a heavy electrical system is not allowed.>*3
Working
Free from corrosive or flammable gas and excessive conductive dusts
environment
Working
altitude < 2000m*4
E-6
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 2 Specifications
FX3U-4DA (4-channel Analog Output) 2.2 Power Supply Specifications
A
2.2 Power Supply Specifications
Common Items
Item Specifications
D/A conversion 24V DC ±10%, 160mA B
circuit drive power (It is necessary to supply 24V DC from the terminal block.)
FX3UC-4AD
FX3U-4AD
5V DC, 120mA
CPU drive power (Since the internal power is supplied from the main unit, it is not necessary to supply power
externally.)
FX3U-4AD-ADP
2.3 Performance Specifications
Item
Specifications
D
Voltage output Current output
FX3G-2AD-BD
Analog output -10V to +10V DC 0mA to 20mA DC, 4mA to 20mA DC
range (External load: 1kΩ to 1MΩ) (External load: 500Ω or less)
Offset*1 -10V to +9V*2 0mA to 17mA*3
Gain*1 -9V to +10V*2 3mA to 30mA*3
E
Digital input With sign, 16bits, binary 15bits, binary
FX3U-4DA
Resolution 0.32mV (20V / 64,000) 0.63μA (20mA / 32,000)
• Ambient temperature: 25°C±5°C • Ambient temperature: 25°C±5°C
±0.3% (±60mV) for 20V full scale ±0.3% (±60μA) for 20mA full scale
Overall accuracy
• Ambient temperature: 0°C to 55°C • Ambient temperature: 0°C to 55°C
±0.5% (±100mV) for 20V full scale ±0.5% (±100μA) for 20mA full scale F
Time required for
FX3U-4DA-ADP
1ms (The number of selected channels will not affect this value.)
D/A conversion
• The photocoupler is used to insulate the analog output area from the PLC.
Insulation method • The DC/DC converter is used to insulate the analog output area from the power supply unit.
• Channels are not insulated from each other.
Number of I/O
8 points (Taken from either the input or output points of the PLC.)
G
points occupied
FX3G-1DA-BD
*1. Adjustment of the offset or gain value will not affect the resolution. In output mode 1 or 4, however, the
offset/gain cannot be adjusted.
*2. The offset and the gain should satisfy the following condition:
1V ≤ (Gain - Offset) ≤ 10 V
H
*3. The offset and the gain should satisfy the following condition:
FX3U-3A-ADP
3 mA ≤ (Gain - Offset) ≤ 30 mA
I
FX3U-4AD-PT
-ADP
J
FX3U-4AD-PTW
-ADP
E-7
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 2 Specifications
FX3U-4DA (4-channel Analog Output) 2.4 Output Mode (Characteristics) BFM #0
10200
value value
-32000 0 -10000 0
-32640
-10200
32000 10000
-10 -10
-10.2 -10.2
Current Current
output (mA) output (mA)
20.4 20.4
20 20
Current
output (mA)
20.32
20
4
0 32000 32640
Digital value
E-8
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 3 Wiring
FX3U-4DA (4-channel Analog Output)
Common Items
3. Wiring
This chapter describes wiring of the FX3U-4DA. B
Observe the following cautions wiring the FX3U-4DA.
FX3UC-4AD
FX3U-4AD
WIRING PRECAUTIONS
• Make sure to cut off all phases of the power supply externally before attempting wiring work.
Failure to do so may cause electric shock or damages to the product. C
FX3U-4AD-ADP
WIRING PRECAUTIONS
• Connect the DC power supply wiring to the dedicated terminals described in this manual.
If an AC power supply is connected to a DC input/output terminal or DC power supply terminal, the PLC will be
burnt out.
D
FX3G-2AD-BD
• Do not wire vacant terminals externally.
Doing so may damage the product.
• Perform class D grounding (grounding resistance: 100Ω or less) to the grounding terminal on the main unit.
Do not use common grounding with heavy electrical systems.
• When drilling screw holes or wiring, make sure cutting or wire debris does not enter the ventilation slits.
Failure to do so may cause fire, equipment failures or malfunctions. E
• Make sure to observe the following precautions in order to prevent malfunctions under the influence of noise:
FX3U-4DA
- Do not bundle the power line or twisted shielded cable together with or lay it close to the main circuit, high-
voltage line, or load line.
Otherwise, noise disturbance and/or surge induction are likely to take place. As a guideline, lay the control line
at least 100mm (3.94") or more away from the main circuit, high-voltage line, or load line.
- Ground the shield of the analog input/output cable at one point on the signal receiving side.
However, do not use common grounding with heavy electrical systems. F
• Make sure to properly wire the terminal block in accordance with the following precautions.
FX3U-4DA-ADP
Failure to do so may cause electric shock, a short-circuit, wire breakage, or damage to the product.
- The disposal size of the cable end should follow the dimensions described in this manual.
- Tightening torque should be between 0.5 and 0.8 N•m.
FX3G-1DA-BD
H
FX3U-3A-ADP
I
FX3U-4AD-PT
-ADP
J
FX3U-4AD-PTW
-ADP
E-9
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 3 Wiring
FX3U-4DA (4-channel Analog Output) 3.1 Terminal Layout
Signal Application
24+
24V DC power supply
24-
Ground terminal
V+
VI- Channel-1 analog output
I+
• Do not connect any lines.
V+
VI- Channel-2 analog output
I+
• Do not connect any lines.
V+
VI- Channel-3 analog output
I+
• Do not connect any lines.
V+
VI- Channel-4 analog output
I+
φ3.2 (0.13")
6.2 mm (0.24") Terminal
’[Žq
or less
φ3.2 (0.13")
6.2 mm (0.24") Terminal Crimp
or less screw terminal
6.3 mm(0.25")
or more
φ3.2 (0.13")
6.2 mm (0.24") Terminal
or less
6.3 mm(0.25")
or more
E-10
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 3 Wiring
FX3U-4DA (4-channel Analog Output) 3.3 Wiring to Power Supply Terminals
A
3.3 Wiring to Power Supply Terminals
Common Items
3.3.1 Examples of Power Supply Circuit
Below are examples of circuits for using the 24V DC service power supply of the FX3G/FX3U Series PLC. B
1) Sink input [- common] wiring
FX3UC-4AD
FX3U-4AD
AC power
100 to 240 V
FX3U-4AD-ADP
Class-D
grounding
L N S/S 0V 24V 24+ 24-
D
+15V
FX3G-2AD-BD
FX3G/FX3U Series PLC
(main unit) -15V
FX3U-4DA
Connect the "S/S" terminal of the main unit to the "24V" terminal. E
FX3U-4DA
2) Source input [+ common] wiring
AC power
100 to 240 V F
FX3U-4DA-ADP
Class-D
grounding
L N S/S 0V 24V 24+ 24-
G
FX3G-1DA-BD
+15V
Connect the "S/S" terminal of the main unit to the "0V" terminal.
• Ground the " " terminal and " " terminal to the Class - D grounding line (100 Ω or less) together
with the ground terminal of the main unit.
-ADP
• For the timing of power-on/off when using an external power supply, see the following manual of the
connected PLC.
→ Refer to the FX3G Series User's Manual - Hardware Edition. J
→ Refer to the FX3U Series User's Manual - Hardware Edition.
FX3U-4AD-PTW
-ADP
E-11
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 3 Wiring
FX3U-4DA (4-channel Analog Output) 3.4 Analog Output Wiring
Class-D grounding
*2
If voltage output is
selected
ch
Shield *3
V+
I+ ch
VI-
*4 *5
If current output is
selected ch
Shield *3 V+
I+ ch
VI-
*5
ch : represents the channel number.
*1. For FX3G/FX3U Series PLC (AC power type), the 24V DC service power supply is also available.
*2. Do not connect any wires to the " • " terminal.
*3. Use a 2-core twisted shield wire for analog output wire, and separate it from other power lines or
inductive lines.
*4. If there is ripple or noise in the output voltage, connect a capacitor of approximately 0.1 to 0.47μF 25V
in the vicinity of the signal receiving side.
*5. Ground the shielded wire at one point on the signal receiving side.
3.5 Grounding
Grounding should be performed as stated below.
• The grounding resistance should be 100Ω or less.
• Independent grounding should be performed for best results.
When independent grounding is not performed, perform "shared grounding" as shown in the following
figure.
→ For details, refer to the User’s Manual - Hardware Edition of each Series.
E-12
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 4 Analog Output
FX3U-4DA (4-channel Analog Output) 4.1 Analog Output Procedures
Common Items
4. Analog Output
This chapter describes the minimum programming necessary for analog output by the FX3U-4DA. B
Follow the procedure below to confirm that correct analog values can be output.
FX3UC-4AD
FX3U-4AD
4.1 Analog Output Procedures
FX3U-4AD-ADP
Unit numbers from 0 to 7 will be assigned to the special function units/blocks starting from the left.
When the units/blocks are connected to the FX3UC-32MT-LT(-2) PLC, the unit numbers from 1 to 7
are assigned. Check the unit number assigned to the FX3U-4DA.
FX3G-2AD-BD
Main unit Input/output Special Special Input/output Special
(FX3U Series extension extension
PLC) block function block function block block function unit
FX3U-4DA
2 Output mode (BFM #0) setting
Depending on the analog signal generator to be connected, set the output mode (BFM #0) for each
channel.
F
FX3U-4DA-ADP
Use hexadecimal numbers for output mode setting. Set the corresponding channel digit to the
output mode setting value specified in the following table:
H G
ch4 ch1
FX3G-1DA-BD
ch3 ch2
Setting
Output mode Analog output range Digital input range
value
0 Voltage output mode -10V to +10V -32000 to +32000 H
FX3U-3A-ADP
Voltage output
1 -10V to +10V -10000 to +10000
analog value mV specification mode
2 Current output mode 0mA to 20mA 0 to 32000
3 Current output mode 4mA to 20mA 0 to 32000
4
Current output
0mA to 20mA 0 to 20000
I
analog value μA specification mode
FX3U-4AD-PT
→ For a detailed description of the output mode (BFM #0), refer to Subsection 5.4.1.
J
FX3U-4AD-PTW
-ADP
E-13
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 4 Analog Output
FX3U-4DA (4-channel Analog Output) 4.1 Analog Output Procedures
T0
FNC 15 Data (BMF #1 to 4) to be output to channels 1
D0 U \G1 K4 to 4 are transferred from D0 to D3.
BMOV
E-14
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 5 Buffer Memory (BFM)
FX3U-4DA (4-channel Analog Output) 5.1 Assignment of Unit Numbers and Outline of Buffer Memory
Common Items
5. Buffer Memory (BFM)
This chapter describes the buffer memory incorporated in FX3U-4DA. B
FX3UC-4AD
FX3U-4AD
5.1 Assignment of Unit Numbers and Outline of Buffer Memory
FX3U-4AD-ADP
When connected to the FX3G/FX3U/FX3UC (D, DSS) Series PLC
FX3G-2AD-BD
Input/output Special Special Input/output Special
Main unit extension extension
block function block function block block function unit
FX3U-4DA
When connected to the FX3UC-32MT-LT(-2) PLC
Unit number: 0
(Incorporated Unit Unit Unit
CC-Link/LT) number: 1 number: 2 number: 3
F
FX3U-4DA-ADP
Main unit Input/output Input/output
(FX3UC-32MT extension Special Special extension Special
-LT(-2)) block function block function block block function unit
FX3G-1DA-BD
H
FX3U-3A-ADP
I
FX3U-4AD-PT
-ADP
J
FX3U-4AD-PTW
-ADP
E-15
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 5 Buffer Memory (BFM)
FX3U-4DA (4-channel Analog Output) 5.2 Buffer Memory Reading/Writing Method
*1. Since buffer memory direct specification (U\G) can directly specify the buffer memory in the source
or destination area of an applied instruction, programs can be created efficiently. (This function is supported
only in FX3U/FX3UC PLCs.)
→ For a detailed description of buffer memory reading/writing, refer to Section 5.2.
→ For a detailed description of the buffer memory, refer to Section 5.4.
E-16
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 5 Buffer Memory (BFM)
FX3U-4DA (4-channel Analog Output) 5.2 Buffer Memory Reading/Writing Method
A
5.2.1 Buffer memory direct specification (FX3U, FX3UC PLC only)
Common Items
When directly specifying the buffer memory, specify the following device in the source or destination area of
the applied instruction as follows:
FX3UC-4AD
FX3U-4AD
Unit number (0 to 7) Buffer memory number (0 - 3098)
1. Example 1
If the following program is created, data in buffer memory (BFM #10) of unit 1 will be multiplied by the data
(K10), and then the multiplication result will be output to the data registers (D10, D11). C
FX3U-4AD-ADP
READ command
FNC 22 U1\G10 K10 D10
MUL
Multiplication result
Unit number
Buffer memory number Multiplier D
FX3G-2AD-BD
2. Example 2
If the following program is created, the value in the data register (D20) is added to K10 and written to buffer
memory (BFM #6) of unit 1.
WRITE command
E
FNC 20
FX3U-4DA
D20 K10 U1\G6
ADD
(
Addition Unit number
result Buffer memory number )
Augend Addend
F
FX3U-4DA-ADP
5.2.2 FROM/TO instruction (FX3G, FX3U, FX3UC PLC)
FX3G-1DA-BD
READ command
FNC 78 K1 K10 D10 K1
FROM
Number of transfer
Unit number data points
Buffer memory number Transfer-to register H
FX3U-3A-ADP
If the above program is created, 1 point of data will be read out from the buffer memory BFM #10 of unit No.1
to the data register (D10).
WRITE command
FNC 79 K1 K0 H3300 K1
TO
-ADP
Number of transfer
Unit number data points
Buffer memory number Transfer source
J
FX3U-4AD-PTW
If the above program is created, 1 point of data (H3300) will be written to buffer memory (BFM #0) of unit
No.1.
-ADP
E-17
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 5 Buffer Memory (BFM)
FX3U-4DA (4-channel Analog Output) 5.3 Buffer Memory List (BFM)
BFM number Description Setting range Initial value Data type Reference
Hexadeci- Subsection
#0*1 Output mode setting for channels 1 to 4 *2 H0000 at delivery
mal 5.4.1
#1 Channel 1 output data K0 Decimal
#2 Channel 2 output data Depending on the K0 Decimal Subsection
#3 Channel 3 output data mode used K0 Decimal 5.4.2
#11*1 Channel-2 offset data (Unit: mV or μA) Depending on the Depending on Decimal Subsection
*1 Channel-3 offset data (Unit: mV or μA) mode used the mode used Decimal 5.4.6
#12
#15*1 Channel-2 gain data (Unit: mV or μA) Depending on the Depending on Decimal Subsection
*1 Channel-3 gain data (Unit: mV or μA) mode used the mode used Decimal 5.4.6
#16
*1. If power failure occurs, the EEPROM will retain the data.
*2. Specify the output mode of each channel setting one of hex code 0 to 4 and F in each digit.
*3. Specify the data to be output from each channel upon PLC stop setting one of hex code 0 to 2 in each
digit.
*4. Use b0 to b3.
E-18
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 5 Buffer Memory (BFM)
FX3U-4DA (4-channel Analog Output) 5.3 Buffer Memory List (BFM)
Common Items
BFM number Description Setting range Initial value Data type Reference
Data to be output from channel 1 upon PLC stop Depending on the
#32*1 (Valid only if BFM #5 = H 2) mode used
K0 Decimal
#33*1
Data to be output from channel 2 upon PLC stop Depending on the
K0 Decimal B
(Valid only if BFM #5 = H 2 ) mode used Subsection
FX3UC-4AD
FX3U-4AD
Data to be output from channel 3 upon PLC stop Depending on the 5.4.12
#34*1 (Valid only if BFM #5 = H 2 ) mode used
K0 Decimal
FX3U-4AD-ADP
#38 Upper/lower limit function setting *2 H0000
mal 5.4.13
Hexadeci- Subsection
#39 Upper/lower limit function status - H0000
mal 5.4.14
Hexadeci- Subsection
#40 Clear of upper/lower limit function status *3 H0000
FX3G-2AD-BD
#42 Channel-2 lower limit of upper/lower limit function Depending on the K-32640 Decimal Subsection
#43 Channel-3 lower limit of upper/lower limit function mode used K-32640 Decimal 5.4.16
FX3U-4DA
#47 Channel-3 upper limit of upper/lower limit function mode used K32640 Decimal 5.4.16
FX3U-4DA-ADP
#52*1 Load resistance value for channel 2 (Unit: Ω) K1000 to K30000 K30000 Decimal Subsection
*1 Load resistance value for channel 3 (Unit: Ω) K1000 to K30000 K30000 Decimal 5.4.17
#53
#54*1 Load resistance value for channel 4 (Unit: Ω) K1000 to K30000 K30000 Decimal
#55 to #59 Not used - - - - G
Subsection
FX3G-1DA-BD
#60*1 Status automatic transfer function setting *5 K0 Decimal
5.4.18
Error status data (BFM #29) automatic transfer-
Subsection
#61*1 to data register specification (Valid if b0 of BFM K200 Decimal
5.4.19
#60 is set to ON)
K0 to 7999 (BFM
#62*1
Upper/lower limit function status data (BFM #39)
automatic transfer-to data register specification
#61, #62 and #63
K201 Decimal
Subsection H
must have different 5.4.20
FX3U-3A-ADP
*1. If power failure occurs, the EEPROM will retain the data.
I
FX3U-4AD-PT
*2. Specify the use of the upper/lower limit function for each channel setting one of hex code 0 to 2 in
each digit.
*3. Use b0 to b1.
-ADP
*4. Specify the use of the corrective function by load resistance for each channel setting a hex code 0 or
1 in each digit. J
FX3U-4AD-PTW
E-19
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 5 Buffer Memory (BFM)
FX3U-4DA (4-channel Analog Output) 5.3 Buffer Memory List (BFM)
BFM number Description Setting range Initial value Data type Reference
Hexadeci-
#80 Start/stop of table output function *1 H0000
mal
#81 Channel-1 output pattern K1 to K10 K1 Decimal
#82 Channel-2 output pattern K1 to K10 K1 Decimal
#83 Channel-3 output pattern K1 to K10 K1 Decimal
#84 Channel-4 output pattern K1 to K10 K1 Decimal
Number of times of output execution of table
#85 K0 to K32767 K0 Decimal
from channel 1
Number of times of output execution of table Chapter 6
#86 K0 to K32767 K0 Decimal
from channel 2
Number of times of output execution of table
#87 K0 to K32767 K0 Decimal
from channel 3
Number of times of output execution of table
#88 K0 to K32767 K0 Decimal
from channel 4
Hexadeci-
#89 Output completion flag of table output function - H0000
mal
#90 Table output error code - K0 Decimal
#91 Table output error occurrence number - K0 Decimal
#92 to #97 Not used - - - -
#98 Head device number in data table K0 to K32767 K1000 Decimal
Hexadeci-
#99 Data table transfer command *2 H0000 Chapter 6
mal
#100 to #398 Data table in pattern 1 - K0 Decimal
#399 Not used - - - -
#400 to #698 Data table in pattern 2 - K0 Decimal Chapter 6
#699 Not used - - - -
#700 to #998 Data table in pattern 3 - K0 Decimal Chapter 6
#999 Not used - - - -
#1000 to
Data table in pattern 4 - K0 Decimal Chapter 6
#1298
#1299 Not used - - - -
#1300 to
Data table in pattern 5 - K0 Decimal Chapter 6
#1598
#1599 Not used - - - -
#1600 to
Data table in pattern 6 - K0 Decimal Chapter 6
#1898
#1899 Not used - - - -
#1900 to
Data table in pattern 7 - K0 Decimal Chapter 6
#2198
#2199 Not used - - - -
#2200 to
Data table in pattern 8 - K0 Decimal Chapter 6
#2498
#2499 Not used - - - -
#2500 to
Data table in pattern 9 - K0 Decimal Chapter 6
#2798
#2799 Not used - - - -
#2800 to
Data table in pattern 10 - K0 Decimal Chapter 6
#3098
*1. Specify whether to start or stop the table output function for each channel setting a hex code 0 or 1
in each digit.
*2. Specify the data table transfer command and the register type setting 0 or 1 in the last two digits of
the hex code.
E-20
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 5 Buffer Memory (BFM)
FX3U-4DA (4-channel Analog Output) 5.4 Buffer Memory Details
A
5.4 Buffer Memory Details
Common Items
5.4.1 BFM #0: Output mode specification
FX3UC-4AD
FX3U-4AD
Specify the output modes of channel 1 to 4.
4 hexadecimal digits are assigned to specify the output modes of the 4 channels.
Change the value of each digit to change the output mode of each channel. 0 to 4 and F can be set for each
digit.
C
H
FX3U-4AD-ADP
ch4 ch1
ch3 ch2
The different types of output modes are shown in the following table:
→ For a detailed description of output characteristics, refer to Section 2.4. D
FX3G-2AD-BD
Set value
Output mode Analog output range Digital input range
[HEX]
0 Voltage output mode -10V to +10V -32000 to +32000
Voltage output
1*1 analog value mV specification mode
-10V to +10V -10000 to +10000
E
2 Current output mode 0mA to 20mA 0 to 32000
FX3U-4DA
3 Current output mode 4mA to 20mA 0 to 32000
Current output
4*1 analog value μA specification mode
0mA to 20mA 0 to 20000
FX3U-4DA-ADP
*1. The offset/gain values cannot be changed.
1. Cautions regarding output mode setting
• While the output mode is being changed, the output is stopped, and H0000 is automatically written in the
output status (BFM #6).
At the completion of change of the output mode, the output status (BFM #6) will automatically change to
G
FX3G-1DA-BD
H1111, and the output is restarted.
• It takes approximately 5 seconds to determine the output mode.
For this reason, after changing the output mode, be sure to wait for 5 seconds or more, and then write the
other data.
• When the output mode is changed, the settings in the following buffer memory are initialized according to
the new output mode. H
FX3U-3A-ADP
*3 These settings are initialized only when the output mode is changed from current output mode
(mode 2, 3 or 4) to voltage output mode (mode 0 or 1).
-ADP
E-21
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 5 Buffer Memory (BFM)
FX3U-4DA (4-channel Analog Output) 5.4 Buffer Memory Details
Initial value: K0
Numeric data type: Decimal (K)
Input the digital values corresponding to the analog signals to be output in BFM #1 to #4.
It is possible to set the output conditions from channel 1 to 4 when the PLC is in the stopped state.
H
ch4 ch1
ch3 ch2
E-22
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 5 Buffer Memory (BFM)
FX3U-4DA (4-channel Analog Output) 5.4 Buffer Memory Details
A
5.4.4 BFM #6: Output status
Common Items
Initial value: H0000
Numeric data type: Hexadecimal (H)
FX3UC-4AD
FX3U-4AD
H
ch4 ch1
ch3 ch2
C
FX3U-4AD-ADP
Value status (HEX) Description
0 Output updating is stopped.*
1 Under output updating
* The output conditions conform to the output setting upon PLC stop (BFM #5).
D
1. Cautions regarding use of output status
FX3G-2AD-BD
• The output status setting is valid only if the PLC is running.
When the PLC is stopped, H0000 is automatically written.
• When the setting in any of the following buffer memory areas is changed, output updating is stopped.
H0000 is automatically written in BFM #6.
E
• BFM #0 (Output mode setting)
FX3U-4DA
• BFM #5 (Output setting upon PLC stop)
• BFM #9 (Offset/gain setting value write command)
• BFM #19 (Setting change prohibition)
• BFM #20 (Initialization function) F
• BFM #32 to #35 (Data to be output from each channel upon PLC stop)
FX3U-4DA-ADP
• BFM #50 (Corrective function setting by load resistance)
• BFM #51 to #54 (Load resistance for each channel)
• BFM #60 (Status automatic transfer function Setting)
• BFM #61 (Error status data automatic transfer-to data register specification) G
FX3G-1DA-BD
• BFM #62 (Upper/lower limit function status with automatic transfer to specified data register)
• BFM #63 (Disconnection detection status with automatic transfer to data register specification)
• BFM #99 (Data table transfer command)
H
FX3U-3A-ADP
I
FX3U-4AD-PT
-ADP
J
FX3U-4AD-PTW
-ADP
E-23
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 5 Buffer Memory (BFM)
FX3U-4DA (4-channel Analog Output) 5.4 Buffer Memory Details
The WRITE command can be given to two or more channels at the same time. (Set "H000F" to write the data
of all the channels in the EEPROM.)
On completion of writing, "H0000" (b0 to b3: OFF) will be set automatically.
E-24
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 5 Buffer Memory (BFM)
FX3U-4DA (4-channel Analog Output) 5.4 Buffer Memory Details
A
5.4.6 BFM #10 to #13: Offset data/BFM #14 to #17: Gain data
Common Items
Setting range: See below
Initial value: See below
Numeric data type: Decimal (K)
If the output mode is specified in BFM #0, the initial value of the offset data and gain data of each channel will
B
FX3UC-4AD
FX3U-4AD
be automatically stored.
The initial offset data and the gain data are set for each mode as shown in the following table:
• Offset data: Analog output value when the output data in BFM #1 to #4 are 0 (reference offset value)
• Gain data: Analog output value when the output data in BFM #1 to #4 are the reference gain values (The
reference gain value depends on the set output mode.) C
FX3U-4AD-ADP
1. Reference offset/gain value and initial value set
Offset (channels 1 to 4: Gain (channels 1 to 4:
Output mode (BFM #0)
BFM #10 to #13) BFM #14 to #17)
Reference Reference
Set value Description Initial value Initial value
value value D
Voltage output
FX3G-2AD-BD
0 0 0mV 16000 5000mV
(-10 V to +10 V: -32000 to +32000)
Voltage output Analog value mV 0 0mV 5000 5000mV
1 specification mode (Data change (Data change (Data change (Data change
(-10 V to +10 V: -10000 to +10000) impossible) impossible) impossible) impossible)
2
Current output
0 0μA 16000 10000μA E
(0 mA to 20 mA: 0 to 32000)
FX3U-4DA
Current output
3 0 4000μA 16000 12000μA
(4 mA to 20 mA: 0 to 32000)
Current output Analog value μA 0 0μA 10000 10000μA
4 specification mode (Data change (Data change (Data change (Data change
(0 mA to 20 mA: 0 to 20000) impossible) impossible) impossible) impossible) F
FX3U-4DA-ADP
2. Offset/gain data change
Set offset data and gain data to change the output characteristics.
The offset and gain data can be set for each channel. If the voltage output mode is set, write the offset and
gain data in mV. If the current output mode is set, write the offset and gain data in μA.
To change the offset or gain data, execute the offset/gain setting value write command (BFM #9).
G
FX3G-1DA-BD
The setting range is shown in the following table.
*1. The offset and gain values should meet the following conditions:
1000 ≤ Gain value - Offset value ≤ 10000
*2. The offset and gain values should meet the following conditions:
3000 ≤ Gain value - Offset value ≤ 30000
I
FX3U-4AD-PT
-ADP
J
FX3U-4AD-PTW
-ADP
E-25
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 5 Buffer Memory (BFM)
FX3U-4DA (4-channel Analog Output) 5.4 Buffer Memory Details
• The offset and gain data should be set before the value write command BFM #9 is executed.
• The resolution cannot be increased by changing the output characteristics.
• When the value specified as the output mode (BFM #0) is changed, the initial value of offset and gain data
in each output mode will be automatically written.
• Even if the output characteristics are changed, the actual valid output range will not be changed:
-10 V to +10 V for the voltage output mode, and 0 mA to 20 mA in the current output mode.
→ For a detailed description of output characteristics change, refer to Chapter 7.
Specify the following value as the setting change prohibition mode (BFM #19).
E-26
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 5 Buffer Memory (BFM)
FX3U-4DA (4-channel Analog Output) 5.4 Buffer Memory Details
A
5.4.8 BFM #20: Initialization function (resetting to factory default status)
Common Items
Setting range: K0 or K1
Initial value: K0
Numeric data type: Decimal (K)
When K1 is set in BFM #20, all functions and all buffer memory (BFM #0 to #3098) will be initialized to the B
default status.
FX3UC-4AD
FX3U-4AD
When BFM #20 is not K0 or K1, this function is invalid. (The settings will not be changed, and the functions
will not be initialized.)
FX3U-4AD-ADP
output will be restarted.
• It takes approximately 5 seconds to initialize all the data. Do not set (write) data in the buffer memory
during this period.
• Priority is given to the setting of the value change prohibition mode (BFM #19).
• At the completion of initialization, the value of BFM #20 will automatically change to K0. D
FX3G-2AD-BD
5.4.9 BFM #28: Disconnection detection status (only in current output mode)
Initial value: H0000
Numeric data type: Hexadecimal (H) E
FX3U-4DA
When a wire-break is detected, the bit corresponding to the relevant channel will turn on.
FX3U-4DA-ADP
b1 Wire-break in channel 2
b2 Wire-break in channel 3
b3 Wire-break in channel 4
b4 to b15 Not used
G
2. Cautions regarding use of disconnection detection status
FX3G-1DA-BD
• When any of b0 to b3 is turned on, b11 of the error status (BFM #29) is turned on.
• The disconnection detection status is valid only if the output mode (BFM #0) is the current output mode
(mode 2 to 4). In other output modes, each corresponding bit of BFM #28 stays off.
If the disconnection detection status with automatic transfer-to data register is specified in BFM #63, the data
in BFM #28 can be transferred to the specified data register.
Only when wire-break is detected, data will be automatically transferred from FX3U-4DA to the PLC. For this
reason, the PLC does not need the program for reading data, and the scan time of the PLC can be shortened.
→ For a detailed description of the status automatic transfer function, refer to Subsection 5.4.18.
I
FX3U-4AD-PT
-ADP
J
FX3U-4AD-PTW
-ADP
E-27
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 5 Buffer Memory (BFM)
FX3U-4DA (4-channel Analog Output) 5.4 Buffer Memory Details
E-28
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 5 Buffer Memory (BFM)
FX3U-4DA (4-channel Analog Output) 5.4 Buffer Memory Details
A
5.4.11 BFM #30: Model code
Common Items
Initial value (at delivery): K3030
Numeric data type: Decimal (K)
K3030 (fixed value) is stored as the model code.
B
FX3UC-4AD
FX3U-4AD
5.4.12 BFM #32 to #35: Data to be output upon PLC stop
Initial value: K0
Numeric data type: Decimal (K)
To enable the output data set when the PLC stops, Set "2" for any digit in the output data (H0000) at PLC's C
stop. Set the BFM values as follows.
FX3U-4AD-ADP
BFM number Description
#32 Data in channel 1
#33 Data in channel 2
#34 Data in channel 3 D
#35 Data in channel 4
FX3G-2AD-BD
The setting range depends on the output mode.
FX3U-4DA
2, 3 0 to 32640
4 0 to 20400
F
1. Cautions regarding data output setting when PLC is in stop
FX3U-4DA-ADP
• While changing the settings, the output is stopped, and H0000 is automatically written in the output status
(BFM #6).
After the completion of writing, the output status (BFM #6) will automatically change to H1111, and output
will be restarted.
• The analog values to be output depend on the output mode. G
FX3G-1DA-BD
• When a value out of any of the above ranges is set, b5 of the error status (BFM #29) is turned on.
I
FX3U-4AD-PT
-ADP
J
FX3U-4AD-PTW
-ADP
E-29
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 5 Buffer Memory (BFM)
FX3U-4DA (4-channel Analog Output) 5.4 Buffer Memory Details
H
ch4 ch1
ch3 ch2
*1. When any value becomes less than the lower limit (BMF #41 to #44) or more than the upper limit
(BFM #45 to #48), the relevant bit of the upper/lower limit function status is turned on.
Upper limit
Lower limit
The value is output even if it is
below the lower limit.
*2. When any value becomes less than the lower limit (BMF #41 to #44) or more than the upper limit
(BFM #45 to #48), the relevant bit of the upper/lower limit function status is turned on.
In this setting, analog values more than the upper limit and less than the lower limit are not output.
Analog value Values more than the upper limit are not
output.
Upper limit
Lower limit
Values less than the lower limit are
not output.
E-30
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 5 Buffer Memory (BFM)
FX3U-4DA (4-channel Analog Output) 5.4 Buffer Memory Details
A
5.4.14 BFM #39: Upper/lower limit function status
Common Items
Initial value: H0000
Numeric data type: Hexadecimal (H)
When any of the output data (BFM #1 to #4) is out of range between the lower limit and the upper limit (BFM
#41 to #48), the relevant bit is turned on. B
FX3UC-4AD
FX3U-4AD
1. Assignment to each bit of BFM #39
Bit Description
b0 Data output from channel 1 < Lower limit (BFM #41)
b1 Data output from channel 1 > Upper limit (BFM #45) C
b2 Data output from channel 2 < Lower limit (BFM #42)
FX3U-4AD-ADP
b3 Data output from channel 2 > Upper limit (BFM #46)
b4 Data output from channel 3 < Lower limit (BFM #43)
b5 Data output from channel 3 > Upper limit (BFM #47)
b6 Data output from channel 4 < Lower limit (BFM #44) D
b7 Data output from channel 4 > Upper limit (BFM #48)
FX3G-2AD-BD
b8 to b15 Not used
FX3U-4DA
• The upper/lower limit function status can be reset by the following methods.
- Use the upper/lower limit function status reset function (BFM #40).
- Turn the power supply off then on.
FX3U-4DA-ADP
transferred to a specified data register.
Only when an error is detected, data will be automatically transferred from the FX3U-4DA to the PLC. For this
reason, the PLC does not need the program for reading data, and the scan time of the PLC can be shortened.
→ For a detailed description of the status automatic transfer function, refer to Subsection 5.4.18.
G
5.4.15 BFM #40: Clearance of upper/lower limit function status
FX3G-1DA-BD
Initial value: H0000
Numeric data type: Hexadecimal (H)
The flags can be reset by turning on the following bits of BFM #40.
H
1. Assignment to each bit of BFM #40
FX3U-3A-ADP
Bit Description
b0 Clearance of lower limit status
b1 Clearance of upper limit status
b2 to b15 Invalid I
FX3U-4AD-PT
J
FX3U-4AD-PTW
-ADP
E-31
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 5 Buffer Memory (BFM)
FX3U-4DA (4-channel Analog Output) 5.4 Buffer Memory Details
5.4.16 BFM #41 to #44: Lower limit values of upper/lower limit function
BFM #45 to #48: Upper limit values of upper/lower limit function
E-32
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 5 Buffer Memory (BFM)
FX3U-4DA (4-channel Analog Output) 5.4 Buffer Memory Details
A
5.4.17 BFM #50: Setting of output corrective function by load resistance
Common Items
(only in voltage output mode)/BFM #51 to #54: Load resistance values
The output characteristics of FX3U-4DA have been adjusted at 30 kΩ load resistance as a factory default.
B
FX3UC-4AD
FX3U-4AD
When the load resistance is 1kΩ, the output deviation is approx. -4.3% to 20V in full scale, whereas the
output deviation is approx. 0.15% to 20V in full scale when the load resistance is 1MΩ. When the load
resistance is 30 kΩ or less (1 kΩ to 30 kΩ), the deviation of the output characteristics can be corrected by
specifying the output corrective function (BFM #50) and the load resistance values (BFM #51 to #54).
Analog value C
FX3U-4AD-ADP
The deviation of output characteristics is
corrected by the corrective function by load
+10V resistance.
-32000 D
32000 Digital value
FX3G-2AD-BD
: Output characteristics after correction
FX3U-4DA
1. Setting of output corrective function (BFM #50)
The corrective function by load resistance is valid or invalid by writing a 4-digit hexadecimal number,
H , in the output corrective function setting (BFM #50).
F
H
FX3U-4DA-ADP
ch4 ch1
ch3 ch2
FX3G-1DA-BD
0 Corrective function by load resistance is invalid.
1 Corrective function by load resistance is valid.
Other than above
Invalid (setting values unchanged)
values
2. Setting range and initial value of load resistance (BFM #51 to #54) H
FX3U-3A-ADP
Set the load resistance value for each channel allocated to the following BFM.
BFM
Description Setting range (Ω) Initial value (Ω)
number
#51 Load resistance value for channel 1
#52 Load resistance value for channel 2 I
1000 to 30000 30000
FX3U-4AD-PT
J
FX3U-4AD-PTW
-ADP
E-33
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 5 Buffer Memory (BFM)
FX3U-4DA (4-channel Analog Output) 5.4 Buffer Memory Details
When the bits, b0 to b2, of BFM #60 are turned on, the assigned functions (see the table below) are valid.
When the bits are turned off, the functions are invalid.
E-34
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 5 Buffer Memory (BFM)
FX3U-4DA (4-channel Analog Output) 5.4 Buffer Memory Details
A
5.4.19 BFM #61: Error status data automatic transfer-to data register specification
Common Items
Setting range: 0 to 7999
Initial value: K200
Numeric data type: Decimal (K)
Use this function to automatically transfer the error status data (BFM #29) to the data register specified in
B
FX3UC-4AD
FX3U-4AD
BFM #61.
When an error is detected, data will be automatically transferred from FX3U-4DA to the PLC. For this reason,
the PLC does not need a program for reading data, and the scan time of the PLC can be shortened.
→ For a detailed description of the error status (BFM #29), refer to Subsection 5.4.12.
FX3U-4AD-ADP
Specified data
Description
register
D200 Value of error status (BFM #29)
FX3G-2AD-BD
register.
• This function is valid by turning on b0 of the status automatic transfer function setting (BFM #60).
• When a value out of the above setting range is set, b9 of the error status BFM #29 is turned on.
• The data set in BFM #61 will be retained in the EEPROM.
E
3. Cautions regarding EEPROM writing
FX3U-4DA
If data is set in BFM #0, #5, #10 to #17, #32 to #35, #50 to #54 or #60 to #63, the data will be written in the
EEPROM of FX3U-4DA.
Do not turn off the power immediately after writing values in these buffer memories.
The maximum number of EEPROM rewritable times is 10,000. Therefore, when creating a program, do not
frequently write data in the above buffer memories (BFM). F
FX3U-4DA-ADP
G
FX3G-1DA-BD
H
FX3U-3A-ADP
I
FX3U-4AD-PT
-ADP
J
FX3U-4AD-PTW
-ADP
E-35
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 5 Buffer Memory (BFM)
FX3U-4DA (4-channel Analog Output) 5.4 Buffer Memory Details
5.4.20 BFM #62: Upper/lower limit function status data automatic transfer-to data register
specification
Use this function to automatically transfer the upper/lower limit function status data (BFM #39) to the data
register specified in BFM #62.
Only when the value becomes more than the upper limit or less than the lower limit, data will be automatically
transferred from FX3U-4DA to the PLC. For this reason, the PLC does not need the program to read data, and
the scan time of the PLC can be shortened.
→ For a detailed description of the upper/lower limit function status (BFM #39),
refer to Subsection 5.4.14.
Specified data
Description
register
D201 Value of upper/lower limit function status (BFM #39)
2. Cautions regarding upper/lower limit function status automatic transfer function setting
• If a data is already specified for the other automatic transfer functions, do not specify the same data
register.
• This function is valid by turning on b1 of the status automatic transfer function setting (BFM #60).
• When a value out of the above setting range is set, b9 of the error status BFM #29 is turned on.
• The data set in BFM #62 will be retained in the EEPROM.
E-36
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 5 Buffer Memory (BFM)
FX3U-4DA (4-channel Analog Output) 5.4 Buffer Memory Details
A
5.4.21 BFM #63: Specification of data register for automatic transfer at disconnection
Common Items
detection
FX3UC-4AD
FX3U-4AD
Use this function to automatically transfer the disconnection detection status data (BFM #28) to the data
register specified in BFM #63.
Only when wire-break is detected, data will be automatically transferred from FX3U-4DA to the PLC. For this
reason, the PLC does not need the program for reading data, and the scan time of the PLC can be shortened.
→ For a detailed description of the disconnection detection status (BFM #28),
refer to Subsection 5.4.9. C
FX3U-4AD-ADP
1. If "BFM #63 = K202 (initial value)"
Specified data
Description
register
D202 Value of disconnection detection status (BFM #28)
D
FX3G-2AD-BD
2. Cautions regarding disconnection detection status automatic transfer function setting
• If a data is already specified for the other automatic transfer functions, do not specify the same data
register.
• This function is valid by turning on b2 of the status automatic transfer function setting (BFM #60).
• When a value out of the above setting range is set, b9 of the error status BFM #29 is turned on. E
FX3U-4DA
• The data set in BFM #63 will be retained in the EEPROM.
FX3U-4DA-ADP
frequently write data in the above buffer memories (BFM).
FX3G-1DA-BD
BFM #80 (start/stop command of table output function)
BFM #81 to #84 (output pattern setting of channels)
BFM #85 to #88 (output execution cycle number of channels)
BFM #89 (completion flag of table output function)
BFM #90 (table output error code)
BFM #91 (table output error source number) H
BFM #98 (data table head device number)
FX3U-3A-ADP
Table output function: Sets predetermined output patterns as data table, and outputs analog signals
according to the data table.
→ For a detailed description of the table output function, refer to Chapter 6.
I
FX3U-4AD-PT
-ADP
J
FX3U-4AD-PTW
-ADP
E-37
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 6 Table Output Function
FX3U-4DA (4-channel Analog Output) 6.1 Outline of Table Output Function
Transfer of data table* The data table is transferred from the PLC main
unit to the relevant buffer memory of FX3U-4DA.
Refer to Section 6.4
* It is possible to write the data table directly in FX3U-4DA using a program (TO instruction, etc.).
E-38
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 6 Table Output Function
FX3U-4DA (4-channel Analog Output) 6.2 Preparation of data table
A
6.2 Preparation of data table
Common Items
1. Outline of data table
The data table to be prepared in the PLC consists of the following items.
(1) Number of patterns (1 to 10 patterns)
(2) Each pattern
B
FX3UC-4AD
FX3U-4AD
(3) Number of points in each pattern (1 to 99 points)
(4) Condition after output at final point in each pattern
(5) Points in each pattern
(6) Data to be output at each point
(7) Output update time at each point
(8) Unit of output update time at each point, and point-to-point interpolation method C
FX3U-4AD-ADP
2. Preparation of data table
Prepare the data table consisting of the following items in the data registers (D1000 to D7999) in the PLC
main unit or the expansion registers (R0 to R32767).
It is convenient to prepare the data table on spreadsheet software and copy and paste the data to the device
memory of GX Developer.
D
FX3G-2AD-BD
Setting item Device number in PLC assignment
(1) Number of patterns (x) Device number specified in BFM #98
(3) Number of points in pattern 1 (n) Device number+1 specified in BFM #98
(2) Pattern 1
(4) Condition after output at final point in pattern Device number+2 specified in BFM #98
(6) Output data Device number+3 specified in BFM #98 E
(7) Output update time Device number+4 specified in BFM #98
FX3U-4DA
(5) Point 1
(8) Unit of output update time at each point,
Device number+5 specified in BFM #98
and point-to-point interpolation method
. . .
. . .
. . . F
(6) Output data
FX3U-4DA-ADP
(7) Output update time
(5) Point n
(8) Unit of output update time at each point,
and point-to-point interpolation method
. .
. . G
. .
FX3G-1DA-BD
(3) Number of points in pattern X (m)
(2) Pattern X
(8) Unit of output update time at each point, Device specified in BFM #98 + total number
and point-to-point interpolation method of data tables -1*1
-ADP
Note) The device number marked by *1 should not exceed D7999 or R32767.
For a detailed description of the data table items (1) to (8), refer to the following pages.
J
FX3U-4AD-PTW
-ADP
E-39
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 6 Table Output Function
FX3U-4DA (4-channel Analog Output) 6.2 Preparation of data table
(4) Condition after output at final point in pattern (number of data items: 1)
The condition after output at the final point in a pattern can be set to continue to output the output signal at
the final point or output the offset signal.
The setting is shown in the following table.
* When a value out of the setting range is set, the error code is stored in the table output error code BFM #90,
the device number or the buffer memory that has developed the table output error is stored in BFM #91,
and b8 of the error status BFM #29 is turned on.
E-40
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 6 Table Output Function
FX3U-4DA (4-channel Analog Output) 6.2 Preparation of data table
A
(8) Output update time unit and point-to-point interpolation method (number of data items: 1)
Common Items
Set the unit of the output update time and the point-to-point interpolation method for each point.
The output update time unit and the point-to-point interpolation method for the n-th point are applied
between the n-th point and the (n+1)-th point.
When the pattern is repeated, the output update time unit and the point-to-point interpolation method are
applied between the final point and the first point.
When the pattern is not repeated, the output update time unit and the point-to-point interpolation method
B
FX3UC-4AD
FX3U-4AD
for the final point are ignored.
A 4-digit hexadecimal number, H , is allocated as shown below.
H
Invalid* Output updating time unit C
Invalid* Point-to-point interpolation method
FX3U-4AD-ADP
• Setting of output update time unit
FX3G-2AD-BD
1 100 ms
2 1s
3 1 min
Other than above
values
Invalid* E
FX3U-4DA
• Interpolation method
Data output between points are interpolated every 1 ms and automatically updated.
FX3U-4DA-ADP
1
interpolated in the shape of a straight line.)
S-shaped interpolation (Data output between points are
2 interpolated in the shape of an S-shaped as shown
below.)
Other than above
Invalid*
G
values
FX3G-1DA-BD
• S-shaped interpolation
Output data
D/8
Point n+1 H
FX3U-3A-ADP
D/2 D/8
Point n
I
FX3U-4AD-PT
Time
T
J
* When a value out of the setting range is set, the error code is stored in the table output error code BFM #90,
FX3U-4AD-PTW
the device number or the buffer memory that has developed the table output error is stored in BFM #91,
and b8 of the error status BFM #29 is turned on.
-ADP
E-41
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 6 Table Output Function
FX3U-4DA (4-channel Analog Output) 6.2 Preparation of data table
Data
Set value Description
register
D5000 K2 Number of patterns 2 patterns
D5001 K3 Number of points in pattern 1 3 points
Pattern 1
Holding of value
D5002 K0 Setting of condition after output at final point in pattern 1
output at final point
D5003 K3000 Data to be output at point 1 in pattern 1 3V
D5004 K18 Point 1 Output update time at point 1 in pattern 1 1800 ms
Output update time unit at point 1 in pattern 1 100 ms
D5005 H0021
Point-to-point interpolation method S-shaped interpolation
D5006 K8000 Data to be output at point 2 in pattern 1 8V
Point 2
D5013 K1 Setting of condition after output at final point in pattern 2 Output of offset value
D5014 K2000 Data to be output at point 1 in pattern 2 2V
Point 1
E-42
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 6 Table Output Function
FX3U-4DA (4-channel Analog Output) 6.2 Preparation of data table
A
5. Example of pattern output
Common Items
Data can be output in a predetermined pattern as shown below. (Example of pattern 1 in output mode 1
shown on the previous page)
FX3UC-4AD
FX3U-4AD
are set to 0 or 2 or
Output higher.)
value
Point 2
8V
Linear
S-shaped
interpolation C
interpolation
FX3U-4AD-ADP
5V
Point 3
Point 1
3V
D
FX3G-2AD-BD
Time
Output update Output update Output update
time at point 1
(1800 ms)
time at point 2
(2600 ms)
time at point 3
(500 ms)
E
FX3U-4DA
6. Caution when preparing the data table
• Prepare the data table in continuous data registers in the PLC main unit or continuous expansion registers.
(Prepare data without spaces between patterns or points.)
If data has spaces, the data cannot be transferred normally to the buffer memory in FX3U-4DA. F
→ For a detailed description of data table errors, refer to Section 6.5.
FX3U-4DA-ADP
G
FX3G-1DA-BD
H
FX3U-3A-ADP
I
FX3U-4AD-PT
-ADP
J
FX3U-4AD-PTW
-ADP
E-43
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 6 Table Output Function
FX3U-4DA (4-channel Analog Output) 6.3 Procedures for transferring data table to buffer memory
1. Specify the head device number of the data table to be transferred. (BFM #98, initial value:
K1000)
Specify the head device number of the data table in BFM #98.
The setting range is K1000 to K7994 for the data registers (D1000 to D7999) (because at least six points are
occupied) or K0 to K32762 for the expansion registers (R0 to R32767) (because at least six points are
occupied).
Example) When the data table is set starting from D1000, set K1000 in BFM #98.
When a value out of the setting range is set, the error code K21 is stored in the table output error code BFM
#90, the number of the buffer memory, K98, that has developed the table output error is stored in BFM #91,
and b8 of the error status BFM #29 is turned on.
2. Start transferring the data table. (BFM #99, initial value: H0000)
Transfer the data table from the PLC to the FX3U-4DA using the data table transfer command (BFM #99).
H
Invalid* Data table transfer command
Invalid* Register type
• Register type
* When a value out of the setting range is set, the error code is stored in the table output error code BFM #90,
the number of the buffer memory, K99, that has developed the table output error is stored in BFM #91, and
b8 of the error status BFM #29 is turned on.
Example) When K1000 is written in the head device number of data table (BFM #98) and H0001 is written
in the data table transfer command (BFM #99), the data table will be transferred from the data
register D1000.
E-44
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 6 Table Output Function
FX3U-4DA (4-channel Analog Output) 6.3 Procedures for transferring data table to buffer memory
A
3. Buffer memory contents in FX3U-4DA after transfer
Common Items
The transferred data table is stored in the following buffer memory areas.
BFM
Description
number
#100
Pattern 1
Number of points B
#101 Condition after output at final point in pattern
FX3UC-4AD
FX3U-4AD
#102 Output data
#103 Output update time
Point 1
Unit of output update time at each point, and point-to-
#104
point interpolation method
. . . C
. . .
FX3U-4AD-ADP
. . .
#396 Output data
#397 Output update time
Point 99
Unit of output update time at each point, and point-to-
#398
point interpolation method D
FX3G-2AD-BD
#399 Not used
. . .
. . .
. . .
#2800 Number of points
#2801 Condition after output at final point in pattern
E
FX3U-4DA
#2802 Output data
#2803 Output update time
Point 1
Unit of output update time at each point, and point-to-
#2804
Pattern 10
FX3U-4DA-ADP
. . .
#3096 Output data
#3097 Output update time
Point 99
Unit of output update time at each point, and point-to-
#3098
point interpolation method G
FX3G-1DA-BD
H
FX3U-3A-ADP
I
FX3U-4AD-PT
-ADP
J
FX3U-4AD-PTW
-ADP
E-45
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 6 Table Output Function
FX3U-4DA (4-channel Analog Output) 6.3 Procedures for transferring data table to buffer memory
E-46
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 6 Table Output Function
FX3U-4DA (4-channel Analog Output) 6.3 Procedures for transferring data table to buffer memory
A
5. Cautions regarding data table transfer
Common Items
• While the table output function is executed, it is impossible to start transferring the data table.
• The number of patterns is not transferred to the buffer memory in FX3U-4DA.
• The transferred data table is stored in the buffer memory in FX3U-4DA. The data table stored in FX3U-4DA
will be erased when power is turned off. Therefore, it is necessary to transfer the data table after rebooting
the power.
B
FX3UC-4AD
FX3U-4AD
• At completion of transfer, BFM #99 will automatically change to H0000. Also when transfer is stopped due
to an error, BFM #99 will automatically change to H0000. When BFM #99 changes to H0000, check the
error flag.
→ For a detailed description of errors related to table output, refer to Subsection 6.5.
• If an error occurs during transfer of the data table, the data up to the error is transferred. Subsequent data C
is not transferred.
FX3U-4AD-ADP
• It is possible to write the data table directly in the buffer memory without using the data table transfer
command (BFM #99).
In this case, the correctness of the data table is not evaluated until the table is output by the table output
start/stop function (BFM #80).
If a data table with incorrect data is output, the data up to the point where incorrect data occurs is output.
At the point where incorrect data occurs, an error is registered and only the data output just before the
D
FX3G-2AD-BD
occurrence of the error is held.
• Execute the data table transfer command (BFM #99) as a pulse execution type instruction.
• During transfer of the data table, the scan time increases by up to about 10 ms.
• The standard data table transfer time is obtained by the following formula.
E
Number of *
FX3U-4DA
data table items
Transfer time = (Scan time) × × (number of FX3U-4DA units connected to main unit)
64
* Fractions omitted
Example) F
• Scan time: 50 ms (including increase in scan time caused by data table transfer)
FX3U-4DA-ADP
• Number of data table items to be transferred: 2991 items (when the number of patterns is 10
and the number of points in each pattern is 99)
• Number of units connected to FX3U-4DA: 8 units
2991
G
Transfer time = (50 ms) × × (8 units)
FX3G-1DA-BD
64
= 18800 ms
H
FX3U-3A-ADP
I
FX3U-4AD-PT
-ADP
J
FX3U-4AD-PTW
-ADP
E-47
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 6 Table Output Function
FX3U-4DA (4-channel Analog Output) 6.4 Procedures for executing table output function
After setting the output patterns for the channels (BFM #81 to #84) and the number outputs for the
channels (BFM #85 to #88), turn on the table output function start/stop command (BFM #80) to
execute the table output function.
1. Set the output patterns for the channels. (BFM #81 to #84, initial value: K1)
Set the output patterns for the channels in BFM #81 to #84.
The output pattern can be changed in the middle of outputting the table.
Setting range for BFM #81 to #84: 1 to 10
When a value out of the setting range is set, the error code K31 is stored in the table output error code BFM
#90, the number of the buffer memory (K81 to K84) that has developed the table output error is stored in BFM
#91, and b8 of the error status BFM #29 is turned on.
2. Set the number of table outputs for the channels. (BFM #85 to #88, initial value: K0)
Set the number of table outputs for the channels in BFM #85 to #88.
The number of outputs can be changed even during outputting the table.
Setting range for BFM #85 to #88: 0 to 32767
When 0 is set, output of the table will be repeated until the table output is stopped by BFM #80.
When a value out of the setting range is set, the error code K32 is stored in the table output error code BFM
#90, the number of the buffer memory (K85 to K88) that has developed the table output error is stored in BFM
#91, and b8 of the error status BFM #29 is turned on.
H
ch4 ch1
ch3 ch2
* When a value out of the setting range is set, the error code K33 is stored in the table output error code BFM
#90, the number of the buffer memory (K80) that has developed the table output error is stored in BFM #91,
and b8 of the error status BFM #29 is turned on.
E-48
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 6 Table Output Function
FX3U-4DA (4-channel Analog Output) 6.4 Procedures for executing table output function
A
4. Cautions regarding table output
Common Items
• When BFM #99 (data table transfer command) is not H0000, the table output function cannot be started.
• When an error occurs during transfer of data table, start the table output after setting the correct data table.
• While the table output completion flag BFM #89 is ON, output of a new table cannot be started.
• The table output function is valid only while the PLC is in RUN mode. B
• While even a single channel is outputting data table (BFM #80 is not H0000), it is prohibited to change
FX3UC-4AD
FX3U-4AD
BFM #0, #5, #9 to #17, #19, #20, #32 to #35, #38, #41 to 48, #50 to #54 and #60 to #63.
• The pattern can be changed during output as shown below. (The change is invalid while the table output
completion flag BFM #89 is ON.)
Output C
value Pattern 5
FX3U-4AD-ADP
Pattern 1
FX3G-2AD-BD
Time
Table output start Change from output pattern
1 to output pattern 5
E
FX3U-4DA
5. Check the table output completion flag. (BFM #89, initial value: H0000)
The value in BFM #89 indicates whether the table output from each channel has been completed.
After data is output at the final point in the last cycle of a pattern, the table output completion flag is turned on.
When the table output (BFM#80) is set to be stopped, the table output completion flag is turned off. F
FX3U-4DA-ADP
H
ch4 ch1
ch3 ch2
G
FX3G-1DA-BD
Value for each
Table output completion flag
channel
0 Table output uncompleted
1 Table output completed
H
FX3U-3A-ADP
I
FX3U-4AD-PT
-ADP
J
FX3U-4AD-PTW
-ADP
E-49
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 6 Table Output Function
FX3U-4DA (4-channel Analog Output) 6.5 Details of table output error
E-50
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 6 Table Output Function
FX3U-4DA (4-channel Analog Output) 6.5 Details of table output error
A
2. Cautions regarding table output errors
Common Items
• Errors in data table
When the data table in the PLC contains an error, the error can be detected during transfer of the data to
the buffer memory in FX3U-4DA. In this case, the error code (BFM #90) is K1 1, and the device number is
written as the error source (BFM #91).
If an error is caused in the data table by directly rewriting the data in BFM after the data table is transferred, B
the error can be detected when the table is output using incorrect data. In this case, the error code (BFM
FX3UC-4AD
FX3U-4AD
#90) is K1 2, and the BFM number is written as the error source (BFM #91).
• Error during transfer of the data table
While transferring of the data table, an error (error codes K31 to K33) does not occur even when the BFM
#80 (table output function start/stop) is set to a value out of the setting range. An error occurs after the
completion of the transfer of the data table. C
• Error during output of the table
FX3U-4AD-ADP
Even if the output value is scaled over during output of the table, the output of the table will not be stopped.
However, while the output value is scaled over, b10 (scale over) of the error status BFM #29 stays on.
When an error (error codes K122 to K172, K31 to K33) occurs during output of the table, the output of the
table is cancelled and the analog output value just before the occurrence of the error is retained.
• Table output errors (BFM #90) and table output error source numbers (BFM #91) are not retained. They D
will be cleared when the next data table transfer command is given or the table output start function is
FX3G-2AD-BD
executed.
FX3U-4DA
F
FX3U-4DA-ADP
G
FX3G-1DA-BD
H
FX3U-3A-ADP
I
FX3U-4AD-PT
-ADP
J
FX3U-4AD-PTW
-ADP
E-51
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 6 Table Output Function
FX3U-4DA (4-channel Analog Output) 6.6 Examples uses of table output function
Output
frequency
(Hz)
60
30
0
5 10V
Analog signal
To control the frequency as shown below, where control the analog signal is proportional to the frequency use
the table output function.
Output
frequency
(Hz)
60
30
0
Time
Output
voltage (V)
Point 2 Point 3
10
No interpolation
S-shaped S-shaped
interpolation interpolation
5
Point 4
0 Point 1
Time
Output update Output update Output update
time at point 1 time at point 2 time at point 3
E-52
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 7 Changing Output Characteristic
FX3U-4DA (4-channel Analog Output) 7.1 Procedure for Changing Output Characteristics
Common Items
7. Changing Output Characteristic
For FX3U-4DA, the standard output characteristics are provided for each output mode (BFM #0)at the time of B
factory shipment.
FX3UC-4AD
FX3U-4AD
Changing the offset data (BFM #10 to #13) and gain data (BFM #14 to #17) can change the output
characteristics of each channel. This chapter describes how to change the output characteristics.
FX3U-4AD-ADP
1 Cancel the setting change prohibition mode.
If setting change is prohibited, write K3030 in BFM #19. The setting change prohibition mode will
be canceled.
D
2
FX3G-2AD-BD
Determine the output mode (BFM #0).
Determine the output mode (BFM #0) optimum for the selected channels and the voltage/current
specifications.
Set value (HEX) Output mode Analog output range Digital input range E
FX3U-4DA
0 Voltage output mode -10V to +10V -32000 to +32000
Voltage output analog value mV
1 The characteristic cannot be changed.
specification mode
2 Current output mode 0mA to 20mA 0 to 32000
3 Current output mode
Current output analog value μA
4mA to 20mA 0 to 32000
F
4 The characteristic cannot be changed.
FX3U-4DA-ADP
specification mode
5 to E Setting not allowed - -
F Channel not used - -
Example: Enter "HFF00" in BFM to set output mode 0 for channels 1 and 2 and prevent use chan- G
nels 3 and 4
FX3G-1DA-BD
Cautions regarding data setting
• If a value "1" or "4" is set for a channel, the output characteristics of the channel cannot be changed.
• Set the optimum output mode for the analog signal to be output.
H
FX3U-3A-ADP
I
FX3U-4AD-PT
-ADP
J
FX3U-4AD-PTW
-ADP
E-53
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 7 Changing Output Characteristic
FX3U-4DA (4-channel Analog Output) 7.1 Procedure for Changing Output Characteristics
Output mode: 0
Output characteristics provided at the time Output characteristics newly provided
of factory shipment
+10.2V
+10V 5V
Digital 1V Digital
-32000 0 value value
+32000 0 32000
-10V
-10.2V
E-54
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 7 Changing Output Characteristic
FX3U-4DA (4-channel Analog Output) 7.1 Procedure for Changing Output Characteristics
A
6
Common Items
Create a sequence program.
To change the output characteristics, write the offset data (BFM #10 to #13) and the gain data
(BFM #14 to #17) in the sequence program, and then turn on the corresponding bit of BFM #9 for
the corresponding channel.
B
Example: Program for changing the output characteristics of channels 1 and 2 (For FX3U, FX3UC
FX3UC-4AD
FX3U-4AD
Series PLCs):
X000
FNC 12 Cancellation of setting change
K3030 U0\G19 prohibition mode
MOV P
FX3U-4AD-ADP
MOV P channels 1 to 4
SET M0
M0
K50
T0
D
T0
FX3G-2AD-BD
FNC 16 K1000 U0\G10 K2 Setting of offset data (channels 1 and 2)
FMOV P
FX3U-4DA
FNC 12 K0 U0\G19 Setting change prohibition
MOV P
F
7 Transfer the sequence program to change the output characteristics.
FX3U-4DA-ADP
Transfer the sequence program, and start the PLC.
After the PLC is started and the output characteristic write command (X000) is turned on, the offset
data and gain data will be written.
Since the offset data and gain data are stored in the EEPROM incorporated in FX3U-4DA, it is pos-
G
FX3G-1DA-BD
sible to delete the pre-written sequence program.
I
FX3U-4AD-PT
-ADP
J
FX3U-4AD-PTW
-ADP
E-55
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 8 Examples of Practical Programs
FX3U-4DA (4-channel Analog Output) 8.1 Example of Program for Analog Output Operation (Regular Operation)
1. Conditions
The sequence program described in this section is under the following conditions.
1) System configuration
FX3U-4DA (unit No.0) should be connected to the FX3U Series PLC.
2) Output mode
Channels 1 and 2 should be set to mode 0 (voltage output, -10 V to +10 V).
Channel 3 should be set to mode 3 (current output, 4 mA to 20 mA).
Channel 4 should be set to mode 2 (current output, 0 mA to 20 mA).
- For FX3U, FX3UC Series PLCs
Initial pulse
Transfer H2300 to BFM #0 (output modes of
M8002 channels 1 to 4).
FNC 12 H2300 U0\G0 ch1 and ch2: Voltage output (-10 to +10 V),
MOV P output mode 0
RUN monitor ch3: Current output (4 mA to 20 mA), output
M8000 mode 3
K50 * ch4: Current output (0 mA to 20 mA), output
T0 mode 2
Data to be output to channel 1 is written in D0. Store the data to be output to channels 1 to 4
Data to be output to channel 2 is written in D1. in D0 to D3 in the following ranges.
Data to be output to channel 3 is written in D2. D0 and D1: -32000 to +32000
Data to be output to channel 4 is written in D3. D2 and D3: 0 to 32000
Initial pulse
Transfer H2300 to BFM #0 (output modes of
M8002 channels 1 to 4).
FNC 79 K0 K0 H2300 K1 ch1 and ch2: Voltage output (-10 to +10 V),
TO P output mode 0
RUN monitor ch3: Current output (4 mA to 20 mA), output
M8000 mode 3
K50 * ch4: Current output (0 mA to 20 mA), output
T0 mode 2
Data to be output to channel 1 is written in D0. Store the data to be output to channels 1 to 4
Data to be output to channel 2 is written in D1. in D0 to D3 in the following ranges.
Data to be output to channel 3 is written in D2. D0 and D1: -32000 to +32000
Data to be output to channel 4 is written in D3. D2 and D3: 0 to 32000
E-56
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 8 Examples of Practical Programs
FX3U-4DA (4-channel Analog Output) 8.2 Example of Program using Useful Functions
A
8.2 Example of Program using Useful Functions
Common Items
This section describes a practical program that uses the disconnection detection function (BFM #28), upper/
lower limit function (BFM #38 to #48), corrective function by load resistance (BFM #50 to #54) and status
automatic transfer function (BFM #60 to #63) of FX3U-4DA.
1. Conditions
B
FX3UC-4AD
FX3U-4AD
The sequence program described in this section is created under the following conditions.
1) System configuration
FX3U-4DA (unit No.0) should be connected to the FX3U Series PLC.
2) Output mode
Channels 1 and 2 should be set to mode 0 (voltage output, -10 V to +10 V). C
Channels 3 and 4 should be set to mode 2 (current output, 0 mA to 20 mA).
FX3U-4AD-ADP
3) Convenient functions
The disconnection detection function, upper/lower limit function, corrective function by load resistance
and status automatic transfer function are used.
4) Device assignment
Device Description
D
FX3G-2AD-BD
X000 Clearance of upper/lower limit function status data
X001 Clearance of error status data
X002 Clearance of disconnection detection status data
Input D10 Data to be output from channel 1
D11 Data to be output from channel 2 E
FX3U-4DA
D12 Data to be output from channel 3
D13 Data to be output from channel 4
Y000 Output of channel-1 lower limit error data
Y001 Output of channel-1 upper limit error data
Y002 Output of channel-2 lower limit error data F
Y003 Output of channel-2 upper limit error data
FX3U-4DA-ADP
Y004 Output of channel-3 lower limit error data
Y005 Output of channel-3 upper limit error data
Y006 Output of channel-4 lower limit error data
Output Y007 Output of channel-4 upper limit error data
Y010 Output of disconnection detection signal
G
FX3G-1DA-BD
Y011 Output of error detection signal
D200 Data register at destination of automatic transfer of error status
Data register at destination of automatic transfer of upper/lower limit
D201
function error status
D202
Data register at destination of automatic transfer of disconnection detection H
error status
FX3U-3A-ADP
I
FX3U-4AD-PT
-ADP
J
FX3U-4AD-PTW
-ADP
E-57
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 8 Examples of Practical Programs
FX3U-4DA (4-channel Analog Output) 8.2 Example of Program using Useful Functions
Initial pulse
M8002
FNC 12 H2200 U0\G0 Output modes of channels 1 to 4 will be specified *1
RUN monitor MOV P
M8000
T0 K50 *2
T0
FNC 12 H1122 U0\G38 Upper/lower limit function setting
MOV P
FNC 16 K-3200 U0\G41 K2 Setting of lower limit values for channels 1 and 2
FMOV P
FNC 16 K6400 U0\G43 K2 Setting of lower limit values for channels 3 and 4
FMOV P
FNC 16 K28800 U0\G45 K2 Setting of upper limit values for channels 1 and 2
FMOV P
FNC 16 K25600 U0\G47 K2 Setting of upper limit values for channels 3 and 4
FMOV P
FNC 16 K5000 U0\G51 K2 Setting of load resistance values for channels 1 and 2 *1
FMOV P
D202.2
Disconnection detected in channels 3 and 4
Y010 Output to Y010
D202.3
D200.0
Y011 Error detected Output to Y011
*1. The output mode setting, setting of corrective function by load characteristics and status automatic
transfer function setting are retained in the EEPROM of FX 3U -4DA. For this reason, even if the
sequence program is deleted, the previously set functions will still be valid.
*2. After setting the output mode, set the data writing time (waiting time) to 5 seconds or more for each
setting. After the output mode is specified, and the same output mode is used, it is not necessary to
set the output mode and the waiting time (T0 K50).
E-58
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 8 Examples of Practical Programs
FX3U-4DA (4-channel Analog Output) 8.2 Example of Program using Useful Functions
A
• For FX3G, FX3U, FX3UC Series PLCs
Common Items
Initial pulse
M8002
FNC 79 K0 K0 H2200 K1 Output modes of channels 1 to 4 will be specified *1
RUN monitor TO P
M8000
K50 *2
B
T0
FX3UC-4AD
FX3U-4AD
T0
FNC 79 K0 K38 H1122 K1 Upper/lower limit function setting
TO P
FNC 79
TO P
K0 K41 K-3200 K2 Setting of lower limit values for channels 1 and 2
C
FX3U-4AD-ADP
FNC 79 K0 K43 K6400 K2 Setting of lower limit values for channels 3 and 4
TO P
FNC 79 K0 K45 K28800 K2 Setting of upper limit values for channels 1 and 2
TO P
FNC 79 K0 K47 K25600 K2 Setting of upper limit values for channels 3 and 4 D
TO P
FX3G-2AD-BD
FNC 79 K0 K50 H0011 K1 Corrective function setting by load resistance *1
TO P
FNC 79 K0 K51 K5000 K2 Setting of load resistance values for channels 1 and 2 *1
TO P
Status automatic transfer function setting *1
E
FNC 79
FX3U-4DA
K0 K60 H0007 K1 (The initial setting of destination data registers is used,
TO P and the sequence program for this function is omitted.)
X000
FNC 79 K0 K40 H0003 K1 Clearance of upper/lower limit function status data
TO P
X001
F
FNC 79 K0 K29 K0 K1 Clearance of error status data
TO P
FX3U-4DA-ADP
X002
FNC 79 K0 K28 K0 K1 Clearance of disconnection detection status data
TO P
RUN monitor
M8000
FNC 79 K0 K1 D10 K4 Transfer of data that will be output from channels 1 to 4
TO
FX3G-1DA-BD
FNC 12 D200 K4M0
MOV
M22
MOV
H
FX3U-3A-ADP
M0
Y011 Error detected Output to Y011
I
FX3U-4AD-PT
*1. The output mode setting, setting of corrective function by load characteristics and status automatic
transfer function setting are retained in the EEPROM of FX 3U -4DA. For this reason, even if the
sequence program is deleted, the previously set functions will still be valid.
-ADP
*2. After setting the output mode, set the data writing time (waiting time) to 5 seconds or more for each
setting. After the output mode is specified, and the same output mode is used, it is not necessary to J
set the output mode and the waiting time (T0 K50).
FX3U-4AD-PTW
-ADP
E-59
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 8 Examples of Practical Programs
FX3U-4DA (4-channel Analog Output) 8.3 Example of Program for Table Output Operation (Pattern Output Operation)
1. Conditions
The sequence program described in this section is under the following conditions.
1) System configuration
FX3U-4DA (unit No.0) should be connected to the FX3U Series PLC.
2) Output mode
Channel 1 should be set to mode 0 (voltage output, -10 V to +10 V).
Channel 3 should be set to mode 2 (current output, 0 mA to 20 mA).
Channels 2 and 4 are out of use.
3) Convenient function
The table output function is used.
4) Device assignment
Device Description
X000 Start of table output function for channels 1 and 3
X001 Stop of table output function
X002 Restart of table output function for channel 3
D10 Data to be output from channel 1
Input
D11 Data to be output from channel 2
D12 Data to be output from channel 3
D13 Data to be output from channel 4
D5000 or more Data table *
Y000 Completion of output of table from channel 1
Y001 Table output error
M0 Data table transfer complete
Output
M1 During output of table from channel 3
D100 Data table transfer command
D101 Table output completion flag
Initial pulse
M8002
FNC 12 HF2F0 U0\G0 Specification of output modes of channels 1 to 4 *1
MOV P
RUN monitor
M8000
T0 K50 *2
Continued
*1. The output mode setting is retained in the EEPROM of the FX3U-4DA. For this reason, even if the
sequence program is deleted, the previously set functions will still be valid.
*2. After setting the output mode, set the data writing time (waiting time) to 5 seconds or more for each
setting. After the output mode is specified, and the same output mode is used, it is not necessary to
set the output mode and the waiting time (T0 K50).
E-60
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 8 Examples of Practical Programs
FX3U-4DA (4-channel Analog Output) 8.3 Example of Program for Table Output Operation (Pattern Output Operation)
Common Items
T0
FNC 12 K1 U0\G81 Channel-1 output pattern
MOV P
FX3UC-4AD
FX3U-4AD
FNC 12 Number of repetitions of output of table
K5 U0\G85 from channel 1
MOV P
FX3U-4AD-ADP
K5000 U0\G98 Number of head device in data table
MOV P
FNC 79
FROM
K0 K99 D100 K1 Readout of data table transfer command D
FX3G-2AD-BD
D100.0
Turning-on of M0 At the completion of transfer
SET M0 of data table
X000
FNC 12 H0100 U0\G80 Start table output function (channel 3)
MOV P
Turning-on of M1 when table is output from E
SET M1 channel 3
FX3U-4DA
X000 M1
FNC 12 H0101 U0\G80 Start table output function (channel 1)
MOV P
X001 M1
FNC 12 H0000 U0\G80 Stop table output function
MOV P F
FX3U-4DA-ADP
Turning-off of M1 when output of table from
RST M1 channel 3 is stopped
X002 M1
FNC 12 H0100 U0\G80 Restart of table output function (channel 3)
MOV P
FX3G-1DA-BD
M1
FNC 79 K0 K89 D101 K2 Readout table output completion flag and table
FROM output error
D101.0
Y000 Completion of table output from channel 1
Output to Y000
FNC 228
H
K0 D102 Y001 Output to Y001 when table output error occurs
FX3U-3A-ADP
LD< >
* Execute the data table transfer command as a pulse execution type instruction.
I
FX3U-4AD-PT
-ADP
J
FX3U-4AD-PTW
-ADP
E-61
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 8 Examples of Practical Programs
FX3U-4DA (4-channel Analog Output) 8.3 Example of Program for Table Output Operation (Pattern Output Operation)
Initial pulse
M8002
FNC 79 K0 K0 HF2F0 K1 Specification of output modes of channels 1 to 4 *1
TO P
RUN monitor
M8000
T0 K50 *2
T0
FNC 79 K0 K81 K1 K1 Channel-1 output pattern
TO P
*1. The output mode setting is retained in the EEPROM of the FX3U-4DA. For this reason, even if the
sequence program is deleted, the previously set functions will still be valid.
*2. After setting the output mode, set the data writing time (waiting time) to 5 seconds or more for each
setting. After the output mode is specified, and the same output mode is used, it is not necessary to
set the output mode and the waiting time (T0 K50).
*3. Execute the data table transfer command as a pulse execution type instruction.
E-62
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 8 Examples of Practical Programs
FX3U-4DA (4-channel Analog Output) 8.4 Program to Initialize FX3U-4DA (Factory Default)
Common Items
M1
FNC 78 K0 K89 D101 K2 Readout table output completion flag and table
FROM output error
FNC 12
MOV
D101 K4M30 B
M30
FX3UC-4AD
FX3U-4AD
Y000 Completion of table output from channel 1
Output to Y000
FNC 228 K0 D102 Y001 Output to Y001 when table output error occurs
LD< >
C
FX3U-4AD-ADP
8.4 Program to Initialize FX3U-4DA (Factory Default)
To initialize FX3U-4DA, execute the following program.
This will return the output mode (BFM #0), the offset data (BFM #10 to #13) and the gain data (BFM #14 to
#17) will be to the factory default status state. D
FX3G-2AD-BD
1. Conditions
The sequence program described in this section is under the following conditions.
1) System configuration
FX3U-4DA (unit No.0) should be connected to the FX3U Series PLC.
2) Device assignment E
Device Description
FX3U-4DA
X000 4AD initialization command
FX3U-4DA-ADP
4DA initialization command
X000
FNC 12 K1 U0\G20 The 4DA will be initialized.
MOV P (BFM #0 to #3098 will be cleared.)
FX3G-1DA-BD
4DA initialization command
X000
FNC 79 K0 K20 K1 K1 The 4DA will be initialized.
TO P (BFM #0 to #3098 will be cleared.)
H
3. Cautions regarding initializing
FX3U-3A-ADP
• During initialization, output is stopped, and H0000 is automatically written in the output status (BFM #6).
At the completion of initialization, the output status (BFM #6) will automatically change to H1111, and the
output will be restarted.
• It takes approximately 5 seconds to complete initialization. Do not set (write) data in the buffer memory
during the period. I
• Priority is given to the setting of the change prohibition mode (BFM #19).
FX3U-4AD-PT
• Once initialization is completed, the value in BFM #20 will automatically change to "K0".
-ADP
J
FX3U-4AD-PTW
-ADP
E-63
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 9 Troubleshooting
FX3U-4DA (4-channel Analog Output) 9.1 PLC Version Number Check
9. Troubleshooting
This chapter describes the troubleshooting methods and error codes.
If the D/A conversion data is not output, or if the proper digital value is not output, check the following items:
• Wiring
• Program
• Error status
1. Power
FX3U-4DA needs driving power. Verify that the power supply line is properly connected. Also check that the
24 V indicator lamp of FX3U-4DA is on.
E-64
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 9 Troubleshooting
FX3U-4DA (4-channel Analog Output) 9.4 Error Status Check
A
9.4 Error Status Check
Common Items
When an error occurs in FX3U-4DA, the bit appropriate to the error is turned on in the error status (BFM #29).
Take measures, referring to the following table.
FX3UC-4AD
FX3U-4AD
b1 O/G error
b2 Power supply error
b3 Hardware error
b4 - C
b5 Error in setting of function for setting output upon PLC stop
FX3U-4AD-ADP
b6 Upper/lower limit function setting error
Error in corrective function setting by load resistance
b7
(Valid only in voltage output mode)
b8 Table output function setting error
b9 Status automatic transfer setting error
D
FX3G-2AD-BD
b10 Over-scale
b11 Disconnection detection (Valid only in current output mode)
b12 Setting data change prohibited
b13 to b15 -
E
1. Error detection (b0)
FX3U-4DA
1) Description of error
If any of b1 is turned on, this bit (b11) will turn on.
FX3U-4DA-ADP
2) Remedy
Check the output mode (BFM #0) and the offset and gain data (BFM #10 to #17).
FX3G-1DA-BD
24 V power is not correctly supplied.
2) Remedy
Check the wiring condition or the supply voltage.
5. Error when setting the function for output upon PLC stop (b5)
1) Description of error I
FX3U-4AD-PT
The bit will turn on when the functions setting value for setting output upon PLC stop is not correctly set.
2) Remedy
Check the output mode (BFM #0) and the setting value of output data upon PLC stop (BFM #32 to #35).
-ADP
J
FX3U-4AD-PTW
-ADP
E-65
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 9 Troubleshooting
FX3U-4DA (4-channel Analog Output) 9.5 FX3U-4DA Initialization and Test Program
E-66
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition
FX3U-4DA-ADP (4-channel analog Output)
Common Items
B
FX3UC-4AD
FX3U-4AD
FX3G/FX3U/FX3UC Series Programmable
Controllers C
FX3U-4AD-ADP
User's Manual [Analog Control Edition]
FX3U-4DA-ADP (4-channel analog Output)
D
FX3G-2AD-BD
E
FX3U-4DA
F
FX3U-4DA-ADP
G
FX3G-1DA-BD
H
FX3U-3A-ADP
Foreword
This manual describes the specifications, wiring, and operation method for the FX3U-4DA-ADP special
adapter (4-channel analog output) and should be read and understood before attempting to install or use the
unit. I
Store this manual in a safe place so that you can take it out and read it whenever necessary. Always forward
FX3U-4AD-PT
This manual confers no industrial property rights or any rights of any other kind, nor does it confer any patent
-ADP
licenses. Mitsubishi Electric Corporation cannot be held responsible for any problems involving industrial property
rights which may occur as a result of using the contents noted in this manual.
J
FX3U-4AD-PTW
F-1
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition
FX3U-4DA-ADP (4-channel analog Output)
F-2
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 1 Outline
FX3U-4DA-ADP (4-channel analog Output) 1.1 Outline of Functions
Common Items
1. Outline
This chapter outlines the FX3U-4DA-ADP (referred to as 4DA-ADP). B
FX3UC-4AD
FX3U-4AD
1.1 Outline of Functions
The FX3U-4DA-ADP is an analog special adapter. Which is connectable with the FX3U, FX3UC and FX3G
Series PLC to output the voltage/current data for up to 4 channels.
C
1) Up to 4 units of 4DA-ADP can be connected to the FX3U/FX3UC Series PLC.
FX3U-4AD-ADP
Up to 2*1 units of 4DA-ADP can be connected to the FX3G Series PLC.
(Including other analog special adapters).
2) Either "voltage output" or "current output" can be specified for each channel.
3) The D/A conversion results will be automatically output as the values to the special data register of the
FX3U/FX3UC/FX3G Series PLC. D
FX3G-2AD-BD
System Point and section to be
referred to
FX3U-4DA
To check the connectable
…… PLC model number, refer
+ + to Section 1.3.
FX3U-4DA-ADP
Expansion
4th 3rd 2nd 1st
adapter adapter adapter adapter board*2
For a detailed
…… description of wiring,
Analog data refer to Chapter 3.
Inverter, etc. G
FX3G-1DA-BD
For FX3U, FX3UC
Series PLC For a detailed description
Contents …… of special devices, refer to
H
Special devices Chapter 4.
Output mode Transfer direction 1st adapter M/D8260 to M/D8269
For a detailed description
FX3U-3A-ADP
Refer to the system configuration shown in the User's Manual - Hardware Edition to check the number of connectable units
and to configure the entire system. I
FX3U-4AD-PT
*1. Only 1 analog special adapter can be connected to the FX3G Series PLC(14-point and 24-point type).
*2. The expansion board is not required when connecting with the FX3UC (D, DSS) PLC.
For the FX3G Series PLC a connector conversion adapter is used.
-ADP
J
FX3U-4AD-PTW
-ADP
F-3
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 1 Outline
FX3U-4DA-ADP (4-channel analog Output) 1.2 Setup Procedure Before Starting Operation
FX3U-4DA-ADP
Refer to Chapter 1.
Wiring Wiring:
• Power supply line
• Analog output line
Refer to Chapter 4.
Programming:
Programming
• Details of special devices
• Examples of basic programs
Refer to Chapter 5.
F-4
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 1 Outline
FX3U-4DA-ADP (4-channel analog Output) 1.3 Connectable PLCs and Version Numbers
A
1.3 Connectable PLCs and Version Numbers
Common Items
The 4DA-ADP is compatible with the following PLCs.
FX3UC-4AD
FX3U-4AD
FX3UC Series PLC Ver.1.20 or later*1 After April 2004
FX3G Series PLC Ver.1.00 or later*1 After June 2008 (initial production)
*1. The FX3U/FX3UC Series PLC version 2.61 or later and FX3G Series PLC version 1.20 or later supports
hardware error check.
The FX3UC-32MT-LT-2 PLC is due to be upgraded later. C
→ For a detailed description of hardware error, refer to Section 6.5.
FX3U-4AD-ADP
1. Version check
Special data register D8001 contains information for determining the PLC version number.
→ For a detailed description of the version check, refer to A. Common Items Subsection 5.1.2.
FX3G-2AD-BD
The year and month of production of the product can be checked on the nameplate, and on the front of the
product.
→ For a detailed description of the How to look at the manufacturer's serial number,
refer to A. Common Items Subsection 5.1.1.
E
1.4 Compatible Programming Tool Version Number
FX3U-4DA
Use the programming tool with the following version number to create programs for the 4DA-ADP of the
FX3U/FX3UC/FX3G Series PLC:
1. GX Developer
F
Software Version number Remarks
FX3U-4DA-ADP
GX Developer Ver.SW8 P or later
(Ver.8.13P) When selecting a model, select FX3U(C)*2
• SW D5C-GPPW-J
• SW D5C-GPPW-E Ver. 8.72A or later When selecting a model, select FX3G.
If a programming tool with the wrong version number is used, programming will not be possible.
G
FX3G-1DA-BD
*2. For Ver. 8.13P to 8.24A of GX Developer, select FX3UC for the PLC type.
1. FX-30P
Model name Version number Remarks
FX-30P Ver.1.00 or later H
FX3U-3A-ADP
I
FX3U-4AD-PT
-ADP
J
FX3U-4AD-PTW
-ADP
F-5
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 2 Specifications
FX3U-4DA-ADP (4-channel analog Output) 2.1 Generic Specifications
2. Specifications
This chapter describes the general, power supply, and performance specifications for 4DA-ADP.
Item Specifications
Ambient 0 to 55°C (32 to 131°F) when operating
temperature -25 to 75°C (-13 to 167°F) when stored
Relative
5 to 95%RH (no condensation) when operating
humidity
Frequency Acceleration Half amplitude
(Hz) (m/s2) (mm)
10 times of testing in
Vibration 10 - 57 - 0.035 each direction (X-, Y-,
DIN Rail Mounting
resistance*1 57 - 150 4.9 - and Z-axis directions)
(Total: 80 min, each)
10 to 57 − 0.075
Direct Mounting*2
57 to 150 9.8 −
Shock
147 m/s2 Acceleration, Action time: 11ms, 3 times by half-sine pulse in each direction X, Y, and Z
resistance*1
Noise Using noise simulator of:
resistance Noise voltage: 1,000Vp-p / Noise width: 1μs / Rise: 1ns / Cycle: 30 to 100Hz
Dielectric
withstand 500 V AC, for 1 min
voltage Between all terminals and ground terminal
Insulation 5MΩ or more using 500V DC
resistance insulation resistance meter
Class D grounding (grounding resistance: 100 Ω or less)
Grounding
<Common grounding with a heavy electrical system is not allowed.>*3
Working
Free from corrosive or flammable gas and excessive conductive dusts
environment
Working
< 2000m*4
altitude
*3.
PLC Other PLC Other PLC Other
equipment equipment equipment
F-6
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 2 Specifications
FX3U-4DA-ADP (4-channel analog Output) 2.2 Power Supply Specifications
A
2.2 Power Supply Specifications
Common Items
Item Specifications
D/A conversion circuit 24V DC +20%-15%, 150mA B
driving power (It is necessary to connect a 24V DC power line to the terminal block.)
FX3UC-4AD
FX3U-4AD
5V DC, 15mA
Interface driving power (Since the internal power is supplied from the main unit of the FX Series, it is not
necessary to supply the power.)
FX3U-4AD-ADP
Specifications
Item
Voltage output Current output
D
Analog output 0V to 10 V DC 4mA to 20mA DC
FX3G-2AD-BD
range (External load: 5kΩ to 1MΩ) (External load: 500Ω or less)
Digital input 12 bits, binary
Resolution 2.5mV(10V/4000) 4μA(16mA/4000)
• ±0.5% (±50mV) for 10V full scale
(when ambient temperature is 25°C±5 °C) E
• ±1.0% (±100mV) for 10V full scale
FX3U-4DA
(when ambient temperature is 0°C to 55°C)
• ±0.5% (±80μA) for 16mA full scale
If the external load resistance (Rs) is less than (when ambient temperature is 25°C±5°C)
Total accuracy
5kΩ, the value calculated from the following • ±1.0% (±160μA) for 16mA full scale
formula will be added: (when ambient temperature is 0°C to 55 °C)
(Addition will be 100mV per 1%.) F
FX3U-4DA-ADP
47×100
-0.9(%)
Rs+47
• FX3U/FX3UC Series PLC : 200μs (The data will be updated at every scan time.)
D/A conversion
• FX3G Series PLC : 250μs (The data will be updated at every scan time.)
time
→ For a detailed description of data update, refer to Section 2.4. G
FX3G-1DA-BD
10V 20mA
Analog output
H
Analog output
Output
characteristics
FX3U-3A-ADP
4mA
• The photocoupler is used to insulate the analog output area from the PLC.
Insulation method • The DC/DC converter is used to insulate the power supply line from the analog output area.
• Channels are not insulated from each other.
-ADP
Numbers of I/O
0 point (This number is not related to the maximum number of input/output points of the PLC.)
points occupied
J
FX3U-4AD-PTW
-ADP
F-7
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 2 Specifications
FX3U-4DA-ADP (4-channel analog Output) 2.4 D/A Conversion Time
FX3U-4DA-ADP FX3U-4DA-ADP
n'th 1st FX3U/FX3UC Series PLC
Sequence
program
Digital value
D/A writing
conversion
D/A conversion
200μs start command
/4ch
END instruction
D/A Digital value writing
conversion
D/A conversion
200μs/4ch start command
F-8
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 2 Specifications
FX3U-4DA-ADP (4-channel analog Output) 2.4 D/A Conversion Time
A
2.4.2 When connected to a FX3G PLC
Common Items
1. D/A conversion and special data register update timing
D/A conversion is performed at every scan time of the PLC.
During execution of the END instruction, the PLC writes the output setting data of the special data registers,
performs D/A conversion of the data, and updates the analog output data. B
FX3UC-4AD
FX3U-4AD
FX3U-4DA-ADP FX3U-4DA-ADP
2nd 1st FX3G Series PLC
Sequence
program
C
FX3U-4AD-ADP
Digital value
D/A writing
conversion
D/A conversion
250μs start command
/4ch
END instruction
D/A Digital value writing D
conversion
FX3G-2AD-BD
D/A conversion
250μs/4ch start command
FX3U-4DA
output.
If the output holding function cancellation setting is enabled, the output at switching from RUN to STOP will be
latched.
Just after power-on, however, the offset value will be output until operation begins.
FX3U-4DA-ADP
During execution of the END instruction, data in all the connected adapters will be subject to D/A conversion
and then output (in the order of 1st adapter → 2nd adapter).
FX3G-1DA-BD
H
FX3U-3A-ADP
I
FX3U-4AD-PT
-ADP
J
FX3U-4AD-PTW
-ADP
F-9
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 3 Wiring
FX3U-4DA-ADP (4-channel analog Output)
3. Wiring
This chapter describes the 4DA-ADP wiring.
Observe the following caution to wire the 4DA-ADP.
WIRING PRECAUTIONS
• Make sure to cut off all phases of the power supply externally before attempting wiring work.
Failure to do so may cause electric shock or damages to the product.
WIRING PRECAUTIONS
• Connect the DC power supply wiring to the dedicated terminals described in this manual.
If an AC power supply is connected to a DC input/output terminal or DC power supply terminal, the PLC will be
burnt out.
• Do not wire vacant terminals externally.
Doing so may damage the product.
• Perform class D grounding (grounding resistance: 100Ω or less) to the grounding terminal on the main unit.
Do not use common grounding with heavy electrical systems.
• When drilling screw holes or wiring, make sure cutting or wire debris does not enter the ventilation slits.
Failure to do so may cause fire, equipment failures or malfunctions.
• Make sure to observe the following precautions in order to prevent malfunctions under the influence of noise:
- Do not bundle the power line or twisted shielded cable together with or lay it close to the main circuit, high-
voltage line, or load line.
Otherwise, noise disturbance and/or surge induction are likely to take place. As a guideline, lay the control line
at least 100mm (3.94") or more away from the main circuit, high-voltage line, or load line.
- Ground the shield of the analog input/output cable at one point on the signal receiving side.
However, do not use common grounding with heavy electrical systems.
• Make sure to properly wire to the European terminal board in accordance with the following precautions.
Failure to do so may cause electric shock, a short-circuit, wire breakage, or damage to the product.
- The disposal size of the cable end should be 9 mm (0.35").
- Tightening torque should be between 0.22 to 0.25 N•m.
- Twist the end of strand wire and make sure there are no loose wires.
- Do not solder-plate the electric wire ends.
- Do not connect more than the specified number of wires or electric wires of unspecified size.
- Affix the electric wires so that neither the terminal block nor the connected parts are directly stressed.
F-10
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 3 Wiring
FX3U-4DA-ADP (4-channel analog Output) 3.1 Terminal Layout
A
3.1 Terminal Layout
Common Items
The terminals of the 4DA-ADP are arranged as follows:
FX3UC-4AD
FX3U-4AD
FX3U-4DA-ADP
POWER
Signal Application
24+
C
External power
24+
FX3U-4AD-ADP
24-
24-
Grounding terminal
V1+
VI+
COM1
V2+ D
I2+ Channel 2 analog output
V3+ COM2 I2+
FX3G-2AD-BD
COM2
V3+
I3+ Channel 3 analog output
V4+ COM3 I3+
COM3
V4+
I4+ Channel 4 analog output E
I4+
FX3U-4DA
COM4
COM4
FX3U-4DA-ADP
G
FX3G-1DA-BD
H
FX3U-3A-ADP
I
FX3U-4AD-PT
-ADP
J
FX3U-4AD-PTW
-ADP
F-11
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 3 Wiring
FX3U-4DA-ADP (4-channel analog Output) 3.2 Applicable Cables and Terminal Tightening Torque
1. Cable
Applicable cable and tightening torque
Wire size (stranded/ Tightening
Termination
single-wire) torque
0.3mm2 to 0.5mm2 • To connect a stranded cable, peel the cover off the cable
Single-wire and then twist the core before connection.
(AWG22 to 20)
• To connect a single-wire cable, just peel the cover off the
2-wire 0.3mm2(AWG22) cable before connection.
0.22N•m to • Rod terminal with insulation sleeve
Rod terminal 0.3mm2 to 0.5mm2 0.25N•m (recommended terminal)
with (AWG22 to 20) AI 0.5-8WH : Manufactured by Phoenix Contact
insulation (Refer to the rod terminal
• Caulking tool
sleeve external view shown in
CRIMPFOX ZA 3 : Manufactured by Phoenix Contact
the following figure.)
(or CRIMPFOX UD 6 : Manufactured by Phoenix Contact)
3. Tool
• To tighten terminals, use a small-sized screwdriver whose head is straight and is not widened as shown in
the figure to the right.
Note:
If the diameter of screwdriver grip is too small, tightening torque will not
The head
be able to be achieved. Use the following recommended screwdriver or should be
an appropriate replacement (grip diameter: approximately 25mm). straight.
Manufacturer Model
Phoenix Contact SZS 0.4×2.5 0.4mm 2.5mm
(0.01") (0.09")
F-12
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 3 Wiring
FX3U-4DA-ADP (4-channel analog Output) 3.3 Power Supply Line
A
3.3 Power Supply Line
Common Items
Connect the 24V DC power supply line of the 4DA-ADP to the 24+ and 24- terminals of the terminal block.
FX3UC-4AD
FX3U-4AD
1. To use an External power supply 2. To use the 24V DC power of the PLC
FX3U-4AD-ADP
24- 24+ 24- 24+ 0V 24V D
FX3G-2AD-BD
Terminal Terminal
block block
Class-D Class-D
24V DC grounding grounding
E
Caution regarding connection of the power supply line:
FX3U-4DA
• Ground the " " terminal to class-D grounded power supply line (100Ω or less) together with the
grounding terminal of the PLC main unit.
• For the timing of power-on/off when using an external power supply, see the following manual of the PLC
to be connected.
→ Refer to the FX3G Series User's Manual - Hardware Edition. F
→ Refer to the FX3U Series User's Manual - Hardware Edition.
FX3U-4DA-ADP
3.3.2 To Connect To the FX3UC Series PLC
FX3G-1DA-BD
Power H
Power Power crossover
FX3U-3A-ADP
Class-D
24V DC grounding
-ADP
• Ground the " " terminal to a class-D grounded power supply line (100Ω or less) together with the
grounding terminal of the PLC main unit.
-ADP
F-13
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 3 Wiring
FX3U-4DA-ADP (4-channel analog Output) 3.4 Analog Output Line
Class-D
grounding
*1. Use 2-core shielded twisted pair cable for the analog output lines, and separate the analog output
lines from other power lines or inductive lines.
*2. 24V DC service power supply of the FX3G/FX3U Series PLC can also be used.
*3. Ground the shielded wire at one point on the signal receiving side.
3.5 Grounding
Grounding should be performed as stated below.
• The grounding resistance should be 100Ω or less.
• Independent grounding should be performed for best results.
When independent grounding is not performed, perform "shared grounding" as shown in the following
figure.
→ For details, refer to User’s Manual - Hardware Edition of the PLC Series.
F-14
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 4 Programming
FX3U-4DA-ADP (4-channel analog Output) 4.1 Writing of D/A Conversion Data
Common Items
4. Programming
This chapter describes how to create programs that can output the analog data using the 4DA-ADP. B
FX3UC-4AD
FX3U-4AD
4.1 Writing of D/A Conversion Data
1) The input digital data will be converted into analog data and then output to the terminals.
2) If data is stored in the special devices, the averaging time can be set, and the output mode can be C
specified.
FX3U-4AD-ADP
3) Special auxiliary relays (10 points) and special data registers (10 points) are assigned automatically
starting from the adapter nearest the main unit.
→ For a detailed description of special device assignment, refer to Section 4.2.
• FX3U, FX3UC Series PLC
Communi- High-speed
D
cation
FX3G-2AD-BD
input/output
FX3U-4DA FX3U-4DA FX3U-4DA special FX3U-4DA special
-ADP -ADP -ADP adapter -ADP adapter FX3U/FX3UC Series PLC
D/A
Special auxiliary relays:
M8260 to M8269 E
Special data registers:
FX3U-4DA
D8260 to D8269
FX3U-4DA-ADP
M8280 to M8289
D/A Special data registers:
D8280 to D8289
FX3G-1DA-BD
The analog special adapter nearest to the main unit is counted as the 1st analog special adapter, and the
next adapter as the 2nd analog special adapter, and so on. In this case, however, do not include the high-
speed input/output special adapter, communication special adapter, and the CF card special adapter.
H
FX3U-3A-ADP
I
FX3U-4AD-PT
-ADP
J
FX3U-4AD-PTW
-ADP
F-15
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 4 Programming
FX3U-4DA-ADP (4-channel analog Output) 4.1 Writing of D/A Conversion Data
2nd*1 1st
Special devices
Special auxiliary relays:
M8280 to M8289
D/A Special data registers:
D8280 to D8289 Sequence
Program
Special auxiliary relays:
M8290 to M8299
D/A Special data registers:
D8290 to D8299
The analog special adapter nearest to the main unit is counted as the 1st analog special adapter, and the
next adapter as the 2nd analog special adapter. In this case, however, do not include the connector
conversion adapter and the communication special adapter.
*1. The second special adapter is not available in the FX3G Series PLC(14-point and 24-point type).
F-16
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 4 Programming
FX3U-4DA-ADP (4-channel analog Output) 4.2 List of Special Devices
A
4.2 List of Special Devices
Common Items
If 4DA-ADP is connected, special devices will be assigned automatically as shown in the following table:
• FX3U, FX3UC Series PLC
R: Read / W: Write
Special Device number
B
Description Attribute Reference
FX3UC-4AD
FX3U-4AD
device 1st 2nd 3rd 4th
M8260 M8270 M8280 M8290 Switches the output mode of channel 1. R/W
M8261 M8271 M8281 M8291 Switches the output mode of channel 2. R/W Section
M8262 M8272 M8282 M8292 Switches the output mode of channel 3. R/W 4.3
M8263 M8273 M8283 M8293 Switches the output mode of channel 4. R/W C
FX3U-4AD-ADP
Sets the cancel of the channel-1 output
M8264 M8274 M8284 M8294 R/W
holding function.
Special
auxiliary Sets the cancel of the channel-2 output
M8265 M8275 M8285 M8295 R/W
relay holding function. Section
Sets the cancel of the channel-3 output 4.4
M8266 M8276 M8286 M8296
holding function.
R/W D
FX3G-2AD-BD
Sets the cancel of the channel-4 output
M8267 M8277 M8287 M8297 R/W
holding function.
M8268 to M8278 to M8288 to M8298 to
Unused (Do not use.) - -
M8269 M8279 M8289 M8299
D8260 D8270 D8280 D8290 Channel-1 output setting data R/W
D8261 D8271 D8281 D8291 Channel-2 output setting data R/W Section
E
FX3U-4DA
D8262 D8272 D8282 D8292 Channel-3 output setting data R/W 4.5
D8263 D8273 D8283 D8293 Channel-4 output setting data R/W
Special
data D8264 to D8274 to D8284 to D8294 to
Unused (Do not use.) - -
register D8267 D8277 D8287 D8297
FX3U-4DA-ADP
Section
D8269 D8279 D8289 D8299 Model code = 2 R
4.7
FX3G-1DA-BD
H
FX3U-3A-ADP
I
FX3U-4AD-PT
-ADP
J
FX3U-4AD-PTW
-ADP
F-17
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 4 Programming
FX3U-4DA-ADP (4-channel analog Output) 4.3 Switching of Output Mode
F-18
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 4 Programming
FX3U-4DA-ADP (4-channel analog Output) 4.4 Output Holding Function Cancellation Setting
A
1. Program Example (For FX3U, FX3UC Series PLC)
Common Items
To switch the output mode of a channel, create a sequence program as follows:
1) To switch the channel output mode of 2) To switch the output mode of channel 2
channel 1 of the 1st analog special of the 1st analog special adapter to the
adapter to the voltage output mode: current output mode:
M8001 M8000 B
M8260 M8261
FX3UC-4AD
FX3U-4AD
Normally OFF Normally ON
FX3U-4AD-ADP
This setting can hold the analog data output or to output the offset data (0V for voltage output mode, 4mA for
current output mode) when the PLC stops.
To cancel or set the output holding function, use the following special auxiliary relays:
• FX3U, FX3UC Series PLC
Special auxiliary relay
D
Description
FX3G-2AD-BD
1st 2nd 3rd 4th
Cancel output holding function
M8264 M8274 M8284 M8294
setting for channel 1
Cancel output holding function OFF: Holds the analog data output
M8265 M8275 M8285 M8295
setting for channel 2 just before stop of the PLC. E
Cancel output holding function ON : Outputs the offset data at
FX3U-4DA
M8266 M8276 M8286 M8296 stop of the PLC.
setting for channel 3
Cancel output holding function
M8267 M8277 M8287 M8297
setting for channel 4
F
• FX3G Series PLC
FX3U-4DA-ADP
Special auxiliary relay
Description
1st 2nd
Cancel output holding function
M8284 M8294
setting for channel 1
Cancel output holding function OFF: Holds the analog data output
G
M8285 M8295
FX3G-1DA-BD
setting for channel 2 just before stop of the PLC.
Cancel output holding function ON : Outputs the offset data at
M8286 M8296 stop of the PLC.
setting for channel 3
Cancel output holding function
M8287 M8297
setting for channel 4
H
FX3U-3A-ADP
M8264 M8265
Normally OFF Normally ON
-ADP
J
FX3U-4AD-PTW
-ADP
F-19
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 4 Programming
FX3U-4DA-ADP (4-channel analog Output) 4.5 Output Setting Data
Using the indicator or the sequence program, input the digital data to be subject to D/A conversion (to be
output as analog data) in D100 and D101.
F-20
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 4 Programming
FX3U-4DA-ADP (4-channel analog Output) 4.6 Error Status
A
4.6 Error Status
Common Items
1. Description of setting
If an error is detected on 4DA-ADP, the error status data will be stored in the corresponding special data
register.
The following table shows the special data registers that store the error status data:
B
FX3UC-4AD
FX3U-4AD
• FX3U, FX3UC Series PLC
FX3U-4AD-ADP
• FX3G Series PLC
FX3G-2AD-BD
Check the ON/OFF status of each bit of the error status data register to check the description of the error.
Errors are assigned to the bits as shown in the following table. Create a program to detect errors.
Bit Description
b0 Channel-1 output data setting error E
FX3U-4DA
b1 Channel-2 output data setting error
b2 Channel-3 output data setting error
b3 Channel-4 output data setting error
b4 EEPROM error
b5 Unused F
FX3U-4DA-ADP
b6 4DA-ADP hardware error (Power supply error included)*1
b7 to b15 Unused
FX3G-1DA-BD
2. Program Example 1 (For FX3G, FX3U, FX3UC Series PLC)
M8000
MOV D8288 K4M0
Normally
ON
M0
H
FX3U-3A-ADP
M2 I
FX3U-4AD-PT
M4 J
Y004 EEPROM error in the 3rd *2 adapter
FX3U-4AD-PTW
F-21
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 4 Programming
FX3U-4DA-ADP (4-channel analog Output) 4.6 Error Status
D8268.0
Y000 Channel-1 output data setting error in
1st adapter
D8268.1
Y001 Channel-2 output data setting error in
1st adapter
D8268.2
Y002 Channel-3 output data setting error in
1st adapter
D8268.3
Y003 Channel-4 output data setting error in
1st adapter
D8268.4
Y004 EEPROM error in 1st adapter
F-22
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 4 Programming
FX3U-4DA-ADP (4-channel analog Output) 4.7 Model Code
A
4.7 Model Code
Common Items
Initial value: K2
Numeric data type: Decimal (K)
1. Description of setting B
When the 4DA-ADP is connected, model code "2" is stored in the corresponding special data register.
FX3UC-4AD
FX3U-4AD
The following table shows the special data registers that store the model code:
• FX3U, FX3UC Series PLC
1st 2nd 3rd 4th Description
D8269 D8279 D8289 D8299 Model code C
FX3U-4AD-ADP
• FX3G Series PLC
1st 2nd Description
D8289 D8299 Model code
Use the special data registers above to check whether 4DA-ADP is connected or not. D
FX3G-2AD-BD
2. Program Example (For FX3U, FX3UC Series PLC)
Checks the model code
FNC 224 D8269 K2 Y007 of the 1st analog special
LD = adapter.
E
FX3U-4DA
4.8 Basic Program Example
Create the following basic program example to output D/A converted analog data.
• For FX3G, FX3U, FX3UC Series PLC
The following program will set channel 1 of the 3rd*1 adapter to the voltage output mode and channel 2 to
F
FX3U-4DA-ADP
current output mode, and will set digital data in D100 and D101 for D/A conversion.
M8001
M8280 Sets the output mode of channel 1 to the voltage
output mode (0 V to 10 V).
FX3G-1DA-BD
M8000
M8281 Sets the output mode of channel 2 to the current
output mode (4 mA to 20 mA).
M8000
FNC 12 Performs D/A conversion with the digital data stored
H
D100 D8280
FX3U-3A-ADP
FNC 12 D101 D8281 Performs D/A conversion with the digital data stored
MOV in D101 for channel 2.
Using the indicator or the sequence program, input the digital data to be subject to D/A conversion (to be
output as analog data) in D100 and D101. I
FX3U-4AD-PT
J
FX3U-4AD-PTW
-ADP
F-23
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 5 Changing of Output Characteristics
FX3U-4DA-ADP (4-channel analog Output) 5.1 Example: Changing of Voltage Output Characteristics
1. Output characteristics
to be changed
value to be actually
10V
Analog output
Y-axis
5V 2000
(5V)
1V 400
(1V)
0 400 2000 4000 X-axis
0 10000
Digital value input
Desired digital value (D100)
M8002
FNC 12 Program for setting scaling instruction data table
K2 D50
MOV
Item Description Value Device
FNC 12 Number of points Sets the number of points. 2 D50
K0 D51
MOV X- Digital value of specified 0 D51
Start coordinate start point on X-axis
FNC 12 point Y- Digital value of desired D/A
K400 D52 400 D52
MOV coordinate conversion start point
X- Digital value of specified end 10000 D53
FNC 12 K10000 D53 End coordinate point on X-axis
MOV point Y- Digital value of desired D/A 2000
coordinate conversion end point D54
FNC 12 K2000 D54
MOV
M8000 The result of operation by scaling instruction will be stored
FNC 259 D100 D50 D8260
SCL in the D8260.
F-24
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 5 Changing of Output Characteristics
FX3U-4DA-ADP (4-channel analog Output) 5.1 Example: Changing of Voltage Output Characteristics
A
3. Example of program 2 (For FX3G Series PLC)
Common Items
• For example, create the following program to change the digital output data (D100) of the 1st analog
special adapter.
M8001
Sets the output mode of channel 1 to the
M8280
voltage output mode. B
FX3UC-4AD
FX3U-4AD
Sets the output holding function for
M8284
channel 1.
FNC 230 D100 K0 FNC 237 D100 K10000 M10 Check to make sure the digital
LD>= AND<= value (D100) is in range.
M10 C
FNC 22
FX3U-4AD-ADP
D100 K1600 D101
MUL
D
FNC 20 D103 K400 D107 Stores the operation result in D8280.
ADD
FX3G-2AD-BD
FNC 12 D107 D8280
MOV
FX3U-4DA
• If the input digital value for the D/A conversion is out of the data table range specified by scaling instruction
(SCL/FNC259), the FX Series PLC will detect an operation error (error code: K6706).
FX3U-4DA-ADP
G
FX3G-1DA-BD
H
FX3U-3A-ADP
I
FX3U-4AD-PT
-ADP
J
FX3U-4AD-PTW
-ADP
F-25
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 6 Troubleshooting
FX3U-4DA-ADP (4-channel analog Output) 6.1 PLC Version Number Check
6. Troubleshooting
This chapter describes the troubleshooting methods and error status.
If analog data is not output, or if the proper analog value is not output, check the following items:
• Version number of PLC
• Wiring
• Special devices
• Programs
• Error status
1. Power
The 4DA-ADP needs driving power. Verify that the power supply line is properly connected. Also check that
the POWER indicator lamp of the 4DA-ADP is on.
3. Error status
Check that no error is detected in the 4DA-ADP.
If an error is detected, check the details of the error, and then check the wiring and programs.
→ For a detailed description of special devices, refer to Chapter 4.
F-26
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 6 Troubleshooting
FX3U-4DA-ADP (4-channel analog Output) 6.4 Program Check
A
6.4 Program Check
Common Items
Check the following items for the program:
FX3UC-4AD
FX3U-4AD
6.5 Error Status Check
If an error occurs in the 4DA-ADP, the corresponding bit will turn on.
Bit Description C
FX3U-4AD-ADP
b0 Channel-1 output data setting error
b1 Channel-2 output data setting error
b2 Channel-3 output data setting error
b3 Channel-4 output data setting error
b4 EEPROM error D
FX3G-2AD-BD
b5 Unused
b6 4DA-ADP hardware error (Power supply error included)*1
b7 to b15 Unused
FX3U-4DA
4DA-ADP FX3U, FX3UC Series PLC FX3G Series PLC
year and month of Former than Former than
production Ver2.61 or later Ver1.20 or later
Ver2.60 Ver1.10
Former than
Not applicable Not applicable Not applicable Not applicable
F
2009 May
FX3U-4DA-ADP
2009 June
Not applicable Applicable Not applicable Applicable
or later
For confirmation of the version of the main unit and checking the 4DA-ADP serial number, refer to the
following.
→ For details of confirmation of the PLC main unit version, G
refer to A. Common Items Subsection 5.1.2.
FX3G-1DA-BD
→ For details of check of the 4DA-ADP serial number,
refer to A. Common Items Subsection 5.2.1.
To solve the problem, refer to the troubleshooting method described below:
1) Description of error
The adjustment data set in the EEPROM before delivery from our factory cannot be read out properly or
is destroyed.
-ADP
2) Remedy
Please contact the nearest Mitsubishi Electric distributor office. J
FX3U-4AD-PTW
-ADP
F-27
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 6 Troubleshooting
FX3U-4DA-ADP (4-channel analog Output) 6.5 Error Status Check
F-28
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition
FX3G-1DA-BD (1-channel analog Output)
Common Items
B
FX3UC-4AD
FX3U-4AD
FX3G/FX3U/FX3UC Series Programmable
Controllers C
FX3U-4AD-ADP
User's Manual [Analog Control Edition]
FX3G-1DA-BD (1-channel analog Output)
D
FX3G-2AD-BD
E
FX3U-4DA
F
FX3U-4DA-ADP
G
FX3G-1DA-BD
H
FX3U-3A-ADP
Foreword
This manual describes the specifications, wiring, and operation method for the FX3G-1DA-BD analog output
expansion board (1-channel analog output) and should be read and understood before attempting to install or
use the unit. I
Store this manual in a safe place so that you can take it out and read it whenever necessary. Always forward
FX3U-4AD-PT
This manual confers no industrial property rights or any rights of any other kind, nor does it confer any patent
licenses. Mitsubishi Electric Corporation cannot be held responsible for any problems involving industrial property
rights which may occur as a result of using the contents noted in this manual. J
FX3U-4AD-PTW
G-1
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition
FX3G-1DA-BD (1-channel analog Output)
G-2
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 1 Outline
FX3G-1DA-BD (1-channel analog Output) 1.1 Outline of Functions
Common Items
1. Outline
This chapter outlines the FX3G-1DA-BD (referred to as 1DA-BD). B
FX3UC-4AD
FX3U-4AD
1.1 Outline of Functions
The FX3G-1DA-BD is an analog expansion board. Which is connectable with the FX3G Series PLC to output
the voltage/current data for up to 1 channel.
C
1) Up to 2*1 units of 1DA-BD can be connected to the FX3G Series PLC.
FX3U-4AD-ADP
(Including other analog expansion boards, analog special adapters).
2) Either "voltage output" or "current output" can be specified.
3) The D/A conversion results will be automatically output as the values to the special data register of the
FX3G Series PLC.
D
FX3G-2AD-BD
System Point and section to be
referred to
2*1 maximum
( (
Number of connectable
including other analog expansion ……
units
boards, analog special adapters. FX3G Series PLC
E
FX3U-4DA
2nd 1st To check the connectable
…… PLC model number, refer
to Section 1.3.
FX3U-4DA-ADP
Analog data Connected to the option connector 2
For a detailed
…… description of wiring,
refer to Chapter 3.
Inverter, etc.
G
FX3G-1DA-BD
For a detailed description
Contents For FX3G Series PLC …… of special devices, refer to
Chapter 4.
Output mode
switching
Transfer direction
1st board
Special devices
M/D8260 to M/D8269
For a detailed description
of a basic program, refer to
H
Output setting data
FX3U-3A-ADP
Section 4.8.
2nd board M/D8270 to M/D8279
Error status
Refer to the system configuration shown in the User's Manual - Hardware Edition to check the number of connectable units
and to configure the entire system.
*1. Only 1 analog board can be connected to the FX3G Series PLC(14-point and 24-point type).
I
FX3U-4AD-PT
-ADP
J
FX3U-4AD-PTW
-ADP
G-3
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 1 Outline
FX3G-1DA-BD (1-channel analog Output) 1.2 Setup Procedure Before Starting Operation
FX3G-1DA-BD
Refer to Chapter 1.
Wiring Wiring:
• Power supply line
• Analog output line
Refer to Chapter 4.
Programming:
Programming
• Details of special devices
• Examples of basic programs
Refer to Chapter 5.
G-4
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 1 Outline
FX3G-1DA-BD (1-channel analog Output) 1.3 Connectable PLCs and Version Numbers
A
1.3 Connectable PLCs and Version Numbers
Common Items
The 1DA-BD is compatible with the following PLC.
FX3UC-4AD
FX3U-4AD
1. Version check
Special data register D8001 contains information for determining the PLC version number.
→ For a detailed description of the version check, refer to A.Common Items Subsection 5.1.2.
C
2. How to look at the manufacturer's serial number
FX3U-4AD-ADP
The year and month of production of the product can be checked on the nameplate, and on the front of the
product.
→ For a detailed description of the How to look at the manufacturer's serial number,
refer to A.Common Items Subsection 5.1.1.
D
1.4 Compatible Programming Tool Version Number
FX3G-2AD-BD
Use the programming tool with the following version number to create programs for the 1DA-BD of the FX3G
Series PLC:
1. GX Developer E
Software Version number Remarks
FX3U-4DA
GX Developer
• SW D5C-GPPW-J Ver. 8.72A or later When selecting a model, select FX3G.
• SW D5C-GPPW-E
If a programming tool with the wrong version number is used, programming will not be possible.
F
FX3U-4DA-ADP
2. FX-30P
Model name Version number Remarks
FX-30P Ver.1.00 or later
G
FX3G-1DA-BD
H
FX3U-3A-ADP
I
FX3U-4AD-PT
-ADP
J
FX3U-4AD-PTW
-ADP
G-5
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 2 Specifications
FX3G-1DA-BD (1-channel analog Output) 2.1 Generic Specifications
2. Specifications
This chapter describes the general and performance specifications for 1DA-BD.
Item Specifications
Ambient 0 to 55°C (32 to 131°F) when operating
temperature -25 to 75°C (-13 to 167°F) when stored
Relative
5 to 95%RH (no condensation) when operating
humidity
Frequency Acceleration Half amplitude
(Hz) (m/s2) (mm)
10 times of testing in
Vibration 10 - 57 - 0.035 each direction (X-, Y-,
DIN Rail Mounting
resistance*1 57 - 150 4.9 - and Z-axis directions)
(Total: 80 min, each)
10 to 57 − 0.075
Direct Mounting
57 to 150 9.8 −
Shock
147 m/s2 Acceleration, Action time: 11ms, 3 times by half-sine pulse in each direction X, Y, and Z
resistance*1
Noise Using noise simulator of:
resistance Noise voltage: 1,000Vp-p / Noise width: 1μs / Rise: 1ns / Cycle: 30 to 100Hz
Class D grounding (grounding resistance: 100 Ω or less)
Grounding
<Common grounding with a heavy electrical system is not allowed.>*2
Working
Free from corrosive or flammable gas and excessive conductive dusts
environment
Working
altitude < 2000m*3
G-6
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 2 Specifications
FX3G-1DA-BD (1-channel analog Output) 2.2 Performance Specifications
A
2.2 Performance Specifications
Common Items
Specifications
Item
Voltage output Current output B
FX3UC-4AD
FX3U-4AD
Analog output 0V to 10 V DC 4mA to 20mA DC
range (External load: 2kΩ to 1MΩ) (External load: 500Ω or less)
Digital input 12 bits, binary 11 bits, binary
Resolution 2.5mV(10V/4000) 8μA(16mA/2000)
• ±0.5% (±50mV) for 10V full scale
(when ambient temperature is 25°C±5 °C)
C
FX3U-4AD-ADP
• ±1.0% (±100mV) for 10V full scale
(when ambient temperature is 0°C to 55°C)
• ±0.5% (±80μA) for 16mA full scale
Shipment adjustment is carried out by external
(when ambient temperature is 25°C±5°C)
Total accuracy load resistance 2kΩ.
• ±1.0% (±160μA) for 16mA full scale
If external load resistance becomes larger
(when ambient temperature is 0°C to 55 °C) D
than 2kΩ, the output voltage will increase
FX3G-2AD-BD
slightly.
When the load is 1MΩ, the output voltage
becomes about 2% higher than the correct
value.
D/A conversion 60μs (The data will be updated at every scan time.)
time → For a detailed description of data update, refer to Section 2.4. E
FX3U-4DA
10V 20mA
F
Analog output
Analog output
FX3U-4DA-ADP
Output
characteristics
4mA
FX3G-1DA-BD
Caution:
An area of dead band is located in the region
of 0V. Therefore the output analog value may
not represent the digital value accurately.
Insulation method • The analog output area is not insulated from the PLC.
Numbers of I/O
H
0 point (This number is not related to the maximum number of input/output points of the PLC.)
FX3U-3A-ADP
points occupied
I
FX3U-4AD-PT
-ADP
J
FX3U-4AD-PTW
-ADP
G-7
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 2 Specifications
FX3G-1DA-BD (1-channel analog Output) 2.3 D/A Conversion Time
Sequence Program
END instruction
D/A D/A
conversion conversion
60μs 60μs
/1ch /1ch
FX3G-1DA-BD FX3G-1DA-BD
1st 2nd
G-8
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 3 Wiring
FX3G-1DA-BD (1-channel analog Output)
Common Items
3. Wiring
This chapter describes the 1DA-BD wiring. B
Observe the following caution to wire the 1DA-BD.
FX3UC-4AD
FX3U-4AD
WIRING PRECAUTIONS
• Make sure to cut off all phases of the power supply externally before attempting wiring work.
Failure to do so may cause electric shock or damages to the product. C
FX3U-4AD-ADP
WIRING PRECAUTIONS
• Connect the DC power supply wiring to the dedicated terminals described in this manual.
If an AC power supply is connected to a DC input/output terminal or DC power supply terminal, the PLC will be
burnt out.
D
FX3G-2AD-BD
• Do not wire vacant terminals externally.
Doing so may damage the product.
• Perform class D grounding (grounding resistance: 100Ω or less) to the grounding terminal on the main unit.
Do not use common grounding with heavy electrical systems.
• When drilling screw holes or wiring, make sure cutting or wire debris does not enter the ventilation slits.
Failure to do so may cause fire, equipment failures or malfunctions. E
• Make sure to observe the following precautions in order to prevent malfunctions under the influence of noise:
FX3U-4DA
- Do not bundle the power line or twisted shielded cable together with or lay it close to the main circuit, high-
voltage line, or load line.
Otherwise, noise disturbance and/or surge induction are likely to take place. As a guideline, lay the control line
at least 100mm (3.94") or more away from the main circuit, high-voltage line, or load line.
- Ground the shield of the analog input/output cable at one point on the signal receiving side.
However, do not use common grounding with heavy electrical systems. F
• Make sure to properly wire to the European terminal board in accordance with the following precautions.
FX3U-4DA-ADP
Failure to do so may cause electric shock, a short-circuit, wire breakage, or damage to the product.
- The disposal size of the cable end should be 9 mm (0.35").
- Tightening torque should be between 0.22 to 0.25 N•m.
- Twist the end of strand wire and make sure there are no loose wires.
- Do not solder-plate the electric wire ends.
- Do not connect more than the specified number of wires or electric wires of unspecified size. G
- Affix the electric wires so that neither the terminal block nor the connected parts are directly stressed.
FX3G-1DA-BD
H
FX3U-3A-ADP
I
FX3U-4AD-PT
-ADP
J
FX3U-4AD-PTW
-ADP
G-9
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 3 Wiring
FX3G-1DA-BD (1-channel analog Output) 3.1 Terminal Layout
Signal • • V+ I+ VI-
Unused Output COM
Application
terminal terminal terminal
G-10
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 3 Wiring
FX3G-1DA-BD (1-channel analog Output) 3.2 Applicable Cables and Terminal Tightening Torque
A
3.2 Applicable Cables and Terminal Tightening Torque
Common Items
Use the following cables to connect with the counterpart equipment. Terminate the cable end as shown below.
1. Cable
Applicable cable and tightening torque
B
FX3UC-4AD
FX3U-4AD
Wire size (stranded/ Tightening
Termination
single-wire) torque
0.3mm2 to 0.5mm2 • To connect a stranded cable, peel the cover off the cable
Single-wire and then twist the core before connection.
(AWG22 to 20)
2-wire 0.3mm2(AWG22)
• To connect a single-wire cable, just peel the cover off the
cable before connection.
C
FX3U-4AD-ADP
0.22N•m to • Rod terminal with insulation sleeve
Rod terminal 0.3mm2 to 0.5mm2 0.25N•m (recommended terminal)
with (AWG22 to 20) AI 0.5-8WH : Manufactured by Phoenix Contact
insulation (Refer to the rod terminal
• Caulking tool
sleeve external view shown in
CRIMPFOX ZA 3 : Manufactured by Phoenix Contact
the following figure.)
(or CRIMPFOX UD 6 : Manufactured by Phoenix Contact) D
FX3G-2AD-BD
2. Termination of cable end
To terminate the cable, treat the stranded/single wire directly or use a rod terminal with insulation sleeve.
• To directly terminate the end of a stranded/single-wire cable: Termination of cable end
- Twist the end of the stranded cable so that the "barbed wires"
cannot protrude. E
- Do not solder-plate the end of the cable.
FX3U-4DA
9mm
(0.35")
• To terminate cable end using a rod terminal with insulation sleeve: Insulation sleeve Contact area
If the cable cover is too thick, it may be difficult to insert the cable into (Crimp area)
the insulation sleeve. For this reason, select an appropriate cable while
referring to the external view. 8mm (0.31")
F
FX3U-4DA-ADP
Manufacturer Model Caulking tool 2.6mm 14mm
(0.1")
CRIMPFOX ZA 3 (0.55")
Phoenix Contact AI 0.5-8WH
(or CRIMPFOX UD 6)
3. Tool
G
• To tighten terminals, use a small-sized screwdriver whose head is straight and is not widened as shown in
FX3G-1DA-BD
the figure to the right.
Note:
If the diameter of screwdriver grip is too small, tightening torque will not
The head
be able to be achieved. Use the following recommended screwdriver or
an appropriate replacement (grip diameter: approximately 25mm).
should be
straight. H
FX3U-3A-ADP
Manufacturer Model
Phoenix Contact SZS 0.4×2.5 0.4mm 2.5mm
(0.01") (0.09")
I
FX3U-4AD-PT
-ADP
J
FX3U-4AD-PTW
-ADP
G-11
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 3 Wiring
FX3G-1DA-BD (1-channel analog Output) 3.3 Analog Output Line
*1. Use 2-core shielded twisted pair cable for the analog output lines, and separate the analog output
lines from other power lines or inductive lines.
*2. Ground the shielded wire at one point on the signal receiving side.
3.4 Grounding
Grounding should be performed as stated below.
• The grounding resistance should be 100Ω or less.
• Independent grounding should be performed for best results.
When independent grounding is not performed, perform "shared grounding" as shown in the following
figure.
→ For details, refer to User’s Manual - Hardware Edition of the PLC Series.
G-12
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 4 Programming
FX3G-1DA-BD (1-channel analog Output) 4.1 Writing of D/A Conversion Data
Common Items
4. Programming
This chapter describes how to create programs that can output the analog data using the 1DA-BD. B
FX3UC-4AD
FX3U-4AD
4.1 Writing of D/A Conversion Data
1) The input digital data will be converted into analog data and then output to the terminals.
2) If data is stored in the special devices, the averaging time can be set, and the output mode can be C
specified.
FX3U-4AD-ADP
3) Special auxiliary relays (10 points) and special data registers (10 points) are assigned respectively to the
analog expansion board connected to the option connector 1 and the analog expansion board connected
to the option connector 2 in this order.
→ For a detailed description of special device assignment, refer to Section 4.2.
• FX3G Series PLC D
FX3G-2AD-BD
FX3G Series PLC
Sequence Program
E
Special auxiliary relays: Special auxiliary relays:
FX3U-4DA
M8260 to M8269 M8270 to M8279
Special data register: Special data register:
D8260 to D8269 D8270 to D8279
FX3U-4DA-ADP
1st 2nd*1
The analog expansion board connected to the option connector 1 is regarded as the 1st unit, and the
analog expansion board connected to the option connector 2 is regarded as the 2nd unit.
*1. The second analog expansion board is not available in the FX3G Series PLC(14-point and 24-point
type).
G
FX3G-1DA-BD
H
FX3U-3A-ADP
I
FX3U-4AD-PT
-ADP
J
FX3U-4AD-PTW
-ADP
G-13
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 4 Programming
FX3G-1DA-BD (1-channel analog Output) 4.2 List of Special Devices
1. Program Example
To switch the output mode, create a sequence program as follows:
G-14
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 4 Programming
FX3G-1DA-BD (1-channel analog Output) 4.4 Output Holding Function Cancellation Setting
A
4.4 Output Holding Function Cancellation Setting
Common Items
This setting can hold the analog data output or to output the offset data (0V for voltage output mode, 4mA for
current output mode) when the PLC stops.
To cancel or set the output holding function, use the following special auxiliary relays:
Special auxiliary relay
B
Description
FX3UC-4AD
FX3U-4AD
1st board 2nd board
OFF: Holds the analog data output
Cancel output holding function just before stop of the PLC.
M8264 M8274
setting. ON : Outputs the offset data at
stop of the PLC.
C
FX3U-4AD-ADP
1. Program Example
To set or cancel the output holding function, create a sequence program as follows:
FX3G-2AD-BD
M8001
M8264
Normally OFF
FX3U-4DA
Numeric data type: Decimal (K)
The 1DA-BD performs D/A conversion on the output setting data (digital data) into analog data, and outputs
the analog data.
Use the special data registers shown in the following table for the output setting data:
Special data register F
Description
FX3U-4DA-ADP
1st board 2nd board
D8260 D8270 Output setting data
1. Program Example
G
FX3G-1DA-BD
M8000 Performs D/A conversion using the digital
FNC 12 D100 D8260 data stored in the D100 for the 1st analog
Normally ON
MOV board.
Using the indicator or the sequence program, input the digital data to be subject to D/A conversion (to be
output as analog data) in D100 and D101.
I
FX3U-4AD-PT
-ADP
J
FX3U-4AD-PTW
-ADP
G-15
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 4 Programming
FX3G-1DA-BD (1-channel analog Output) 4.6 Error Status
1. Description of setting
If an error is detected on 1DA-BD, the error status data will be stored in the corresponding special data
register.
The following table shows the special data registers that store the error status data:
Check the ON/OFF status of each bit of the error status data register to check the description of the error.
Errors are assigned to the bits as shown in the following table. Create a program to detect errors.
Bit Description
b0 Output data setting error
b1 to b3 Unused
b4 EEPROM error
b5 to b15 Unused
2. Program Example
M8000 FNC 12
D8268 K4M0
MOV
Normally
ON
M0
Y000 Output data setting error on
1st board.
M4
Y004 EEPROM error on the 1st board.
Initial value: K4
Numeric data type: Decimal (K)
1. Description of setting
When the 1DA-BD is connected, model code "4" is stored in the corresponding special data register.
The following table shows the special data registers that store the model code:
1st board 2nd board Description
D8269 D8279 Model code
Use the special data registers above to check whether 1DA-BD is connected or not.
2. Program Example
Checks the model code
FNC 224 D8269 K4 Y007 of the 1st analog board.
LD =
G-16
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 4 Programming
FX3G-1DA-BD (1-channel analog Output) 4.8 Basic Program Example
A
4.8 Basic Program Example
Common Items
Create the following basic program example to output D/A converted analog data.
The following program will set the 1st board to the voltage output mode and 2nd board to current output
mode, and will set digital data in D100 and D101 for D/A conversion.
M8001
B
Sets the output mode of the 1st board to the voltage
FX3UC-4AD
FX3U-4AD
M8260
output mode (0 V to 10 V).
Normally
OFF
M8264 Sets the output holding function for the 1st board.
M8000
Normally
M8270 Sets the output mode of the 2nd board to the current
output mode (4 mA to 20 mA). C
FX3U-4AD-ADP
ON
M8274 Cancels the output holding function for the 2nd board.
M8000
FNC 12 D100 D8260 Performs D/A conversion with the digital data stored
MOV in D100 for the 1st board.
FNC 12 D101 D8270 Performs D/A conversion with the digital data stored
D
in D101 for the 2nd board.
FX3G-2AD-BD
MOV
Using the indicator or the sequence program, input the digital data to be subject to D/A conversion (to be
output as analog data) in D100 and D101.
FX3U-4DA
F
FX3U-4DA-ADP
G
FX3G-1DA-BD
H
FX3U-3A-ADP
I
FX3U-4AD-PT
-ADP
J
FX3U-4AD-PTW
-ADP
G-17
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 5 Changing of Output Characteristics
FX3G-1DA-BD (1-channel analog Output) 5.1 Example: Changing of Voltage Output Characteristics
1. Output characteristics
value to be actually
10V
Analog output
Y-axis
5V 2000
(5V)
1V 400
(1V)
0 400 2000 4000 X-axis
0 10000
Digital value input
Desired digital value (D100)
2. Example of program
For example, create the following program to change the digital output data (D100) of the 1st analog board.
M8001
M8260 Sets the output mode of 1st board
Normally to the voltage output mode (0V to 10V).
OFF
FNC 23
D101 K10000 D103
DDIV Calculation for changing output
characteristics.
FNC 20 Stores the operation result in D8260.
D103 K400 D107
ADD
G-18
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 6 Troubleshooting
FX3G-1DA-BD (1-channel analog Output) 6.1 PLC Version Number Check
Common Items
6. Troubleshooting
This chapter describes the troubleshooting methods and error status. B
If analog data is not output, or if the proper analog value is not output, check the following items:
FX3UC-4AD
FX3U-4AD
• Version number of PLC
• Installation
• Wiring
• Special devices C
• Programs
FX3U-4AD-ADP
• Error status
FX3G-2AD-BD
→ For a detailed description of the version number check method, refer to Section 1.3.
FX3U-4DA
of the 1DA-BD is lit correctly.
→ For a detailed description of installing, refer to FX3G User’s Manual-Hardware Edition.
FX3U-4DA-ADP
1. Analog output line
Use the 2-core twisted shielded pair cable for the analog output line. In addition, be sure to separate the
analog output line from other power lines or inductive lines.
→ For a detailed description of wiring, refer to Chapter 3.
G
FX3G-1DA-BD
6.4 Special Device Check
Check whether the special devices for the 1DA-BD are being used correctly:
Turn off the device to set the output mode to the voltage output mode. Turn on the device to set the output
mode to the current output mode.
3. Error status
Check that no error is detected in the 1DA-BD.
If an error is detected, check the details of the error, and then check the wiring and programs.
-ADP
G-19
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 6 Troubleshooting
FX3G-1DA-BD (1-channel analog Output) 6.5 Program Check
Bit Description
b0 Output data setting error
b1 to b3 Unused
b4 EEPROM error
b5 to b15 Unused
To solve the problem, refer to the troubleshooting method described below:
G-20
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition
FX3U-3A-ADP (2-channel analog Input, 1-channel analog output)
Common Items
B
FX3UC-4AD
FX3U-4AD
FX3G/FX3U/FX3UC Series Programmable
Controllers C
FX3U-4AD-ADP
User's Manual [Analog Control Edition]
FX3U-3A-ADP
D
(2-channel analog Input, 1-channel analog output)
FX3G-2AD-BD
E
FX3U-4DA
F
FX3U-4DA-ADP
G
FX3G-1DA-BD
H
FX3U-3A-ADP
Foreword
This manual describes the specifications, wiring, and operation methods for the FX3U-3A-ADP analog special
adapter (2-channel analog input, 1-channel analog output) and should be read and understood before
attempting to install or use the unit. I
FX3U-4AD-PT
Store this manual in a safe place so that you can take it out and read it whenever necessary. Always forward
it to the end user.
-ADP
This manual confers no industrial property rights or any rights of any other kind, nor does it confer any patent
licenses. Mitsubishi Electric Corporation cannot be held responsible for any problems involving industrial property
rights which may occur as a result of using the contents noted in this manual. J
FX3U-4AD-PTW
H-1
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition
FX3U-3A-ADP (2-channel analog Input, 1-channel analog output)
H-2
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 1 Outline
FX3U-3A-ADP (2-channel analog Input, 1-channel analog output) 1.1 Outline of Functions
Common Items
1. Outline
This chapter outlines the FX3U-3A-ADP (referred to as the 3A-ADP). B
FX3UC-4AD
FX3U-4AD
1.1 Outline of Functions
The analog special adapter FX3U-3A-ADP receives voltage/current data from 2 channels and outputs voltage/
current data from 1 channel when connected to a FX3U/FX3UC/FX3G Series PLC.
C
FX3U-4AD-ADP
1) Up to 4 3A-ADP units can be connected to the FX3U/FX3UC Series PLC.
Up to 2*1 3A-ADP units can be connected to the FX3G Series PLC.
(including the other analog special adapters).
2) The 3A-ADP receives and outputs voltage/current data.
3) A/D conversion data of each channel will be automatically written to the special data register of the FX3U/ D
FX3UC/FX3G Series PLC.
FX3G-2AD-BD
4) D/A conversion results will be automatically output as the values to the special data register of the FX3U/
FX3UC/FX3G Series PLC.
FX3U-4DA
FX3G Series PLC : 2*1 maximum
…… Number of connectable
(including other analog special adapters) units
FX3U/FX3UC/FX3G Series PLC
FX3U-4DA-ADP
*2
4th 3rd 2nd 1st Expansion board
adapter adapter adapter adapter
…… For a detailed G
Analog data description of wiring,
FX3G-1DA-BD
refer to Chapter 3.
Flowmeter, Inverter, etc.
pressure sensor, etc
H
For FX3U/FX3UC
FX3U-3A-ADP
Series PLC
Contents Special devices …… For a detailed description
of special devices, refer to
•Analog data Transfer direction 1st adapter M/D8260 to M/D8269 Chapter 4.
•Error status
2nd adapter M/D8270 to M/D8279 For a detailed description
•Switching of input mode
•Setting of averaging time 3rd adapter M/D8280 to M/D8289
of a basic program, refer to
Section 4.12. I
•Output mode switching
FX3U-4AD-PT
Refer to the system configuration shown in the User's Manual - Hardware Edition to check the number of connectable units
and to configure the entire system.
J
*1.Only 1 analog special adapter can be connected to the FX3G Series PLC(14-point and 24-point type).
FX3U-4AD-PTW
*2.The expansion board is not required when connecting with the FX3UC (D, DSS) PLC.
For the FX3G Series PLC a connector conversion adapter is used.
-ADP
H-3
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 1 Outline
FX3U-3A-ADP (2-channel analog Input, 1-channel analog output) 1.2 Setup Procedure Before Starting Operation
FX3U-3A-ADP
Refer to Chapter 1.
Wiring Wiring:
• Selection of sensor cable
• Power supply line
Refer to Chapter 4. • Analog input/output line
Programming Programming:
• Details of special devices
• Examples of basic programs
Refer to Chapter 5.
H-4
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 1 Outline
FX3U-3A-ADP (2-channel analog Input, 1-channel analog output) 1.3 Connectable PLCs and Version Number
A
1.3 Connectable PLCs and Version Number
Common Items
The 3A-ADP is compatible with the following PLC.
FX3UC-4AD
FX3U-4AD
FX3UC Series PLC*1 Ver.2.61 or later After July 2009
FX3G Series PLC Ver.1.20 or later After June 2009
1. Version check C
Special data register D8001 contains information for determining the PLC version number.
FX3U-4AD-ADP
→ For a detailed description of the version check, refer to A. Common Items Subsection 5.1.2.
FX3G-2AD-BD
1.4 Compatible Programming Tool Version Number
Use the programming tool with following version numbers to create programs for the 3A-ADP: E
FX3U-4DA
1. GX Developer
Software Version number Remarks
GX Developer Ver.SW8 P or later
(Ver.8.13P) When selecting a model, select FX3U(C)*2.
• SW D5C-GPPW-J
• SW D5C-GPPW-E Ver. 8.72A or later When selecting a model, select FX3G. F
FX3U-4DA-ADP
If a programming tool with the wrong version number is used, programming will not be possible.
*2. For Ver. 8.13P to 8.24A of GX Developer, select FX3UC for the PLC type.
2. FX-30P
Model name Version number Remarks G
FX-30P Ver.1.00 or later
FX3G-1DA-BD
H
FX3U-3A-ADP
I
FX3U-4AD-PT
-ADP
J
FX3U-4AD-PTW
-ADP
H-5
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 2 Specifications
FX3U-3A-ADP (2-channel analog Input, 1-channel analog output) 2.1 Generic Specifications
2. Specifications
This chapter describes the general, power supply, and performance specifications for the 3A-ADP.
Item Specifications
Ambient 0 to 55°C (32 to 131°F) when operating
temperature -25 to 75°C (-13 to 167°F) when stored
Relative humidity 5 to 95%RH (no condensation) when operating
Frequency Acceleration Half amplitude
(Hz) (m/s2) (mm)
Tests 10 times in each
Vibration 10 to 57 - 0.035 direction (X-, Y-, and Z-
DIN Rail Mounting
resistance*1 57 to 150 4.9 - axis directions) (Total:
80 min, each)
10 to 57 - 0.075
Direct Mounting*2
57 to 150 9.8 -
*1 2
Shock resistance 147 m/s Acceleration, Action time: 11ms, 3 times by half-sine pulse in each direction X, Y, and Z
Using noise simulator of:
Noise resistance
Noise voltage: 1,000Vp-p / Noise width: 1μs / Rise: 1ns / Cycle: 30 to 100Hz
Dielectric withstand
500 V AC, for 1 min
voltage
Between all terminals and ground terminal
Insulation 5MΩ or more using 500V DC
resistance insulation resistance meter
Class D grounding (grounding resistance: 100 Ω or less)
Grounding
<Common grounding with a heavy electrical system is not allowed.>*3
Working
Free from corrosive or flammable gas and excessive conductive dusts
environment
Working altitude < 2000m*4
*1. The criterion is shown in IEC61131-2.
*2. If 3A-ADP is connected to the FX3UC Series PLC, direct installation is not possible.
*3.
PLC Other PLC Other PLC Other
equipment equipment equipment
Item Specifications
Conversion circuit driving 24V DC +20%-15%, 90mA
power (It is necessary to connect a 24V DC power line to the terminal block.)
5V DC, 20mA
Interface driving power (Since the internal power is supplied from the main unit of the FX Series, it is not
necessary to supply the power.)
H-6
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 2 Specifications
FX3U-3A-ADP (2-channel analog Input, 1-channel analog output) 2.3 Performance Specifications
A
2.3 Performance Specifications
Common Items
Specifications
Item
Voltage input Current input Voltage output Current output B
FX3UC-4AD
FX3U-4AD
Number of input/
2ch 1ch
output points
4mA to 20mA DC
Analog input/ 0V to 10V DC 4mA to 20mA DC 0V to 10V DC
(External load:
output range (Input resistance:198.7kΩ) (Input resistance:250Ω) (External load:5k to 1MΩ)
500Ω or less)
Absolute -0.5V, -2mA,
- -
C
maximum input +15V +30mA
FX3U-4AD-ADP
Digital input/
12 bits, binary
output
Resolution 2.5mV(10V×1/4000) 5μA(16mA×1/3200) 2.5mV(10V×1/4000) 4μA(16mA×1/4000)
Ambient
temperature:
±0.5%(±50mV) ±0.5%(±80μA) ±0.5%(±50mV) ±0.5%(±80μA) D
for 10V full scale for 16mA full scale for 10V full scale for 16mA full scale
FX3G-2AD-BD
25±5°C
Ambient
±1.0%(±100mV) ±1.0%(±160μA) ±1.0%(±100mV) ±1.0%(±160μA)
temperature:
for 10V full scale for 16mA full scale for 10V full scale for 16mA full scale
Overall accuracy
0 to 55°C
If the external load
resistance (Rs) is less E
than 5kΩ, the accuracy
FX3U-4DA
increases as shown in the
Reference - - following formula: -
(Increase: 100 mV per
1%)
47×100
Rs+47
-0.9(%) F
FX3U-4DA-ADP
• FX3U/FX3UC Series PLC :
80μs for each selected input channel + 40μs for each selected output channel
(Operation synchronized with sequence program)
Time required for
• FX3G Series PLC :
conversion
90μs for each selected input channel + 50μs for each selected output channel
(Operation synchronized with sequence program) G
→ For a detailed description of data update, refer to Section 2.4.
FX3G-1DA-BD
4080 3280
4000 3200 10V 20mA
Analog output
H
Analog output
Digital output
Digital output
I/O
characteristics
FX3U-3A-ADP
20.4mA
10.2V
4080
4080
4mA
0 10V 0 4mA 20mA 0 4000 0 4000
Analog input Analog input Digital input Digital input
Insulation
• The photocoupler is used to insulate the analog input and output area from the PLC. I
• The DC/DC converter is used to insulate the power supply from the analog input and output area.
FX3U-4AD-PT
method
• Channels are not insulated from each other.
Number of I/O 0 points
-ADP
points occupied (This number of points is not related to the maximum number of input/output points of the PLC.)
J
FX3U-4AD-PTW
-ADP
H-7
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 2 Specifications
FX3U-3A-ADP (2-channel analog Input, 1-channel analog output) 2.4 Conversion Time
H-8
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 2 Specifications
FX3U-3A-ADP (2-channel analog Input, 1-channel analog output) 2.4 Conversion Time
A
2.4.2 When connected to a FX3G PLC
Common Items
1. Conversion and special data register update timing
A/D and D/A conversion is performed at every scan time of the PLC.
During execution of END instruction, the PLC performs A/D conversion, reads out the A/D converted data,
and then writes the data in the special data registers. B
The PLC writes output setting data to special data registers, performs D/A conversion, and updates analog
FX3UC-4AD
FX3U-4AD
output values.
FX3U-3A-ADP FX3U-3A-ADP
2nd 1st FX3G Series PLC
A/D conversion
A/D,D/A conversion Sequence C
90μs for each program
FX3U-4AD-ADP
selected input start command
channel
+ Digital value writing
D/A conversion
A/D conversion 50μ s for each
Digital value reading
90μs for each selected output
selected input
channel
channel A/D,D/A conversion
start command
End instruction D
FX3G-2AD-BD
+
D/A conversion Digital value writing
50μ s for each
selected output Digital value reading
channel
FX3U-4DA
1) A/D conversion
Even if the PLC is stopped, A/D conversion will be performed and the special data registers will be
updated.
2) D/A conversion
If the output holding function cancellation setting is disabled by the special device, the offset value will be F
output.
FX3U-4DA-ADP
If the output holding function cancellation setting is enabled, the output at switching from RUN to STOP
will be latched.
Just after power-on, however, the offset value will be output until operation begins.
FX3G-1DA-BD
During execution of the END instruction, data will be read out from all the connected adapters (in the
order of 1st adapter → 2nd adapter).
2) D/A conversion
During execution of the END instruction, data in all the connected adapters will be subject to D/A
conversion and then output (in the order of 1st adapter → 2nd adapter).
H
4. Conversion speed (data update time)
FX3U-3A-ADP
1) A/D conversion
During execution of END instruction, the A/D converted data of "90μs for each selected input channel",
and the data read out will be written to the special data registers.
END instruction execution time will be "90μs for each selected input channel × number of connected
analog adapters." I
FX3U-4AD-PT
2) D/A conversion
During execution of END instruction, the output setting digital data per of "50μs for each selected output
channel", after which the analog data will be output.
-ADP
END instruction execution time will be "50μs for each selected output channel × number of connected
adapters."
J
FX3U-4AD-PTW
-ADP
H-9
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 3 Wiring
FX3U-3A-ADP (2-channel analog Input, 1-channel analog output)
3. Wiring
This chapter describes the 3A-ADP wiring.
Observe the following caution to wire the 3A-ADP.
WIRING PRECAUTIONS
• Make sure to cut off all phases of the power supply externally before attempting wiring work.
Failure to do so may cause electric shock or damages to the product.
WIRING PRECAUTIONS
• Connect the DC power supply wiring to the dedicated terminals described in this manual.
If an AC power supply is connected to a DC input/output terminal or DC power supply terminal, the PLC will be
burnt out.
• Do not wire vacant terminals externally.
Doing so may damage the product.
• Perform class D grounding (grounding resistance: 100Ω or less) to the grounding terminal on the main unit.
Do not use common grounding with heavy electrical systems.
• When drilling screw holes or wiring, make sure cutting or wire debris does not enter the ventilation slits.
Failure to do so may cause fire, equipment failures or malfunctions.
• Make sure to observe the following precautions in order to prevent malfunctions under the influence of noise:
- Do not bundle the power line or twisted shielded cable together with or lay it close to the main circuit,
highvoltage line, or load line.
Otherwise, noise disturbance and/or surge induction are likely to take place. As a guideline, lay the control line
at least 100mm (3.94") or more away from the main circuit, high-voltage line, or load line.
- Ground the shield of the analog input/output cable at one point on the signal receiving side.
However, do not use common grounding with heavy electrical systems.
• Make sure to properly wire to the European terminal board in accordance with the following precautions.
Failure to do so may cause electric shock, a short-circuit, wire breakage, or damage to the product.
- The disposal size of the cable end should be 9 mm (0.35").
- Tightening torque should be between 0.22 to 0.25 N•m.
- Twist the end of strand wire and make sure there are no loose wires.
- Do not solder-plate the electric wire ends.
- Do not connect more than the specified number of wires or electric wires of unspecified size.
- Affix the electric wires so that neither the terminal block nor the connected parts are directly stressed.
H-10
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 3 Wiring
FX3U-3A-ADP (2-channel analog Input, 1-channel analog output) 3.1 Terminal Layout
A
3.1 Terminal Layout
Common Items
The terminals of the 3A-ADP are arranged as follows:
FX3UC-4AD
FX3U-4AD
Signal Application
24+
24-
External power
C
Grounding terminal
FX3U-4AD-ADP
• Do not connect any lines.
V1+
I1+ Channel 1 analog input
COM1
V2+
I2+ Channel 2 analog input
D
FX3G-2AD-BD
COM2
V0
I0 Analog output
COM
•
•
Do not connect any lines.
E
FX3U-4DA
F
FX3U-4DA-ADP
G
FX3G-1DA-BD
H
FX3U-3A-ADP
I
FX3U-4AD-PT
-ADP
J
FX3U-4AD-PTW
-ADP
H-11
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 3 Wiring
FX3U-3A-ADP (2-channel analog Input, 1-channel analog output) 3.2 Applicable Cables and Terminal Tightening Torque
1. Cables
Applicable cable and tightening torque
Wire size (stranded/ Tightening
Termination
single-wire) torque
0.3mm2 to 0.5mm2 • To connect a stranded cable, peel the cover off the cable
Single-wire and then twist the core before connection.
(AWG22 to 20)
• To connect a single-wire cable, just strip the cover off the
2-wire 0.3mm2(AWG22) cable before connection.
0.22N•m to • Rod terminal with insulation sleeve
Rod terminal 0.3mm2 to 0.5mm2 0.25N•m (recommended terminal)
with (AWG22 to 20) AI 0.5-8WH : Manufactured by Phoenix Contact
insulation (Refer to the rod terminal
• Caulking tool
sleeve external view shown in the
CRIMPFOX ZA 3 : Manufactured by Phoenix Contact
following figure.)
(or CRIMPFOX UD 6 : Manufactured by Phoenix Contact)
3. Tool
• To tighten terminals, use a small-sized screwdriver whose head is straight and is not widened as shown in
the figure to the right.
Note:
If the diameter of screwdriver grip is too small, tightening torque will not
The head
be able to be achieved. Use the following recommended screwdriver or should be
an appropriate replacement (grip diameter: approximately 25mm). straight.
Manufacturer Model
Phoenix Contact SZS 0.4×2.5 0.4mm 2.5mm
(0.01") (0.09")
H-12
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 3 Wiring
FX3U-3A-ADP (2-channel analog Input, 1-channel analog output) 3.3 Power Supply Line
A
3.3 Power Supply Line
Common Items
Connect the 24V DC power supply line of the 3A-ADP to the 24+ and 24- terminals of the terminal block.
FX3UC-4AD
FX3U-4AD
1. To use an External power supply 2. To use the 24V DC power of the PLC
FX3U-4AD-ADP
24- 24+ 24- 24+ 0V 24V D
FX3G-2AD-BD
Terminal
block Terminal
block
Class-D Class-D
24V DC grounding grounding
E
Caution regarding connection of the power supply line:
FX3U-4DA
• Ground the " " terminal to a class-D grounded power supply line (100Ω or less) together with the
grounding terminal of the PLC main unit.
• For the timing of power-on/off when using an external power supply, see the following manual of the PLC
to be connected.
→ Refer to the FX3G Series User's Manual - Hardware Edition.
F
FX3U-4DA-ADP
→ Refer to the FX3U Series User's Manual - Hardware Edition.
FX3G-1DA-BD
15V block)
Power H
Power crossover
FX3U-3A-ADP
Power
connector connector connector
Class-D
24V DC grounding
-ADP
• Ground the " " terminal to a class-D grounded power supply line (100Ω or less) together with the
grounding terminal of the PLC main unit.
-ADP
H-13
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 3 Wiring
FX3U-3A-ADP (2-channel analog Input, 1-channel analog output) 3.4 Analog Input / output Line
*1 110kΩ ch
V +
250Ω
I +
COM
88.7kΩ
Connection of external
power supply line +15V
24+
24V DC
24-
Class-D
grounding
V +,I +,ch : represents the channel number.
*1. Use the 2-core shielded twisted pair cable for the analog input lines, and separate the analog input
lines from other power lines or inductive lines.
*2. If "current input" is selected, be sure to short the line between the V + terminal and the I + terminal.
( : Channel number).
*1. Use 2-core shielded twisted pair cable for the analog output lines, and separate the analog output
lines from other power lines or inductive lines.
*2. Ground the shielded wire at one point on the signal receiving side.
H-14
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 3 Wiring
FX3U-3A-ADP (2-channel analog Input, 1-channel analog output) 3.5 Grounding
A
3.5 Grounding
Common Items
Grounding should be performed as stated below.
• The grounding resistance should be 100Ω or less.
• Independent grounding should be performed for best results.
When independent grounding is not performed, perform "shared grounding" as shown in the following
B
FX3UC-4AD
FX3U-4AD
figure.
→ For details, refer to the User's Manual - Hardware Edition of the PLC Series.
FX3U-4AD-ADP
Best condition Good condition Not allowed
FX3G-2AD-BD
E
FX3U-4DA
F
FX3U-4DA-ADP
G
FX3G-1DA-BD
H
FX3U-3A-ADP
I
FX3U-4AD-PT
-ADP
J
FX3U-4AD-PTW
-ADP
H-15
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 4 Programming
FX3U-3A-ADP (2-channel analog Input, 1-channel analog output) 4.1 Loading/Writing of Conversion Data
4. Programming
This chapter explains how to create programs for inputting and outputting analog data using the 3A-ADP.
Communic High-speed
FX3U-3A FX3U-3A FX3U-3A -ation FX3U-3A input/output
-ADP -ADP -ADP special -ADP special
adapter adapter FX3U/FX3UC Series PLC
The analog special adapter nearest to the main unit is counted as the 1st analog special adapter, and the
next adapter as the 2nd analog special adapter, and so on. However, in this case, do not include the
highspeed input/output special adapter, communication special adapter, and the CFcard special adapter.
H-16
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 4 Programming
FX3U-3A-ADP (2-channel analog Input, 1-channel analog output) 4.2 List of Special Devices
A
• FX3G Series PLC
Common Items
Communi-
cation Connector
FX3U-3A special FX3U-3A conversion
-ADP adapter -ADP adapter FX3G Series PLC
2nd
*1
1st
Special devices B
FX3UC-4AD
FX3U-4AD
Special auxiliary relays:
A/D M8280 to M8289
or Special data registers:
D/A D8280 to D8289.
Sequence
program
Special auxiliary relays:
A/D
or
M8290 to M8299
Special data registers:
C
FX3U-4AD-ADP
D/A D8290 to D8299.
The analog special adapter nearest to the main unit is counted as the 1st analog special adapter, and the
next adapter as the 2nd analog special adapter.In this case , however, do not include the connecter
conversion adapter and the communication special adapter.
*1. The second special adapter is not available in the 14-point and 24-point type FX3G PLC main unit.
D
FX3G-2AD-BD
4.2 List of Special Devices
If the 3A-ADP is connected, special devices will be assigned automatically as shown in the following table:
• FX3U, FX3UC Series PLC E
FX3U-4DA
R: Read / W: Write
Device number
Special device Description Attribute Reference
1st 2nd 3rd 4th
M8260 M8270 M8280 M8290 Switches the input mode of channel 1 R/W
Section 4.3
M8261 M8271 M8281 M8291 Switches the input mode of channel 2 R/W F
M8262 M8272 M8282 M8292 Switches the output mode. R/W Section 4.4
FX3U-4DA-ADP
M8263 M8273 M8283 M8293
Special auxiliary M8264 M8274 M8284 M8294 Unused (Do not use.) - -
relay M8265 M8275 M8285 M8295
M8266 M8276 M8286 M8296 Sets the cancel of output holding function.
M8267 M8277 M8287 M8297 Sets whether or not input channel 1 is used.
R/W
R/W
Section 4.5
G
FX3G-1DA-BD
M8268 M8278 M8288 M8298 Sets whether or not input channel 2 is used. R/W Section 4.6
M8269 M8279 M8289 M8299 Sets whether or not output channel is used. R/W
D8260 D8270 D8280 D8290 Channel-1 input data R
Section 4.7
D8261 D8271 D8281 D8291 Channel-2 input data R
D8262 D8272 D8282 D8292 Output setting data R/W Section 4.8 H
FX3U-3A-ADP
J
FX3U-4AD-PTW
-ADP
H-17
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 4 Programming
FX3U-3A-ADP (2-channel analog Input, 1-channel analog output) 4.3 Switching of Input Mode
H-18
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 4 Programming
FX3U-3A-ADP (2-channel analog Input, 1-channel analog output) 4.4 Switching of Output Mode
A
4.4 Switching of Output Mode
Common Items
Turn the special auxiliary relay on/off to switch the output mode of 3A-ADP between the current output mode
and the voltage output mode.
To switch the output mode, use the following special auxiliary relays:
• FX3U, FX3UC Series PLC B
FX3UC-4AD
FX3U-4AD
Special auxiliary relay
Description
1st 2nd 3rd 4th
OFF:Voltage output
M8262 M8272 M8282 M8292 Switches the output mode
ON :Current output
FX3U-4AD-ADP
Special auxiliary relay
Description
1st 2nd
OFF:Voltage output
M8282 M8292 Switches the output mode
ON :Current output
FX3G-2AD-BD
To switch the output mode of a channel, create a sequence program as follows:
1) To switch the channel output mode of
channel 1 of the 1st analog special
adapter to the voltage output mode:
M8001
M8262 E
FX3U-4DA
Normally OFF
FX3U-4DA-ADP
To cancel or set the output holding function, use the following special auxiliary relays:
• FX3U, FX3UC Series PLC
Special auxiliary relay
Description
1st 2nd 3rd 4th
OFF: Holds the analog data output G
Cancel output holding just before stop of the PLC.
FX3G-1DA-BD
M8266 M8276 M8286 M8296
function setting ON : Outputs the offset data at stop
of the PLC.
To set or cancel the output holding function for a channel, create a sequence program as follows:
Normally OFF
M8266
J
FX3U-4AD-PTW
-ADP
H-19
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 4 Programming
FX3U-3A-ADP (2-channel analog Input, 1-channel analog output) 4.6 Setting whether or not a channel is used
POINT
When the setting whether or not the output channel is used is changed from "Used (OFF)" to "Not used (ON)",
the last output before the change is held.
H-20
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 4 Programming
FX3U-3A-ADP (2-channel analog Input, 1-channel analog output) 4.7 Input Data
A
4.7 Input Data
Common Items
Numeric data type: Decimal (K)
The data converted by the 3A-ADP will be stored in the special data registers.
The special data registers that store the input data are shown in the following table:
B
• FX3U, FX3UC Series PLC
FX3UC-4AD
FX3U-4AD
Special auxiliary relay
Description
1st 2nd 3rd 4th
D8260 D8270 D8280 D8290 Stores the channel-1 input data
D8261 D8271 D8281 D8291 Stores the channel-2 input data
C
• FX3G Series PLC
FX3U-4AD-ADP
Special auxiliary relay
Description
1st 2nd
D8280 D8290 Stores the channel-1 input data
D8281 D8291 Stores the channel-2 input data
D
FX3G-2AD-BD
The converted A/D immediate data or averaged data (data average conforming to the specified averaging
time) will be stored in the above data registers as the input data.
When the channel is not used, "0" will be stored.
→ For a detailed description of the averaging time, refer to Section 4.9.
FX3U-4DA
Input data is for reading only.
Do not change (rewrite) the input data using sequence program, indicator, or device monitor of the
programming tool.
FX3U-4DA-ADP
M8000 Stores the channel-1 input data
FNC 12 D8260 D100 of the 1st analog special adapter
Normally
MOV in the D100.
ON
Stores the channel-2 input data
FNC 12
G
D8261 D101 of the 1st analog special adapter
MOV in the D101
FX3G-1DA-BD
Even if the input data is not stored in D100 or D101, data registers D8260 or D8261 can be directly used in
the timer/counter set value or in a PID instruction.
H
FX3U-3A-ADP
I
FX3U-4AD-PT
-ADP
J
FX3U-4AD-PTW
-ADP
H-21
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 4 Programming
FX3U-3A-ADP (2-channel analog Input, 1-channel analog output) 4.8 Output Setting Data
Using the indicator or the sequence program, input the digital data to be subject to D/A conversion (to be
output as analog data) in D102.
H-22
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 4 Programming
FX3U-3A-ADP (2-channel analog Input, 1-channel analog output) 4.9 Averaging Time
A
4.9 Averaging Time
Common Items
Setting range: 1 to 4095
Initial value: K1
Numeric data type: Decimal (K)
If the averaging time is set for the 3A-ADP, the average data will be stored as the input data. The averaging B
FX3UC-4AD
FX3U-4AD
time can be set for each channel.
Set the averaging time in the following special data registers:
• FX3U, FX3UC Series PLC
Special auxiliary relay
1st 2nd 3rd 4th
Description
C
FX3U-4AD-ADP
D8264 D8274 D8284 D8294 Averaging time for channel-1 data
D8265 D8275 D8285 D8295 Averaging time for channel-2 data
FX3G-2AD-BD
D8284 D8294 Averaging time for channel-1 data
D8285 D8295 Averaging time for channel-2 data
FX3U-4DA
• If the averaging time is set in the range from 2 to 4095, the average value will be calculated to conform to
the set averaging time, and the average value obtained will be stored in the special data register.
• After turning the PLC power on, the current data is stored to special data registers until the number of data
items reaches the set averaging time. After this, the average data will be stored.
• Set the averaging time in the range from 1 to 4095. If the set value is outside the setting range, an error
F
FX3U-4DA-ADP
signal will be output.
• If the averaging time is set to "0" or smaller, the PLC will perform as if the averaging time is set to "1".
If the averaging time is set to "4096" or larger, the PLC will perform as if the averaging time is set to "4096".
→ For a detailed description of the error status, refer to Section 6.5.
FX3G-1DA-BD
M8000 Sets the averaging time for
FNC 12 K1 D8264 channel-1 of the 1st analog
MOV special adapter to 1.
Normally
ON
Sets the averaging time for
FNC 12
MOV
K5 D8265 channel-2 of the 1st analog
special adapter to 5.
H
FX3U-3A-ADP
I
FX3U-4AD-PT
-ADP
J
FX3U-4AD-PTW
-ADP
H-23
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 4 Programming
FX3U-3A-ADP (2-channel analog Input, 1-channel analog output) 4.10 Error Status
Check the ON/OFF status of each bit of the error status data register to check the description of the error.
Errors are assigned to the bits as shown in the following table. Create a program to detect errors.
→ For a detailed description of the error status, refer to Section 6.5.
*1. A 3A-ADP hardware error (b6) is valid only when the use of analog input is set.
Detection of power supply error is valid only when the use of analog input channel 2 is set.
*2. A 3A-ADP communication data error (b7) is valid only when the use of analog input is set.
M8000
MOV D8288 K4M0
Normally ON
M8002 *1
Error status of 3rd analog special adapter
RST M6 b6 = OFF (hardware error)
Initial pulse
*1
RST M7 Error status of 3rd analog status register
b7 = OFF (communication data error)
H-24
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 4 Programming
FX3U-3A-ADP (2-channel analog Input, 1-channel analog output) 4.10 Error Status
A
2. Program Example 1 (FX3G, FX3U, FX3UC Series PLC)
Common Items
M8000
MOV D8288 K4M0
M0
Y000 Detects over-scale in channel 1 of
the 3rd *1 adapter. B
M1
FX3UC-4AD
FX3U-4AD
Y001 Detects over-scale in channel 2 of
the 3rd *1 adapter.
M2
Y002 Output data setting error of the 3rd *1
adapter.
M4
C
EEPROM error in 3rd *1 adapter
FX3U-4AD-ADP
Y004
M5
Y005 Averaging time setting error in
3rd *1 adapter
M6
Y006 Hardware error in 3rd *1 3A-ADP D
FX3G-2AD-BD
M7
Y007 Communication data error in 3rd *1
3A-ADP
FX3U-4DA
D8268.0
Y000 Detects over-scale in channel 1 of
the 1st adapter.
D8268.1
Y001 Detects over-scale in channel 2 of
the 1st adapter.
F
D8268.2
FX3U-4DA-ADP
Y002 Output data setting error of the 1st
adapter.
D8268.4
Y004 EEPROM error in 1st adapter
D8268.5
Y005 Averaging time setting error in
G
FX3G-1DA-BD
1st adapter
D8268.6
Y006 Hardware error in 1st 3A-ADP
D8268.7
Y007 Communication data error in 1st
3A-ADP H
FX3U-3A-ADP
I
FX3U-4AD-PT
-ADP
J
FX3U-4AD-PTW
-ADP
H-25
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 4 Programming
FX3U-3A-ADP (2-channel analog Input, 1-channel analog output) 4.11 Model Code
Use the special data registers above to check whether a 3A-ADP is connected or not.
FNC224 D8289 K50 Y007 Checks the model code of the 1st
LD = analog special adapter
H-26
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 4 Programming
FX3U-3A-ADP (2-channel analog Input, 1-channel analog output) 4.12 Basic Program Example
A
4.12 Basic Program Example
Common Items
Create the following basic program example to input/output analog conversion data.
• FX3G, FX3U, FX3UC Series PLC
The following program will set channel 1 of the 3rd*1 adapter to voltage input mode and channel 2 to current
input mode, and will store the converted A/D value of channel-1 data into D100 and that of channel-2 data
B
FX3UC-4AD
FX3U-4AD
into D101. The program also sets "voltage output" for output channels, and sets the D/A conversion output to
D102.
FX3U-4AD-ADP
Normally ON input mode (4 mA to 20 mA).
M8001 Set the output mode to the voltage output mode
M8282
Normally (0 V to 10 V).
OFF
D
M8286 Set the output holding function.
M8000
FX3G-2AD-BD
FNC 12 D8288 K4M0
MOV
M8002
RST M6 Error status: b6 = OFF
Initial
pulse
Error status: b7 = OFF
E
RST M7
FX3U-4DA
FNC 12 K4M0 D8288
MOV
M8000
FNC 12
MOV
K5 D8284 Set the averaging time to "5" for channel-1 data.
F
FX3U-4DA-ADP
FNC 12 K5 D8285 Set the averaging time to "5" for channel-2 data.
MOV
M8000
FNC 12 Stores the A/D converted channel-1 digital data
D8280 D100
MOV into D100.
FNC 12 D8281 D101 Stores the A/D converted channel-2 digital data G
MOV into D101.
FX3G-1DA-BD
M8000
FNC 12 D102 D8282 Performs D/A conversion with the digital data
MOV stored in D102.
Even if the input data is not stored into D100 or D101, the data registers D8280 or D8281 can be directly used
in the timer/counter setting value or in a PID instruction. H
Using the indicator or the sequence program, input the digital data to be subject to D/A conversion (to be
FX3U-3A-ADP
I
FX3U-4AD-PT
-ADP
J
FX3U-4AD-PTW
-ADP
H-27
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 4 Programming
FX3U-3A-ADP (2-channel analog Input, 1-channel analog output) 4.12 Basic Program Example
M8002
RST D8268.6 Error status: b6 = OFF
Initial
pulse
RST D8268.7 Error status: b7 = OFF
M8000
FNC 12 K5 D8264 Set the averaging time to "5" for channel-1 data.
MOV
FNC 12 K5 D8265 Set the averaging time to "5" for channel-2 data.
MOV
M8000
FNC 12 D8260 D100 Stores the A/D converted channel-1 digital data
MOV into D100.
FNC 12 D8261 D101 Stores the A/D converted channel-2 digital data
MOV into D101.
M8000
FNC 12 D102 D8262 Performs D/A conversion with the digital data
MOV stored in D102.
Even if the input data is not stored into D100 or D101, the data registers D8260 or D8261 can be directly used
in the timer/counter setting value or in a PID instruction.
Using the indicator or the sequence program, input the digital data to be subject to D/A conversion (to be
output as analog data) in D102.
H-28
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 5 Changing of Input/output Characteristics
FX3U-3A-ADP (2-channel analog Input, 1-channel analog output) 5.1 Example: Changing of Voltage Input Characteristics
Common Items
5. Changing of Input/output Characteristics
Use the scaling instruction (SCL/FNC 259) for the FX3U/FX3UC Series PLC to change the input/output B
characteristics. FX3G Series PLCs do not support the scaling instruction. Use sequence programs to change
FX3UC-4AD
FX3U-4AD
the input/output characteristics.
→ For a detailed description of scaling instruction, refer to the FX3G/FX3U/FX3UC Series Programming
Manual - Basic & Applied Instruction Edition.
FX3U-4AD-ADP
This section describes an example of a program that can change the digital output range of 400 to 2000
(when the voltage input is 1 to 5V) to the digital output range of 0 to 10000.
1. Input characteristics
Voltage input characteristics Digital output value to be changed D
(product specifications)
FX3G-2AD-BD
Y-axis
Digital output
4000 10000
Digital output to
be calculated
(D110)
2000 E
FX3U-4DA
400
0 X-axis
1V 5V 10V 0 400(1V) 2000(5V)
Analog input
Digital value actually obtained
F
FX3U-4DA-ADP
by A/D conversion
FX3G-1DA-BD
H
FX3U-3A-ADP
I
FX3U-4AD-PT
-ADP
J
FX3U-4AD-PTW
-ADP
H-29
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 5 Changing of Input/output Characteristics
FX3U-3A-ADP (2-channel analog Input, 1-channel analog output) 5.1 Example: Changing of Voltage Input Characteristics
M8000
FNC 12 K1 D8264 Sets the averaging time to "1" for the channel-1 data
MOV
M8002 FNC 12 K2 D50 Program for setting scaling instruction data table
MOV
Item Description Value Device
FNC 12 K400 D51 Number of points Sets the number of points 2 D50
MOV X- A/D converted digital value 400 D51
Start coordinate start point data
FNC 12 K0 D52 point Y- Digital output value of changed
MOV coordinate X-axis value start point 0 D52
H-30
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 5 Changing of Input/output Characteristics
FX3U-3A-ADP (2-channel analog Input, 1-channel analog output) 5.1 Example: Changing of Voltage Input Characteristics
A
3. Example of program 2 (FX3G Series PLC)
Common Items
• For example, create the following program to change the digital input data (D110) of the 1st analog special
adapter:
M8001
M8280 Sets the input mode of channel 1 to the
voltage input mode
(0V to 10V).
B
M8000
FX3UC-4AD
FX3U-4AD
FNC 12 D8288 K4M0
MOV
M8002
RST M6 Error status: b6 = OFF
FX3U-4AD-ADP
FNC 12 K4M0 D8288
MOV
M8000 Sets the averaging scaling to "1"
FNC 12
K1 D8284 for the channel-1 data.
MOV
M8000
FNC 12
D
D8280 D110
FX3G-2AD-BD
MOV
FX3U-4DA
FNC 22 D111 K10000 D112 characteristics.
MUL
Stores the operation result in D100.
FNC 23 D112 K1600 D100
DDIV
F
4. Cautions regarding programming
FX3U-4DA-ADP
• GX Developer version 8.13P or later supports scaling instruction (SCL/FNC 259).
• If the A/D converted digital value is out of the data table range specified by the scaling instruction (SCL/
FNC 259), the FX Series PLC will detect an operation error (error code: K6706).
FX3G-1DA-BD
H
FX3U-3A-ADP
I
FX3U-4AD-PT
-ADP
J
FX3U-4AD-PTW
-ADP
H-31
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 5 Changing of Input/output Characteristics
FX3U-3A-ADP (2-channel analog Input, 1-channel analog output) 5.2 Example: Changing of Voltage Output Characteristics
1. Output characteristics
value to be actually
10V
Analog output
Y-axis
5V 2000
(5V)
1V 400
(1V)
0 400 2000 4000 X-axis
0 10000
Digital value input
Desired digital value (D120)
M8002
FNC 12 Program for setting scaling instruction data table
K2 D50
MOV
Item Description Value Device
FNC 12 Number of points Sets the number of points. 2 D50
K0 D51
MOV X- Digital value of specified 0 D51
Start coordinate start point on X-axis
FNC 12 point Y- Digital value of desired D/A
K400 D52 400 D52
MOV coordinate conversion start point
X- Digital value of specified end 10000 D53
FNC 12 K10000 D53 End coordinate point on X-axis
MOV point Y- Digital value of desired D/A 2000
coordinate conversion end point D54
FNC 12 K2000 D54
MOV
M8000 The result of operation by scaling instruction will be stored
FNC 259 D120 D50 D8262
SCL in the D8262.
H-32
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 5 Changing of Input/output Characteristics
FX3U-3A-ADP (2-channel analog Input, 1-channel analog output) 5.2 Example: Changing of Voltage Output Characteristics
A
3. Example of program 2 (FX3G Series PLC)
Common Items
• For example, create the following program to change the digital output data (D120) of the 1st analog
special adapter.
M8001
Sets the output mode to the voltage
Normally
M8282
output mode. B
FX3UC-4AD
FX3U-4AD
OFF
M8286 Sets the output holding function.
FNC 230 D120 K0 FNC 237 D120 K10000 M20 Check to make sure the digital
LD>= AND<= value (D120) is in range.
M20 C
FNC 22
FX3U-4AD-ADP
D120 K1600 D121
MUL
D
FNC 20 D123 K400 D127 Stores the operation result in D8282.
ADD
FX3G-2AD-BD
FNC 12 D127 D8282
MOV
FX3U-4DA
• If the input digital value for the D/A conversion is out of the data table range specified by scaling instruction
(SCL/FNC259), the FX Series PLC will detect an operation error (error code: K6706).
FX3U-4DA-ADP
G
FX3G-1DA-BD
H
FX3U-3A-ADP
I
FX3U-4AD-PT
-ADP
J
FX3U-4AD-PTW
-ADP
H-33
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 6 Troubleshooting
FX3U-3A-ADP (2-channel analog Input, 1-channel analog output) 6.1 PLC Version Number Check
6. Troubleshooting
This chapter describes troubleshooting methods and error statuses.
Refer to the following items when conversion data is not input or output, or when correct digital values are not
input or output.
• PLC version number
• Installation
• Wiring
• Special devices
• Programs
• Error status
1. Power
The 3A-ADP needs driving power. Verify that the power supply line is properly connected. Also check that the
POWER indicator lamp of the 3A-ADP is on.
3. Input data
Verify that the special device of the selected channel is correctly selected. This special device should be
selected depending on the connecting position and the channel.
H-34
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 6 Troubleshooting
FX3U-3A-ADP (2-channel analog Input, 1-channel analog output) 6.4 Program Check
A
4. Output setting data
Common Items
Check that the special device of the selected channel is correctly selected. This special device should be
selected depending on the connected position and the channel.
5. Averaging time
Check that the set averaging time is within the specified range. The averaging time should be set in the range
from 1 to 4095. If the set averaging time is outside the specified range, an error occurs.
B
FX3UC-4AD
FX3U-4AD
6. Setting whether or not each channel is used
Check whether each channel is set correctly.
Set a channel to OFF when using it. Set a channel to ON when not using it.
7. Error status C
Check that no error is detected in the 3A-ADP.
FX3U-4AD-ADP
If an error is detected, check the details of the error, and then check the wiring and programs.
→ For a detailed description of special devices, refer to Chapter 4.
FX3G-2AD-BD
1. Clearing of error status at power on
When the power is turned off and then on again, the error status should be cleared (b6 and b7 should turn off)
using the program.
FX3U-4DA
Verify that different values are not being stored in the same device by other parts of the program.
FX3U-4DA-ADP
If an error occurs in the 3A-ADP, the corresponding bit will turn on.
FX3G-1DA-BD
b1 Channel-2 over-scale detection b6
(Power supply error included)*1
b2 Output data setting error b7 3A-ADP communication data error*2
b3 Unused b8 to b15 Unused
b4 EEPROM error - -
H
*1. 3A-ADP hardware error (b6) is valid only when use of analog input is set.
FX3U-3A-ADP
Detection of power supply error is valid only when use of the analog input channel 2 is set.
*2. 3A-ADP communication data error (b7) is valid only when use of analog input is set.
1) Description of error
The input analog value (voltage or current value) is outside the specified range.
The digital value is out of the range specified for the voltage input mode (0 to 4080) or outside the range
-ADP
H-35
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 6 Troubleshooting
FX3U-3A-ADP (2-channel analog Input, 1-channel analog output) 6.5 Error Status Check
H-36
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition
FX3U-4AD-PT-ADP (4-channel Platinum Resistance Thermometer Data Input)
Common Items
B
FX3UC-4AD
FX3U-4AD
FX3G/FX3U/FX3UC Series Programmable
Controllers C
FX3U-4AD-ADP
User's Manual [Analog Control Edition]
FX3U-4AD-PT-ADP
D
(4-channel Platinum Resistance Thermometer Data Input)
FX3G-2AD-BD
E
FX3U-4DA
F
FX3U-4DA-ADP
G
FX3G-1DA-BD
H
FX3U-3A-ADP
Foreword
This manual describes the specifications, wiring, and operation methods for the FX3U-4AD-PT-ADP special
adapter (4-channel platinum resistance thermometer input) and should be read and understood before I
attempting to install or use the unit.
FX3U-4AD-PT
Store this manual in a safe place so that you can take it out and read it whenever necessary. Always forward
it to the end user.
-ADP
This manual confers no industrial property rights or any rights of any other kind, nor does it confer any patent
licenses. Mitsubishi Electric Corporation cannot be held responsible for any problems involving industrial property
rights which may occur as a result of using the contents noted in this manual.
J
FX3U-4AD-PTW
I-1
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition
FX3U-4AD-PT-ADP (4-channel Platinum Resistance Thermometer Data Input)
I-2
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 1 Outline
FX3U-4AD-PT-ADP (4-channel Platinum Resistance Thermometer Data Input) 1.1 Outline of Functions
Common Items
1. Outline
This chapter describes the outline of FX3U-4AD-PT-ADP (referred to as PT-ADP). B
FX3UC-4AD
FX3U-4AD
1.1 Outline of Functions
The FX3U-4AD-PT-ADP is an analog special adapter. Connect the FX3U-4AD-PT-ADP to the FX3U/FX3UC/
FX3G Series PLC to read the temperature data from the 4-channel platinum resistance thermometers.
C
1) Up to 4 PT-ADP units can be connected to the FX3U/FX3UC Series PLC.
FX3U-4AD-ADP
Up to 2*1 PT-ADP units can be connected to the FX3G Series PLC.
(including other analog special adapters)
2) After connection of the platinum resistance thermometer (Pt100), measurement of temperature will be
possible.
3) The temperature measurement data will be automatically written to the special data registers of the FX3U/ D
FX3UC/FX3G Series PLC.
FX3G-2AD-BD
System Point and section to be
referred to
FX3U-4DA
To check the connectable
…… PLC model number, refer
+ + to Section 1.3.
FX3U-4DA-ADP
Expansion
4th 3rd 2nd 1st
adapter adapter adapter adapter board*2
For a detailed
…… description of wiring,
Analog data refer to Chapter 3.
FX3G-1DA-BD
For FX3U, FX3UC
Series PLC For a detailed description
Description
Measurement
Special devices
1st adapter M/D8260 to M/D8269
…… of special devices, refer to
Chapter 4. H
temperature Transfer direction
FX3U-3A-ADP
Refer to the system configuration shown in the User's Manual - Hardware Edition to check the number of connectable units
and to configure the entire system. I
FX3U-4AD-PT
*1. Only 1 analog special adapter can be connected to the 14-point and 24-point type main unit.
*2. The expansion board is not required when connecting with the FX3UC (D, DSS) PLC.
-ADP
J
FX3U-4AD-PTW
-ADP
I-3
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 1 Outline
FX3U-4AD-PT-ADP (4-channel Platinum Resistance Thermometer Data Input) 1.2 Setup Procedure Before Starting Operation
FX3U-4AD-PT-ADP
Refer to Chapter 1.
I-4
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 1 Outline
FX3U-4AD-PT-ADP (4-channel Platinum Resistance Thermometer Data Input) 1.3 Connectable PLC and Its Version Number
A
1.3 Connectable PLC and Its Version Number
Common Items
PT-ADP is compatible with the following PLC.
FX3UC-4AD
FX3U-4AD
FX3UC Series PLC Ver. 1.30 or later After August 2004
FX3G Series PLC Ver. 1.00 or later After June 2008 (initial production)
1. Version check
Special data register D8001 contains information for determining the PLC version.
C
FX3U-4AD-ADP
→ For a detailed description of the version check, refer to A. Common Items Subsection 5.1.2.
FX3G-2AD-BD
1.4 Compatible Programming Tool Version Number
Use the programming tool with the following version number to create programs for PT-ADP of the FX3U/
FX3UC/FX3G Series PLC: E
FX3U-4DA
1. GX Developer
Software Version number Remarks
GX Developer Ver. SW8 P or later
When selecting a model, select FX3U(C)*1.
• SW D5C-GPPW-J
• SW D5C-GPPW-E
(Ver. 8.13P)
F
Ver. 8.72A or later When selecting a model, select FX3G.
FX3U-4DA-ADP
If a programming tool with the wrong version number is used, programming will not be possible.
*1. For Ver. 8.13P to 8.24A of GX Developer, select FX3UC for the PLC type.
2. FX-30P G
FX3G-1DA-BD
Model name Version number Remarks
FX-30P Ver.1.00 or later
H
FX3U-3A-ADP
I
FX3U-4AD-PT
-ADP
J
FX3U-4AD-PTW
-ADP
I-5
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 2 Specifications
FX3U-4AD-PT-ADP (4-channel Platinum Resistance Thermometer Data Input) 2.1 Generic Specifications
2. Specifications
This chapter describes the general, power supply, and performance specifications for the PT-ADP.
Item Specifications
Ambient 0 to 55°C (32 to 131°F) when operating
temperature -25 to 75°C (-13 to 167°F) when stored
Relative
5 to 95%RH (no condensation) when operating
humidity
Frequency Acceleration Half amplitude
(Hz) (m/s2) (mm)
Tested 10 times in each
Vibration 10 - 57 - 0.035 direction (X-, Y-, and Z-
DIN Rail Mounting
resistance*1 57 - 150 4.9 - axis directions) (Total:
80 min, each)
10 to 57 − 0.075
Direct Mounting*2
57 to 150 9.8 −
Shock
147 m/s2 Acceleration, Action time: 11ms, 3 times by half-sine pulse in each direction X, Y, and Z
resistance*1
Noise Using noise simulator of:
resistance Noise voltage: 1,000Vp-p / Noise width: 1μs / Rise: 1ns / Cycle: 30 to 100Hz
Dielectric
withstand 500 V AC, for 1 min
voltage Between all terminals and ground terminal
Insulation 5MΩ or more using 500V DC
resistance insulation resistance meter
Class D grounding (grounding resistance: 100 Ω or less)
Grounding
<Common grounding with a heavy electrical system is not allowed.>*3
Working
Free from corrosive or flammable gas and excessive conductive dusts
environment
Working
altitude < 2000m*4
I-6
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 2 Specifications
FX3U-4AD-PT-ADP (4-channel Platinum Resistance Thermometer Data Input) 2.2 Power Supply Specifications
A
2.2 Power Supply Specifications
Common Items
Items Specification
A/D conversion circuit 24V DC +20% -15%, 50mA B
driving power (It is necessary to connect a 24V DC power supply to the terminal block.)
FX3UC-4AD
FX3U-4AD
5V DC, 15mA
Interface driving power (Since the internal power is supplied from the FX Series main unit, it is not
necessary to supply the power.)
FX3U-4AD-ADP
Specifications
Items
Centigrade (°C) Fahrenheit (°F)
Input signal
3-wire platinum resistance thermometer sensor
Pt100 JIS C 1604-1997
D
FX3G-2AD-BD
Rated temperature
-50°C to +250°C -58°F to +482°F
range
Digital output -500 to +2500 -580 to +4820
Resolution 0.1°C 0.18°F
Total accuracy
• ±0.5% for full scale (when ambient temperature is 25°C±5°C) E
• ±1.0% for full scale (when ambient temperature is in the range from 0 to 55°C)
FX3U-4DA
• FX3U/FX3UC Series PLC : 200μs (The data will be updated at every scan time.)
A/D conversion
• FX3G Series PLC : 250μs (The data will be updated at every scan time.)
time
→For a detailed description of data update, refer to Section 2.4.
+2550 +4910
F
FX3U-4DA-ADP
+2500 +4820
+255°C
+491°F
Input
characteristics -50°C 0 -58°F 0
+250°C +482°F G
-55°C
-67°F
FX3G-1DA-BD
-500 -580
-550 -670
• The photocoupler is used to insulate the analog input area from the PLC.
• The DC/DC converter is used to insulate the power supply line from the analog input
Insulation method
area. H
• Channels are not insulated from each other.
FX3U-3A-ADP
I
FX3U-4AD-PT
-ADP
J
FX3U-4AD-PTW
-ADP
I-7
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 2 Specifications
FX3U-4AD-PT-ADP (4-channel Platinum Resistance Thermometer Data Input) 2.4 A/D Conversion Time
Sequence
program
A/D conversion start
A/D command
conversion
Digital value reading
200μs/4ch
A/D conversion start END instruction
A/D command
conversion
Digital value reading
200μs/4ch
I-8
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 2 Specifications
FX3U-4AD-PT-ADP (4-channel Platinum Resistance Thermometer Data Input) 2.5 Temperature Measurement
A
2.4.2 When connected to a FX3G PLC
Common Items
1. A/D conversion and special data register update timing
A/D conversion is performed at every scan time of the PLC.
During execution of END instruction, the PLC performs A/D conversion, reads out the A/D converted data,
and then writes the data in the special data registers. B
FX3UC-4AD
FX3U-4AD
FX3U-4AD-PT-ADP FX3U-4AD-PT-ADP
2nd 1st FX3G Series PLC
Sequence
FX3U-4AD-ADP
A/D command
conversion
Digital value reading
250μs/4ch
A/D conversion start END instruction
A/D
conversion
command
D
FX3G-2AD-BD
Digital value reading
250μs/4ch
FX3U-4DA
3. If two analog special adapters are connected
During execution of the END instruction, data will be read out from all the connected adapters (in the order of
1st adapter → 2nd adapter).
FX3U-4DA-ADP
and the data read out will be written to the special data registers.
END instruction execution time will be "250μs × number of connected adapters."
FX3G-1DA-BD
H
FX3U-3A-ADP
I
FX3U-4AD-PT
-ADP
J
FX3U-4AD-PTW
-ADP
I-9
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 3 Wiring
FX3U-4AD-PT-ADP (4-channel Platinum Resistance Thermometer Data Input)
3. Wiring
This chapter describes the PT-ADP wiring.
Observe the following caution to wire the PT-ADP.
WIRING PRECAUTIONS
• Make sure to cut off all phases of the power supply externally before attempting wiring work.
Failure to do so may cause electric shock or damages to the product.
WIRING PRECAUTIONS
• Connect the DC power supply wiring to the dedicated terminals described in this manual.
If an AC power supply is connected to a DC input/output terminal or DC power supply terminal, the PLC will be
burnt out.
• Do not wire vacant terminals externally.
Doing so may damage the product.
• Perform class D grounding (grounding resistance: 100Ω or less) to the grounding terminal on the main unit.
Do not use common grounding with heavy electrical systems.
• When drilling screw holes or wiring, make sure cutting or wire debris does not enter the ventilation slits.
Failure to do so may cause fire, equipment failures or malfunctions.
• Make sure to observe the following precautions in order to prevent malfunctions under the influence of noise:
- Do not bundle the power line or twisted shielded cable together with or lay it close to the main circuit, high-
voltage line, or load line.
Otherwise, noise disturbance and/or surge induction are likely to take place. As a guideline, lay the control line
at least 100mm (3.94") or more away from the main circuit, high-voltage line, or load line.
- Ground the shield of the analog input/output cable at one point on the signal receiving side.
However, do not use common grounding with heavy electrical systems.
• Make sure to properly wire to the European terminal board in accordance with the following precautions.
Failure to do so may cause electric shock, a short-circuit, wire breakage, or damage to the product.
- The disposal size of the cable end should be 9 mm (0.35").
- Tightening torque should be between 0.22 to 0.25 N•m.
- Twist the end of strand wire and make sure there are no loose wires.
- Do not solder-plate the electric wire ends.
- Do not connect more than the specified number of wires or electric wires of unspecified size.
- Affix the electric wires so that neither the terminal block nor the connected parts are directly stressed.
I-10
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 3 Wiring
FX3U-4AD-PT-ADP (4-channel Platinum Resistance Thermometer Data Input) 3.1 Terminal Layout
A
3.1 Terminal Layout
Common Items
The terminals of the PT-ADP are arranged as follows:
FX3UC-4AD
FX3U-4AD
FX3U-4AD-PT
-ADP
POWER
Signal Application C
24+
24+
FX3U-4AD-ADP
External power
24-
24-
Ground terminal
L1+
L1+
Channel-1 platinum
resistance thermometer
L1-
L1-
sensor input
I1-
I1-
D
L2+
resistance thermometer
FX3G-2AD-BD
L2-
sensor input
I2-
I2-
L3+
FX3U-4DA
sensor input
I4-
I4-
FX3U-4DA-ADP
G
FX3G-1DA-BD
H
FX3U-3A-ADP
I
FX3U-4AD-PT
-ADP
J
FX3U-4AD-PTW
-ADP
I-11
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 3 Wiring
FX3U-4AD-PT-ADP (4-channel Platinum Resistance Thermometer Data Input) 3.2 Applicable Cable and Terminal Tightening Torque
1. Cables
Applicable cable and tightening torque
Wire size Tightening
Termination
(stranded/single-wire) torque
2 2 • To connect a stranded cable, peel the cover off the cable
Single-wire 0.3mm to 0.5mm and then twist the core before connection.
(AWG22 to 20)
• To connect a single-wire cable, just strip the cover off the
2-wire 0.3mm2 (AWG22) cable before connection.
0.22 N•m to • Rod terminal with insulation sleeve
Rod 0.3mm2 to 0.5mm2 0.25 N•m (recommended terminal)
terminal (AWG22 to 20) AI 0.5-8WH : Manufactured by Phoenix Contact
with (Refer to the rod terminal
• Caulking tool
insulation external view shown in
CRIMPFOX ZA 3 : Manufactured by Phoenix Contact
sleeve the following figure.)
(or CRIMPFOX UD 6 : Manufactured by Phoenix Contact)
3. Tool
• To tighten terminals, use a small-sized screwdriver whose head is straight and is not widened as shown in
the figure to the right.
Note:
If the diameter of screwdriver grip is too small, tightening torque will not
The head
be able to be achieved. Use the following recommended screwdriver or should be
an appropriate replacement (grip diameter: approximately 25mm). straight.
Manufacturer Type
Phoenix Contact SZS 0.4 × 2.5 0.4mm 2.5mm
(0.01") (0.09")
I-12
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 3 Wiring
FX3U-4AD-PT-ADP (4-channel Platinum Resistance Thermometer Data Input) 3.3 Power Supply Line
A
3.3 Power Supply Line
Common Items
Connect the 24V DC power supply line of the PT-ADP to the 24+ and 24- terminals of the terminal block.
FX3UC-4AD
FX3U-4AD
1. To use an external power 2. To use the 24V DC power of the PLC
FX3U-4AD-ADP
24- 24+ 24- 24+ 0V 24V D
FX3G-2AD-BD
Terminal Terminal
block block
Class-D Class-D
24V DC grounding grounding
E
Caution regarding connection of the power supply line:
FX3U-4DA
• Ground the " " terminal to a class-D grounding power supply line (100Ω or less) together with the
ground terminal of the PLC main unit.
• For the timing of power-on/off when using an external power supply, see the following manual of the PLC
to be connected.
→ Refer to the FX3G Series User's Manual - Hardware Edition. F
→ Refer to the FX3U Series User's Manual - Hardware Edition.
FX3U-4DA-ADP
3.3.2 To Connect To The FX3UC Series PLC
FX3G-1DA-BD
+5V (Input extension
block)
Power
H
Power crossover
FX3U-3A-ADP
Power
connector connector connector
Class-D
24V DC grounding
-ADP
• Ground the " " terminal to a class-D grounding power supply line (100Ω or less) together with the
grounding terminal of the PLC main unit.
-ADP
I-13
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 3 Wiring
FX3U-4AD-PT-ADP (4-channel Platinum Resistance Thermometer Data Input) 3.4 Selection of the Platinum Resistance Thermometer Sensor
PT-ADP
+5V
Shield +5V
+5V
24+
24V DC
24-
Class-D grounding
L +, L -, I -, ch : represents the channel number.
*1. Separate the cable of the platinum resistance thermometer sensor from the other power cables or
areas easily affected by inductive noise (of the commercial power, etc.).
3.6 Grounding
Grounding should be performed as stated below.
• The grounding resistance should be 100Ω or less.
• Independent grounding should be performed for best results.
When independent grounding is not performed, perform "shared grounding" as shown in the following
figure.
→ For details, refer to the User’s Manual - Hardware Edition of the PLC Series.
I-14
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 4 Programming
FX3U-4AD-PT-ADP (4-channel Platinum Resistance Thermometer Data Input) 4.1 Loading of A/D Conversion Data
Common Items
4. Programming
This chapter describes how to create programs that can read analog data using the PT-ADP. B
FX3UC-4AD
FX3U-4AD
4.1 Loading of A/D Conversion Data
1) The input analog data will be converted into digital data and then stored in the special devices of the
FX3U/FX3UC/FX3G Series PLC.
C
2) If data is stored in the special devices, the averaging time can be set, and the input mode can be
FX3U-4AD-ADP
specified.
3) Special auxiliary relays (10 points) and special data registers (10 points) are assigned automatically
starting from the adapter nearest to the main unit.
→ For a detailed description of special device assignment, refer to Section 4.2.
• FX3U, FX3UC Series PLC D
FX3G-2AD-BD
Communi- High-speed
cation input/output
FX3U-4AD FX3U-4AD FX3U-4AD special FX3U-4AD special
-PT-ADP -PT-ADP -PT-ADP adapter -PT-ADP adapter FX3U/FX3UC Series PLC
FX3U-4DA
A/D M8260 to M8269
Special data registers:
D8260 to D8269
FX3U-4DA-ADP
Special auxiliary relays:
A/D M8280 to M8289
Special data registers:
D8280 to D8289
A/D
Special auxiliary relays:
M8290 to M8299 G
Special data registers:
FX3G-1DA-BD
D8290 to D8299
The analog special adapter nearest to the main unit is counted as the 1st analog special adapter, and the
next adapter as the 2nd analog special adapter, and so on. However, in this case, do not include the high-
speed input/output special adapter, communication special adapter, and the CF card special adapter.
H
FX3U-3A-ADP
I
FX3U-4AD-PT
-ADP
J
FX3U-4AD-PTW
-ADP
I-15
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 4 Programming
FX3U-4AD-PT-ADP (4-channel Platinum Resistance Thermometer Data Input) 4.1 Loading of A/D Conversion Data
2nd*1 1st
Special devices
Special auxiliary relays:
M8280 to M8289
A/D Special data registers:
D8280 to D8289 Sequence
Program
Special auxiliary relays:
M8290 to M8299
A/D Special data registers:
D8290 to D8299
The analog special adapter nearest to the main unit is counted as the 1st analog special adapter, and the
next adapter as the 2nd analog special adapter. However, in this case, do not include the connector
conversion adapter and the communication special adapter.
*1. The second special adapter is not available in the FX3G Series PLC(14-point and 24-point type).
I-16
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 4 Programming
FX3U-4AD-PT-ADP (4-channel Platinum Resistance Thermometer Data Input) 4.2 List of Special Devices
A
4.2 List of Special Devices
Common Items
If the PT-ADP is connected, special devices will be assigned automatically as shown in the following table:
• FX3U, FX3UC Series PLC
R: Read / W: Write
Special Device number
B
Description Attribute Reference
FX3UC-4AD
FX3U-4AD
device 1st 2nd 3rd 4th
Section
Special M8260 M8270 M8280 M8290 Selects the temperature unit. R/W
4.3
auxiliary
relay M8261 to M8271 to M8281 to M8291 to
Unused (Do not use.) - -
M8269 M8279 M8289 M8299
C
Channel-1 temperature
FX3U-4AD-ADP
D8260 D8270 D8280 D8290 R
measurement data
Channel-2 temperature
D8261 D8271 D8281 D8291 R
measurement data Section
Channel-3 temperature 4.4
D8262 D8272 D8282 D8292 R
measurement data
D
Channel-4 temperature
D8263 D8273 D8283 D8293 R
FX3G-2AD-BD
measurement data
Averaging time for channel 1
Special D8264 D8274 D8284 D8294 R/W
(Setting range: 1 to 4095)
data
register Averaging time for channel 2
D8265 D8275 D8285 D8295 R/W
(Setting range: 1 to 4095) Section
4.5
E
Averaging time for channel 3
D8266 D8276 D8286 D8296 R/W
FX3U-4DA
(Setting range: 1 to 4095)
Averaging time for channel 4
D8267 D8277 D8287 D8297 R/W
(Setting range: 1 to 4095)
Section
D8268 D8278 D8288 D8298 Error status R/W
4.6
Section
F
D8269 D8279 D8289 D8299 Model code = 20 R
FX3U-4DA-ADP
4.7
FX3G-1DA-BD
H
FX3U-3A-ADP
I
FX3U-4AD-PT
-ADP
J
FX3U-4AD-PTW
-ADP
I-17
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 4 Programming
FX3U-4AD-PT-ADP (4-channel Platinum Resistance Thermometer Data Input) 4.3 Selection of Temperature Unit
I-18
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 4 Programming
FX3U-4AD-PT-ADP (4-channel Platinum Resistance Thermometer Data Input) 4.4 Temperature Measurement
A
4.4 Temperature Measurement
Common Items
The temperature data input in the PT-ADP will be stored in the special data registers.
The special data registers that store the temperature data are shown in the following table:
• FX3U, FX3UC Series PLC
B
Special data register
FX3UC-4AD
FX3U-4AD
Description
1st 2nd 3rd 4th
D8260 D8270 D8280 D8290 Stores the channel-1 temperature measurement data.
D8261 D8271 D8281 D8291 Stores the channel-2 temperature measurement data.
D8262 D8272 D8282 D8292 Stores the channel-3 temperature measurement data. C
D8263 D8273 D8283 D8293 Stores the channel-4 temperature measurement data.
FX3U-4AD-ADP
• FX3G Series PLC
FX3G-2AD-BD
D8280 D8290 Stores the channel-1 temperature measurement data.
D8281 D8291 Stores the channel-2 temperature measurement data.
D8282 D8292 Stores the channel-3 temperature measurement data.
D8283 D8293 Stores the channel-4 temperature measurement data.
E
FX3U-4DA
The immediate data or the average data (data averaged in accordance with the specified averaging time) will
be stored in the above data registers as the temperature measurement data.
→ For a detailed description of the averaging time, refer to Section 4.6.
FX3U-4DA-ADP
Do not change (rewrite) the current data using the sequence program, indicator, or device monitor of the
programming tool.
FX3G-1DA-BD
ON
Even if the temperature measurement data is not stored in the D100 or the D101, the D8260 or the D8261
can be directly used in the arithmetic operation instruction or a PID instruction.
H
FX3U-3A-ADP
I
FX3U-4AD-PT
-ADP
J
FX3U-4AD-PTW
-ADP
I-19
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 4 Programming
FX3U-4AD-PT-ADP (4-channel Platinum Resistance Thermometer Data Input) 4.5 Averaging Time
I-20
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 4 Programming
FX3U-4AD-PT-ADP (4-channel Platinum Resistance Thermometer Data Input) 4.6 Error Status
A
4.6 Error Status
Common Items
If an error is detected in the PT-ADP, the error status data will be stored in the corresponding special data
register.
The following table shows the special data registers that store the error status data:
• FX3U, FX3UC Series PLC B
FX3UC-4AD
FX3U-4AD
Special data register
Description
1st 2nd 3rd 4th
D8268 D8278 D8288 D8298 Stores the error status data.
C
• FX3G Series PLC
FX3U-4AD-ADP
Special data register
Description
1st 2nd
D8288 D8298 Stores the error status data.
D
FX3G-2AD-BD
Check the ON/OFF status of each bit of the error status data register to determine the error. Errors are
assigned to the bits as shown in the following table. Create a program to detect errors.
b0
The temperature measurement data
of channel 1 is outside the specified b5 Averaging time setting error
E
FX3U-4DA
range, or disconnection is detected.
The temperature measurement data
b1 of channel 2 is outside the specified b6 PT-ADP hardware error
range, or disconnection is detected.
The temperature measurement data
b2 of channel 3 is outside the specified b7 PT-ADP communication data error F
range, or disconnection is detected.
FX3U-4DA-ADP
The temperature measurement data
b3 of channel 4 is outside the specified b8 to b15 Unused
range, or disconnection is detected.
b4 EEPROM error - -
G
1. Caution regarding use of error status data
FX3G-1DA-BD
If a PT-ADP hardware error (b6) or PT-ADP communication data error (b7) is detected, it is necessary to clear
the error status with a program at the next power-on of the PLC.
For this reason, be sure to create the following program:
• For FX3G, FX3U, FX3UC Series PLC
M8000
H
FX3U-3A-ADP
I-21
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 4 Programming
FX3U-4AD-PT-ADP (4-channel Platinum Resistance Thermometer Data Input) 4.6 Error Status
M8002
RST D8268.6 Error status of 1st analog special adapter
b6 = OFF (hardware error)
Initial pulse
M8000
MOV D8288 K4M0
M0
Y000 The temperature measurement data
of channel 1 is outside the specified
range, or disconnection is detected.
M1
Y001 The temperature measurement data
of channel 2 is outside the specified
range, or disconnection is detected.
M2
Y002 The temperature measurement data
of channel 3 is outside the specified
range, or disconnection is detected.
M3
Y003 The temperature measurement data
of channel 4 is outside the specified
range, or disconnection is detected.
M4
Y004 EEPROM error in 3rd*1 adapter
M5
Y005 Averaging time setting error in 3rd*1
adapter
M6
Y006 PT-ADP hardware error in 3rd*1
adapter
M7
Y007 PT-ADP communication data error in
3rd*1 adapter
I-22
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 4 Programming
FX3U-4AD-PT-ADP (4-channel Platinum Resistance Thermometer Data Input) 4.6 Error Status
A
3. Program Example 2 (For FX3U, FX3UC Series PLC)
Common Items
D8268.0
Y000 The temperature measurement data
of channel 1 is outside the specified
D8268.1
range, or disconnection is detected. B
Y001 The temperature measurement data
FX3UC-4AD
FX3U-4AD
of channel 2 is outside the specified
range, or disconnection is detected.
D8268.2
Y002 The temperature measurement data
of channel 3 is outside the specified
D8268.3
range, or disconnection is detected. C
Y003 The temperature measurement data
FX3U-4AD-ADP
of channel 4 is outside the specified
range, or disconnection is detected.
D8268.4
Y004 EEPROM error in 1st adapter
D8268.5
D
Averaging time setting error in 1st
FX3G-2AD-BD
Y005
adapter
D8268.6
Y006 PT-ADP hardware error in 1st
adapter
D8268.7
E
PT-ADP communication data error in
FX3U-4DA
Y007
1st adapter
FX3U-4DA-ADP
G
FX3G-1DA-BD
H
FX3U-3A-ADP
I
FX3U-4AD-PT
-ADP
J
FX3U-4AD-PTW
-ADP
I-23
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 4 Programming
FX3U-4AD-PT-ADP (4-channel Platinum Resistance Thermometer Data Input) 4.7 Model Code
Use the special data registers above to check whether PT-ADP is connected or not.
FNC224 D8269 K20 Y010 Checks the model code of the 1st
LD = analog special adapter.
I-24
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 4 Programming
FX3U-4AD-PT-ADP (4-channel Platinum Resistance Thermometer Data Input) 4.8 Basic Program Example
A
4.8 Basic Program Example
Common Items
Create the following basic program example to read out the temperature measurement data.
• For FX3G, FX3U, FX3UC Series PLC
The following program will store the temperature measurement data (°C) from channels 1 and 2 of the 3rd*1
adapter to D100 and D101, respectively. The averaging time is set to "1" (immediate data) for channel 1, and
B
FX3UC-4AD
FX3U-4AD
"5" for channel 2.
M8000
MOV D8288 K4M0
M8002
RST M6
Error status of 3rd*1 analog special
adapter C
Initial b6 = OFF (hardware error)
FX3U-4AD-ADP
pulse Error status of 3rd*1 analog special
RST M7
adapter
b7 = OFF (communication data error)
MOV K4M0 D8288
M8001
Sets the temperature unit to centigrade
D
M8280
FX3G-2AD-BD
(°C).
M8002
FNC 12 Sets the averaging time to "1" for
K1 D8284 channel-1 data.
MOV
FX3U-4DA
FNC 12 D8280 D100 Stores the current value of the channel-1
MOV temperature measurement data in the D100.
Even if the temperature measurement data is not stored in D100 or D101, data register D8280 or D8281 can F
be directly used in the arithmetic operation instruction or a PID instruction.
FX3U-4DA-ADP
*1. "1st" for the FX3G PLC.
• For FX3U, FX3UC Series PLC
The following program will store the temperature measurement data (°C) from channels 1 and 2 of the 1st
adapter to D100 and D101, respectively. The averaging time is set to "1" (immediate data) for channel 1, and
"5" for channel 2. G
FX3G-1DA-BD
M8002 Error status of 1st analog special
RST D8268.6 adapter
b6 = OFF (hardware error)
M8260 (°C).
M8002
FNC 12 Sets the averaging time to "1" for
K1 D8264 channel-1 data.
MOV
FNC 12
MOV
K5 D8265 Sets the averaging time to "5" for
channel-2 data. I
FX3U-4AD-PT
M8000
FNC 12 D8260 D100 Stores the current value of the channel-1
MOV temperature measurement data in the D100.
-ADP
Even if the temperature measurement data is not stored in D100 or D101, data register D8260 or D8261 can
J
FX3U-4AD-PTW
I-25
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 5 Troubleshooting
FX3U-4AD-PT-ADP (4-channel Platinum Resistance Thermometer Data Input) 5.1 PLC Version Number Check
5. Troubleshooting
This chapter describes the troubleshooting methods and error status.
If the temperature measurement data is not input, or if the proper digital value is not input, check the following
items:
• Version number of the PLC
• Wiring
• Special devices
• Programs
• Error status
1. Power
The PT-ADP needs driving power. Verify that the power supply line is properly connected. Also check that the
POWER indicator lamp of the PT-ADP is on.
1. Temperature measurement
Verify that the special device for the selected channel is correctly selected. This special device should be
selected depending on the connecting position and the channel.
2. Averaging time
Check that the set averaging time is within the specified range. The averaging time should be set in the range
from 1 to 4095. If the set averaging time is outside the specified range, an error occurs.
3. Error status
Check that no error is detected in the PT-ADP.
If an error is detected, check the details of the error, and then check the wiring and programs.
→ For a detailed description of special devices, refer to Chapter 4.
I-26
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 5 Troubleshooting
FX3U-4AD-PT-ADP (4-channel Platinum Resistance Thermometer Data Input) 5.4 Program Check
A
5.4 Program Check
Common Items
Check the following items for the program:
FX3UC-4AD
FX3U-4AD
2. Check of storage devices
Verify that different values are not being stored in the same device by the other parts of the programs.
FX3U-4AD-ADP
If an error occurs in the PT-ADP, the corresponding bit will turn on.
FX3G-2AD-BD
The temperature measurement data of
b1 channel 2 is outside the specified b6 PT-ADP hardware error
range, or disconnection is detected.
The temperature measurement data of
b2 channel 3 is outside the specified
range, or disconnection is detected.
b7 PT-ADP communication data error
E
FX3U-4DA
The temperature measurement data of
b3 channel 4 is outside the specified b8 to 15 Unused
range, or disconnection is detected.
b4 EEPROM error - -
To solve a problem, refer to the troubleshooting method described below: F
FX3U-4DA-ADP
1. Temperature measurement out of specified range or disconnection of line (b0 to b3)
1) Description of error
The input temperature measurement value is outside the specified range.
The temperature measurement value is not in the range between -55°C to 255°C.
Or the line between PT-ADP and the platinum resistance thermometer sensor is disconnected. G
2) Remedy
FX3G-1DA-BD
Check that the input temperature measurement value is within the specified range. Also check the wiring
condition.
is destroyed.
2) Remedy
Please contact the nearest Mitsubishi Electric distributor office.
The averaging time set for one of the channels (channels 1 to 4) is outside the specified
range: 1 to 4095.
2) Remedy
-ADP
Check that the averaging time is correctly set for each channel.
J
FX3U-4AD-PTW
-ADP
I-27
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 5 Troubleshooting
FX3U-4AD-PT-ADP (4-channel Platinum Resistance Thermometer Data Input) 5.5 Error Status Check
I-28
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition
FX3U-4AD-PTW-ADP (4-channel Platinum Resistance Thermometer Data Input)
Common Items
B
FX3UC-4AD
FX3U-4AD
FX3G/FX3U/FX3UC Series Programmable
Controllers C
FX3U-4AD-ADP
User's Manual [Analog Control Edition]
FX3U-4AD-PTW-ADP
D
(4-channel Platinum Resistance Thermometer Data Input)
FX3G-2AD-BD
E
FX3U-4DA
F
FX3U-4DA-ADP
G
FX3G-1DA-BD
H
FX3U-3A-ADP
Foreword
This manual describes the specifications, wiring, and operation methods for the FX3U-4AD-PTW-ADP special
adapter (4-channel platinum resistance thermometer input) and should be read and understood before I
attempting to install or use the unit.
FX3U-4AD-PT
Store this manual in a safe place so that you can take it out and read it whenever necessary. Always forward
it to the end user.
-ADP
This manual confers no industrial property rights or any rights of any other kind, nor does it confer any patent
licenses. Mitsubishi Electric Corporation cannot be held responsible for any problems involving industrial property
rights which may occur as a result of using the contents noted in this manual.
J
FX3U-4AD-PTW
J-1
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition
FX3U-4AD-PTW-ADP (4-channel Platinum Resistance Thermometer Data Input)
J-2
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 1 Outline
FX3U-4AD-PTW-ADP (4-channel Platinum Resistance Thermometer Data Input) 1.1 Outline of Functions
Common Items
1. Outline
This chapter describes the outline of FX3U-4AD-PTW-ADP (referred to as PTW-ADP). B
FX3UC-4AD
FX3U-4AD
1.1 Outline of Functions
The FX3U-4AD-PTW-ADP is an analog special adapter. Connect the FX3U-4AD-PTW-ADP to the FX3U/
FX3UC/FX3G Series PLC to read the temperature data from the 4-channel platinum resistance thermometers.
C
1) Up to 4 PTW-ADP units can be connected to the FX3U/FX3UC Series PLC.
FX3U-4AD-ADP
Up to 2*1 PTW-ADP units can be connected to the FX3G Series PLC.
(including other analog special adapters)
2) After connection of the platinum resistance thermometer (Pt100), measurement of temperature will be
possible.
3) The temperature measurement data will be automatically written to the special data registers of the FX3U/ D
FX3UC/FX3G Series PLC.
FX3G-2AD-BD
System Point and section to be
referred to
FX3U-4DA
To check the connectable
…… PLC model number, refer
+ + to Section 1.3.
FX3U-4DA-ADP
Expansion
4th 3rd 2nd 1st
adapter adapter adapter adapter board*2
For a detailed
…… description of wiring,
Analog data refer to Chapter 3.
FX3G-1DA-BD
For FX3U, FX3UC
Series PLC For a detailed description
…… of special devices, refer to
H
Description Special devices Chapter 4.
Measurement 1st adapter M/D8260 to M/D8269
temperature Transfer direction
For a detailed description
FX3U-3A-ADP
Refer to the system configuration shown in the User's Manual - Hardware Edition to check the number of connectable units
and to configure the entire system. I
FX3U-4AD-PT
*1. Only 1 analog special adapter can be connected to the 14-point and 24-point type main unit.
*2. The expansion board is not required when connecting with the FX3UC (D, DSS) PLC.
For the FX3G Series PLC a connector conversion adapter is used.
-ADP
J
FX3U-4AD-PTW
-ADP
J-3
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 1 Outline
FX3U-4AD-PTW-ADP (4-channel Platinum Resistance Thermometer Data Input) 1.2 Setup Procedure Before Starting Operation
FX3U-4AD-PTW-ADP
Refer to Chapter 1.
J-4
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 1 Outline
FX3U-4AD-PTW-ADP (4-channel Platinum Resistance Thermometer Data Input) 1.3 Connectable PLC and Its Version Number
A
1.3 Connectable PLC and Its Version Number
Common Items
PTW-ADP is compatible with the following PLC.
FX3UC-4AD
FX3U-4AD
FX3UC Series PLC Ver. 1.30 or later After August 2004
FX3G Series PLC Ver. 1.00 or later After June 2008 (initial production)
1. Version check
Special data register D8001 contains information for determining the PLC version.
C
FX3U-4AD-ADP
→ For a detailed description of the version check, refer to A. Common Items Subsection 5.1.2.
FX3G-2AD-BD
1.4 Compatible Programming Tool Version Number
Use the programming tool with the following version number to create programs for PTW-ADP of the FX3U/
FX3UC/FX3G Series PLC: E
FX3U-4DA
1. GX Developer
Software Version number Remarks
GX Developer Ver. SW8 P or later
When selecting a model, select FX3U(C)*1.
• SW D5C-GPPW-J
• SW D5C-GPPW-E
(Ver. 8.13P)
F
Ver. 8.72A or later When selecting a model, select FX3G.
FX3U-4DA-ADP
If a programming tool with the wrong version number is used, programming will not be possible.
*1. For Ver. 8.13P to 8.24A of GX Developer, select FX3UC for the PLC type.
2. FX-30P G
FX3G-1DA-BD
Model name Version number Remarks
FX-30P Ver.1.00 or later
H
FX3U-3A-ADP
I
FX3U-4AD-PT
-ADP
J
FX3U-4AD-PTW
-ADP
J-5
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 2 Specifications
FX3U-4AD-PTW-ADP (4-channel Platinum Resistance Thermometer Data Input) 2.1 Generic Specifications
2. Specifications
This chapter describes the general, power supply, and performance specifications for the PTW-ADP.
Item Specifications
Ambient 0 to 55°C (32 to 131°F) when operating
temperature -25 to 75°C (-13 to 167°F) when stored
Relative
5 to 95%RH (no condensation) when operating
humidity
Frequency Acceleration Half amplitude
(Hz) (m/s2) (mm)
Tested 10 times in each
Vibration 10 - 57 - 0.035 direction (X-, Y-, and Z-
DIN Rail Mounting
resistance*1 57 - 150 4.9 - axis directions) (Total:
80 min, each)
10 to 57 − 0.075
Direct Mounting*2
57 to 150 9.8 −
Shock
147 m/s2 Acceleration, Action time: 11ms, 3 times by half-sine pulse in each direction X, Y, and Z
resistance*1
Noise Using noise simulator of:
resistance Noise voltage: 1,000Vp-p / Noise width: 1μs / Rise: 1ns / Cycle: 30 to 100Hz
Dielectric
withstand 500 V AC, for 1 min
voltage Between all terminals and ground terminal
Insulation 5MΩ or more using 500V DC
resistance insulation resistance meter
Class D grounding (grounding resistance: 100 Ω or less)
Grounding
<Common grounding with a heavy electrical system is not allowed.>*3
Working
Free from corrosive or flammable gas and excessive conductive dusts
environment
Working
altitude < 2000m*4
J-6
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 2 Specifications
FX3U-4AD-PTW-ADP (4-channel Platinum Resistance Thermometer Data Input) 2.2 Power Supply Specifications
A
2.2 Power Supply Specifications
Common Items
Items Specification
A/D conversion circuit 24V DC +20% -15%, 50mA B
driving power (It is necessary to connect a 24V DC power supply to the terminal block.)
FX3UC-4AD
FX3U-4AD
5V DC, 15mA
Interface driving power (Since the internal power is supplied from the FX Series main unit, it is not
necessary to supply the power.)
FX3U-4AD-ADP
Specifications
Items
Centigrade (°C) Fahrenheit (°F)
Input signal
3-wire platinum resistance thermometer sensor
Pt100 JIS C 1604-1997
D
FX3G-2AD-BD
Rated temperature
-100°C to +600°C -148°F to +1112°F
range
Digital output -1000 to +6000 -1480 to +11120
Resolution 0.2°C to 0.3°C 0.4°F to 0.5°F
Total accuracy
• ±0.5% for full scale (when ambient temperature is 25°C±5°C) E
• ±1.0% for full scale (when ambient temperature is in the range from 0 to 55°C)
FX3U-4DA
• FX3U/FX3UC Series PLC : 200μs (The data will be updated at every scan time.)
A/D conversion
• FX3G Series PLC : 250μs (The data will be updated at every scan time.)
time
→For a detailed description of data update, refer to Section 2.4.
+6150 +11390
F
FX3U-4DA-ADP
+6000 +11120
+1139°F
+615°C
Input
characteristics -100°C 0 -148°F 0
+600°C G
-115°C
+1112°F
-175°F
FX3G-1DA-BD
-1000 -1480
-1150 -1750
• The photocoupler is used to insulate the analog input area from the PLC.
• The DC/DC converter is used to insulate the power supply line from the analog input
Insulation method
area. H
• Channels are not insulated from each other.
FX3U-3A-ADP
I
FX3U-4AD-PT
-ADP
J
FX3U-4AD-PTW
-ADP
J-7
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 2 Specifications
FX3U-4AD-PTW-ADP (4-channel Platinum Resistance Thermometer Data Input) 2.4 A/D Conversion Time
Sequence
program
A/D conversion start
A/D command
conversion
Digital value reading
200μs/4ch
A/D conversion start END instruction
A/D command
conversion
Digital value reading
200μs/4ch
J-8
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 2 Specifications
FX3U-4AD-PTW-ADP (4-channel Platinum Resistance Thermometer Data Input) 2.5 Temperature Measurement
A
2.4.2 When connected to a FX3G PLCs
Common Items
1. A/D conversion and special data register update timing
A/D conversion is performed at every scan time of the PLC.
During execution of END instruction, the PLC performs A/D conversion, reads out the A/D converted data,
and then writes the data in the special data registers. B
FX3UC-4AD
FX3U-4AD
FX3U-4AD-PTW-ADP FX3U-4AD-PTW-ADP
2nd 1st FX3G Series PLC
Sequence
FX3U-4AD-ADP
A/D command
conversion
Digital value reading
250μs/4ch
A/D conversion start END instruction
A/D
conversion
command
D
FX3G-2AD-BD
Digital value reading
250μs/4ch
FX3U-4DA
3. If two analog special adapters are connected
During execution of the END instruction, data will be read out from all the connected adapters (in the order of
1st adapter → 2nd adapter).
FX3U-4DA-ADP
and the data read out will be written to the special data registers.
END instruction execution time will be "250μs × number of connected adapters."
FX3G-1DA-BD
H
FX3U-3A-ADP
I
FX3U-4AD-PT
-ADP
J
FX3U-4AD-PTW
-ADP
J-9
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 3 Wiring
FX3U-4AD-PTW-ADP (4-channel Platinum Resistance Thermometer Data Input)
3. Wiring
This chapter describes the PTW-ADP wiring.
Observe the following caution to wire the PTW-ADP.
WIRING PRECAUTIONS
• Make sure to cut off all phases of the power supply externally before attempting wiring work.
Failure to do so may cause electric shock or damages to the product.
WIRING PRECAUTIONS
• Connect the DC power supply wiring to the dedicated terminals described in this manual.
If an AC power supply is connected to a DC input/output terminal or DC power supply terminal, the PLC will be
burnt out.
• Do not wire vacant terminals externally.
Doing so may damage the product.
• Perform class D grounding (grounding resistance: 100Ω or less) to the grounding terminal on the main unit.
Do not use common grounding with heavy electrical systems.
• When drilling screw holes or wiring, make sure cutting or wire debris does not enter the ventilation slits.
Failure to do so may cause fire, equipment failures or malfunctions.
• Make sure to observe the following precautions in order to prevent malfunctions under the influence of noise:
- Do not bundle the power line or twisted shielded cable together with or lay it close to the main circuit, high-
voltage line, or load line.
Otherwise, noise disturbance and/or surge induction are likely to take place. As a guideline, lay the control line
at least 100mm (3.94") or more away from the main circuit, high-voltage line, or load line.
- Ground the shield of the analog input/output cable at one point on the signal receiving side.
However, do not use common grounding with heavy electrical systems.
• Make sure to properly wire to the European terminal board in accordance with the following precautions.
Failure to do so may cause electric shock, a short-circuit, wire breakage, or damage to the product.
- The disposal size of the cable end should be 9 mm (0.35").
- Tightening torque should be between 0.22 to 0.25 N•m.
- Twist the end of strand wire and make sure there are no loose wires.
- Do not solder-plate the electric wire ends.
- Do not connect more than the specified number of wires or electric wires of unspecified size.
- Affix the electric wires so that neither the terminal block nor the connected parts are directly stressed.
J-10
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 3 Wiring
FX3U-4AD-PTW-ADP (4-channel Platinum Resistance Thermometer Data Input) 3.1 Terminal Layout
A
3.1 Terminal Layout
Common Items
The terminals of the PTW-ADP are arranged as follows:
FX3UC-4AD
FX3U-4AD
FX3U-4AD-PTW
-ADP
POWER
Signal Application C
24+
24+
FX3U-4AD-ADP
External power
24-
24-
Ground terminal
L1+
L1+
Channel-1 platinum
resistance thermometer
L1-
L1-
sensor input
I1-
I1-
D
L2+
resistance thermometer
FX3G-2AD-BD
L2-
sensor input
I2-
I2-
L3+
FX3U-4DA
sensor input
I4-
I4-
FX3U-4DA-ADP
G
FX3G-1DA-BD
H
FX3U-3A-ADP
I
FX3U-4AD-PT
-ADP
J
FX3U-4AD-PTW
-ADP
J-11
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 3 Wiring
FX3U-4AD-PTW-ADP (4-channel Platinum Resistance Thermometer Data Input) 3.2 Applicable Cable and Terminal Tightening Torque
1. Cables
Applicable cable and tightening torque
Wire size Tightening
Termination
(stranded/single-wire) torque
2 2 • To connect a stranded cable, peel the cover off the cable
Single-wire 0.3mm to 0.5mm and then twist the core before connection.
(AWG22 to 20)
• To connect a single-wire cable, just strip the cover off the
2-wire 0.3mm2 (AWG22) cable before connection.
0.22 N•m to • Rod terminal with insulation sleeve
Rod 0.3mm2 to 0.5mm2 0.25 N•m (recommended terminal)
terminal (AWG22 to 20) AI 0.5-8WH : Manufactured by Phoenix Contact
with (Refer to the rod terminal
• Caulking tool
insulation external view shown in
CRIMPFOX ZA 3 : Manufactured by Phoenix Contact
sleeve the following figure.)
(or CRIMPFOX UD 6 : Manufactured by Phoenix Contact)
3. Tool
• To tighten terminals, use a small-sized screwdriver whose head is straight and is not widened as shown in
the figure to the right.
Note:
If the diameter of screwdriver grip is too small, tightening torque will not
The head
be able to be achieved. Use the following recommended screwdriver or should be
an appropriate replacement (grip diameter: approximately 25mm). straight.
Manufacturer Type
Phoenix Contact SZS 0.4 × 2.5 0.4mm 2.5mm
(0.01") (0.09")
J-12
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 3 Wiring
FX3U-4AD-PTW-ADP (4-channel Platinum Resistance Thermometer Data Input) 3.3 Power Supply Line
A
3.3 Power Supply Line
Common Items
Connect the 24V DC power supply line of the PTW-ADP to the 24+ and 24- terminals of the terminal block.
FX3UC-4AD
FX3U-4AD
1. To use an external power 2. To use the 24V DC power of the PLC
FX3U-4AD-ADP
24- 24+ 24- 24+ 0V 24V D
FX3G-2AD-BD
Terminal Terminal
block block
Class-D Class-D
grounding
24V DC grounding
E
Caution regarding connection of the power supply line:
FX3U-4DA
• Ground the " " terminal to a class-D grounding power supply line (100Ω or less) together with the
ground terminal of the PLC main unit.
• For the timing of power-on/off when using an external power supply, see the following manual of the PLC
to be connected.
→ Refer to the FX3G Series User's Manual - Hardware Edition. F
→ Refer to the FX3U Series User's Manual - Hardware Edition.
FX3U-4DA-ADP
3.3.2 To Connect To The FX3UC Series PLC
FX3G-1DA-BD
+5V (Input extension
block)
Power
H
Power crossover
FX3U-3A-ADP
Power
connector connector connector
Class-D
24V DC grounding
-ADP
• Ground the " " terminal to a class-D grounding power supply line (100Ω or less) together with the
grounding terminal of the PLC main unit.
-ADP
J-13
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 3 Wiring
FX3U-4AD-PTW-ADP (4-channel Platinum Resistance Thermometer Data Input)
3.4 Selection of the Platinum Resistance Thermometer Sensor
PTW-ADP
+5V
Shield +5V
+5V
24+
24V DC
24-
Class-D grounding
L +, L -, I -, ch : represents the channel number.
*1. Separate the cable of the platinum resistance thermometer sensor from the other power cables or
areas easily affected by inductive noise (of the commercial power, etc.).
3.6 Grounding
Grounding should be performed as stated below.
• The grounding resistance should be 100Ω or less.
• Independent grounding should be performed for best results.
When independent grounding is not performed, perform "shared grounding" as shown in the following
figure.
→ For details, refer to the User’s Manual - Hardware Edition of the PLC Series.
J-14
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 4 Programming
FX3U-4AD-PTW-ADP (4-channel Platinum Resistance Thermometer Data Input) 4.1 Loading of A/D Conversion Data
Common Items
4. Programming
This chapter describes how to create programs that can read analog data using the PTW-ADP. B
FX3UC-4AD
FX3U-4AD
4.1 Loading of A/D Conversion Data
1) The input analog data will be converted into digital data and then stored in the special devices of the
FX3U/FX3UC/FX3G Series PLC.
C
2) If data is stored in the special devices, the averaging time can be set, and the input mode can be
FX3U-4AD-ADP
specified.
3) Special auxiliary relays (10 points) and special data registers (10 points) are assigned automatically
starting from the adapter nearest to the main unit.
→ For a detailed description of special device assignment, refer to Section 4.2.
• FX3U, FX3UC Series PLC D
FX3G-2AD-BD
Communi High-speed
-cation input/output
FX3U-4AD FX3U-4AD FX3U-4AD special FX3U-4AD special
-PTW-ADP -PTW-ADP -PTW-ADP adapter -PTW-ADP adapter FX3U/FX3UC Series PLC
FX3U-4DA
A/D M8260 to M8269
Special data registers:
D8260 to D8269
FX3U-4DA-ADP
Special auxiliary relays:
A/D M8280 to M8289
Special data registers:
D8280 to D8289
A/D
Special auxiliary relays:
M8290 to M8299 G
Special data registers:
FX3G-1DA-BD
D8290 to D8299
The analog special adapter nearest to the main unit is counted as the 1st analog special adapter, and the
next adapter as the 2nd analog special adapter, and so on. However, in this case, do not include the high-
speed input/output special adapter, communication special adapter, and the CF card special adapter. H
FX3U-3A-ADP
I
FX3U-4AD-PT
-ADP
J
FX3U-4AD-PTW
-ADP
J-15
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 4 Programming
FX3U-4AD-PTW-ADP (4-channel Platinum Resistance Thermometer Data Input) 4.1 Loading of A/D Conversion Data
2nd*1 1st
Special devices
Special auxiliary relays:
M8280 to M8289
A/D Special data registers:
D8280 to D8289 Sequence
Program
Special auxiliary relays:
M8290 to M8299
A/D Special data registers:
D8290 to D8299
The analog special adapter nearest to the main unit is counted as the 1st analog special adapter, and the
next adapter as the 2nd analog special adapter. However, in this case, do not include the connector
conversion adapter and the communication special adapter.
*1. The second special adapter is not available in the FX3G Series PLC(14-point and 24-point type).
J-16
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 4 Programming
FX3U-4AD-PTW-ADP (4-channel Platinum Resistance Thermometer Data Input) 4.2 List of Special Devices
A
4.2 List of Special Devices
Common Items
If the PTW-ADP is connected, special devices will be assigned automatically as shown in the following table:
• FX3U, FX3UC Series PLC
R: Read / W: Write
Special Device number
B
Description Attribute Reference
FX3UC-4AD
FX3U-4AD
device 1st 2nd 3rd 4th
Section
Special M8260 M8270 M8280 M8290 Selects the temperature unit. R/W
4.3
auxiliary
relay M8261 to M8271 to M8281 to M8291 to
Unused (Do not use.) - -
M8269 M8279 M8289 M8299
C
Channel-1 temperature
FX3U-4AD-ADP
D8260 D8270 D8280 D8290 R
measurement data
Channel-2 temperature
D8261 D8271 D8281 D8291 R
measurement data Section
Channel-3 temperature 4.4
D8262 D8272 D8282 D8292 R
measurement data
D
Channel-4 temperature
D8263 D8273 D8283 D8293 R
FX3G-2AD-BD
measurement data
Averaging time for channel 1
Special D8264 D8274 D8284 D8294 R/W
(Setting range: 1 to 4095)
data
register Averaging time for channel 2
D8265 D8275 D8285 D8295 R/W
(Setting range: 1 to 4095) Section
4.5
E
Averaging time for channel 3
D8266 D8276 D8286 D8296 R/W
FX3U-4DA
(Setting range: 1 to 4095)
Averaging time for channel 4
D8267 D8277 D8287 D8297 R/W
(Setting range: 1 to 4095)
Section
D8268 D8278 D8288 D8298 Error status R/W
4.6
Section
F
D8269 D8279 D8289 D8299 Model code = 21 R
FX3U-4DA-ADP
4.7
FX3G-1DA-BD
H
FX3U-3A-ADP
I
FX3U-4AD-PT
-ADP
J
FX3U-4AD-PTW
-ADP
J-17
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 4 Programming
FX3U-4AD-PTW-ADP (4-channel Platinum Resistance Thermometer Data Input) 4.3 Selection of Temperature Unit
J-18
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 4 Programming
FX3U-4AD-PTW-ADP (4-channel Platinum Resistance Thermometer Data Input) 4.4 Temperature Measurement
A
4.4 Temperature Measurement
Common Items
The temperature data input in the PTW-ADP will be stored in the special data registers.
The special data registers that store the temperature data are shown in the following table:
• FX3U, FX3UC Series PLC
B
Special data register
FX3UC-4AD
FX3U-4AD
Description
1st 2nd 3rd 4th
D8260 D8270 D8280 D8290 Stores the channel-1 temperature measurement data.
D8261 D8271 D8281 D8291 Stores the channel-2 temperature measurement data.
D8262 D8272 D8282 D8292 Stores the channel-3 temperature measurement data. C
D8263 D8273 D8283 D8293 Stores the channel-4 temperature measurement data.
FX3U-4AD-ADP
• FX3G Series PLC
FX3G-2AD-BD
D8281 D8291 Stores the channel-2 temperature measurement data.
D8282 D8292 Stores the channel-3 temperature measurement data.
D8283 D8293 Stores the channel-4 temperature measurement data.
The immediate data or the average data (data averaged in accordance with the specified averaging time) will
E
FX3U-4DA
be stored in the above data registers as the temperature measurement data.
→ For a detailed description of the averaging time, refer to Section 4.6.
FX3U-4DA-ADP
2. Program Example (For FX3U, FX3UC Series PLC)
M8000
FNC 12 D8260 D100 Stores the channel-1 temperature measurement
MOV data of the 1st analog special adapter in D100.
Normally
ON
G
FX3G-1DA-BD
FNC 12 D8261 D101 Stores the channel-2 temperature measurement
MOV data of the 1st analog special adapter in D101.
Even if the temperature measurement data is not stored in the D100 or the D101, the D8260 or the D8261
can be directly used in the arithmetic operation instruction or a PID instruction.
H
FX3U-3A-ADP
I
FX3U-4AD-PT
-ADP
J
FX3U-4AD-PTW
-ADP
J-19
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 4 Programming
FX3U-4AD-PTW-ADP (4-channel Platinum Resistance Thermometer Data Input) 4.5 Averaging Time
J-20
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 4 Programming
FX3U-4AD-PTW-ADP (4-channel Platinum Resistance Thermometer Data Input) 4.6 Error Status
A
4.6 Error Status
Common Items
If an error is detected in the PTW-ADP, the error status data will be stored in the corresponding special data
register.
The following table shows the special data registers that store the error status data:
• FX3U, FX3UC Series PLC B
FX3UC-4AD
FX3U-4AD
Special data register
Description
1st 2nd 3rd 4th
D8268 D8278 D8288 D8298 Stores the error status data.
FX3U-4AD-ADP
Special data register
Description
1st 2nd
D8288 D8298 Stores the error status data.
Check the ON/OFF status of each bit of the error status data register to determine the error. Errors are
D
FX3G-2AD-BD
assigned to the bits as shown in the following table. Create a program to detect errors.
FX3U-4DA
The temperature measurement data
b1 of channel 2 is outside the specified b6 PTW-ADP hardware error
range, or disconnection is detected.
The temperature measurement data
b2 of channel 3 is outside the specified b7 PTW-ADP communication data error
range, or disconnection is detected. F
The temperature measurement data
FX3U-4DA-ADP
b3 of channel 4 is outside the specified b8 to b15 Unused
range, or disconnection is detected.
b4 EEPROM error - -
FX3G-1DA-BD
clear the error status with a program at the next power-on of the PLC.
For this reason, be sure to create the following program:
• For FX3G, FX3U, FX3UC Series PLC
M8000
MOV D8288 K4M0 H
FX3U-3A-ADP
Normally
ON
M8002
RST M6 Error status of 3rd*1 analog special adapter
b6 = OFF (hardware error)
Initial pulse
J
*1. "1st " for the FX3G PLC.
FX3U-4AD-PTW
-ADP
J-21
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 4 Programming
FX3U-4AD-PTW-ADP (4-channel Platinum Resistance Thermometer Data Input) 4.6 Error Status
M8002
RST D8268.6 Error status of 1st analog special adapter
b6 = OFF (hardware error)
Initial pulse
M8000
MOV D8288 K4M0
M0
Y000 The temperature measurement data
of channel 1 is outside the specified
range, or disconnection is detected.
M1
Y001 The temperature measurement data
of channel 2 is outside the specified
range, or disconnection is detected.
M2
Y002 The temperature measurement data
of channel 3 is outside the specified
range, or disconnection is detected.
M3
Y003 The temperature measurement data
of channel 4 is outside the specified
range, or disconnection is detected.
M4
Y004 EEPROM error in 3rd*1 adapter
M5
Y005 Averaging time setting error in 3rd*1
adapter
M6
Y006 PTW-ADP hardware error in 3rd*1
adapter
M7
Y007 PTW-ADP communication data error
in 3rd*1 adapter
J-22
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 4 Programming
FX3U-4AD-PTW-ADP (4-channel Platinum Resistance Thermometer Data Input) 4.6 Error Status
A
3. Program Example 2 (For FX3U, FX3UC Series PLC)
Common Items
D8268.0
Y000 The temperature measurement data
of channel 1 is outside the specified
D8268.1
range, or disconnection is detected. B
FX3UC-4AD
FX3U-4AD
Y001 The temperature measurement data
of channel 2 is outside the specified
range, or disconnection is detected.
D8268.2
Y002 The temperature measurement data
of channel 3 is outside the specified
D8268.3
range, or disconnection is detected. C
Y003 The temperature measurement data
FX3U-4AD-ADP
of channel 4 is outside the specified
range, or disconnection is detected.
D8268.4
Y004 EEPROM error in 1st adapter
D
D8268.5
FX3G-2AD-BD
Y005 Averaging time setting error in 1st
adapter
D8268.6
Y006 PTW-ADP hardware error in 1st
adapter
D8268.7
E
FX3U-4DA
Y007 PTW-ADP communication data error
in 1st adapter
FX3U-4DA-ADP
G
FX3G-1DA-BD
H
FX3U-3A-ADP
I
FX3U-4AD-PT
-ADP
J
FX3U-4AD-PTW
-ADP
J-23
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 4 Programming
FX3U-4AD-PTW-ADP (4-channel Platinum Resistance Thermometer Data Input) 4.7 Model Code
Use the special data registers above to check whether PTW-ADP is connected or not.
FNC224 D8269 K21 Y010 Checks the model code of the 1st
LD = analog special adapter.
J-24
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 4 Programming
FX3U-4AD-PTW-ADP (4-channel Platinum Resistance Thermometer Data Input) 4.8 Basic Program Example
A
4.8 Basic Program Example
Common Items
Create the following basic program example to read out the temperature measurement data.
• For FX3G, FX3U, FX3UC Series PLC
The following program will store the temperature measurement data (°C) from channels 1 and 2 of the 3rd*1
adapter to D100 and D101, respectively. The averaging time is set to "1" (immediate data) for channel 1, and
B
FX3UC-4AD
FX3U-4AD
"5" for channel 2.
M8000
MOV D8288 K4M0
Normally
ON
M8002 Error status of 3rd*1 analog special
C
FX3U-4AD-ADP
RST M6 adapter
Initial b6 = OFF (hardware error)
pulse Error status of 3rd*1 analog special
RST M7 adapter
b7 = OFF (communication data error)
FX3G-2AD-BD
M8001
Sets the temperature unit to centigrade
M8280 (°C).
M8002
FNC 12 Sets the averaging time to "1" for
K1 D8284 channel-1 data.
MOV
FX3U-4DA
MOV
M8000
FNC 12 D8280 D100 Stores the current value of the channel-1
MOV temperature measurement data in the D100.
FX3U-4DA-ADP
Even if the temperature measurement data is not stored in D100 or D101, data register D8280 or D8281 can
be directly used in the arithmetic operation instruction or a PID instruction.
*1. "1st " for the FX3G PLC.
• For FX3U, FX3UC Series PLC
The following program will store the temperature measurement data (°C) from channels 1 and 2 of the 1st
adapter to D100 and D101, respectively. The averaging time is set to "1" (immediate data) for channel 1, and
G
FX3G-1DA-BD
"5" for channel 2.
M8002 Error status of 1st analog special
RST D8268.6 adapter
b6 = OFF (hardware error)
M8001
Sets the temperature unit to centigrade
M8260 (°C).
M8002
FNC 12 Sets the averaging time to "1" for
K1 D8264 channel-1 data.
MOV
MOV
M8000
FNC 12 D8260 D100 Stores the current value of the channel-1
MOV temperature measurement data in the D100.
-ADP
Even if the temperature measurement data is not stored in D100 or D101, data register D8260 or D8261 can
be directly used in the arithmetic operation instruction or a PID instruction.
-ADP
J-25
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 5 Troubleshooting
FX3U-4AD-PTW-ADP (4-channel Platinum Resistance Thermometer Data Input) 5.1 PLC Version Number Check
5. Troubleshooting
This chapter describes the troubleshooting methods and error status.
If the temperature measurement data is not input, or if the proper digital value is not input, check the following
items:
• Version number of the PLC
• Wiring
• Special devices
• Programs
• Error status
1. Power
The PTW-ADP needs driving power. Verify that the power supply line is properly connected. Also check that
the POWER indicator lamp of the PTW-ADP is on.
1. Temperature measurement
Verify that the special device for the selected channel is correctly selected. This special device should be
selected depending on the connecting position and the channel.
2. Averaging time
Check that the set averaging time is within the specified range. The averaging time should be set in the range
from 1 to 4095. If the set averaging time is outside the specified range, an error occurs.
3. Error status
Check that no error is detected in the PTW-ADP.
If an error is detected, check the details of the error, and then check the wiring and programs.
→ For a detailed description of special devices, refer to Chapter 4.
J-26
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 5 Troubleshooting
FX3U-4AD-PTW-ADP (4-channel Platinum Resistance Thermometer Data Input) 5.4 Program Check
A
5.4 Program Check
Common Items
Check the following items for the program:
FX3UC-4AD
FX3U-4AD
2. Check of storage devices
Verify that different values are not being stored in the same device by the other parts of the programs.
FX3U-4AD-ADP
If an error occurs in the PTW-ADP, the corresponding bit will turn on.
FX3G-2AD-BD
The temperature measurement data of
b1 channel 2 is outside the specified b6 PTW-ADP hardware error
range, or disconnection is detected.
The temperature measurement data of
b2 channel 3 is outside the specified
range, or disconnection is detected.
b7 PTW-ADP communication data error
E
FX3U-4DA
The temperature measurement data of
b3 channel 4 is outside the specified b8 to 15 Unused
range, or disconnection is detected.
b4 EEPROM error - -
To solve a problem, refer to the troubleshooting method described below: F
FX3U-4DA-ADP
1. Temperature measurement out of specified range or disconnection of line (b0 to b3)
1) Description of error
The input temperature measurement value is outside the specified range.
The temperature measurement value is not in the range between -115°C to 615°C.
Or the line between PTW-ADP and the platinum resistance thermometer sensor is disconnected. G
2) Remedy
FX3G-1DA-BD
Check that the input temperature measurement value is within the specified range. Also check the wiring
condition.
is destroyed.
2) Remedy
Please contact the nearest Mitsubishi Electric distributor office.
The averaging time set for one of the channels (channels 1 to 4) is outside the specified
range: 1 to 4095.
2) Remedy
-ADP
Check that the averaging time is correctly set for each channel.
J
FX3U-4AD-PTW
-ADP
J-27
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 5 Troubleshooting
FX3U-4AD-PTW-ADP (4-channel Platinum Resistance Thermometer Data Input) 5.5 Error Status Check
J-28
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition
FX3U-4AD-PNK-ADP (4-channel Resistance Thermometer Data Input)
FX3U-4AD-PNK
-ADP
L
FX3U-4AD-TC
FX3G/FX3U/FX3UC Series Programmable
-ADP
Controllers M
PID Instruction
User's Manual [Analog Control Edition]
(FNC 88)
FX3U-4AD-PNK-ADP (4-channel Resistance
Thermometer Data Input)
Foreword
This manual describes the specifications, wiring, and operation methods for the FX3U-4AD-PNK-ADP special
adapter (4-channel resistance thermometer data input) and should be read and understood before attempting
to install or use the unit.
Store this manual in a safe place so that you can take it out and read it whenever necessary. Always forward
it to the end user.
This manual confers no industrial property rights or any rights of any other kind, nor does it confer any patent
licenses. Mitsubishi Electric Corporation cannot be held responsible for any problems involving industrial property
rights which may occur as a result of using the contents noted in this manual.
K-1
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition
FX3U-4AD-TC-ADP (4-channel Resistance Thermocouple Data Input)
K-2
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 1 Outline
FX3U-4AD-PNK-ADP (4-channel Resistance Thermometer Data Input) 1.1 Outline of Functions
FX3U-4AD-PNK
1. Outline
-ADP
This chapter describes the outline of FX3U-4AD-PNK-ADP (referred to as PNK-ADP). L
FX3U-4AD-TC
1.1 Outline of Functions
-ADP
The FX3U-4AD-PNK-ADP is an analog special adapter. Connect the FX3U-4AD-PNK-ADP to the FX3G/FX3U/
FX3UC Series PLC to read the data from the 4-channel resistance thermometer.
M
1) Up to 4 PNK-ADP units can be connected to the FX3U/FX3UC Series PLC.
PID Instruction
Up to 2*1 PNK-ADP units can be connected to the FX3G Series PLC.
(Including other analog special adapters)
(FNC 88)
2) Thermometer types Pt1000 and Ni1000 can be connected. (However, it's impossible to use both types
Pt1000 and Ni1000 with 1 adapter.)
3) The temperature data will be automatically written to the special data register of the FX3G/FX3U/FX3UC
Series PLC.
+ + to Section 1.3.
Expansion
4th 3rd 2nd 1st
adapter adapter adapter adapter board*2
For a detailed
…… description of wiring,
Analog data refer to Chapter 3.
Refer to the system configuration shown in the User's Manual - Hardware Edition to check the number of connectable units
and to configure the entire system.
*1. Only 1 analog special adapter can be connected to the 14-point and 24-point type main unit.
*2. The expansion board is not required when connecting with the FX3UC (D, DSS) PLC.
For the FX3G Series PLC a connector conversion adapter is used.
K-3
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 1 Outline
FX3U-4AD-PNK-ADP (4-channel Resistance Thermometer Data Input) 1.2 Setup Procedure Before Starting Operation
FX3U-4AD-PNK-ADP
Refer to Chapter 1.
Wiring Wiring:
•Selection of sensor cable
•Power supply line
Refer to Chapter 4. •Analog input line
Programming Programming:
•Details of special devices
•Examples of basic programs
K-4
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 1 Outline
FX3U-4AD-PNK-ADP (4-channel Resistance Thermometer Data Input) 1.3 Connectable PLC and Its Version Number
K
1.3 Connectable PLC and Its Version Number
FX3U-4AD-PNK
PNK-ADP is compatible with the following PLC.
-ADP
Compatible PLC Version number Date of production
FX3U Series PLC Ver. 2.20 or later After May 2005 (initial production) L
FX3U-4AD-TC
FX3UC Series PLC Ver. 1.30 or later After August 2004
FX3G Series PLC Ver. 1.00 or later After June 2008 (initial production)
-ADP
1. Version check
Special data register D8001 contains information for determining the PLC version number.
M
PID Instruction
→ For a detailed description of the version check, refer to A. Common Items Subsection 5.1.2.
(FNC 88)
2. How to look at the manufacturer's serial number
The year and month of production of the product can be checked on the nameplate, and on the front of the
product.
→ For a detailed description of the How to look at the manufacturer's serial number,
refer to A. Common Items Subsection 5.1.1.
1. GX Developer
If a programming tool with the wrong version number is used, programming will not be possible.
*1. For Ver. 8.13P to 8.24A of GX Developer, select FX3UC for the PLC type.
2. FX-30P
K-5
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 2 Specifications
FX3U-4AD-PNK-ADP (4-channel Resistance Thermometer Data Input) 2.1 Generic Specifications
2. Specifications
This chapter describes the general, power supply, and performance specifications for the PNK-ADP.
Item Specifications
0 to 55°C (32 to 131°F) when operating
Ambient temperature
-25 to 75°C (-13 to 167°F) when stored
Relative humidity 5 to 95%RH (no condensation) when operating
Frequency Acceleration Half amplitude
(Hz) (m/s2) (mm)
Tested 10 times in
Vibration 10 - 57 - 0.035 each direction (X-, Y-,
DIN Rail Mounting
resistance*1 57 - 150 4.9 - and Z-axis directions)
(Total: 80 min, each)
10 to 57 − 0.075
Direct Mounting*2
57 to 150 9.8 −
147 m/s2 Acceleration, Action time: 11ms, 3 times by half-sine pulse in each direction X, Y,
Shock resistance*1
and Z
Using noise simulator of:
Noise resistance
Noise voltage: 1,000Vp-p / Noise width: 1μs / Rise: 1ns / Cycle: 30 to 100Hz
Dielectric withstand
500 V AC, for 1 min
voltage
Between batch of all terminals and ground terminal
5MΩ or more using 500V DC
Insulation resistance
insulation resistance meter
Class D grounding (grounding resistance: 100 Ω or less)
Grounding
<Common grounding with a heavy electrical system is not allowed.>*3
Working
Free from corrosive or flammable gas and excessive conductive dusts
environment
Working altitude < 2000m*4
Item Specifications
A/D conversion circuit 24V DC +20% -15%, 45mA
driving power (It is necessary to connect a 24V DC power supply to the terminal block.)
5V DC, 15mA
Interface driving power (Since the internal power is supplied from the FX Series main unit, it is not
necessary to supply the power.)
K-6
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 2 Specifications
FX3U-4AD-PNK-ADP (4-channel Resistance Thermometer Data Input) 2.3 Performance Specifications
K
2.3 Performance Specifications
FX3U-4AD-PNK
-ADP
Specifications
Item
Centigrade (°C) Fahrenheit (°F) L
FX3U-4AD-TC
Platinum resistance thermometer sensor (2-wire or 3-wire) Pt1000
JIS C 1604-1997
Input signal
Nickel resistance thermometer sensor (2-wire or 3-wire) Ni1000
-ADP
DIN 43760-1987
PID Instruction
Pt1000 -500 to +2500 Pt1000 -580 to +4820
Digital output
(FNC 88)
Ni1000 -400 to +1100 Ni1000 -400 to +2300
Pt1000 Pt1000
Resolution 0.1°C 0.2°F
Ni1000 Ni1000
±0.5% for full scale (when ambient temperature is 25°C±5°C)
Total accuracy
±1.0% for full scale (when ambient temperature is in the range of 0 to 55°C)
• FX3U/FX3UC Series PLC : 200μs (The data will be updated at every scan time.)
A/D conversion
• FX3G PLC : 250μs (The data will be updated at every scan time.)
time
→For a detailed description of data update, refer to Section2.4.
-Pt1000 -Pt1000
+2560 +4920
+2500 +4820
+492.8°F
Approx.
+256°C
Approx.
-50°C 0 -58°F 0
Approx.
Approx.
+250°C +482 °F
-55°C
-67°F
-500 -580
Input -550 -670
characteristics
-Ni1000 -Ni1000
+1150 +2390
+1100 +2300
Approx.
Approx.
+115°C
+239°F
-40°C 0 -40°F 0
Approx.
Approx.
+110°C +230°F
-45°C
-49°F
-400 -400
-450 -490
• The photocoupler is used to insulate the analog input area from the PLC.
Insulation method • The DC/DC converter is used to insulate the power supply line from the analog input area.
• Channels are not insulated from each other.
Number of I/O 0 points
points occupied (This number is not related to the maximum number of input/output points of the PLC.)
K-7
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 2 Specifications
FX3U-4AD-PNK-ADP (4-channel Resistance Thermometer Data Input) 2.4 A/D Conversion Time
FX3U-4AD-PNK-ADP FX3U-4AD-PNK-ADP
n'th 1st FX3U/FX3UC Series PLC
Sequence
program
A/D conversion start
A/D command
conversion
Digital value reading
200 μs/4ch
A/D conversion start END instruction
A/D command
conversion
Digital value reading
200 μs/4ch
K-8
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 2 Specifications
FX3U-4AD-PNK-ADP (4-channel Resistance Thermometer Data Input) 2.5 Temperature Measurement
K
2.4.2 When connected to a FX3G PLC
FX3U-4AD-PNK
1. A/D conversion and special data register update timing
-ADP
A/D conversion is performed at every scan time of the PLC.
During execution of END instruction, the PLC performs A/D conversion, reads out the A/D converted data,
and then writes the data in the special data registers. L
FX3U-4AD-TC
FX3U-4AD-PNK-ADP FX3U-4AD-PNK-ADP
2nd 1st FX3G Series PLC
-ADP
Sequence
program
M
PID Instruction
A/D conversion start
A/D command
(FNC 88)
conversion
Digital value reading
250 μs/4ch
A/D conversion start END instruction
A/D command
conversion
Digital value reading
250 μs/4ch
K-9
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 3 Wiring
FX3U-4AD-PNK-ADP (4-channel Thermometer Data Input)
3. Wiring
This chapter describes the PNK-ADP wiring.
Observe the following caution to wire the PNK-ADP.
WIRING PRECAUTIONS
• Make sure to cut off all phases of the power supply externally before attempting wiring work.
Failure to do so may cause electric shock or damages to the product.
WIRING PRECAUTIONS
• Connect the DC power supply wiring to the dedicated terminals described in this manual.
If an AC power supply is connected to a DC input/output terminal or DC power supply terminal, the PLC will be
burnt out.
• Do not wire vacant terminals externally.
Doing so may damage the product.
• Perform class D grounding (grounding resistance: 100Ω or less) to the grounding terminal on the main unit.
Do not use common grounding with heavy electrical systems.
• When drilling screw holes or wiring, make sure cutting or wire debris does not enter the ventilation slits.
Failure to do so may cause fire, equipment failures or malfunctions.
• Make sure to observe the following precautions in order to prevent malfunctions under the influence of noise:
- Do not bundle the power line or twisted shielded cable together with or lay it close to the main circuit, high-
voltage line, or load line.
Otherwise, noise disturbance and/or surge induction are likely to take place. As a guideline, lay the control line
at least 100mm (3.94") or more away from the main circuit, high-voltage line, or load line.
- Ground the shield of the analog input/output cable at one point on the signal receiving side.
However, do not use common grounding with heavy electrical systems.
• Make sure to properly wire to the European terminal board in accordance with the following precautions.
Failure to do so may cause electric shock, a short-circuit, wire breakage, or damage to the product.
- The disposal size of the cable end should be 9 mm (0.35").
- Tightening torque should be between 0.22 to 0.25 N•m.
- Twist the end of strand wire and make sure there are no loose wires.
- Do not solder-plate the electric wire ends.
- Do not connect more than the specified number of wires or electric wires of unspecified size.
- Affix the electric wires so that neither the terminal block nor the connected parts are directly stressed.
K-10
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 3 Wiring
FX3U-4AD-PNK-ADP (4-channel Resistance Thermometer Data Input) 3.1 Terminal Layout
K
3.1 Terminal Layout
FX3U-4AD-PNK
The terminals of the PNK-ADP are arranged as follows:
-ADP
L
FX3U-4AD-TC
FX3U-4AD-PNK
-ADP
-ADP
POWER
Signal Application M
PID Instruction
24+
24+
External power
24-
24-
(FNC 88)
Ground terminal
L1+
L1+
Channel-1 Pt1000/Ni1000
L1-
L1-
sensor input
l1-
I1-
L2+
L2+
Channel-2 Pt1000/Ni1000
L2-
l2-
L3+
L3+
Channel-3 Pt1000/Ni1000
L3-
L3-
sensor input
l3-
I3-
L4+
L4+
Channel-4 Pt1000/Ni1000
L4-
L4-
sensor input
l4-
I4-
K-11
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 3 Wiring
FX3U-4AD-PNK-ADP (4-channel Resistance Thermometer Data Input) 3.2 Applicable Cables and Terminal Tightening Torque
1. Cables
Applicable cable and tightening torque
Wire size Tightening
Termination
(stranded/single-wire) torque
0.3 mm2 to 0.5 mm2 • To connect a stranded cable, peel the cover off the cable
Single-wire and then twist the core before connection.
(AWG22 to 20)
• To connect a single-wire cable, just strip the cover off the
2-wire 0.3mm2(AWG22) cable before connection.
0.22 N•m to • Rod terminal with insulation sleeve
Rod terminal 0.3 mm2 to 0.5 mm2 0.25 N•m (recommended terminal)
with (AWG22-20) AI 0.5-8WH : Manufactured by Phoenix Contact
insulation (Refer to the rod terminal
• Caulking tool
sleeve external view shown in the
CRIMPFOX ZA 3 : Manufactured by Phoenix Contact
following figure.)
(or CRIMPFOX UD 6 : Manufactured by Phoenix Contact)
3. Tool
• To tighten terminals, use a small-sized screwdriver whose head is straight and is not widened as shown in
the figure to the right.
Note:
If the diameter of screwdriver grip is too small, tightening torque will not
The head
be able to be achieved. Use the following recommended screwdriver or should be
an appropriate replacement (grip diameter: approximately 25mm). straight.
Manufacturer Model
Phoenix Contact SZS 0.4×2.5 0.4mm 2.5mm
(0.01") (0.09")
K-12
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 3 Wiring
FX3U-4AD-PNK-ADP (4-channel Resistance Thermometer Data Input) 3.3 Power Supply Line
K
3.3 Power Supply Line
FX3U-4AD-PNK
Connect the 24V DC power supply line of the PNK-ADP to the 24+ and 24- terminals of the terminal block.
-ADP
3.3.1 To connect to FX3G, FX3U Series PLC
L
FX3U-4AD-TC
1. To use an external power 2. To use the 24V DC power of the PLC
PNK-ADP PNK-ADP
FX3G/FX3U FX3G/FX3U
-ADP
+5V Series PLC +5V Series PLC
(Main unit) (Main unit)
M
PID Instruction
(FNC 88)
24- 24+ 24- 24+ 0V 24V
Terminal Terminal
block block
Class-D Class-D
grounding grounding
24V DC
PNK-ADP FX2NC
FX3UC Series PLC Series PLC
+5V (Main unit) (Input extension
block)
Power
Power Power crossover
connector connector connector
Class-D
24V DC grounding
K-13
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 3 Wiring
FX3U-4AD-PNK-ADP (4-channel Resistance Thermometer Data Input) 3.4 Selection of the Resistance Thermometer Sensor
+5V
2-wire
sensors 47kΩ 47kΩ
type
1MΩ ch
L+
L-
*2 1MΩ
I-
24+
24V DC*1
24-
Class-D grounding
L+, L-, I-, ch: represents the channel number.
*1. 24V DC service power supply of the FX3G/FX3U Series PLC can also be used.
*2. When using a 2-wire temperature sensor type, short-circuit the [L -] terminal and the [I -] terminal.
For the lead wire use a 10Ω resistance or less per line.
*3. Separate the cable of the platinum resistance themometer sensor from the other power cables or
areas easily affected by inductive noise (of the commercial power, etc.).
K-14
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 3 Wiring
FX3U-4AD-PNK-ADP (4-channel Resistance Thermometer Data Input) 3.6 Caution Regarding Wiring
K
3.6 Caution Regarding Wiring
FX3U-4AD-PNK
• It is not possible to connect different types of resistance thermometer to 4 channels of PNK-ADP. Be sure
-ADP
to use the same type of resistance thermometer for all the channels.
3.7 Grounding
L
FX3U-4AD-TC
Grounding should be performed as stated below.
-ADP
• The grounding resistance should be 100Ω or less.
• Independent grounding should be performed for best results.
When independent grounding is not performed, perform "shared grounding" as shown in the following M
figure.
PID Instruction
→ For details, refer to the User’s Manual - Hardware Edition of the PLC Series.
(FNC 88)
PLC Other PLC Other PLC Other
equipment equipment equipment
K-15
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 4 Programming
FX3U-4AD-PNK-ADP (4-channel Resistance Thermometer Data Input) 4.1 Loading of A/D Conversion Data
4. Programming
This chapter describes how to create programs that can read out the analog data using the PNK-ADP.
The analog special adapter nearest to the main unit is counted as the 1st analog special adapter, and the
next adapter as the 2nd analog special adapter, and so on. However, in this case, do not include the high-
speed input/output special adapter, communication special adapter, and the CF card special adapter.
K-16
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 4 Programming
FX3U-4AD-PNK-ADP (4-channel Resistance Thermometer Data Input) 4.1 Loading of A/D Conversion Data
K
• FX3G Series PLC
FX3U-4AD-PNK
Communi-
cation Connector
FX3U-4AD FX3U-4AD
-ADP
special conversion
-PNK-ADP -PNK-ADP
adapter adapter FX3G Series PLC
2nd*1 1st
Special devices L
FX3U-4AD-TC
Special auxiliary relays:
M8280 to M8289
A/D Special data registers:
D8280 to D8289
-ADP
Sequence
Program
Special auxiliary relays:
A/D
M8290 to M8299
Special data registers:
M
PID Instruction
D8290 to D8299
(FNC 88)
The analog special adapter nearest to the main unit is counted as the 1st analog special adapter, and the
next adapter as the 2nd analog special adapter, and so on. However, in this case, do not include the
connect conversion adapter and the communication special adapter.
*1. The second special adapter is not available in the FX3G Series PLC(14-point and 24-point type).
K-17
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 4 Programming
FX3U-4AD-PNK-ADP (4-channel Resistance Thermometer Data Input) 4.2 List of Special Devices
K-18
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 4 Programming
FX3U-4AD-PNK-ADP (4-channel Resistance Thermometer Data Input) 4.3 Selection of Temperature Unit
K
• FX3G Series PLC
FX3U-4AD-PNK
R: Read / W: Write
Device number
Special device Description Attribute Refer to
-ADP
1st 2nd
M8280 M8290 Selects the temperature unit R/W Section 4.3
M8281 M8291 Input sensor selection R/W Section 4.4
L
Special auxiliary relay
FX3U-4AD-TC
M8282 to M8292 to
Unused (Do not use.) - -
M8289 M8299
Channel-1 temperature measurement
-ADP
D8280 D8290 R
data
D8281 D8291
Channel-2 temperature measurement
data
R M
Section 4.5
PID Instruction
Channel-3 temperature measurement
D8282 D8292 R
data
(FNC 88)
Channel-4 temperature measurement
D8283 D8293 R
data
Averaging time for channel 1
Special data register D8284 D8294 R/W
(Setting range: 1 to 4095)
Averaging time for channel 2
D8285 D8295 R/W
(Setting range: 1 to 4095)
Section 4.6
Averaging time for channel 3
D8286 D8296 R/W
(Setting range: 1 to 4095)
Averaging time for channel 4
D8287 D8297 R/W
(Setting range: 1 to 4095)
D8288 D8298 Error status R/W Section 4.7
D8289 D8299 Model code = 11 R Section 4.8
K-19
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 4 Programming
FX3U-4AD-PNK-ADP (4-channel Resistance Thermometer Data Input) 4.4 Input sensor selection
1) To select Pt1000 for the 1st adapter: 2)To select Ni1000 for the 2nd adapter :
M8001 M8000
M8261 M8271
Normally OFF Normally ON
K-20
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 4 Programming
FX3U-4AD-PNK-ADP (4-channel Resistance Thermometer Data Input) 4.5 Temperature Measurement
K
4.5 Temperature Measurement
FX3U-4AD-PNK
The temperature data input in the PNK-ADP will be stored in the special data registers.
-ADP
The special data registers that store the temperature data are shown in the following table:
• FX3U, FX3UC Series PLC
L
Special data register
FX3U-4AD-TC
Description
1st 2nd 3rd 4th
D8260 D8270 D8280 D8290 Stores the channel-1 temperature measurement data.
-ADP
D8261 D8271 D8281 D8291 Stores the channel-2 temperature measurement data.
D8262 D8272 D8282 D8292 Stores the channel-3 temperature measurement data. M
D8263 D8273 D8283 D8293 Stores the channel-4 temperature measurement data.
PID Instruction
• FX3G Series PLC
(FNC 88)
Special data register
Description
1st 2nd
D8280 D8290 Stores the channel-1 temperature measurement data.
D8281 D8291 Stores the channel-2 temperature measurement data.
D8282 D8292 Stores the channel-3 temperature measurement data.
D8283 D8293 Stores the channel-4 temperature measurement data.
The immediate data or the average data (data averaged in accordance with the specified averaging time) will
be stored in the above data registers as the temperature measurement data.
→ For a detailed description of the averaging time, refer to Section 4.6.
Even if the temperature measurement data is not stored in D100 or D101, data registers D8260 or D8261 can
be directly used in the arithmetic operation instruction or a PID instruction.
K-21
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 4 Programming
FX3U-4AD-PNK-ADP (4-channel Resistance Thermometer Data Input) 4.6 Averaging Time
FNC 12 K128 D8265 Sets the averaging time to "128" for the channel-2
MOV data of the 1st analog special adapter.
K-22
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 4 Programming
FX3U-4AD-PNK-ADP (4-channel Resistance Thermometer Data Input) 4.7 Error Status
K
4.7 Error Status
FX3U-4AD-PNK
If an error is detected on PNK-ADP, the error status data will be stored in the corresponding special data
-ADP
register.
The following table shows the special data registers that store the error status data:
• FX3U, FX3UC Series PLC L
FX3U-4AD-TC
Special data register
Description
1st 2nd 3rd 4th
-ADP
D8268 D8278 D8288 D8298 Stores the error status data.
PID Instruction
Special data register
Description
(FNC 88)
1st 2nd
D8288 D8298 Stores the error status data.
Check the ON/OFF status of each bit of the error status data register to determine the error. Errors are
assigned to the bits as shown in the following table. Create a program to detect errors.
M8000
MOV D8288 K4M0
Normally
ON
M8002 Error status in the 3rd*1 analog special adapter
RST M6 b6 = OFF (hardware error)
Initial pulse
K-23
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 4 Programming
FX3U-4AD-PNK-ADP (4-channel Resistance Thermometer Data Input) 4.7 Error Status
M8000
MOV D8288 K4M0
M0
Y000 The temperature measurement data
of channel 1 is outside the specified
range, or disconnection is detected.
M1
Y001 The temperature measurement data
of channel 2 is outside the specified
range, or disconnection is detected.
M2
Y002 The temperature measurement data
of channel 3 is outside the specified
range, or disconnection is detected.
M3
Y003 The temperature measurement data
of channel 4 is outside the specified
range, or disconnection is detected.
M4
Y004 EEPROM error in 3rd*1 adapter
M5
Y005 Averaging time setting error in 3rd*1
adapter
M6
Y006 PNK-ADP hardware error in 3rd*1
adapter
M7
Y007 PNK-ADP communication data error
in the 3rd*1 adapter
K-24
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 4 Programming
FX3U-4AD-PNK-ADP (4-channel Resistance Thermometer Data Input) 4.7 Error Status
K
3. Program Example 2 (For FX3U, FX3UC Series PLC)
FX3U-4AD-PNK
D8268.0
-ADP
Y000 The temperature measurement data
of channel 1 is outside the specified
D8268.1
range, or disconnection is detected. L
FX3U-4AD-TC
Y001 The temperature measurement data
of channel 2 is outside the specified
range, or disconnection is detected.
D8268.2
-ADP
Y002 The temperature measurement data
of channel 3 is outside the specified
D8268.3
range, or disconnection is detected. M
PID Instruction
Y003 The temperature measurement data
of channel 4 is outside the specified
(FNC 88)
range, or disconnection is detected.
D8268.4
Y004 EEPROM error in 1st adapter
D8268.5
Y005 Averaging time setting error in 1st
adapter
D8268.6
Y006 PNK-ADP hardware error in 1st
adapter
D8268.7
Y007 PNK-ADP communication data error
in the 1st adapter
K-25
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 4 Programming
FX3U-4AD-PNK-ADP (4-channel Resistance Thermometer Data Input) 4.8 Model Code
Use the above special data registers to check whether PNK-ADP is connected or not.
K-26
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 4 Programming
FX3U-4AD-PNK-ADP (4-channel Resistance Thermometer Data Input) 4.9 Basic Program Example
K
4.9 Basic Program Example
FX3U-4AD-PNK
Create the following basic program to read out the temperature measurement data.
-ADP
• For FX3G, FX3U, FX3UC Series PLC
The following program will select Pt1000 and will store the temperature measurement data (°C) of channels 1
and 2 of the 3rd*1 adapter in the D100 and the D101, respectively. The averaging time will be set to "32" for
L
FX3U-4AD-TC
channel 1, and "128" for channel 2.
M8000
-ADP
MOV D8288 K4M0
Normally
ON
M8002 Error status of 3rd*1 analog special
M
PID Instruction
RST M6 adapter
b6 = OFF (hardware error)
Initial
(FNC 88)
pulse Error status of 3rd*1 analog special
RST M7 adapter
b7 = OFF (communication data error)
M8001
M8280 Sets the temperature unit to
centigrade (°C)
M8002
FNC 12 K32 D8284 Sets the averaging time to "32" for
MOV channel-1 data
Even if the temperature measurement data is not stored to D100 or D101, data registers D8280 or D8281 can
be directly used in the arithmetic operation instruction or a PID instruction.
*1. "1st" for the FX3G PLC.
K-27
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 4 Programming
FX3U-4AD-PNK-ADP (4-channel Resistance Thermometer Data Input) 4.9 Basic Program Example
M8002
FNC 12 K32 D8264 Sets the averaging time to "32" for
MOV channel-1 data
Even if the temperature measurement data is not stored to D100 or D101, data registers D8260 or D8261 can
be directly used in the arithmetic operation instruction or a PID instruction.
K-28
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 5 Troubleshooting
FX3U-4AD-PNK-ADP (4-channel Resistance Thermometer Data Input) 5.1 PLC Version Number Check
FX3U-4AD-PNK
5. Troubleshooting
-ADP
This chapter describes the troubleshooting methods and error status. L
If the temperature measurement data is not input, or if the proper digital value is not input, check the following
FX3U-4AD-TC
items:
• Version number of the PLC
-ADP
• Wiring
• Special devices
M
• Programs
PID Instruction
• Error status
(FNC 88)
5.1 PLC Version Number Check
• Any versions (from Ver.2.20 (initial version) to the latest version) of the FX3U Series are compatible.
• Check the version number of FX3UC Series. The version number should be 1.30 or later.
• Any versions (from Ver.1.00 (initial version) to the latest version) of the FX3G Series are compatible.
→ For a detailed description of the version number check method, refer to Section 1.3.
1. Power
The PNK-ADP needs driving power. Verify that the power supply line is properly connected. Also check that
the POWER indicator lamp of the PNK-ADP is on.
2. Temperature measurement
Check if the special device of the selected channel is correctly set.
This special device should be selected depending on the connecting position and the channel.
3. Averaging time
Verify if the set averaging time is within the specified range. The averaging time should be set in the range
from 1 to 4095. If the set averaging time is outside the specified range, an error occurs.
4. Error status
Check that no error is detected in the PNK-ADP.
If an error is detected, check the details of the error, and then check the wiring and programs.
→ For a detailed description of special devices, refer to Chapter 4.
K-29
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 5 Troubleshooting
FX3U-4AD-PNK-ADP (4-channel Resistance Thermometer Data Input) 5.4 Program Check
K-30
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 5 Troubleshooting
FX3U-4AD-PNK-ADP (4-channel Resistance Thermometer Data Input) 5.5 Error Status Check
K
4. PNK-ADP hardware error (b6)
FX3U-4AD-PNK
1) Description of error
The PNK-ADP does not operate properly.
-ADP
2) Remedy
Check that the 24V DC power is properly supplied to the PNK-ADP.
Also check that the PNK-ADP is correctly connected to the PLC. L
If the problem cannot be solved even after the above check, please contact the nearest Mitsubishi
FX3U-4AD-TC
Electric distributor office.
-ADP
1) Description of error
A communication error is detected between the PNK-ADP and the PLC. M
2) Remedy
PID Instruction
Check that the PNK-ADP is correctly connected to the PLC.
(FNC 88)
If the problem cannot be solved even after the above check, please contact the nearest Mitsubishi
Electric distributor office.
K-31
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 5 Troubleshooting
FX3U-4AD-PNK-ADP (4-channel Resistance Thermometer Data Input) 5.5 Error Status Check
MEMO
K-32
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition
FX3U-4AD-TC-ADP (4-channel Thermocouple Data Input)
FX3U-4AD-PNK
-ADP
L
FX3U-4AD-TC
FX3G/FX3U/FX3UC Series Programmable
-ADP
Controllers M
PID Instruction
User's Manual [Analog Control Edition]
(FNC 88)
FX3U-4AD-TC-ADP (4-channel Thermocouple Data Input)
Foreword
This manual describes the specifications, wiring, and operation methods for the FX3U-4AD-TC-ADP special
adapter (4-channel thermocouple input) and should be read and understood before attempting to install or
use the unit.
Store this manual in a safe place so that you can take it out and read it whenever necessary. Always forward
it to the end user.
This manual confers no industrial property rights or any rights of any other kind, nor does it confer any patent
licenses. Mitsubishi Electric Corporation cannot be held responsible for any problems involving industrial property
rights which may occur as a result of using the contents noted in this manual.
L-1
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition
FX3U-4AD-TC-ADP (4-channel Thermocouple Data Input)
L-2
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 1 Outline
FX3U-4AD-TC-ADP (4-channel Thermocouple Data Input) 1.1 Outline of Functions
FX3U-4AD-PNK
1. Outline
-ADP
This chapter describes the outline of FX3U-4AD-TC-ADP (referred to as TC-ADP). L
FX3U-4AD-TC
1.1 Outline of Functions
-ADP
The FX3U-4AD-TC-ADP is an analog special adapter. Connect the FX3U-4AD-TC-ADP to the FX3U/FX3UC/
FX3G Series PLC to read the data from the 4-channel thermocouple.
M
1) Up to 4 TC-ADP units can be connected to the FX3U/FX3UC Series PLC.
PID Instruction
Up to 2*1 TC-ADP units can be connected to the FX3G Series PLC.
(Including other analog special adapters)
(FNC 88)
2) Thermocouple types K and J can be connected. (However, it's impossible to use both types K and J with
1 adapter.)
3) A/D conversion data will be automatically written to the special data register of the FX3U/FX3UC/FX3G
Series PLC.
+ + to Section 1.3.
Expansion
4th 3rd 2nd 1st
adapter adapter adapter adapter board*2
For a detailed
…… description of wiring,
Analog data refer to Chapter 3.
Refer to the system configuration shown in the User's Manual - Hardware Edition to check the number of connectable units
and to configure the entire system.
*1. Only 1 analog special adapter can be connected to the 14-point and 24-point type main unit.
*2. The expansion board is not required when connecting with the FX3UC (D, DSS) PLC.
For the FX3G Series PLC a connector conversion adapter is used.
L-3
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 1 Outline
FX3U-4AD-TC-ADP (4-channel Thermocouple Data Input) 1.2 Setup Procedure Before Starting Operation
FX3U-4AD-TC-ADP
Refer to Chapter 1.
Wiring Wiring:
•Selection of sensor cable
•Power supply line
Refer to Chapter 4. •Analog input line
Programming Programming:
•Details of special devices
•Examples of basic programs
L-4
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 1 Outline
FX3U-4AD-TC-ADP (4-channel Thermocouple Data Input) 1.3 Connectable PLC and Its Version Number
K
1.3 Connectable PLC and Its Version Number
FX3U-4AD-PNK
TC-ADP is compatible with the following PLC.
-ADP
Compatible PLC Version number Date of production
FX3U Series PLC Ver. 2.20 or later After May 2005 (initial production) L
FX3U-4AD-TC
FX3UC Series PLC Ver. 1.30 or later After August 2004
FX3G Series PLC Ver. 1.00 or later After June 2008 (initial production)
-ADP
1. Version check
Special data register D8001 contains information for determining the PLC version number.
M
PID Instruction
→ For a detailed description of the version check, refer to A. Common Items Subsection 5.1.2.
(FNC 88)
2. How to look at the manufacturer's serial number
The year and month of production of the product can be checked on the nameplate, and on the front of the
product.
→ For a detailed description of the How to look at the manufacturer's serial number,
refer to A. Common Items Subsection 5.1.1.
1. GX Developer
If a programming tool with the wrong version number is used, programming will not be possible.
*1. For Ver. 8.13P to 8.24A of GX Developer, select FX3UC for the PLC type.
2. FX-30P
L-5
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 2 Specifications
FX3U-4AD-TC-ADP (4-channel Thermocouple Data Input) 2.1 Generic Specifications
2. Specifications
This chapter describes the general, power supply, and performance specifications for the TC-ADP.
Item Specifications
0 to 55°C (32 to 131°F) when operating
Ambient temperature
-25 to 75°C (-13 to 167°F) when stored
Relative humidity 5 to 95%RH (no condensation) when operating
Frequency Acceleration Half amplitude
(Hz) (m/s2) (mm)
Tested 10 times in
Vibration 10 - 57 - 0.035 each direction (X-, Y-,
DIN Rail Mounting
resistance*1 57 - 150 4.9 - and Z-axis directions)
(Total: 80 min, each)
10 to 57 − 0.075
Direct Mounting*2
57 to 150 9.8 −
147 m/s2 Acceleration, Action time: 11ms, 3 times by half-sine pulse in each direction X, Y,
Shock resistance*1
and Z
Using noise simulator of:
Noise resistance
Noise voltage: 1,000Vp-p / Noise width: 1μs / Rise: 1ns / Cycle: 30 to 100Hz
Dielectric withstand
500 V AC, for 1 min
voltage
Between batch of all terminals and ground terminal
5MΩ or more using 500V DC
Insulation resistance
insulation resistance meter
Class D grounding (grounding resistance: 100 Ω or less)
Grounding
<Common grounding with a heavy electrical system is not allowed.>*3
Working
Free from corrosive or flammable gas and excessive conductive dusts
environment
Working altitude < 2000m*4
Item Specifications
A/D conversion circuit 24V DC +20% -15%, 45mA
driving power (It is necessary to connect a 24V DC power supply to the terminal block.)
5V DC, 15mA
Interface driving power (Since the internal power is supplied from the FX Series main unit, it is not
necessary to supply the power.)
L-6
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 2 Specifications
FX3U-4AD-TC-ADP (4-channel Thermocouple Data Input) 2.3 Performance Specifications
K
2.3 Performance Specifications
FX3U-4AD-PNK
-ADP
Specifications
Item
Centigrade (°C) Fahrenheit (°F) L
FX3U-4AD-TC
Thermocouple type K or J
Input signal
JIS C 1602-1995
-ADP
range Type J -100°C to +600°C Type J -148°F to +1112°F
Digital output
Type K -1000 to +10000 Type K -1480 to +18320 M
PID Instruction
Type J -1000 to +6000 Type J -1480 to +11120
Type K 0.4°C Type K 0.72°F
(FNC 88)
Resolution
Type J 0.3°C Type J 0.54°F
Total accuracy ±(0.5% full scale +1°C)
• FX3U/FX3UC Series PLC : 200μs (The data will be updated at every scan time.)
A/D conversion
• FX3G Series PLC : 250μs (The data will be updated at every scan time.)
time
→For a detailed description of data update, refer to Section2.4.
• Type K •Type K
+10100 +18500
+10000 +18320
+1010°C
+1850° F
-100°C 0 -148° F 0
+1000°C +1832° F
-110°C
-166° F
-1000 -1480
Input -1100 -1660
characteristics
•Type J •Type J
+6100 +11300
+6000 +11120
+1130°F
+610°C
-100°C 0 -148°F 0
+600°C +1112°F
-166°F
-110°C
-1000 -1480
-1100 -1660
• The photocoupler is used to insulate the analog input area from the PLC.
Insulation method • The DC/DC converter is used to insulate the power supply line from the analog input area.
• Channels are not insulated from each other.
Number of I/O 0 points
points occupied (This number is not related to the maximum number of input/output points of the PLC.)
L-7
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 2 Specifications
FX3U-4AD-TC-ADP (4-channel Thermocouple Data Input) 2.4 A/D Conversion Time
FX3U-4AD-TC-ADP FX3U-4AD-TC-ADP
n'th 1st FX3U/FX3UC Series PLC
Sequence
program
A/D conversion start
A/D command
conversion
Digital value reading
200 μs/4ch
A/D conversion start END instruction
A/D command
conversion
Digital value reading
200 μs/4ch
L-8
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 2 Specifications
FX3U-4AD-TC-ADP (4-channel Thermocouple Data Input) 2.5 Temperature Measurement
K
2.4.2 When connected to a FX3G PLC
FX3U-4AD-PNK
1. A/D conversion and special data register update timing
-ADP
A/D conversion is performed at every scan time of the PLC.
During execution of END instruction, the PLC performs A/D conversion, reads out the A/D converted data,
and then writes the data in the special data registers. L
FX3U-4AD-TC
FX3U-4AD-TC-ADP FX3U-4AD-TC-ADP
2nd 1st FX3G Series PLC
-ADP
Sequence
program
M
PID Instruction
A/D conversion start
A/D command
(FNC 88)
conversion
Digital value reading
250 μs/4ch
A/D conversion start END instruction
A/D command
conversion
Digital value reading
250 μs/4ch
L-9
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 3 Wiring
FX3U-4AD-TC-ADP (4-channel Thermocouple Data Input)
3. Wiring
This chapter describes the TC-ADP wiring.
Observe the following caution to wire the TC-ADP.
WIRING PRECAUTIONS
• Make sure to cut off all phases of the power supply externally before attempting wiring work.
Failure to do so may cause electric shock or damages to the product.
WIRING PRECAUTIONS
• Connect the DC power supply wiring to the dedicated terminals described in this manual.
If an AC power supply is connected to a DC input/output terminal or DC power supply terminal, the PLC will be
burnt out.
• Do not wire vacant terminals externally.
Doing so may damage the product.
• Perform class D grounding (grounding resistance: 100Ω or less) to the grounding terminal on the main unit.
Do not use common grounding with heavy electrical systems.
• When drilling screw holes or wiring, make sure cutting or wire debris does not enter the ventilation slits.
Failure to do so may cause fire, equipment failures or malfunctions.
• Make sure to observe the following precautions in order to prevent malfunctions under the influence of noise:
- Do not bundle the power line or twisted shielded cable together with or lay it close to the main circuit, high-
voltage line, or load line.
Otherwise, noise disturbance and/or surge induction are likely to take place. As a guideline, lay the control line
at least 100mm (3.94") or more away from the main circuit, high-voltage line, or load line.
- Ground the shield of the analog input/output cable at one point on the signal receiving side.
However, do not use common grounding with heavy electrical systems.
• Make sure to properly wire to the European terminal board in accordance with the following precautions.
Failure to do so may cause electric shock, a short-circuit, wire breakage, or damage to the product.
- The disposal size of the cable end should be 9 mm (0.35").
- Tightening torque should be between 0.22 to 0.25 N•m.
- Twist the end of strand wire and make sure there are no loose wires.
- Do not solder-plate the electric wire ends.
- Do not connect more than the specified number of wires or electric wires of unspecified size.
- Affix the electric wires so that neither the terminal block nor the connected parts are directly stressed.
L-10
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 3 Wiring
FX3U-4AD-TC-ADP (4-channel Thermocouple Data Input) 3.1 Terminal Layout
K
3.1 Terminal Layout
FX3U-4AD-PNK
The terminals of the TC-ADP are arranged as follows:
-ADP
L
FX3U-4AD-TC
FX3U-4AD-TC
-ADP
-ADP
POWER
Signal Application M
PID Instruction
24+
24+
External power
24-
24-
(FNC 88)
Ground terminal
• Unused
• •
L1-
L2+
L-11
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 3 Wiring
FX3U-4AD-TC-ADP (4-channel Thermocouple Data Input) 3.2 Applicable Cables and Terminal Tightening Torque
1. Cables
Applicable cable and tightening torque
Wire size Tightening
Termination
(stranded/single-wire) torque
0.3 mm2 to 0.5 mm2 • To connect a stranded cable, peel the cover off the cable
Single-wire and then twist the core before connection.
(AWG22 to 20)
• To connect a single-wire cable, just strip the cover off the
2-wire 0.3mm2(AWG22) cable before connection.
0.22 N•m to • Rod terminal with insulation sleeve
Rod terminal 0.3 mm2 to 0.5 mm2 0.25 N•m (recommended terminal)
with (AWG22-20) AI 0.5-8WH : Manufactured by Phoenix Contact
insulation (Refer to the rod terminal
• Caulking tool
sleeve external view shown in the
CRIMPFOX ZA 3 : Manufactured by Phoenix Contact
following figure.)
(or CRIMPFOX UD 6 : Manufactured by Phoenix Contact)
3. Tool
• To tighten terminals, use a small-sized screwdriver whose head is straight and is not widened as shown in
the figure to the right.
Note:
If the diameter of screwdriver grip is too small, tightening torque will not
The head
be able to be achieved. Use the following recommended screwdriver or should be
an appropriate replacement (grip diameter: approximately 25mm). straight.
Manufacturer Model
Phoenix Contact SZS 0.4×2.5 0.4mm 2.5mm
(0.01") (0.09")
L-12
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 3 Wiring
FX3U-4AD-TC-ADP (4-channel Thermocouple Data Input) 3.3 Power Supply Line
K
3.3 Power Supply Line
FX3U-4AD-PNK
Connect the 24V DC power supply line of the TC-ADP to the 24+ and 24- terminals of the terminal block.
-ADP
3.3.1 To connect to FX3G, FX3U Series PLC
L
FX3U-4AD-TC
1. To use an external power 2. To use the 24V DC power of the PLC
-ADP
+5V Series PLC
(Main unit) +5V
(Main unit)
M
PID Instruction
(FNC 88)
24- 24+ 24- 24+ 0V 24V
Terminal Terminal
block block
Class-D Class-D
24V DC grounding grounding
TC-ADP FX2NC
FX3UC Series PLC Series PLC
+5V (Main unit) (Input extension
block)
Power
Power Power crossover
connector connector connector
Class-D
24V DC grounding
L-13
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 3 Wiring
FX3U-4AD-TC-ADP (4-channel Thermocouple Data Input) 3.4 Selection of the Thermocouple
• There are 2 types of thermocouples: K type and J type. When selecting the thermocouple type, make sure
that the same type of thermocouple is connection to all the channels.
• Be sure to use a non-grounded thermocouple type.
• The compensating lead wire indicates a temperature value of approximately 0.12°C higher than that of the
wire resistor (10Ω). Use the appropriate compensating lead wire when considering this difference.
• If the compensating lead wire is very long, the wire may be easily affected by noise, etc. It is, therefore,
recommended for the length of the compensating lead wire to be 100 m or less.
Shield
Temperature
compensating circuit
3kΩ ch
L +
L -
+5V
24+
24V DC
24-
Class-D
grounding
*1. It is not necessary to connect lines to the J-type terminals. Leave these terminals disconnected.
*2. Keep the thermocouple away from inductive noise (commercial power, etc.).
L-14
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 3 Wiring
FX3U-4AD-TC-ADP (4-channel Thermocouple Data Input) 3.6 Caution Regarding Wiring
K
3.5.2 Wiring of the thermocouple type J
FX3U-4AD-PNK
Terminal block
-ADP
TC-ADP
type J
*1
Thermocouple Compensating
type J Temperature
compensating circuit L
type J*2 lead wire
FX3U-4AD-TC
3kΩ ch
L +
L -
-ADP
Shield
Temperature
compensating circuit M
3kΩ
PID Instruction
L + ch
L -
(FNC 88)
+5V
24+
24V DC
24-
Class-D
grounding
*1. To use a J thermocouple type, be sure to connect the thermocouple to these terminals. In addition,
select J type by turning on the type K/J selection special auxiliary relay.
*2. Keep the thermocouple away from inductive noise (commercial power, etc.).
3.7 Grounding
Grounding should be performed as stated below.
• The grounding resistance should be 100Ω or less.
• Independent grounding should be performed for best results.
When independent grounding is not performed, perform "shared grounding" as shown in the following
figure.
→ For details, refer to the User’s Manual - Hardware Edition of the PLC Series.
L-15
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 4 Programming
FX3U-4AD-TC-ADP (4-channel Thermocouple Data Input) 4.1 Loading of A/D Conversion Data
4. Programming
This chapter describes how to create programs that can read out the analog data using the TC-ADP.
The analog special adapter nearest to the main unit is counted as the 1st analog special adapter, and the
next adapter as the 2nd analog special adapter, and so on. However, in this case, do not include the high-
speed input/output special adapter, communication special adapter, and the CF card special adapter.
L-16
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 4 Programming
FX3U-4AD-TC-ADP (4-channel Thermocouple Data Input) 4.1 Loading of A/D Conversion Data
K
• FX3G Series PLC
FX3U-4AD-PNK
Communi-
cation Connector
FX3U-4AD FX3U-4AD
-ADP
special conversion
-TC-ADP -TC-ADP
adapter adapter FX3G Series PLC
2nd*1 1st
Special devices
L
FX3U-4AD-TC
Special auxiliary relays:
M8280 to M8289
A/D Special data registers:
-ADP
D8280 to D8289 Sequence
Program
Special auxiliary relays:
A/D
M8290 to M8299
Special data registers:
M
PID Instruction
D8290 to D8299
(FNC 88)
The analog special adapter nearest to the main unit is counted as the 1st analog special adapter, and the
next adapter as the 2nd analog special adapter. However, in this case, do not include the connector
conversion adapter and the communication special adapter.
*1. The second special adapter is not available in the FX3G Series PLC(14-point and 24-point type).
L-17
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 4 Programming
FX3U-4AD-TC-ADP (4-channel Thermocouple Data Input) 4.2 List of Special Devices
L-18
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 4 Programming
FX3U-4AD-TC-ADP (4-channel Thermocouple Data Input) 4.3 Selection of Temperature Unit
K
• FX3G Series PLC
FX3U-4AD-PNK
R: Read / W: Write
Device number
Special device Description Attribute Refer to
-ADP
1st 2nd
M8280 M8290 Selects the temperature unit R/W Section 4.3
Switches the thermocouple type
L
M8281 M8291 R/W Section 4.4
FX3U-4AD-TC
Special auxiliary relay between type K and type J
M8282 to M8292 to
Unused (Do not use.) - -
M8289 M8299
-ADP
Channel-1 temperature measurement
D8280 D8290 R
data
Channel-2 temperature measurement
M
D8281 D8291 R
PID Instruction
data
Section 4.5
Channel-3 temperature measurement
D8282 D8292 R
(FNC 88)
data
Channel-4 temperature measurement
D8283 D8293 R
data
Averaging time for channel 1
Special data register D8284 D8294 R/W
(Setting range: 1 to 4095)
Averaging time for channel 2
D8285 D8295 R/W
(Setting range: 1 to 4095)
Section 4.6
Averaging time for channel 3
D8286 D8296 R/W
(Setting range: 1 to 4095)
Averaging time for channel 4
D8287 D8297 R/W
(Setting range: 1 to 4095)
D8288 D8298 Error status R/W Section 4.7
D8289 D8299 Model code = 10 R Section 4.8
L-19
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 4 Programming
FX3U-4AD-TC-ADP (4-channel Thermocouple Data Input) 4.4 Selection of Type K or J
L-20
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 4 Programming
FX3U-4AD-TC-ADP (4-channel Thermocouple Data Input) 4.5 Temperature Measurement
K
4.5 Temperature Measurement
FX3U-4AD-PNK
The temperature data input in the TC-ADP will be stored in the special data registers.
-ADP
The special data registers that store the temperature data are shown in the following table:
• FX3U, FX3UC Series PLC
L
Special data register
FX3U-4AD-TC
Description
1st 2nd 3rd 4th
D8260 D8270 D8280 D8290 Stores the channel-1 temperature measurement data.
-ADP
D8261 D8271 D8281 D8291 Stores the channel-2 temperature measurement data.
D8262 D8272 D8282 D8292 Stores the channel-3 temperature measurement data. M
D8263 D8273 D8283 D8293 Stores the channel-4 temperature measurement data.
PID Instruction
• FX3G Series PLC
(FNC 88)
Special data register
Description
1st 2nd
D8280 D8290 Stores the channel-1 temperature measurement data.
D8281 D8291 Stores the channel-2 temperature measurement data.
D8282 D8292 Stores the channel-3 temperature measurement data.
D8283 D8293 Stores the channel-4 temperature measurement data.
The immediate data or the average data (data averaged in accordance with the specified averaging time) will
be stored in the above data registers as the temperature measurement data.
→ For a detailed description of the averaging time, refer to Section 4.6.
Even if the temperature measurement data is not stored in D100 or D101, data registers D8260 or D8261 can
be directly used in the arithmetic operation instruction or a PID instruction.
L-21
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 4 Programming
FX3U-4AD-TC-ADP (4-channel Thermocouple Data Input) 4.6 Averaging Time
FNC 12 K128 D8265 Sets the averaging time to "128" for the channel-2
MOV data of the 1st analog special adapter.
L-22
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 4 Programming
FX3U-4AD-TC-ADP (4-channel Thermocouple Data Input) 4.7 Error Status
K
4.7 Error Status
FX3U-4AD-PNK
If an error is detected on TC-ADP, the error status data will be stored in the corresponding special data
-ADP
register.
The following table shows the special data registers that store the error status data:
• FX3U, FX3UC Series PLC L
FX3U-4AD-TC
Special data register
Description
1st 2nd 3rd 4th
-ADP
D8268 D8278 D8288 D8298 Stores the error status data.
PID Instruction
Special data register
Description
(FNC 88)
1st 2nd
D8288 D8298 Stores the error status data.
Check the ON/OFF status of each bit of the error status data register to determine the error. Errors are
assigned to the bits as shown in the following table. Create a program to detect errors.
M8000
MOV D8288 K4M0
Normally
ON
M8002 Error status in the 3rd*1 analog special adapter
RST M6 b6 = OFF (hardware error)
Initial pulse
L-23
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 4 Programming
FX3U-4AD-TC-ADP (4-channel Thermocouple Data Input) 4.7 Error Status
M8000
MOV D8288 K4M0
M0
Y000 The temperature measurement data
of channel 1 is outside the specified
range, or disconnection is detected.
M1
Y001 The temperature measurement data
of channel 2 is outside the specified
range, or disconnection is detected.
M2
Y002 The temperature measurement data
of channel 3 is outside the specified
range, or disconnection is detected.
M3
Y003 The temperature measurement data
of channel 4 is outside the specified
range, or disconnection is detected.
M4
Y004 EEPROM error in 3rd*1 adapter
M5
Y005 Averaging time setting error in 3rd*1
adapter
M6
Y006 TC-ADP hardware error in 3rd*1
adapter
M7
Y007 TC-ADP communication data error
in the 3rd*1 adapter
L-24
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 4 Programming
FX3U-4AD-TC-ADP (4-channel Thermocouple Data Input) 4.7 Error Status
K
3. Program Example 2 (For FX3U, FX3UC Series PLC)
FX3U-4AD-PNK
D8268.0
-ADP
Y000 The temperature measurement data
of channel 1 is outside the specified
D8268.1
range, or disconnection is detected. L
FX3U-4AD-TC
Y001 The temperature measurement data
of channel 2 is outside the specified
range, or disconnection is detected.
D8268.2
-ADP
Y002 The temperature measurement data
of channel 3 is outside the specified
D8268.3
range, or disconnection is detected. M
Y003 The temperature measurement data
PID Instruction
of channel 4 is outside the specified
range, or disconnection is detected.
(FNC 88)
D8268.4
Y004 EEPROM error in 1st adapter
D8268.5
Y005 Averaging time setting error in 1st
adapter
D8268.6
Y006 TC-ADP hardware error in 1st
adapter
D8268.7
Y007 TC-ADP communication data error
in the 1st adapter
L-25
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 4 Programming
FX3U-4AD-TC-ADP (4-channel Thermocouple Data Input) 4.8 Model Code
Use the above special data registers to check whether TC-ADP is connected or not.
FNC224 D8269 K10 Y010 Checks the model code of the 1st
LD = analog special adapter.
L-26
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 4 Programming
FX3U-4AD-TC-ADP (4-channel Thermocouple Data Input) 4.9 Basic Program Example
K
4.9 Basic Program Example
FX3U-4AD-PNK
Create the following basic program to read out the temperature measurement data.
-ADP
• For FX3G, FX3U, FX3UC Series PLCs
The following program will select thermocouple type K and will store the temperature measurement data (°C)
of channels 1 and 2 of the 3rd*1 adapter in the D100 and the D101, respectively. The averaging time will be
L
FX3U-4AD-TC
set to "32" for channel 1, and "128" for channel 2.
M8000
-ADP
MOV D8288 K4M0
Normally
ON
M8002 Error status of 3rd*1 analog special
M
PID Instruction
RST M6 adapter
b6 = OFF (hardware error)
Initial
(FNC 88)
pulse Error status of 3rd*1 analog special
RST M7 adapter
b7 = OFF (communication data error)
M8001
M8280 Sets the temperature unit to
centigrade (°C)
M8002
FNC 12 K32 D8284 Sets the averaging time to "32" for
MOV channel-1 data
Even if the temperature measurement data is not stored to D100 or D101, data registers D8280 or D8281 can
be directly used in the arithmetic operation instruction or a PID instruction.
*1. "1st" for the FX3G PLC.
L-27
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 4 Programming
FX3U-4AD-TC-ADP (4-channel Thermocouple Data Input) 4.9 Basic Program Example
M8002
FNC 12 K32 D8264 Sets the averaging time to "32" for
MOV channel-1 data
Even if the temperature measurement data is not stored to D100 or D101, data registers D8260 or D8261 can
be directly used in the arithmetic operation instruction or a PID instruction.
L-28
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 5 Troubleshooting
FX3U-4AD-TC-ADP (4-channel Thermocouple Data Input) 5.1 PLC Version Number Check
FX3U-4AD-PNK
5. Troubleshooting
-ADP
This chapter describes the troubleshooting methods and error status. L
If the temperature measurement data is not input, or if the proper digital value is not input, check the following
FX3U-4AD-TC
items:
• Version number of the PLC
-ADP
• Wiring
• Special devices
M
• Programs
PID Instruction
• Error status
(FNC 88)
5.1 PLC Version Number Check
• Any versions (from Ver.2.20 (initial version) to the latest version) of the FX3U Series are compatible.
• Check the version number of FX3UC Series. The version number should be 1.30 or later.
• Any versions (from Ver.1.00 (initial version) to the latest version) of the FX3G Series are compatible.
→ For a detailed description of the version number check method, refer to Section 1.3.
1. Power
The TC-ADP needs driving power. Verify that the power supply line is properly connected. Also check that the
POWER indicator lamp of the TC-ADP is on.
2. Thermocouple cable
Use a non-grounded type thermocouple and connect the thermocouple using the compensating lead wire.
In addition, separate the cable of the thermocouple from the other power cables or inductive cables.
1. Selection of type K or J
Check if the special device for type K/J selection is correctly set.
Turn off the device to select thermocouple type K. Turn on the device to select thermocouple type J.
2. Temperature measurement
Check if the special device of the selected channel is correctly set.
This special device should be selected depending on the connecting position and the channel.
3. Averaging time
Verify if the set averaging time is within the specified range. The averaging time should be set in the range
from 1 to 4095. If the set averaging time is outside the specified range, an error occurs.
4. Error status
Check that no error is detected in the TC-ADP.
If an error is detected, check the details of the error, and then check the wiring and programs.
→ For a detailed description of special devices, refer to Chapter 4.
L-29
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 5 Troubleshooting
FX3U-4AD-TC-ADP (4-channel Thermocouple Data Input) 5.4 Program Check
L-30
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 5 Troubleshooting
FX3U-4AD-TC-ADP (4-channel Thermocouple Data Input) 5.5 Error Status Check
K
4. TC-ADP hardware error (b6)
FX3U-4AD-PNK
1) Description of error
The TC-ADP does not operate properly.
-ADP
2) Remedy
Check that the 24V DC power is properly supplied to the TC-ADP.
Also check that the TC-ADP is correctly connected to the PLC. L
If the problem cannot be solved even after the above check, please contact the nearest Mitsubishi
FX3U-4AD-TC
Electric distributor office.
-ADP
1) Description of error
A communication error is detected between the TC-ADP and the PLC. M
2) Remedy
PID Instruction
Check that the TC-ADP is correctly connected to the PLC.
(FNC 88)
If the problem cannot be solved even after the above check, please contact the nearest Mitsubishi
Electric distributor office.
L-31
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 5 Troubleshooting
FX3U-4AD-TC-ADP (4-channel Thermocouple Data Input) 5.5 Error Status Check
MEMO
L-32
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition
PID Instruction (FNC 88)
FX3U-4AD-PNK
-ADP
L
FX3U-4AD-TC
FX3G/FX3U/FX3UC Series Programmable
-ADP
Controllers M
PID Instruction
User's Manual [Analog Control Edition]
(FNC 88)
PID Instruction (FNC 88)
Foreword
This manual describes the control methods for using the PID instruction in combination with analog products
and should be read and understood before attempting to install or use the unit.
Store this manual in a safe place so that you can take it out and read it whenever necessary. Always forward
it to the end user.
This manual confers no industrial property rights or any rights of any other kind, nor does it confer any patent
licenses. Mitsubishi Electric Corporation cannot be held responsible for any problems involving industrial property
rights which may occur as a result of using the contents noted in this manual.
M-1
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition
PID Instruction (FNC 88)
M-2
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 1 Outline
PID Instruction (FNC 88) 1.1 Outline of function
FX3U-4AD-PNK
1. Outline
-ADP
This chapter describes the outline of PID instruction (FNC88) for the FX3U/FX3UC/FX3G Series PLC. L
FX3U-4AD-TC
1.1 Outline of function
-ADP
The PID instruction requires the system to calculate the output (MV) value from the measured (PV) value.
Through combining the P (proportional) action, I (integral) action, and D (derivative) action the target (SV)
value can be obtained. See diagram below. M
PID Instruction
1) Alarm output function
The alarm function can be set for input variation (measured value) or output variation (value).
(FNC 88)
2) Setting limit values
The upper limit and lower limit can be set for the output value.
3) Auto-tuning function
The proportional gain (KP), integral time (TI) and differential time (TD) can be set automatically for both
the limit cycle method and step response method.
4) Operation method of the PID instruction
Both PID speed type operation and measured value differential type operation are executed.
Target value
(SV)
Controlled
PID Instruction object
M-3
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 1 Outline
PID Instruction (FNC 88) 1.2 Basic Operation Expressions in PID Instruction (Reference)
TS
ΔMV = KP{(EVn − EVn-1) + EVn + Dn}
TI
Forward operation EVn = PVnf-SV
(OFF) TD KD TD
Dn = (−2PVnf−1 + PVnf + PVnf−2) + Dn-1
TS + KD TD TS + KD TD
MVn = ΣΔMV
TS
ΔMV = KP{(EVn − EVn−1) + EVn + Dn}
TI
Backward EVn = SV − PVnf
operation (ON) TD KD TD
Dn = (2PVnf−1 − PVnf − PVnf−2) + Dn-1
TS + KD TD TS + KD TD
MVn = ΣΔMV
1) Symbols
EVn : Deviation in sampling at this time Dn : Differential term at this time
EVn-1 : Deviation in previous cycle Dn-1 : Differential term in previous cycle
SV : Target value KP : Proportional gain
PVnf : Measured value in sampling at this time (after filter) TS : Sampling cycle
PVnf-1 : Measured value in previous cycle (after filter) TI : Integral constant
PVnf-2 : Measured value in two cycles before (after filter) TD : Differential constant
ΔMV : Output variation KD : Differential gain
MVn : Operation quantity at this time
2) Expression for calculating the measured value (after the filter) in sampling at this time (PVnf)
The value "PVnf" is obtained from the following expression based on the read measured value.
M-4
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 2 How to Use PID Instruction
PID Instruction (FNC 88) 2.1 Explanation of function and operation
FX3U-4AD-PNK
2. How to Use PID Instruction
-ADP
1. Instruction format L
FX3U-4AD-TC
16-bit Mnemonic Operation Condition 32-bit Mnemonic Operation Condition
FNC 88 lnstruction lnstruction
PID 9 steps PID Continuous ⎯
PID
Operation
-ADP
2. Set data M
PID Instruction
Operand type Description Data type
(FNC 88)
S2 Data register storing the measured value (PV) Binary 16-bit
3. Target devices
Bit devices Word devices Others
Real Char-
Special Con- Poin-
Operand System User Digit Specification System User Index Num- acter
Unit stant ber String ter
type
Mod-
X Y M T C S D .b KnX KnY KnM KnS T C D R U \G V Z K H E " " P
ify
S1 S
S2 S
S3
D S
M-5
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 2 How to Use PID Instruction
PID Instruction (FNC 88) 2.2 Relationship Between Parameter Setting and Auto-Tuning
*1. When auto-tuning is not executed for the limit cycle method, the same number of devices as those
occupied in the step response method become occupied.
M-6
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 3 Parameter
PID Instruction (FNC 88) 3.1 Parameter List: (S3) to (S3) + 28
FX3U-4AD-PNK
3. Parameter
-ADP
This chapter describes various parameters of PID instruction. L
FX3U-4AD-TC
3.1 Parameter List: (S3) to (S3) + 28
-ADP
Set item Setting Remarks Reference
It cannot be shorter than operation Subsection
M
Sampling time (TS) 1 to 32767 (ms)
PID Instruction
S3
cycle of the PLC. 3.2.1
0: Forward operation
(FNC 88)
bit0 Operation direction
1: Backward operation
0: Input variation alarm is invalid.
bit1
1: Input variation alarm is valid.
0: Output variation alarm is invalid. Do not set to ON bit 2 and bit 5 at
bit2
1: Output variation alarm is valid. same time.
bit3 Not available
Operation 0: Auto-tuning is not executed. Subsection
S3 +1 bit4
setting (ACT) 1: Auto-tuning is executed. 3.2.2
0: Upper and lower limits of output
value are not valid. Do not set to ON bit 2 and bit 5 at
bit5
1: Upper and lower limits of output same time.
value are valid.
0: Step response method
bit6 Select auto-tuning mode.
1: Limit cycle method
bit7 to bit15 Not available
When "0" is set, input filter is not Subsection
S3 +2 Input filter constant (α) 0 to 99 (%)
provided. 3.2.3
Subsection
S3 +3 Proportional gain (KP) 1 to 32767 (%)
3.2.4
When "0" is set, it is handled as "∞" Subsection
S3 +4 Integral time (TI) 0 to 32767 (× 100 ms)
(no integration). 3.2.5
When "0" is set, differential gain is Subsection
S3 +5 Differential gain (KD) 0 to 100 (%)
not provided. 3.2.6
When "0" is set, differential is not Subsection
S3 +6 Differential time (TD) 0 to 32767 (× 10 ms)
executed. 3.2.7
S3 +7
: These devices are occupied for internal processing of PID operation. Do not change data. ⎯
S3 +19
M-7
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 3 Parameter
PID Instruction (FNC 88) 3.1 Parameter List: (S3) to (S3) + 28
*1. S3 +20 to +24 become occupied only if bits 1, 2, or 5 are set to "1" to determine the action (ACT) of
S3 +1.
M-8
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 3 Parameter
PID Instruction (FNC 88) 3.2 Details of Parameters
FX3U-4AD-PNK
3.2.1 Sampling time (TS): (S3)
-ADP
Setting range: 1 to 32767 [ms]
Set the cycle time (ms) for the PID operation.
L
FX3U-4AD-TC
• In the PID control
Set the sampling time longer than the operation cycle of the PLC.
• In the auto-tuning
-ADP
Set the sampling time to 1,000 ms (= 1 second) or more.
1. Maximum error
M
PID Instruction
The maximum error of the sampling time (TS) is from "-(one operation cycle + 1 ms)" to "+(one operation
cycle)."
(FNC 88)
1) When the sampling time (TS) is a small value
Fluctuation of the maximum error described above may cause a problem.
In such a case, execute the PID instruction in the constant scan mode, or program it in a timer interrupt
routine.
2) When the sampling time (TS) is shorter than one operation cycle of the PLC
A PID operation error (K6740) occurs, however when PID operation is executed, the sampling time (TS) is
equal to the operation cycle of the PLC.
In such a case, use the PID instruction in a timer interrupt (I6 to I8 ), and clear S3 +7 just before
executing the PID instruction.
→ For a detailed description, refer to FX3U/FX3UC/FX3G Series Programming Manual - Basic & Applied
Instruction Edition
S3 +7 is reset.
X000 (When the interrupt routine is executed for the
FNC 12 K 0 D107
I610 first time,the register for internal processing is
MOVP
cleared by the pulse generation command.)
M-9
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 3 Parameter
PID Instruction (FNC 88) 3.2 Details of Parameters
Time
Time
Relationship between the forward/backward operation and the output (MV), measured value (PV) and
target value (SV)
The relationship is as follows.
Target value (SV)
Output (MV)
Backward Forward
operation operation
M-10
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 3 Parameter
PID Instruction (FNC 88) 3.2 Details of Parameters
2. Alarm setting (for input variation and output variation): S3 +1, bit 1 and bit 2
K
FX3U-4AD-PNK
Setting range: OFF, ON
The input variation and output variation can be checked arbitrarily.
These parameters can be set in S3 +24.
-ADP
→ For the operation of upper/lower limit alarm output for the input and output values,
refer to Subsection 3.2.8.
L
FX3U-4AD-TC
Input variation: S3 +1, bit 1
When using the input variation alarm, it is necessary to set to ON the following bits and set the values to be
checked.
-ADP
Set item Setting (setting range)
Operation setting
(ACT) S3 +1 bit1 Input variation alarm
ON: Used
OFF: Not used
M
PID Instruction
Input variation S3 +20 Input variation (incremental) alarm set value 0 to 32767
alarm set value
(FNC 88)
S3 +21 Input variation (decremental) alarm set value 0 to 32767
Output variation S3 +22 Output variation (incremental) alarm set value 0 to 32767
alarm set value Output variation (decremental) alarm set value 0 to 32767
S3 +23
Output value
When the upper limit and lower These values
limit of output value are not set are not output.
S3 +22
Output value
upper limit
S3 +23
Output value
lower limit These values
are not output.
When the upper limit and lower
limit of output value are set
Time
M-11
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 3 Parameter
PID Instruction (FNC 88) 3.2 Details of Parameters
Because the input filter (α) is effective to the target value (SV), all of the proportional operation, integral
operation and differential operation are affected.
Input amplitude
Measured Input amplitude
value (PV) processed by input filter
processed by
input filter
M-12
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 3 Parameter
PID Instruction (FNC 88) 3.2 Details of Parameters
FX3U-4AD-PNK
Setting range: 1 to 32767[%]
PID control: Proportional operation
-ADP
During the proportional operation, the output (MV) increases in proportion to the deviation (difference
between the target value (SV) and the measured value (PV)).
This deviation is called proportional gain (Kp), and expressed in the following relational expression: L
FX3U-4AD-TC
Output (MV) = Proportional gain (KP) x Deviation (EV)
The reciprocal of the proportional gain (KP) is called proportional band.
As the proportional gain (KP) is larger (as shown in the example below), the motion to let the measured value
-ADP
(PV) be nearer to the target value (SV) becomes stronger.
PID Instruction
Target value (SV)
Temperature
(FNC 88)
KP3 Remaining deviation
Proportional gain
KP2 KP3 > KP2 > KP1
KP1
Time
Output (MV)
Proportional gain
KP3 > KP2 > KP1
KP3 KP2 KP1
Time
Proportional gain
KP3 > KP2 > KP1
KP3 KP2 KP1
Measured value (PV)
Proportional gain
KP3 > KP2 > KP1
KP3 KP2 KP1
Time
Setting range: 0 to 32767 [ × 100 ms] "0" is handled as "∞" (no integration).
PID operation: Integral operation
During the integral operation, the time after deviation is generated until the integral operation output becomes
the proportional operation output. This is called integral time and is expressed as "TI".
As TI becomes smaller, the integral operation becomes stronger.
M-13
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 3 Parameter
PID Instruction (FNC 88) 3.2 Details of Parameters
Time
Time
TI3 TI2
Target TI1
Measured value in proportional operation
value(SV)
Measured value in PI operation
Time
Time
Important point
The integral operation changes the output so that the continuously generated deviation is eliminated.
As a result, the remaining deviation generated in the proportional operation can be eliminated.
Deviation
Deviation(EV)
Time
Output of
"proportional operation + integral operation"
Time
M-14
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 3 Parameter
PID Instruction (FNC 88) 3.2 Details of Parameters
FX3U-4AD-PNK
Setting range: 0 to 100[%]
PID control: Differential operation
-ADP
The filter is applied to the output at the differential operation.
Only the differential operation is affected by the differential gain (KD).
• When the differential gain (KD) is small, the output is immediately given with regard to changes in the
L
FX3U-4AD-TC
measured value (PV) caused by disturbance, etc.
• When the differential gain (KD) is large, the output is given after a long time with respect to changes in the
measured value (PV) caused by disturbance, etc.
-ADP
Important points
Set the differential gain (KD) to "0", and then adjust the operation using the input filter (α). M
If the output response is too close to the disturbance, increase the differential gain (KD).
PID Instruction
(FNC 88)
3.2.7 Differential time (TD): (S3)+6
Disturbance
TD1 (PID operation) Deviation (EV)
TD2 (PID operation)
Time
Time
M-15
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 3 Parameter
PID Instruction (FNC 88) 3.2 Details of Parameters
Time
Output (MV)
Time
Time
Time
M-16
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 3 Parameter
PID Instruction (FNC 88) 3.2 Details of Parameters
FX3U-4AD-PNK
When the input variation [ S3 +1, bit 1] is set to 1
-ADP
Variation
L
Measured value (PV)
FX3U-4AD-TC
-ADP
M
PID Instruction
(FNC 88)
Time
Sampling time (TS)
Alarm flag
ON
S3 +24
bit0
ON
S3 +24
bit1
Variation
Output (MV)
Variation
Time
Sampling time (TS)
Alarm flag
ON
S3 +24
bit2
ON
S3 +24
bit3
M-17
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 4 Auto-Tuning
PID Instruction (FNC 88) 4.1 Limit Cycle Method
4. Auto-Tuning
This chapter describes the auto-tuning function of PID instruction.
The auto-tuning function will automatically set the important constants, such as the proportional gain and the
integral time, to ensure optimum PID control.
There are two auto-tuning methods: limit cycle method and step response method.
M-18
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 4 Auto-Tuning
PID Instruction (FNC 88) 4.1 Limit Cycle Method
FX3U-4AD-PNK
1 Set the forward or backward operation
-ADP
Set the operation direction flag (bit 0) in the operation setting parameter (ACT) S3 +1.
L
2 Select the auto-tuning method (limit cycle method)
FX3U-4AD-TC
Set the auto-tuning method to ON (bit 6) in the operation setting parameter (ACT) S3 +1.
(When bit 6 is set to OFF, the step response method is selected.)
-ADP
3 Set the auto-tuning execution flag to ON M
PID Instruction
Set the auto-tuning execution flag to ON (bit 4) in the operation setting parameter (ACT) S3 +1.
(FNC 88)
Set the input filter
Set the input filter in the operation setting parameter (ACT) S3 +2.
M-19
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 4 Auto-Tuning
PID Instruction (FNC 88) 4.1 Limit Cycle Method
4.1.3 Reference: How to obtain three constants in PID control (limit cycle method)
For acquiring satisfactory control results in PID control, it is necessary to obtain the optimal value of each
constant (parameter) suitable to the control target.
This paragraph explains the limit cycle method to obtain the amplitude (a) and vibration cycle (τ, τon) of the
input value, and then calculate the proportional gain (KP), integral time (TI) and differential time (TD) based on
the expressions shown in the table below.
Output value
ULV
(Output upper
limit value)
LLV τon
50 × τ on 1 -
(Output lower τ
limit value)
Time
Input value
SV+SHPV
SV(target value) a
SV-SHPV
τ
τ on τw
τ0 τ1 τ2 Time(s)
M-20
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 4 Auto-Tuning
PID Instruction (FNC 88) 4.2 Step Response Method
FX3U-4AD-PNK
4.2.1 Parameters to be set by auto-tuning (step response method)
-ADP
Parameter
Operation setting (ACT)
Setting position Parameter
Integral time (TI)
Setting position
L
S3 +1, bit 0 (operation direction) S3 +4
FX3U-4AD-TC
Proportional gain (KP) S3 +3 Differential time (TD) S3 +6
-ADP
4.2.2 Auto-tuning procedure
M
1 Transferring the output value for auto-tuning to the output value D
PID Instruction
Set the output value for auto-tuning to the maximum available output value multiplied by 0.5 to 1 for
(FNC 88)
the output equipment.
2 Setting the parameter S3 , target value (SV), etc. that cannot be set in auto-
tuning according to the system
Note that auto-tuning may not be executed normally if the cautions described below are not fol-
lowed
1. Set items
Set item and parameter Remarks
The difference from the measured value (PV) should be 150 or more.
Target value (SV) S1
(For the details, refer to "2. Cautions on setting" below.)
Sampling time (TS) S3 1,000 ms or more (For the details, refer to "2. Cautions on setting" below.)
Input filter (α) S3 +2
Differential gain (KD) S3 +5 When setting the input filter, set the differential gain to "0" usually.
Others Set other items, as necessary.
2. Cautions on setting
1) Difference between the target value (SV) and the measured value (PV)
If the difference between the target value (SV) and the measured value (PV) is less than 150 when auto-
tuning is started, auto-tuning is not executed normally.
Accordingly, if the difference is less than 150, set the target value for auto-tuning.
Set the target value again when auto-tuning is completed.
Set item Setting in PID instruction
Make sure that the difference from the measured value is 150 or
Target value (SV) S1
more when auto-tuning is started.
1. Important point
Start auto-tuning while the system is stable.
If the system is unstable when auto-tuning is started, auto-tuning may not be executed normally.
M-21
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 4 Auto-Tuning
PID Instruction (FNC 88) 4.3 Cautions on Auto-Tuning Execution
4.2.3 Reference: How to obtain three constants in PID control (step response method)
For acquiring satisfactory control results during PID control, it is necessary to obtain the optimal value of each
constant (parameter) suitable for the control target.
This paragraph explains the step response method to obtain three constants in the PID control (proportional
gain (KP), integral time (TI) and differential time (TD)).
Operation characteristics
100%
Output value Output value (MV)
0%
Time
Input value
variation Maximum ramp (R)
Time (s)
Dead time (L) 1 (s)
[s]
1. Countermeasures with in the program when the input value (PV) does not change
When the input value (PV) does not change normally due to factors such as wire breakage in an analog input
line, auto-tuning is not finished.
Detect and avoid such occurrences by introducing a sequence to monitor the input value or the elapsed time
from the start of auto-tuning.
M-22
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 5 Example of Practical Programs (for Step Response Method)
PID Instruction (FNC 88) 5.1 Example: System and operation
FX3U-4AD-PNK
5. Example of Practical Programs (for Step Response Method)
-ADP
The following is an example of a program for the operation application system shown below. L
FX3U-4AD-TC
5.1 Example: System and operation
System configuration
-ADP
Temperature sensor Shielded compensating
(Thermocouple) conductor
M
PID Instruction
X10 X11
ch2
FX3U-32MR/ FX2N-16EYT-
(FNC 88)
FX2N-4AD-
ES ESS/UL*1
TC
COM Y20 Y21
Temperature
Error indication
chamber
Setting contents
During auto- During PID
Item
tuning control
Target value S1 500 (+50°C) 500 (+50°C)
2000
Output value upper limit S3 +22 2000
(2 seconds)
Output value lower limit S3 +23 0 0
OFF ON ON ON ON ON
1.8 sec (1800 ms) 1.8 sec (1800 ms) 1.8 sec (1800 ms)
M-23
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 5 Example of Practical Programs (for Step Response Method)
PID Instruction (FNC 88) 5.2 Program example of auto-tuning (step response method) and PID control
5.2 Program example of auto-tuning (step response method) and PID control
Initial pulse
M8002
FNC 12 K500 D500 The target value is set (to 50°C).
MOV
Initial pulse
M8002 The mode of FX2N-4AD-TC is set.
FNC 79 K0 K0 H3303 K1 Ch 1: Unused Ch 3: Unused
TO Ch 2: K type Ch 4: Unused
RUN monitor
M8000
FNC 78 K0 K 10 D501 K1 Data is read from the channel 2 in
FROM FX2N-4AD-TC.
Initial pulse
M8002
RST D502 The PID operation is initialized.
PID control is
started after PID control is started
auto-tuning (without auto-tuning)
X010 X011
M-24
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 5 Example of Practical Programs (for Step Response Method)
PID Instruction (FNC 88) 5.2 Program example of auto-tuning (step response method) and PID control
FX3U-4AD-PNK
Auto-tuning ON flag
M1
-ADP
FNC 12 Auto-tuning operation is
D511 K2M10 confirmed.
MOV
Auto-tuning ON flag L
M14
FX3U-4AD-TC
PLF M2 Auto-tuning is finished.
Auto-tuning is finished
-ADP
M2
RST M1 The normal operation is started.
M
PID operation is executed.
PID Instruction
M3
T246 Heater operation cycle
(FNC 88)
K2000
Heater operation cycle
T246
[ RST T246 ] Preset
PID operation
is executed.
M3
Error flag
M8067
Y020 Error occurs.
END
M-25
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 5 Example of Practical Programs (for Step Response Method)
PID Instruction (FNC 88) 5.3 Program example of auto-tuning (step response method)
Auto-tuning is started.
X010
FNC 12 K500 D500 The target value is set (to 50°C).
MOVP
Auto-tuning is started.
M0
SET M1 PID instruction operation
Initial pulse
M8002 The mode of FX2N-4AD-TC is set.
FNC 79 K0 K0 H3303 K1 Ch 1: Unused Ch 3: Unused
TO Ch 2: K type Ch 4: Unused
RUN monitor
M8000
FNC 78 K0 K 10 D501 K1 Data is read from the channel 2
FROM in FX2N-4AD-TC.
Auto-tuning is started.
X010
RST D502 The PID output is initialized.
PID
operation
M1
PID
operation
M1
FNC 88 D500 D501 D510 D502 PID instruction
PID
Auto-tuning is finished.
M2
RST M1 Auto-tuning is completed.
M-26
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 5 Example of Practical Programs (for Step Response Method)
PID Instruction (FNC 88) 5.3 Program example of auto-tuning (step response method)
FX3U-4AD-PNK
PID operation
M1
-ADP
Heater operation cycle timer
T246 (2 sec)
K2000
L
T246
FX3U-4AD-TC
The heater operation cycle timer
RST T246 is preset.
PID
operation
M1
-ADP
PID operation
M1
M
FNC226
PID Instruction
T246 D502 Y021 Heater output
LD <
(FNC 88)
Error flag
M8067
Y020 Error occurs.
END
M-27
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 6 Troubleshooting
PID Instruction (FNC 88) 6.1 Error Codes
6. Troubleshooting
Error
Error description Action
code
6730 Incorrect sampling time (TS) (TS ≤ 0)
Incorrect input filter constant (α)
6732
(α < 0 or 100 ≤ α)
<PID operation is stopped.>
6733 Incorrect proportional gain (KP) (KP < 0) A data error has occurred in the set value in a control parameter
6734 Incorrect integral time (TI) (TI < 0) or in the middle of PID operation.
Check the parameters.
Incorrect derivative gain (KD)
6735
(KD < 0 or 201 ≤ KD)
6736 Incorrect derivative time (TD) (TD < 0)
<Auto-tuning is continued.>
6740 Sampling time (TS) ≤ Operation cycle The operation is continued in the condition "sampling time (TS)
= cyclic time (operation cycle)."
Variation of measured value exceeds limit.
6742
(UPV < −32768 or +32767 < UPV)
Deviation exceeds limit.
6743
(EV < −32768 or +32767 < EV)
Integral result exceeds limit.
6744 <PID operation is continued.>
(Out of range from −32768 to +32767)
The operation is continued with each parameter set to the
Derivative value exceeds limit due to derivative gain maximum or minimum value.
6745
(KD).
Derivative result exceeds limit.
6746
(Out of range from −32768 to +32767)
PID operation result exceeds limit.
6747
(Out of range from −32768 to +32767)
<Output upper limit value and output lower limit value are
PID output upper limit set value < PID output lower limit
6748 exchanged for each other. → PID operation is continued.>
set value
Check whether the target settings are correct.
Abnormal PID input variation alarm set value or output <Alarm output is not given. → PID operation is continued.>
6749
variation alarm set value (Set value < 0) Check whether the target settings are correct.
<Auto-tuning is finished. → PID operation is started.>
• The deviation at start of auto-tuning is 150 or less.
<Step response method> • The deviation at end of auto-tuning is 1/3 or more of the
6750
Improper auto-tuning result deviation at start of auto-tuning.
Confirm the measured value and target value, and then execute
auto-tuning again.
<Auto-tuning is forced to finish. → PID operation does not
started.>
The operation direction estimated from the measured value at
<Step response method> the start of auto-tuning was different from the actual operation
6751
Auto-tuning operation direction mismatch direction of the output during auto-tuning.
Correct the relationship among the target value, output value
for auto-tuning and measured value, and then execute auto-
tuning again.
M-28
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 6 Troubleshooting
PID Instruction (FNC 88) 6.1 Error Codes
Error
K
Error description Action
FX3U-4AD-PNK
code
<Auto-tuning is finished. → PID operation is not started.>
Because the set value fluctuated during auto-tuning, auto-
-ADP
<Step response method> tuning was not executed correctly.
6752
Improper auto-tuning operation Set the sampling time to a value larger than the output change
cycle, or set a larger value to the input filter constant.
After changing the setting, execute auto-tuning again.
L
FX3U-4AD-TC
<Limit cycle method>
6753 Abnormal output set value for auto-tuning
[ULV (upper limit) ≤ LLV (lower limit)] <Auto-tuning is forcibly finished. → PID operation is not
-ADP
started.>
<Limit cycle method> Check whether the target settings are correct.
6754 Abnormal PV threshold (hysteresis) set value for auto-
tuning (SHPV < 0) M
PID Instruction
<Limit cycle method> <Auto-tuning is forcibly finished. → PID operation is not
Abnormal auto-tuning transfer status started.>
6755
(FNC 88)
(Data of device controlling transfer status is abnormally Verify that devices occupied by PID instruction are not
overwritten.) overwritten in the program.
<Auto-tuning is forcibly finished. → PID operation is not
started.>
The auto-tuning time is too long.
<Limit cycle method>
Increase the difference (ULV - LLV) between the upper limit and
6756 Abnormal result due to excessive auto-tuning
the lower limit of the output value for auto-tuning, set a smaller
measurement time (τon > τ, τon < 0, τ < 0)
value to the input filter constant (α), or set a smaller value to the
PV threshold (SHPV) for auto-tuning, and then check whether
the result is improved.
<Auto-tuning is finished (KP = 32767). → PID operation is
started.>
<Limit cycle method>
The variation of the measured value (PV) is small compared
6757 Auto-tuning result exceeds proportional gain. (KP = Out
with the output value. Multiply the measured value (PV) by "10"
of range from 0 to 32767)
so that the variation of the measured value will increase during
auto-tuning.
<Limit cycle method> <Auto-tuning is finished (KP = 32767). → PID operation is
6758 Auto-tuning result exceeds integral time. started.>
(TI = Out of range from 0 to 32767) The auto-tuning time is too long.
Increase the difference (ULV - LLV) between the upper limit and
<Limit cycle method> the lower limit of the output value for auto-tuning, set a smaller
6759 Auto-tuning result exceeds derivative time. value to the input filter constant (α), or set a smaller value to the
(TD = Out of range from 0 to 32767) PV threshold (SHPV) for auto-tuning, and then check whether
the result is improved.
Caution
With regard to the measured value (PV) in PID, normal measurement data should be read before PID
operation begins.
Especially when the PID operation is executed to the input value in an analog input block, pay attention to the
conversion time.
M-29
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition 6 Troubleshooting
PID Instruction (FNC 88) 6.1 Error Codes
MEMO
M-30
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition Warranty
Warranty
Please confirm the following product warranty details before using this product.
1. Gratis Warranty Term and Gratis Warranty Range 2. Onerous repair term after discontinuation of
If any faults or defects (hereinafter "Failure") found to be production
the responsibility of Mitsubishi occurs during use of the 1) Mitsubishi shall accept onerous product repairs for
product within the gratis warranty term, the product shall be seven (7) years after production of the product is
repaired at no cost via the sales representative or discontinued.
Mitsubishi Service Company. However, if repairs are Discontinuation of production shall be notified with
required onsite at domestic or overseas location, expenses Mitsubishi Technical Bulletins, etc.
to send an engineer will be solely at the customer's
discretion. Mitsubishi shall not be held responsible for any 2) Product supply (including repair parts) is not available
re-commissioning, maintenance, or testing on-site that after production is discontinued.
involves replacement of the failed module. 3. Overseas service
Overseas, repairs shall be accepted by Mitsubishi's local
[Gratis Warranty Term]
overseas FA Center. Note that the repair conditions at
The gratis warranty term of the product shall be for one
each FA Center may differ.
year after the date of purchase or delivery to a designated
place. Note that after manufacture and shipment from 4. Exclusion of loss in opportunity and secondary
Mitsubishi, the maximum distribution period shall be six (6) loss from warranty liability
months, and the longest gratis warranty term after Regardless of the gratis warranty term, Mitsubishi shall not
manufacturing shall be eighteen (18) months. The gratis be liable for compensation of damages caused by any
warranty term of repair parts shall not exceed the gratis cause found not to be the responsibility of Mitsubishi, loss
warranty term before repairs. in opportunity, lost profits incurred to the user or third
person by Failures of Mitsubishi products, special
[Gratis Warranty Range]
damages and secondary damages whether foreseeable or
1) The range shall be limited to normal use within the not , compensation for accidents, and compensation for
usage state, usage methods and usage environment, damages to products other than Mitsubishi products,
etc., which follow the conditions and precautions, etc., replacement by the user, maintenance of on-site
given in the instruction manual, user's manual and equipment, start-up test run and other tasks.
caution labels on the product.
5. Changes in product specifications
2) Even within the gratis warranty term, repairs shall be
The specifications given in the catalogs, manuals or
charged for in the following cases.
technical documents are subject to change without prior
a) Failure occurring from inappropriate storage or
notice.
handling, carelessness or negligence by the user.
Failure caused by the user's hardware or software 6. Product application
design. 1) In using the Mitsubishi MELSEC programmable logic
b) Failure caused by unapproved modifications, etc., controller, the usage conditions shall be that the
to the product by the user. application will not lead to a major accident even if any
c) When the Mitsubishi product is assembled into a problem or fault should occur in the programmable
user's device, Failure that could have been logic controller device, and that backup and fail-safe
avoided if functions or structures, judged as functions are systematically provided outside of the
necessary in the legal safety measures the user's device for any problem or fault.
device is subject to or as necessary by industry
2) The Mitsubishi programmable logic controller has
standards, had been provided.
been designed and manufactured for applications in
d) Failure that could have been avoided if
general industries, etc. Thus, applications in which the
consumable parts (battery, backlight, fuse, etc.)
public could be affected such as in nuclear power
designated in the instruction manual had been
plants and other power plants operated by respective
correctly serviced or replaced.
power companies, and applications in which a special
e) Relay failure or output contact failure caused by
quality assurance system is required, such as for
usage beyond the specified Life of contact
Railway companies or Public service purposes shall
(cycles).
be excluded from the programmable logic controller
f) Failure caused by external irresistible forces such
applications.
as fires or abnormal voltages, and failure caused
In addition, applications in which human life or
by force majeure such as earthquakes, lightning,
property that could be greatly affected, such as in
wind and water damage.
aircraft, medical applications, incineration and fuel
g) Failure caused by reasons unpredictable by
devices, manned transportation, equipment for
scientific technology standards at time of
recreation and amusement, and safety devices, shall
shipment from Mitsubishi.
also be excluded from the programmable logic
h) Any other failure found not to be the responsibility
controller range of applications.
of Mitsubishi or that admitted not to be so by the
However, in certain cases, some applications may be
user.
possible, providing the user consults their local
Mitsubishi representative outlining the special
requirements of the project, and providing that all
parties concerned agree to the special circumstances,
solely at the users discretion.
i
FX3G/FX3U/FX3UC PLC User's Manual - Analog Control Edition Revised History
Revised History
Date Revision Description
7/2005 A First Edition
2/2006 B • FX3U-4AD is added to B.
• FX3U-4DA is inserted to D.
• Adding and revising the other descriptions.
3/2006 C • B-8 page, 2.2 The Power Supply Specification for the FX3U-4AD, regarding the
A/D conversion circuit drive power:
Revised from [24V DC ±10%, 80mA] to [24VDC ±10%, 90mA]
3/2007 D • JIS (Japanese Industrial Standards) for temperature sensors are added
• Clerical Error Correction
12/2007 E • FX3UC (D, DSS) Series PLC added
• FX3U-4AD-PTW-ADP is inserted to G
• Clerical Error Correction
11/2008 F • FX3G Series PLC added
• FX3G-2AD-BD is added to D.
• FX3G-1DA-BD is added to G.
• FX3U-4AD-PNK-ADP is added to H.
• Adding and revising the other descriptions.
6/2009 G • FX3U-3A-ADP is added to H.
• Explanation corrections for manufacture's serial number.
• Adding and revising the other descriptions.
ii
USER'S MANUAL - Analog Control Edition
HEAD OFFICE: TOKYO BUILDING, 2-7-3 MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPAN
HIMEJI WORKS: 840, CHIYODA CHO, HIMEJI, JAPAN
MODEL FX3U-U-ANALOG-E
MODEL CODE 09R619