Generator-Protection-Functions-And-Test-Methods-Part 1
Generator-Protection-Functions-And-Test-Methods-Part 1
PROTECTION
FUNCTIONS AND
TEST METHODS
Created by:
VASUMURUGAN.R
SPD-VEPL.
GENERATOR PROTECTION FUNCTIONS AND TEST
METHODS
AN OVER VIEW OF GENERATOR SINGLE LINE DIAGRAM:
CLASS – A :- This covers all electrical protections for faults within the generating unit in which
generator field breaker, generator breaker and turbine should be tripped.
CLASS – B:- This covers all mechanical protections of the turbine in which turbine will be tripped
first and following this generator will trip on reverse power / low forward power
protections.
CLASS – C:- This covers electrical protection for faults in the system in which generator will be
unloaded by tripping of generator breaker only. The unit will come to house load
operation and the UAT will be in service. Various protections of this class are:
2
PROTECTION FUNTIONS:
Differential
Inter-turn fault
Stator Earth Fault (95% & 100%)
Rotor Earth fault (2 Stage)
Differential protection
Bias test
REF protection
3
FOR INSULATION FAILURES PROTECTIONS:
1. GENERATOR DIFFERENTIAL PROTECTION (87 G): -
It is unit type protection, covering the stator winding for phase to phase faults due to breakdown of
insulation between stator phase windings. This relay is not sensitive for single line to earth faults as the
earth fault current is limited due to the high neutral earthing resistance. If CTs of identical ratios are used
on neutral and line side of generator, an operating current setting of 20% it can be adopted. It is
instantaneous in operation and it trips the generator breaker (Class – A) to eliminate the system in – feed to
the fault along with field breaker and turbines.
For all machines of ratings 10 MVA and above, this protection shall be provided.
Diagram:
Settings:
Pickup Value of Differential Current : 0.10 I/InO
T I-DIFF> Time Delay : 0.00 sec
Pickup Value of High Set Trip : 2.0 I/InO
T I-DIFF>> Time Delay : 0.00 sec
Testing Method: