Se Three Phase Inverter With Setapp Configuration Datasheet
Se Three Phase Inverter With Setapp Configuration Datasheet
12 - 20
YEAR
WARRANTY
Optional RS485 and type 2 AC surge protection Future-proofed for SolarEdge energy storage
solutions
solaredge.com
Three Phase Inverter
For Europe
SE25K / SE30K / SE33.3K
Applicable to inverters with part number SEXXK-RWX0IXXXX
SE25K SE30K SE33.3K
OUTPUT
Rated AC Active Power Output 25000 29990 33300 W
Maximum AC Apparent Output Power 25000 29990 33300 VA
AC Output Voltage - Line to Line / Line to Neutral (Nominal) 380 / 220; 400 / 230 Vac
AC Output Voltage - Line to Line / Line to Neutral 304 - 437 / 176 - 253; 320 - 460 / 184 - 264.5 Vac
AC Frequency 50/60 ± 5% Hz
Maximum Continuous Output Current (per Phase) 36,25 43,5 48,25 Aac
AC Output Line Connections 3W + PE, 4W + PE
Utility Monitoring, Islanding Protection, Configurable Power
Yes
Factor, Country Configurable Thresholds
Total Harmonic Distortion <3 %
Power Factor Range +/-0.2 to 1
Maximum Residual Current Injection(1) 100 mA
INPUT
Maximum DC Power (Module STC) 43750 52500 58275 W
Transformer-less, Ungrounded Yes
Maximum Input Voltage DC+ to DC- 1000 Vdc
Operating Voltage Range 680-1000 Vdc
Maximum Input Current 36,25 43,5 48,25 Adc
Reverse-Polarity Protection Yes
Ground-Fault Isolation Detection 167kΩ Sensitivity(2)
Maximum Inverter Efficiency 98,3 %
European Weighted Efficiency 98 %
Nighttime Power Consumption <4 W
ADDITIONAL FEATURES
Supported Communication Interfaces 2 x RS485, Ethernet, Wi-Fi (optional)(3), Cellular (optional)
Smart Energy Management Export Limitation
Inverter Commissioning With the SetApp mobile application using built-in Wi-Fi access point for local connection
Arc Fault Protection Integrated, User Configurable (According to UL1699B)
Rapid Shutdown Optional(4) (Automatic upon AC Grid Disconnect)
RS485 Surge Protection Optional
DC Surge Protection Type II, field replaceable, integrated
AC Surge Protection Type II, field replaceable, optional
DC SAFETY UNIT (OPTIONAL)
2-pole Disconnection 1000V / 48,25A
DC Fuses (Single Pole) Optional, 25A
Compliance UTE-C15-712-1
STANDARD COMPLIANCE
Safety IEC-62109, AS3100
VDE-AR-N-4105, AS-4777, EN50438, CEI-021, VDE 0126-1-1, CEI-016, EN50549-1, EN50549-2, VDE-
Grid Connection Standards (5)
AR-N-4110, TOR Erzeuger Typ A, G99, G99 (NI), VFR 2019
Emissions IEC61000-6-2, IEC61000-6-3 Class A, IEC61000-3-11, IEC61000-3-12
RoHS Yes
INSTALLATION SPECIFICATIONS
AC Output Gland Diameter / Line cross section / PE cross section Cable diameter 19-28 mm / 4 - 16 mm2 / 4 - 16 mm2
DC Input(6) 4 MC4 pairs
4 MC4 pairs
DC Input with Safety Unit (6)(7) 4 Strings: Gland: Cable outer diameter 5 - 10 mm / Wire cross section 2,5 - 16 mm2
Dimensions (H x W x D) 550 x 317 x 273 mm
Dimensions with Safety Unit (H x W x D) 836 x 317 x 300 (DC MC4); 819 x 317 x 300 (DC Gland) mm
Weight 32 kg
Weight with Safety Unit 36,5 kg
Operating Temperature Range -40 to +60(8) ˚C
Cooling Fan (user replaceable)
Noise < 62 dBA
Protection Rating IP65 - outdoor and indoor
Mounting Brackets provided
© SolarEdge Technologies, Ltd. All rights reserved. SOLAREDGE, the SolarEdge logo, OPTIMIZED BY SOLAREDGE are trademarks or registered trademarks of SolarEdge Technologies, Inc.
All other trademarks mentioned herein are trademarks of their respective owners. Date: August 8, 2022 DS-000053-EU. Subject to change without notice.