Lecture 12
Lecture 12
http://nptel.iitm.ac.in/courses/Webcourse-contents/IIT-KANPUR/power-system/ui/Course_home-1.htm
Capacitance of Single-Phase Line
Capacitance of Single-Phase Line
𝑞
𝐶𝐴𝐵 =
𝑉𝐴𝐵
Phase to Ground Capacitance of Single-
Phase Line
Three Phase Line: VAB due to charge QA
A B C
QA DAB
𝐷𝐴𝐵
𝑄𝐴 𝑄𝐴 𝐷𝐴𝐵
𝑉𝐴𝐵_𝐴 = න 𝑑𝑥 = ln
2𝜋𝜀0 𝑥 2𝜋𝜀0 𝑟𝐴
𝑟𝐴
VAB due to charge QB
A B C
DAB QB
𝑅𝐵
𝑄𝐵 𝑄𝐵 𝑟𝐵
𝑉𝐴𝐵_𝐵 = න 𝑑𝑥 = ln
2𝜋𝜀0 𝑥 2𝜋𝜀0 𝐷𝐴𝐵
𝐷𝐴𝐵
VAB due to charge QC
A B C
DBC
QC
DAC
𝐷𝐵𝐶
𝑄𝐶 𝑄𝐶 𝐷𝐵𝐶
𝑉𝐴𝐵_𝐶 = න 𝑑𝑥 = ln
2𝜋𝜀0 𝑥 2𝜋𝜀0 𝐷𝐴𝐶
𝐷𝐴𝐶
Voltage Difference between conductor A
and B
𝑄𝐴 𝐷𝐴𝐵 𝑄𝐵 𝑟𝐵 𝑄𝐶 𝐷𝐵𝐶
𝑉𝐴𝐵_𝐴 = ln 𝑉𝐴𝐵_𝐵 = ln 𝑉𝐴𝐵_𝐶 = ln
2𝜋𝜀0 𝑟𝐴 2𝜋𝜀0 𝐷𝐴𝐵 2𝜋𝜀0 𝐷𝐴𝐶
Similarly,
𝑄𝐴 𝐷𝐴𝐶 𝑄𝐵 𝐷𝐵𝐶 𝑄𝐶 𝑟𝐶
𝑉𝐴𝐶 = ln + ln + ln
2𝜋𝜀0 𝑟𝐴 2𝜋𝜀0 𝐷𝐴𝐵 2𝜋𝜀0 𝐷𝐴𝐶
Symmetric Spacing
C 𝑄𝐴 𝐷𝐴𝐵 𝑄𝐵 𝑟𝐵 𝑄𝐶 𝐷𝐵𝐶
𝑉𝐴𝐵 = ln + ln + ln
2𝜋𝜀0 𝑟𝐴 2𝜋𝜀0 𝐷𝐴𝐵 2𝜋𝜀0 𝐷𝐴𝐶
𝑄𝐴 𝐷 𝑄𝐵 𝑟 𝑄𝐶 𝐷
= ln + ln + ln
2𝜋𝜀0 𝑟 2𝜋𝜀0 𝐷 2𝜋𝜀0 𝐷
1 𝐷 𝑟
D D = 𝑄𝐴 ln + 𝑄𝐵 ln
2𝜋𝜀0 𝑟 𝐷
D
A B Similarly,
𝑄𝐴 𝐷𝐴𝐶 𝑄𝐵 𝐷𝐵𝐶 𝑄𝐶 𝑟𝐶
𝑉𝐴𝐶 = ln + ln + ln
2𝜋𝜀0 𝑟𝐴 2𝜋𝜀0 𝐷𝐴𝐵 2𝜋𝜀0 𝐷𝐴𝐶
𝑄𝐴 𝐷 𝑄𝐵 𝐷 𝑄𝐶 𝑟
= ln + ln + ln
2𝜋𝜀0 𝑟 2𝜋𝜀0 𝐷 2𝜋𝜀0 𝐷
1 𝐷 𝑟
= 𝑄𝐴 ln + 𝑄𝐶 ln
2𝜋𝜀0 𝑟 𝐷
Attendance
Phase Voltage
1 𝐷 𝑟 1 𝐷 𝑟
𝑉𝐴𝐵 = 𝑞𝐴 ln + 𝑞𝐵 ln 𝑉𝐴𝐶 = 𝑞𝐴 ln + 𝑞𝐶 ln
2𝜋𝜀0 𝑟 𝐷 2𝜋𝜀0 𝑟 𝐷
Capacitance of Symmetric Three-Phase
Line
1 𝐷 𝐷
= 2𝑞𝐴 ln + 𝑞𝐴 ln
6𝜋𝜀0 𝑟 𝑟
Three-Phase Asymmetric Transmission
Line
->a ->a
->b ->b
->c ->c
1 𝐷𝐴𝐵 𝑟 𝐷𝐵𝐶
𝑉𝐴𝐵𝐹𝑖𝑟𝑠𝑡 = 𝑞𝐴 ln + 𝑞𝐵 ln + 𝑞𝐶 ln
2𝜋𝜀0 𝑟 𝐷𝐴𝐵 𝐷𝐴𝐶
1 𝐷𝐵𝐶 𝑟 𝐷𝐶𝐴
𝑉𝐴𝐵𝑆𝑒𝑐𝑜𝑛𝑑 = 𝑞𝐴 ln + 𝑞𝐵 ln + 𝑞𝐶 ln
2𝜋𝜀0 𝑟 𝐷𝐵𝐶 𝐷𝐵𝐴
1 𝐷𝐶𝐴 𝑟 𝐷𝐴𝐵
𝑉𝐴𝐵𝑇ℎ𝑖𝑟𝑑 = 𝑞𝐴 ln + 𝑞𝐵 ln + 𝑞𝐶 ln
2𝜋𝜀0 𝑟 𝐷𝐶𝐴 𝐷𝐶𝐵
Three-Phase Asymmetric Transmission
Line
->a ->a
->b ->b
->c ->c
𝑄𝐴 𝐷𝐴𝐶 𝑄𝐵 𝐷𝐵𝐶 𝑄𝐶 𝑟𝐶
𝑉𝐴𝐶𝑓𝑖𝑟𝑠𝑡 = ln + ln + ln
2𝜋𝜀0 𝑟𝐴 2𝜋𝜀0 𝐷𝐴𝐵 2𝜋𝜀0 𝐷𝐴𝐶
𝑄𝐴 𝐷𝐵𝐴 𝑄𝐵 𝐷𝐶𝐴 𝑄𝐶 𝑟𝐶
𝑉𝐴𝐶𝑠𝑒𝑐𝑜𝑛𝑑 = ln + ln + ln
2𝜋𝜀0 𝑟𝐴 2𝜋𝜀0 𝐷𝐵𝐶 2𝜋𝜀0 𝐷𝐵𝐴
𝑄𝐴 𝐷𝐶𝐵 𝑄𝐵 𝐷𝐴𝐵 𝑄𝐶 𝑟𝐶
𝑉𝐴𝐶𝑡ℎ𝑖𝑟𝑑 = ln + ln + ln
2𝜋𝜀0 𝑟𝐴 2𝜋𝜀0 𝐷𝐶𝐴 2𝜋𝜀0 𝐷𝐶𝐵
Three-Phase Asymmetric Transmission
Line
1 𝐷𝐴𝐵 𝑟 𝐷𝐴𝐵
𝑉𝐴𝐵𝐹𝑖𝑟𝑠𝑡 = 𝑞𝐴 ln + 𝑞𝐵 ln + 𝑞𝐶 ln
2𝜋𝜀0 𝑟 𝐷𝐴𝐵 𝐷𝐴𝐶
1 𝐷𝐵𝐶 𝑟 𝐷𝐵𝐶
𝑉𝐴𝐵𝑆𝑒𝑐𝑜𝑛𝑑 = 𝑞𝐴 ln + 𝑞𝐵 ln + 𝑞𝐶 ln
2𝜋𝜀0 𝑟 𝐷𝐵𝐶 𝐷𝐴𝐵
1 𝐷𝐴𝐶 𝑟 𝐷𝐴𝐶
𝑉𝐴𝐵𝑇ℎ𝑖𝑟𝑑 = 𝑞𝐴 ln + 𝑞𝐵 ln + 𝑞𝐶 ln
2𝜋𝜀0 𝑟 𝐷𝐴𝐶 𝐷𝐵𝐶
𝑉𝐴𝑁𝑇𝑟𝑎𝑛𝑠𝑝
1 𝐷𝐴𝐵 𝐷𝐴𝐶 𝐷𝐵𝐶 𝑟3
= 2𝑞𝐴 ln − 𝑞𝐴 ln
18𝜋𝜀0 𝑟3 𝐷𝐴𝐵 𝐷𝐴𝐶 𝐷𝐵𝐶
𝑉𝐴𝑁𝑇𝑟𝑎𝑛𝑠𝑝
1 𝐷𝐴𝐵 𝐷𝐴𝐶 𝐷𝐵𝐶 𝐷𝐴𝐵 𝐷𝐴𝐶 𝐷𝐵𝐶
= 2𝑞𝐴 ln + 𝑞𝐴 ln
18𝜋𝜀0 𝑟3 𝑟3
1/3
1 𝐷𝐴𝐵 𝐷𝐴𝐶 𝐷𝐵𝐶
= 𝑞 ln
2𝜋𝜀0 𝐴 𝑟3
Capacitance of Three-Phase Asymmetric
Transmission Line
Effect of Earth on Capacitance
Without ground