0% found this document useful (0 votes)
5 views

Lecture 12

The document discusses the capacitance of single-phase and three-phase transmission lines, including symmetric and asymmetric configurations. It defines the capacitance between conductors using integrals and derives expressions for voltage differences and phase voltages in terms of the line parameters and conductor charges.

Uploaded by

anshul240903
Copyright
© © All Rights Reserved
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
5 views

Lecture 12

The document discusses the capacitance of single-phase and three-phase transmission lines, including symmetric and asymmetric configurations. It defines the capacitance between conductors using integrals and derives expressions for voltage differences and phase voltages in terms of the line parameters and conductor charges.

Uploaded by

anshul240903
Copyright
© © All Rights Reserved
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 22

EEN-206

Power Transmission and Distribution


Lecture 12: Line parameters
Dr. Deep Kiran
Capacitance of the Line
Capacitance of a Straight Conductor

http://nptel.iitm.ac.in/courses/Webcourse-contents/IIT-KANPUR/power-system/ui/Course_home-1.htm
Capacitance of Single-Phase Line
Capacitance of Single-Phase Line

𝑞
𝐶𝐴𝐵 =
𝑉𝐴𝐵
Phase to Ground Capacitance of Single-
Phase Line
Three Phase Line: VAB due to charge QA

A B C

QA DAB

𝐷𝐴𝐵
𝑄𝐴 𝑄𝐴 𝐷𝐴𝐵
𝑉𝐴𝐵_𝐴 = න 𝑑𝑥 = ln
2𝜋𝜀0 𝑥 2𝜋𝜀0 𝑟𝐴
𝑟𝐴
VAB due to charge QB

A B C
DAB QB

𝑅𝐵
𝑄𝐵 𝑄𝐵 𝑟𝐵
𝑉𝐴𝐵_𝐵 = න 𝑑𝑥 = ln
2𝜋𝜀0 𝑥 2𝜋𝜀0 𝐷𝐴𝐵
𝐷𝐴𝐵
VAB due to charge QC

A B C
DBC
QC

DAC

𝐷𝐵𝐶
𝑄𝐶 𝑄𝐶 𝐷𝐵𝐶
𝑉𝐴𝐵_𝐶 = න 𝑑𝑥 = ln
2𝜋𝜀0 𝑥 2𝜋𝜀0 𝐷𝐴𝐶
𝐷𝐴𝐶
Voltage Difference between conductor A
and B
𝑄𝐴 𝐷𝐴𝐵 𝑄𝐵 𝑟𝐵 𝑄𝐶 𝐷𝐵𝐶
𝑉𝐴𝐵_𝐴 = ln 𝑉𝐴𝐵_𝐵 = ln 𝑉𝐴𝐵_𝐶 = ln
2𝜋𝜀0 𝑟𝐴 2𝜋𝜀0 𝐷𝐴𝐵 2𝜋𝜀0 𝐷𝐴𝐶

Using the principle of superposition


𝑉𝐴𝐵 = 𝑉𝐴𝐵_𝐴 + 𝑉𝐴𝐵_𝐵 + 𝑉𝐴𝐵_𝐶
𝑄𝐴 𝐷𝐴𝐵 𝑄𝐵 𝑟𝐵 𝑄𝐶 𝐷𝐵𝐶
= ln + ln + ln
2𝜋𝜀0 𝑟𝐴 2𝜋𝜀0 𝐷𝐴𝐵 2𝜋𝜀0 𝐷𝐴𝐶

Similarly,
𝑄𝐴 𝐷𝐴𝐶 𝑄𝐵 𝐷𝐵𝐶 𝑄𝐶 𝑟𝐶
𝑉𝐴𝐶 = ln + ln + ln
2𝜋𝜀0 𝑟𝐴 2𝜋𝜀0 𝐷𝐴𝐵 2𝜋𝜀0 𝐷𝐴𝐶
Symmetric Spacing
C 𝑄𝐴 𝐷𝐴𝐵 𝑄𝐵 𝑟𝐵 𝑄𝐶 𝐷𝐵𝐶
𝑉𝐴𝐵 = ln + ln + ln
2𝜋𝜀0 𝑟𝐴 2𝜋𝜀0 𝐷𝐴𝐵 2𝜋𝜀0 𝐷𝐴𝐶
𝑄𝐴 𝐷 𝑄𝐵 𝑟 𝑄𝐶 𝐷
= ln + ln + ln
2𝜋𝜀0 𝑟 2𝜋𝜀0 𝐷 2𝜋𝜀0 𝐷
1 𝐷 𝑟
D D = 𝑄𝐴 ln + 𝑄𝐵 ln
2𝜋𝜀0 𝑟 𝐷
D

A B Similarly,
𝑄𝐴 𝐷𝐴𝐶 𝑄𝐵 𝐷𝐵𝐶 𝑄𝐶 𝑟𝐶
𝑉𝐴𝐶 = ln + ln + ln
2𝜋𝜀0 𝑟𝐴 2𝜋𝜀0 𝐷𝐴𝐵 2𝜋𝜀0 𝐷𝐴𝐶
𝑄𝐴 𝐷 𝑄𝐵 𝐷 𝑄𝐶 𝑟
= ln + ln + ln
2𝜋𝜀0 𝑟 2𝜋𝜀0 𝐷 2𝜋𝜀0 𝐷
1 𝐷 𝑟
= 𝑄𝐴 ln + 𝑄𝐶 ln
2𝜋𝜀0 𝑟 𝐷
Attendance
Phase Voltage
1 𝐷 𝑟 1 𝐷 𝑟
𝑉𝐴𝐵 = 𝑞𝐴 ln + 𝑞𝐵 ln 𝑉𝐴𝐶 = 𝑞𝐴 ln + 𝑞𝐶 ln
2𝜋𝜀0 𝑟 𝐷 2𝜋𝜀0 𝑟 𝐷
Capacitance of Symmetric Three-Phase
Line

1 𝐷 𝐷
= 2𝑞𝐴 ln + 𝑞𝐴 ln
6𝜋𝜀0 𝑟 𝑟
Three-Phase Asymmetric Transmission
Line
->a ->a
->b ->b
->c ->c

First Second Third

1 𝐷𝐴𝐵 𝑟 𝐷𝐵𝐶
𝑉𝐴𝐵𝐹𝑖𝑟𝑠𝑡 = 𝑞𝐴 ln + 𝑞𝐵 ln + 𝑞𝐶 ln
2𝜋𝜀0 𝑟 𝐷𝐴𝐵 𝐷𝐴𝐶

1 𝐷𝐵𝐶 𝑟 𝐷𝐶𝐴
𝑉𝐴𝐵𝑆𝑒𝑐𝑜𝑛𝑑 = 𝑞𝐴 ln + 𝑞𝐵 ln + 𝑞𝐶 ln
2𝜋𝜀0 𝑟 𝐷𝐵𝐶 𝐷𝐵𝐴

1 𝐷𝐶𝐴 𝑟 𝐷𝐴𝐵
𝑉𝐴𝐵𝑇ℎ𝑖𝑟𝑑 = 𝑞𝐴 ln + 𝑞𝐵 ln + 𝑞𝐶 ln
2𝜋𝜀0 𝑟 𝐷𝐶𝐴 𝐷𝐶𝐵
Three-Phase Asymmetric Transmission
Line
->a ->a
->b ->b
->c ->c

First Second Third

𝑄𝐴 𝐷𝐴𝐶 𝑄𝐵 𝐷𝐵𝐶 𝑄𝐶 𝑟𝐶
𝑉𝐴𝐶𝑓𝑖𝑟𝑠𝑡 = ln + ln + ln
2𝜋𝜀0 𝑟𝐴 2𝜋𝜀0 𝐷𝐴𝐵 2𝜋𝜀0 𝐷𝐴𝐶

𝑄𝐴 𝐷𝐵𝐴 𝑄𝐵 𝐷𝐶𝐴 𝑄𝐶 𝑟𝐶
𝑉𝐴𝐶𝑠𝑒𝑐𝑜𝑛𝑑 = ln + ln + ln
2𝜋𝜀0 𝑟𝐴 2𝜋𝜀0 𝐷𝐵𝐶 2𝜋𝜀0 𝐷𝐵𝐴

𝑄𝐴 𝐷𝐶𝐵 𝑄𝐵 𝐷𝐴𝐵 𝑄𝐶 𝑟𝐶
𝑉𝐴𝐶𝑡ℎ𝑖𝑟𝑑 = ln + ln + ln
2𝜋𝜀0 𝑟𝐴 2𝜋𝜀0 𝐷𝐶𝐴 2𝜋𝜀0 𝐷𝐶𝐵
Three-Phase Asymmetric Transmission
Line
1 𝐷𝐴𝐵 𝑟 𝐷𝐴𝐵
𝑉𝐴𝐵𝐹𝑖𝑟𝑠𝑡 = 𝑞𝐴 ln + 𝑞𝐵 ln + 𝑞𝐶 ln
2𝜋𝜀0 𝑟 𝐷𝐴𝐵 𝐷𝐴𝐶

1 𝐷𝐵𝐶 𝑟 𝐷𝐵𝐶
𝑉𝐴𝐵𝑆𝑒𝑐𝑜𝑛𝑑 = 𝑞𝐴 ln + 𝑞𝐵 ln + 𝑞𝐶 ln
2𝜋𝜀0 𝑟 𝐷𝐵𝐶 𝐷𝐴𝐵

1 𝐷𝐴𝐶 𝑟 𝐷𝐴𝐶
𝑉𝐴𝐵𝑇ℎ𝑖𝑟𝑑 = 𝑞𝐴 ln + 𝑞𝐵 ln + 𝑞𝐶 ln
2𝜋𝜀0 𝑟 𝐷𝐴𝐶 𝐷𝐵𝐶

𝑉𝐴𝐵𝐹𝑖𝑟𝑠𝑡 + 𝑉𝐴𝐵𝑆𝑒𝑐𝑜𝑛𝑑 + 𝑉𝐴𝐵𝑇ℎ𝑖𝑟𝑑


𝑉𝐴𝐵𝑇𝑟𝑎𝑛𝑠𝑝 =
3
1 𝐷𝐴𝐵 𝐷𝐴𝐶 𝐷𝐵𝐶 𝑟3 𝐷𝐴𝐵 𝐷𝐴𝐶 𝐷𝐵𝐶
= 𝑞𝐴 ln + 𝑞𝐵 ln + 𝑞𝐶 ln
6𝜋𝜀0 𝑟3 𝐷𝐴𝐵 𝐷𝐴𝐶 𝐷𝐵𝐶 𝐷𝐴𝐵 𝐷𝐴𝐶 𝐷𝐵𝐶

𝑉𝐴𝐶𝐹𝑖𝑟𝑠𝑡 + 𝑉𝐴𝐶𝑆𝑒𝑐𝑜𝑛𝑑 + 𝑉𝐴𝐶𝑇ℎ𝑖𝑟𝑑


𝑉𝐴𝐶𝑇𝑟𝑎𝑛𝑠𝑝 =
3
1 𝐷𝐴𝐵 𝐷𝐴𝐶 𝐷𝐵𝐶 𝐷𝐴𝐵 𝐷𝐴𝐶 𝐷𝐵𝐶 𝑟3
= 𝑞𝐴 ln + 𝑞𝐵 ln + 𝑞𝐶 ln
6𝜋𝜀0 𝑟3 𝐷𝐴𝐵 𝐷𝐴𝐶 𝐷𝐵𝐶 𝐷𝐴𝐵 𝐷𝐴𝐶 𝐷𝐵𝐶
Capacitance of Three-Phase Asymmetric
Transmission Line
𝑉𝐴𝐵𝐹𝑖𝑟𝑠𝑡 + 𝑉𝐴𝐵𝑆𝑒𝑐𝑜𝑛𝑑 + 𝑉𝐴𝐵𝑇ℎ𝑖𝑟𝑑
𝑉𝐴𝐵𝑇𝑟𝑎𝑛𝑠𝑝 =
3
1 𝐷𝐴𝐵 𝐷𝐴𝐶 𝐷𝐵𝐶 𝑟3
= 𝑞 ln + 𝑞𝐵 ln
6𝜋𝜀0 𝐴 𝑟3 𝐷𝐴𝐵 𝐷𝐴𝐶 𝐷𝐵𝐶
𝑉𝐴𝐶𝐹𝑖𝑟𝑠𝑡 + 𝑉𝐴𝐶𝑆𝑒𝑐𝑜𝑛𝑑 + 𝑉𝐴𝐶𝑇ℎ𝑖𝑟𝑑
𝑉𝐴𝐶𝑇𝑟𝑎𝑛𝑠𝑝 =
3
1 𝐷𝐴𝐵 𝐷𝐴𝐶 𝐷𝐵𝐶 𝑟3
= 𝑞 ln + 𝑞𝐶 ln
6𝜋𝜀0 𝐴 𝑟3 𝐷𝐴𝐵 𝐷𝐴𝐶 𝐷𝐵𝐶
Capacitance of Three-Phase Asymmetric
Transmission Line

𝑉𝐴𝑁𝑇𝑟𝑎𝑛𝑠𝑝
1 𝐷𝐴𝐵 𝐷𝐴𝐶 𝐷𝐵𝐶 𝑟3
= 2𝑞𝐴 ln − 𝑞𝐴 ln
18𝜋𝜀0 𝑟3 𝐷𝐴𝐵 𝐷𝐴𝐶 𝐷𝐵𝐶
𝑉𝐴𝑁𝑇𝑟𝑎𝑛𝑠𝑝
1 𝐷𝐴𝐵 𝐷𝐴𝐶 𝐷𝐵𝐶 𝐷𝐴𝐵 𝐷𝐴𝐶 𝐷𝐵𝐶
= 2𝑞𝐴 ln + 𝑞𝐴 ln
18𝜋𝜀0 𝑟3 𝑟3
1/3
1 𝐷𝐴𝐵 𝐷𝐴𝐶 𝐷𝐵𝐶
= 𝑞 ln
2𝜋𝜀0 𝐴 𝑟3
Capacitance of Three-Phase Asymmetric
Transmission Line
Effect of Earth on Capacitance

Without ground

With presence of Ground


Effect of Earth on Capacitance