VLT Danfoss
VLT Danfoss
Operating Guide
VLT® HVAC Drive FC 102
110–400 kW, Enclosure Sizes D1h–D8h
vlt-drives.danfoss.com
Contents Operating Guide
Contents
1 Introduction 4
1.1 Purpose of the Manual 4
1.2 Additional Resources 4
1.3 Manual and Software Version 4
1.4 Approvals and Certifications 4
1.5 Disposal 4
2 Safety 5
2.1 Safety Symbols 5
2.2 Qualified Personnel 5
2.3 Safety Precautions 5
3 Product Overview 7
3.1 Intended Use 7
3.2 Power Ratings, Weight, and Dimensions 7
3.3 Interior View of D1h Drive 9
3.4 Interior View of D2h Drive 10
3.5 View of Control Shelf 11
3.6 Extended Options Cabinets 12
3.7 Local Control Panel (LCP) 13
3.8 LCP Menus 15
4 Mechanical Installation 16
4.1 Items Supplied 16
4.2 Tools Needed 16
4.3 Storage 17
4.4 Operating Environment 17
4.5 Installation and Cooling Requirements 18
4.6 Lifting the Drive 19
4.7 Mounting the Drive 20
5 Electrical Installation 23
5.1 Safety Instructions 23
5.2 EMC-compliant Installation 23
5.3 Wiring Schematic 26
5.4 Connecting to Ground 27
5.5 Connecting the Motor 29
5.6 Connecting the AC Mains 31
5.7 Connecting Regen/Load Share Terminals 33
5.8 Terminal Dimensions 35
6 Pre-start Checklist 67
7 Commissioning 68
7.1 Applying Power 68
7.2 Programming the Drive 68
7.3 Testing Before System Start-up 70
7.4 System Start-up 70
7.5 Parameter Setting 71
10 Specifications 96
10.1 Electrical Data 96
10.2 Mains Supply 101
10.3 Motor Output and Torque Data 102
10.4 Ambient Conditions 102
10.5 Cable Specifications 102
10.6 Control Input/Output and Control Data 103
10.7 Fuses and Circuit Breakers 106
11 Appendix 144
11.1 Abbreviations and Conventions 144
11.2 International/North American Default Parameter Settings 145
11.3 Parameter Menu Structure 145
Index 151
1 1 1 Introduction
2 Safety
2 2
2.1 Safety Symbols WARNING
The following symbols are used in this guide: UNINTENDED START
When the drive is connected to the AC mains, DC supply,
or load sharing, the motor can start at any time.
WARNING Unintended start during programming, service, or repair
Indicates a potentially hazardous situation that could work can result in death, serious injury, or property
result in death or serious injury. damage. The motor can start with an external switch, a
fieldbus command, an input reference signal from the
Indicates important information, including situations that • Completely wire and assemble the drive, motor,
can result in damage to equipment or property. and any driven equipment before connecting
the drive to the AC mains, DC supply, or load
sharing.
2.2 Qualified Personnel
Correct and reliable transport, storage, installation,
operation, and maintenance are required for the trouble- WARNING
free and safe operation of the drive. Only qualified DISCHARGE TIME
personnel are allowed to install or operate this equipment. The drive contains DC-link capacitors, which can remain
charged even when the drive is not powered. High
Qualified personnel are defined as trained staff, who are voltage can be present even when the warning LED
authorized to install, commission, and maintain equipment, indicator lights are off. Failure to wait the specified time
systems, and circuits in accordance with pertinent laws and after power has been removed before performing service
regulations. Also, the personnel must be familiar with the or repair work can result in death or serious injury.
instructions and safety measures described in this manual.
• Stop the motor.
2.3 Safety Precautions • Disconnect AC mains and remote DC-link power
supplies, including battery back-ups, UPS, and
WARNING DC-link connections to other drives.
HIGH VOLTAGE • Disconnect or lock PM motor.
Drives contain high voltage when connected to AC mains
• Wait for the capacitors to discharge fully. The
input, DC supply, load sharing, or permanent motors. minimum waiting time is 20 minutes.
Failure to use qualified personnel to install, start up, and
maintain the drive can result in death or serious injury. • Before performing any service or repair work,
use an appropriate voltage measuring device to
• Only qualified personnel must install, start up, make sure that the capacitors are fully
and maintain the drive. discharged.
WARNING
LEAKAGE CURRENT HAZARD
Leakage currents exceed 3.5 mA. Failure to ground the
drive properly can result in death or serious injury.
• Ensure the correct grounding of the equipment
by a certified electrical installer.
WARNING NOTICE
EQUIPMENT HAZARD MAINS SHIELD SAFETY OPTION
2 2 Contact with rotating shafts and electrical equipment
A mains shield option is available for enclosures with a
protection rating of IP21/IP54 (Type 1/Type 12). The
can result in death or serious injury.
mains shield is a cover installed inside the enclosure to
• Ensure that only trained and qualified personnel protect against the unintended touch of the power
install, start up, and maintain the drive. terminals, according to BGV A2, VBG 4.
• Ensure that electrical work conforms to national
and local electrical codes.
• Follow the procedures in this guide.
WARNING
UNINTENDED MOTOR ROTATION
WINDMILLING
Unintended rotation of permanent magnet motors
creates voltage and can charge the unit, resulting in
death, serious injury, or equipment damage.
• Ensure that permanent magnet motors are
blocked to prevent unintended rotation.
WARNING
INTERNAL FAILURE HAZARD
Under certain circumstances, an internal failure can
cause a component to explode. Failure to keep the
enclosure closed and properly secured can cause death
or serious injury.
• Do not operate the drive with the door open or
panels off.
• Ensure that the enclosure is properly closed and
secured during operation.
CAUTION
HOT SURFACES
The drive contains metal components that are still hot
even after the drive has been powered off. Failure to
observe the high temperature symbol (yellow triangle)
on the drive can result in serious burns.
• Be aware that internal components, such as
busbars, can be extremely hot even after the
drive has been powered off.
• Exterior areas marked by the high-temperature
symbol (yellow triangle) are hot while the drive
is in use and immediately after being powered
off.
3 Product Overview
The drive is designed for industrial and commercial environments in accordance with local laws and standards. Depending
on configuration, the drive can be used in standalone applications or form part of a larger system or installation.
NOTICE
In a residential environment, this product can cause radio interference, in which case supplementary mitigation
measures can be required.
Foreseeable misuse
Do not use the drive in applications which are non-compliant with specified operating conditions and environments. Ensure
compliance with the conditions specified in chapter 10 Specifications.
3 3
IP 21/54 21/54 21/54 21/54
NEMA Type 1/12 Type 1/12 Type 1/12 Type 1/12
Shipping dimensions Height 660 (26) 660 (26) 660 (26) 660 (26)
[mm (in)] Width 1820 (71.7) 1820 (71.7) 2470 (97.4) 2470 (97.4)
Depth 510 (20.1) 510 (20.1) 590 (23.2) 590 (23.2)
Height 1324 (52.1) 1663 (65.5) 1978 (77.9) 2284 (89.9)
Drive dimensions [mm
Width 325 (12.8) 325 (12.8) 420 (16.5) 420 (16.5)
(in)]
Depth 381 (15) 381 (15) 386 (15.2) 406 (16)
Maximum weight [kg (lb)] 116 (256) 129 (284) 200 (441) 225 (496)
3 3
e30bg269.10
5
3 8
4
9
10
3 3
e30bg271.10
6
1 7
4 10
11
12
6
3 3
e30bg270.10
1
2
9
3 10
4
11
12
e30bg830.10
If a drive is ordered with any of the following options, it is
supplied with an extended options cabinet to contain the
optional components. 1
3 3 • Brake chopper.
• Mains disconnect.
• Contactor.
• Mains disconnect with contactor.
• Circuit breaker.
• Regeneration terminals.
• Load sharing terminals.
• Oversized wiring cabinet.
• Multiwire kit.
Illustration 3.4 shows an example of a drive with an options
cabinet. Table 3.3 lists the variants of the drive that include
these options.
A1.2
Status 1(1)
A1.1 0.0 % 0.00 A 0.00 kW A1.3
0.0 Hz A2
2605 kWh A3
B2 B3
C2
Ca
ck
nc
Ba
C1
el
C3
Info
On OK
D1
Warn.
D2 C4
Alarm C5
D3
130BF153.11
E1 Hand
Off
Auto Reset E3
On On
E2 E4
A. Display area
Each display readout has a parameter associated with it. See Table 3.4. The information shown on the LCP can be
customized for specific applications. Refer to chapter 3.8.1.2 Q1 My Personal Menu.
3 3
configure and operate the drive. Select Quick Menus by parameter 0-20 Display Line 1.1 Small through
pressing the [Quick Menu] key. The resulting readout parameter 0-24 Display Line 3 Large can be viewed. It is
appears on the LCP display. possible to store up to 120 samples in the memory for
later reference.
130BF241.10
0.0% 0.00 1(1) Q6 Loggings
Quick Menus Parameter 0-20 Display Line 1.1 Small Reference [%]
Parameter 0-21 Display Line 1.2 Small Motor current [A]
01 My Personal Menu Parameter 0-22 Display Line 1.3 Small Power [kW]
02 Quick Setup Parameter 0-23 Display Line 2 Large Frequency [Hz]
e30bg272.10
The parameters found in Q2 Quick Setup contain basic
1(1)
system and motor data that are always necessary for Main Menu
configuring the drive. See chapter 7.2.3 Entering System
Information for the set-up procedures. O-** Operation / Display
1-** Load and Motor
3.8.1.4 Q4 Smart Setup
2-** Brakes
Q4 Smart Setup guides the user through typical parameter 3-** Reference / Ramps
settings used to configure 1 of the following 3
Illustration 3.7 Main Menu View
applications:
• Mechanical brake.
• Conveyor. All parameters can be changed in the main menu. Option
cards added to the unit enable extra parameters associated
• Pump/fan.
with the option device.
The [Info] key can be used to display help information for
various selections, settings, and messages.
4 Mechanical Installation
e30bg624.10
VLT R AutomationDrive
www.danfoss.com
Items supplied may vary according to product configu- 1 T/C: FC-102N315T4E54H2TGC3XXSXXXXA0BXCXXXXDX
S/N: 123456H123
2 P/N: 134U6872
ration. Use the following Typecode to order Drive-only replacement:
T/C: FC-102N315T4E54H2TGC7XXSXXXXA0BXCXXXXDX
• Check the packaging and the drive visually for SCCR 100 kA at UL Voltage range 380-480 V
ASSEMBLED IN USA
damage caused by inappropriate handling during Listed 36U0 E70524 IND. CONT. EQ.
UL Voltage range 380-480 V
shipment. File any claim for damage with the Danfoss A/S
6430 Nordborg
carrier. Retain damaged parts for clarification. Denmark
CAUTION - ATTENTION:
e30bg623.10
3 132kW / 200 HP
Cabinet (D5h-D8h)
CAUTION - ATTENTION:
See manual for special condition / mains fuse
`
Voir manuel de conditions speciales / fusibles
WARNING - AVERTISSEMENT:
6 Stored charge, wait 20 min.
Charge residuelle,
` attendez 20 min. NOTICE
LOSS OF WARRANTY
1 Type code Do not remove the nameplate from the drive. Removing
2 Part number and serial number the nameplate can result in loss of warranty.
3 Power rating
4 Input voltage, frequency, and current 4.2 Tools Needed
5 Output voltage, frequency, and current
6 Discharge time Receiving/unloading
• I-beam and hooks rated to lift the weight of the
Illustration 4.1 Example Nameplate for Drive Only (D1h–D4h) drive. Refer to chapter 3.2 Power Ratings, Weight,
and Dimensions.
• Crane or other lifting aid to place the unit into
position.
Installation
• Drill with 10 mm (0.39 in) or 12 mm (0.47 in) drill
bits.
• Tape measurer.
• Various sizes of Phillips and flat bladed
screwdrivers.
• Sheet metal punch for conduits or cable glands. • Do not operate in environments where the
ambient temperature exceeds 55 °C (131 °F).
• I-beam and hooks to lift the weight of the drive.
Refer to chapter 3.2 Power Ratings, Weight, and • The drive can operate at temperatures down to
Dimensions. -10 °C (14 °F). However, proper operation at
rated load is only guaranteed at 0 °C (32 °F) or 4 4
• Crane or other lifting aid to place the drive onto
higher.
pedestal and into position.
• If temperature exceeds ambient temperature
4.3 Storage limits, extra air conditioning of the cabinet or
installation site is required.
Store the drive in a dry location. Keep the equipment
sealed in its packaging until installation. Refer to
chapter 10.4 Ambient Conditions for recommended ambient 4.4.1 Gases
temperature.
Aggressive gases, such as hydrogen sulfide, chlorine, or
Periodic forming (capacitor charging) is not necessary ammonia can damage the electrical and mechanical
during storage unless storage exceeds 12 months. components. The unit uses conformal-coated circuit boards
to reduce the effects of aggressive gases. For conformal-
4.4 Operating Environment coating class specifications and ratings, see
chapter 10.4 Ambient Conditions.
NOTICE
In environments with airborne liquids, particles, or
corrosive gases, ensure that the IP/type rating of the 4.4.2 Dust
equipment matches the installation environment. Failure
to meet requirements for ambient conditions can reduce When installing the drive in dusty environments, pay
the lifetime of the drive. Ensure that requirements for attention to the following:
humidity, temperature, and altitude are met.
Periodic maintenance
Voltage [V] Altitude restrictions When dust accumulates on electronic components, it acts
200–240 At altitudes above 3000 m (9842 ft), contact as a layer of insulation. This layer reduces the cooling
Danfoss regarding PELV. capacity of the components, and the components become
380–480 At altitudes above 3000 m (9842 ft), contact warmer. The hotter environment decreases the life of the
Danfoss regarding PELV. electronic components.
525–690 At altitudes above 2000 m (6562 ft), contact Keep the heat sink and fans free from dust buildup. For
Danfoss regarding PELV. more service and maintenance information, refer to
chapter 9 Maintenance, Diagnostics, and Troubleshooting.
Table 4.1 Installation at High Altitudes
Cooling fans
For detailed ambient conditions specifications, refer to Fans provide airflow to cool the drive. When fans are
chapter 10.4 Ambient Conditions. exposed to dusty environments, the dust can damage the
fan bearings and cause premature fan failure. Also, dust
NOTICE can accumulate on fan blades causing an imbalance which
CONDENSATION prevents the fans from properly cooling the unit.
Moisture can condense on the electronic components
and cause short circuits. Avoid installation in areas
subject to frost. Install an optional space heater when
the drive is colder than the ambient air. Operating in
standby mode reduces the risk of condensation as long
as the power dissipation keeps the circuitry free of
moisture.
Systems operated in potentially explosive atmospheres • Ensure unit stability by mounting vertically to a
must fulfill special conditions. EU Directive 94/9/EC solid flat surface.
(ATEX 95) classifies the operation of electronic devices in • Ensure that the strength of the mounting location
potentially explosive atmospheres. supports the unit weight. Refer to
chapter 3.2 Power Ratings, Weight, and Dimensions.
• Class d specifies that if a spark occurs, it is • Ensure that the mounting location allows access
contained in a protected area. to open the enclosure door. See
• Class e prohibits any occurrence of a spark. chapter 10.9 Enclosure Dimensions.
Motors with class d protection • Ensure that there is adequate space around the
Do not require approval. Special wiring and containment unit for cooling airflow.
are required. • Place the unit as near to the motor as possible.
Motors with class e protection Keep the motor cables as short as possible. See
When combined with an ATEX–approved PTC monitoring chapter 10.5 Cable Specifications.
device like the VLT® PTC Thermistor Card MCB 112, the • Ensure that the location allows for cable entry at
installation does not need an individual approval from an the bottom of the unit.
approbated organization.
Cooling and airflow requirements
Motors with class d/e protection
The motor itself has an e ignition protection class, while • Ensure that top and bottom clearance for air
cooling is provided. Clearance requirement:
the motor cabling and connection environment is in
225 mm (9 in).
compliance with the d classification. To attenuate the high
peak voltage, use a sine-wave filter at the drive output. • Consider derating for temperatures starting
between 45 °C (113 °F) and 50 °C (122 °F) and
When using a drive in a potentially explosive
elevation 1000 m (3300 ft) above sea level. See
atmosphere, use the following:
the product-specific design guide for detailed
• Motors with ignition protection class d or e. information.
• PTC temperature sensor to monitor the motor The drive uses back-channel cooling to circulate the heat
temperature. sink cooling air. The cooling duct carries approximately
• Short motor cables. 90% of the heat out of the back channel of the drive.
Redirect the back-channel air from the panel or room by
• Sine-wave output filters when shielded motor
using:
cables are not used.
• Duct cooling. Back-channel cooling kits are
NOTICE available to direct the air away from the panel
MOTOR THERMISTOR SENSOR MONITORING when an IP20/chassis drive is installed in a Rittal
Drives with the VLT® PTC Thermistor Card MCB 112 enclosure. Use of a kit reduces the heat in the
option are PTB-certified for potentially explosive panel and smaller door fans can be specified on
atmospheres. the enclosure.
• Cooling out the back (top and base covers). The
back-channel cooling air can be ventilated out of
the room so that the heat from the back channel
is not dissipated into the control room.
Enclosure size Door fan/top Power size Heat sink fan • Move the unit using a hoist, crane, forklift, or
fan other lifting device with the appropriate weight
D1h/D3h/D5h/ 102 m3/hr 90–110 kW,
rating. See chapter 3.2 Power Ratings, Weight,
420 m3/hr
D6h 380–480 V
and Dimensions for the weight of the drive.
(60 CFM) (250 CFM)
75–132 kW, 420 m3/hr • Failure to locate the center of gravity and
525–690 V (250 CFM) correctly position the load can cause
132 kW, 380– 840 m3/hr unexpected shifting during lifting and
480 V (500 CFM) transport. For measurements and center of
gravity, see chapter 10.9 Enclosure Dimensions.
All, 200–240 V 840 m3/hr
(500 CFM) • The angle from the top of the drive module to
D2h/D4h/D7h/ 204 m3/hr 160 kW, 380– 420 m3/hr the lifting cables affects the maximum load
D8h (120 CFM) 480 V (250 CFM) force on the cable. This angle must be 65° or
160 kW, 525– 420 m3/hr
greater. Refer to Illustration 4.3. Attach and
690 V (250 CFM)
dimension the lifting cables properly.
All, 200–240 V 840 m3/hr • Never walk under suspended loads.
(500 CFM)
• To guard against injury, wear personal
protective equipment such as gloves, safety
Table 4.2 Airflow
glasses, and safety shoes.
130BE566.11
65° min
130BF662.10
1
Depending on the drive model and configuration, the
drive can floor-mounted or wall-mounted.
on the drive.
4. Fasten 4 M5 screws through the front flange of
the pedestal and into the gland plate mounting
holes.
1
2
e30bg484.10
1
2
3
4
4 4
6
7
200 (7.9)
10
e30bg288.10
mounting flange at the top of the drive. See
Illustration 4.6.
4. Fasten 2–4 M10 bolts in the mounting holes at
the top of the drive, securing it to the wall. Use 1
bolt for each mounting hole. The number varies
with enclosure size. See Illustration 4.6. e30bg289.10
1 Mounting holes
2 Bottom of pedestal
5 Electrical Installation
Wire type and ratings • Use shielded cables for motor output cables. An
• All wiring must comply with local and national alternative is unshielded motor cables within
regulations regarding cross-section and ambient metal conduit.
temperature requirements.
NOTICE
• Power connection wire recommendation: SHIELDED CABLES
Minimum 75 °C (167 °F) rated copper wire. If shielded cables or metal conduits are not used, the
See chapter 10.5 Cable Specifications for recommended wire unit and the installation do not meet regulatory limits
sizes and types. on radio frequency (RF) emission levels.
NOTICE
INSTALLATION AT HIGH ALTITUDE
There is a risk of overvoltage. Isolation between
components and critical parts could be insufficient, and
not comply with PELV requirements. Reduce the risk of
overvoltage by using external protective devices or
galvanic isolation.
For installations above 2000 m (6500 ft) altitude, contact
Danfoss regarding PELV compliance.
NOTICE
PELV COMPLIANCE
Prevent electric shock by using protective extra low
voltage (PELV) electrical supply and complying with local
and national PELV regulations.
e30bf228.11
6
8
9 5 5
10
11
1 12
90
13
2 14
3
15
u
4
v 16
4
w
4 PE
L1 17
L2
L3
PE
18
e30bf111.12
TB5
230 V AC R1 Space heater (optional)
50/60 Hz
TB6 Contactor 1)
= = =
91 (L1) (U) 96
3-phase 92 (L2) (V) 97
power
input 93 (L3) (W) 98
95 PE (PE) 99
Motor
Load share 88 (-) Switch mode Regen +
power supply
5 5
(optional) (R+) 82 Brake
89 (+) resistor
10 V DC 24 V DC
15 mA 200 mA (optional) Regen (optional)
(R-) 81
50 (+10 V OUT) + - + -
+10 V DC Regen -
A53 U-I (S201) 83
53 (A IN)
1 2
-10 V DC to +10 V DC
ON
ON=0/4-20 mA Relay1
0/4-20 mA A54 U-I (S202) 03
OFF=0 to ±10 V 240 V AC, 2A
1 2
54 (A IN)
ON
-10 V DC to +10 V DC 02
0/4-20 mA 400 V AC, 2A
55 (COM A IN) 01
Relay2
12 (+24 V OUT) 06
240 V AC, 2A
13 (+24 V OUT) P 5-00 05
400 V AC, 2A
24 V (NPN)
18 (D IN) 04
0 V (PNP)
24 V (NPN)
19 (D IN) 0 V (PNP) (COM A OUT) 39 Analog output
0/4-20 mA
(A OUT) 42
20 (COM D IN)
S801/Bus Term.
24 V (NPN)
27 (D IN/OUT) 0 V (PNP) OFF-ON
24V ON=Terminated
1 2
ON
OFF=Open 1
Brake temperature
0V 5V 2 (NC)
24 V (NPN)
29 (D IN/OUT) 0 V (PNP)
24V
0V
S801
0V RS485 (P RS485) 68 RS485
24 V (NPN) interface
32 (D IN) 0 V (PNP) (N RS485) 69
24 V (NPN) (COM RS485) 61
33 (D IN) 0 V (PNP)
(PNP) = Source
(NPN) = Sink
37 (D IN)2)
1) TB6 contactor is found only in D6h and D8h drives with a contactor option.
2) Terminal 37 (optional) is used for Safe Torque Off. Refer to the VLT® FC Series - Safe Torque Off Operating Guide for installation
instructions.
WARNING
LEAKAGE CURRENT HAZARD
Leakage currents exceed 3.5 mA. Failure to ground the drive properly can result in death or serious injury.
• Ensure the correct grounding of the equipment by a certified electrical installer.
NOTICE
POTENTIAL EQUALIZATION
There is a risk of burst transient when the ground potential between the drive and the control system is different.
Install equalizing cables between the system components. Recommended cable cross-section: 16 mm2 (5 AWG).
e30bg266.10
5 5
WARNING
INDUCED VOLTAGE
Induced voltage from output motor cables that run together can charge equipment capacitors, even with the
equipment turned off and locked out. Failure to run output motor cables separately or use shielded cables could result
in death or serious injury.
• Comply with local and national electrical codes for cable sizes. For maximum wire sizes, see chapter 10.5 Cable
Specifications.
•
•
Follow motor manufacturer wiring requirements.
Motor wiring knockouts or access panels are provided at the base of IP21 (NEMA1/12) and higher units.
5 5
• Do not wire a starting or pole-changing device (for example Dahlander motor or slip ring asynchronous motor)
between the drive and the motor.
Procedure
1. Strip a section of the outer cable insulation.
2. Position the stripped wire under the cable clamp, establishing mechanical fixation and electrical contact between
the cable shield and ground.
3. Connect the ground wire to the nearest grounding terminal in accordance with the grounding instructions
provided in chapter 5.4 Connecting to Ground. See Illustration 5.4.
4. Connect the 3-phase motor wiring to terminals 96 (U), 97 (V), and 98 (W). See Illustration 5.4.
5. Tighten the terminals in accordance with the information provided in chapter 10.8.1 Fastener Torque Ratings.
e30bg268.10
5 5
Procedure
1. Strip a section of the outer cable insulation.
2. Position the stripped wire under the cable clamp, establishing mechanical fixation and electrical contact between
the cable shield and ground.
3. Connect the ground wire to the nearest grounding terminal in accordance with the grounding instructions
provided in chapter 5.4 Connecting to Ground.
4. Connect the 3-phase AC input power wiring to terminals R, S, and T. See Illustration 5.5.
5 5
5. Tighten the terminals in accordance with the information provided in chapter 10.8.1 Fastener Torque Ratings.
6. When supplied from an isolated mains source (IT mains or floating delta) or TT/TN-S mains with a grounded leg
(grounded delta), ensure that parameter 14-50 RFI Filter is set to [0] Off to avoid damage to the DC link and to
reduce ground capacity currents.
NOTICE
OUTPUT CONTACTOR
Danfoss does not recommend using an output contactor on 525–690 V drives that are connected to an IT mains
network.
e30bg267.10
5 5
Illustration 5.5 AC Mains Terminals (D1h shown). For a detailed view of terminals, see chapter 5.8 Terminal Dimensions.
• Size the wiring according to the current of the drive. For maximum wire sizes, see chapter 10.1 Electrical Data.
• Comply with local and national electrical codes for cable sizes.
Procedure
1. Remove 2 plugs (for either top entry or side entry) from the terminal cover.
2. Insert cable fittings into the terminal cover holes.
3. Strip a section of the outer cable insulation. 5 5
4. Position the stripped cable through the fittings.
5. Connect the DC(+) cable to the DC(+) terminal, and secure with 1 M10 fastener.
6. Connect the DC(-) cable to the DC(-) terminal, and secure with 1 M10 fastener.
7. Tighten the terminals in accordance with chapter 10.8.1 Fastener Torque Ratings.
e30bg485.10
6
1
7
2
3 8
5 5
32 (1.3)
9
244 (9.6)
14 (0.6)
16 (0.6)
10
87 (3.4)
5 12
130BF342.10
5 5
1
200 (7.9) 3
94 (3.7)
88 (3.5)
0.0
0.0
33 (1.3)
62 (2.4)
101 (4.0)
140 (5.5)
163 (6.4)
185 (7.3)
224 (8.8)
263 (10.4)
293 (11.5)
130BF343.10
1 2
5 5
0.0
272 (10.7)
244 (9.6)
0.0
M10
M10
13 13
(0.5) (0.5)
32 32
(1.3) (1.3)
130BF345.10
1
331 (13.0) 3
5 5
2 211 (8.3)
0.0
0.0
42 (1.6)
68 (2.7)
126 (5.0)
184 (7.2)
246 (9.7)
300 (11.8)
354 (13.9)
378 (14.9)
130BF346.10
1 2
5 5
0.0
284 (11.2)
255 (10.0)
0.0
M10 M10
15 (0.6) 15 (0.6)
19 (0.8) 18 (0.7)
38 (1.5) 35 (1.4)
130BF341.10
152 (6.0)
217 (8.5)
292 (11.5)
5 5
2
1
3
188 (7.4)
83 (3.3)
0.0
4
0.0
22 (0.9)
62 (2.4)
101 (4.0)
145 (5.7)
184 (7.2)
223 (8.8)
130BF344.10
1
3 2
5 5
0.0
0.0
244 (9.6)
272 (10.7)
290 (11.4)
M10
4 12 (0.5) 6
10 (0.4) 38 (1.5)
3X M8x18
0
59 (2.3)
145 (5.7)
182 (7.2)
M10
M10
5
7
13 (0.5)
13 (0.5)
32 (1.3) 32 (1.3)
293 (11.5)
130BF347.10
237 (9.3)
376 (14.8)
5 5
1 2
319 (12.6) 3
200 (7.9)
0.0
4
o.o
33 (1.3)
91 (3.6)
149 (5.8)
211 (8.3)
265 (10.4)
319 (12.6)
130BF348.10
1
3 2
5 5
306 (12.1)
255 (10.0)
284 (11.2)
0.0
0.0
4 M10
6
0
13 (0.5)
3X M10X20 19 (0.7)
0
91 (3.6)
200 (7.9)
259 (10.2)
16 (0.6)
32 (1.3)
M10 M10
7
5 22 (0.9)
15 (0.6)
19 (0.8) 18 (0.7)
38 (1.5)
35 (1.4)
130BF349.10
5 5
1 227 (9.0)
221 (8.7)
196 (7.7)
4
2
148 (5.8)
118 (4.6)
90 (3.6)
0.0
0.0
45 (1.8)
46 (1.8)
99 (3.9)
146 (5.8)
153 (6.0)
182 (7.2)
193 (7.6)
221 (8.7)
249 (9.8)
260 (10.2)
Illustration 5.15 D5h Terminal Dimensions with Disconnect Option (Front View)
130BF350.10
5 5
2
1
3
206 (8.1)
113 (4.4)
0.0
0.0
Illustration 5.16 D5h Terminal Dimensions with Disconnect Option (Side Views)
256 (10.1)
263 (10.4)
293 (11.5)
101 (4.0)
140 (5.5)
163 (6.4)
185 (7.3)
191 (7.5)
224 (8.8)
130BF351.10
33 (1.3)
62 (2.4)
0.0
727 (28.6) 2
5 5
623 (24.5) 3
517 (20.4)
511 (20.1)
4
0.0
Illustration 5.17 D5h Terminal Dimensions with Brake Option (Front View)
130BF352.10
1
2
3
5 5
0.0
274 (10.8)
293 (11.5)
246 (9.7)
0.0
Illustration 5.18 D5h Terminal Dimensions with Brake Option (Side Views)
130BF353.10
1
458 (18.0)
5 5
4
227 (8.9)
195 (7.7)
2
5
153 (6.0)
123 (4.8)
96 (3.8)
0.0
0.0
46 (1.8)
50 (2.0)
99 (3.9)
146 (5.8)
147 (5.8)
182 (7.2)
193 (7.6)
221 (8.7)
249 (9.8)
260 (10.2)
Illustration 5.19 D6h Terminal Dimensions with Contactor Option (Front View)
e30bf354.10
1
5 5
3
0.0
286 (11.2)
206 (8.1)
113 (4.4)
2 Brake terminals – –
Illustration 5.20 D6h Terminal Dimensions with Contactor Option (Side Views)
130BF355.10
5 5
225 (8.9) 4
0.0
153 (6.0)
45 (1.8)
99 (3.9)
0.0
Illustration 5.21 D6h Terminal Dimensions with Contactor and Disconnect Options (Front View)
130BF356.10
5 5
1
2
3
0.0
286 (11.2)
Illustration 5.22 D6h Terminal Dimensions with Contactor and Disconnect Options (Side Views)
130BF357.10
1 5 5
467 (18.4)
0.0
0.0
52 (2.1)
99 (3.9)
145 (5.7)
Illustration 5.23 D6h Terminal Dimensions with Circuit Breaker Option (Front View)
130BF358.10
1
5 5
3
0.0
163 (6.4)
Illustration 5.24 D6h Terminal Dimensions with Circuit Breaker Option (Side Views)
130BF359.10
1 545 (21.4)
2 515 (20.3)
3 5 5
412 (16.2)
395 (15.6)
372 (14.7) 4
0.0
0.0
49 (1.9)
66 (2.6)
95 (3.7)
131 (5.1)
151 (5.9)
195 (7.7)
198 (7.8)
238 (9.4)
292 (11.5)
346 (13.6)
368 (14.5)
Illustration 5.25 D7h Terminal Dimensions with Disconnect Option (Front View)
130BF360.10
1
3
2
5 5
0.0
276 (10.9)
119 (4.7)
Illustration 5.26 D7h Terminal Dimensions with Disconnect Option (Side Views)
130BF361.10
269 (10.6)
297 (11.7)
325 (12.8)
351 (13.8)
375 (14.8)
123 (4.9)
181 (7.1)
243 (9.6)
40 (1.6)
66 (2.6)
0.0
1260 (49.6)
1 3
1202 (47.3) 4
1082 (42.6)
5 5
2
1034 (40.7)
1009 (39.7)
0.0
Illustration 5.27 D7h Terminal Dimensions with Brake Option (Front View)
290 (11.4)
309 (12.1)
257 (10.1)
130BF362.10
0.0
0.0
1
2 3
5 5
Illustration 5.28 D7h Terminal Dimensions with Brake Option (Side Views)
130BF367.10
1
898 (35.3)
5 5
4
5
2 521 (20.5)
3
418 (16.5)
401 (15.8)
378 (14.9)
0.0
0.0
49 (1.9)
69 (2.7)
95 (3.7)
123 (4.9)
151 (5.9)
177 (7.0)
198 (7.8)
238 (9.4)
292 (11.5)
346 (13.6)
378 (14.9)
Illustration 5.29 D8h Terminal Dimensions with Contactor Option (Front View)
130BF368.10
1
5 5
2 3
0.0
119 (4.7)
252 (9.9)
127 (5.0)
0.0
Illustration 5.30 D8h Terminal Dimensions with Contactor Option (Side Views)
130BF369.10
4
5 5
1
567 (22.3)
5
2
0.0
0.0
58 (2.3)
123 (4.9)
188 (7.4)
Illustration 5.31 D8h Terminal Dimensions with Contactor and Disconnect Options (Front View)
130BF370.10
5 5
1
2
3
0.0
246 (9.7)
Illustration 5.32 D8h Terminal Dimensions with Contactor and Disconnect Options (Side View)
130BF371.10
5 5
1
605
(23.8)
4
2
0
154 (6.1)
224 (8.8)
0
85 (3.3)
Illustration 5.33 D8h Terminal Dimensions with Circuit Breaker Option (Front View)
130BF372.10
M10
5 5 20 (0.8) 15 (0.6)
40 (1.6)
2
3 M10
2
15 (0.6)
16 (0.6) 32 (1.3)
M10
20
(0.8)
14 (0.5)
35 (1.4)
18 (0.7)
202 (8.0)
0.0
Illustration 5.34 D8h Terminal Dimensions with Circuit Breaker Option (Side View)
130BF145.10
1
All terminals to the control cables are inside the drive 61 68 69 39 42 50 53 54 55
below the LCP. To access the control terminals, either open
the door (D1h/D2h/D5h/D6h/D7h/D8h) or remove the front 3
panel (D3h/D4h). 2
12 13 18 19 27 29 32 33 20 37
5.9.1 Control Cable Routing
Digital input/output terminals Either solid or flexible wire can be connected to the
Terminal Parameter Default Description control terminals. Use the following procedures to connect
setting or disconnect the control wires.
27 Parameter 5-12 [2] Coast For digital input or
Terminal 27 inverse output. Default NOTICE
Digital Input setting is input.
Minimize interference by keeping control wires as short
29 Parameter 5-13 [14] JOG as possible and separate from high-power cables.
Terminal 29
Digital Input
Connecting wire to control terminals
20 – – Common for digital
inputs and 0 V 1. Strip 10 mm (0.4 in) of the outer plastic layer
from the end of the wire.
5 5
potential for 24 V
supply. 2. Insert the control wire into the terminal.
37 – STO When not using the
optional STO feature,
• For a solid wire, push the bare wire into
the contact. See Illustration 5.37.
a jumper wire is
required between • For a flexible wire, open the contact by
terminal 12 (or 13) inserting a small screwdriver into the
and terminal 37. This slot between the terminal holes and
set-up allows the push the screwdriver inward. See
drive to operate with Illustration 5.38. Then, insert the stripped
factory default wire into the contact, and remove the
programming values. screwdriver.
3. Pull gently on the wire to ensure that the contact
Table 5.2 Digital Input/Output Terminal Descriptions
is firmly established. Loose control wiring can be
the source of equipment faults or reduced
Analog input/output terminals
performance.
Terminal Parameter Default Description
setting
e30bg283.10
39 – – Common for analog
12 13 18 19 27 29 32 33
output.
42 Parameter 6-50 [0] No Programmable analog
Terminal 42 operation output. 0–20 mA or
Output 4–20 mA at a
maximum of 500 Ω.
50 – +10 V DC 10 V DC analog
4)
(0.
potentiometer or
thermistor. 15 mA
Illustration 5.37 Connecting Solid Control Wires
maximum.
53 Parameter Reference Analog input. For
group 6-1* voltage or current.
130BD546.11
Disconnecting wires from the control terminals card documentation for installation and operation
instructions.
1. To open the contact, insert a small screwdriver
into the slot between the terminal holes and • A switch (BUS TER) is provided on the control
push the screwdriver inward. card for bus termination resistance. See
Illustration 5.40.
2. Pull gently on the wire to free it from the control
terminal contact. For basic serial communication set-up, perform the
following steps:
See chapter 10.5 Cable Specifications for control terminal
1. Connect RS485 serial communication wiring to
wiring sizes and chapter 8 Wiring Configuration Examples for
terminals (+)68 and (-)69.
typical control wiring connections.
1a Use shielded serial communication cable
5.9.4 Enabling Motor Operation (recommended).
(Terminal 27) 1b See chapter 5.4 Connecting to Ground for 5 5
proper grounding.
A jumper wire is required between terminal 12 (or 13) and
2. Select the following parameter settings:
terminal 27 for the drive to operate when using factory
default programming values. 2a Protocol type in parameter 8-30 Protocol.
2b Drive address in parameter 8-31 Address.
• Digital input terminal 27 is designed to receive 2c Baud rate in parameter 8-32 Baud Rate.
24 V DC external interlock command.
130BB489.10
• When no interlock device is used, wire a jumper
between control terminal 12 (recommended) or
13 to terminal 27. This wire provides an internal 61
24 V signal on terminal 27.
• When the status line at the bottom of the LCP
reads AUTO REMOTE COAST, the unit is ready to 68 +
5.9.8 Wiring the Auxiliary Contacts to the 5.9.10 Selecting Voltage/Current Input
Disconnect Signal
The disconnect is an option that is installed at the factory. The analog input terminals 53 and 54 allow setting of
The auxiliary contacts, which are signal accessories used input signal to voltage (0–10 V) or current (0/4–20 mA).
with the disconnect, are not installed at the factory to
allow more flexibility during installation. The contacts snap Default parameter setting:
into place without the need for tools. • Terminal 53: Speed reference signal in open loop
(see parameter 16-61 Terminal 53 Switch Setting).
Contacts must be installed in specific locations on the
disconnect depending on their functions. Refer to the
• Terminal 54: Feedback signal in closed loop (see
parameter 16-63 Terminal 54 Switch Setting).
5 5 datasheet included in the accessory bag that comes with
the drive. NOTICE
Disconnect power to the drive before changing switch
Specifications positions.
• Ui/[V]: 690
1. Remove the LCP. See Illustration 5.40.
• Uimp/[kV]: 4
2. Remove any optional equipment covering the
• Pollution degree: 3
switches.
• Ith/[A]: 16
3. Set switches A53 and A54 to select the signal
• Cable size: 1...2x0.75...2.5 mm2 type (U = voltage, I = current).
• Maximum fuse: 16 A/gG
130BF146.10
• NEMA: A600, R300, wire size: 18–14 AWG, 1(2)
N O
U- I U- I
104–106) on the power card. See Illustration 3.3.
2
1
N O
2
N O
N O
2
6 Pre-start Checklist
Before completing installation of the unit, inspect the entire installation as detailed in Table 6.1. Check and mark the items
when completed.
• Confirm that the supply voltage matches the voltage of the drive and the motor.
Switches • Ensure that all switch and disconnect settings are in the proper positions.
Auxiliary equipment • Look for auxiliary equipment, switches, disconnects, or input fuses/circuit breakers that reside on the input
power side of the drive or output side to the motor. Ensure that they are ready for full-speed operation.
•
•
Check function and installation of any sensors used for feedback to the drive.
Cable routing • Ensure that motor wiring, brake wiring (if equipped), and control wiring are separated or shielded, or in 3
separate metallic conduits for high-frequency interference isolation.
Control wiring • Check for broken or damaged wires and loose connections.
• Check that control wiring is isolated from high-power wiring for noise immunity.
• Use shielded cable or twisted pair and ensure that the shield is terminated correctly.
Grounding • Check for good ground connections that are tight and free of oxidation.
• Grounding to conduit, or mounting the back panel to a metal surface, is not a suitable grounding.
• Measure top and bottom clearance of the drive to verify adequate airflow for cooling, see
chapter 4.5 Installation and Cooling Requirements.
Ambient conditions • Check that requirements for ambient conditions are met. See chapter 10.4 Ambient Conditions.
Interior of the drive • Inspect that the unit interior is free of dirt, metal chips, moisture, and corrosion.
• Verify that all installation tools have been removed from unit interior.
• For D3h and D4h enclosures, ensure that the unit is mounted on an unpainted, metal surface.
Vibration • Check that the unit is mounted solidly, or that shock mounts are used, if necessary.
7 Commissioning
Apply power to the drive using the following steps: 7.2.2 Parameter Navigation
1. Confirm that the input voltage is balanced within
3%. If not, correct the input voltage imbalance Use the following LCP keys to navigate through the
before proceeding. Repeat this procedure after parameters:
the voltage correction.
2. Ensure that any optional equipment wiring • Press [▲] [▼] to scroll up or down.
matches the installation requirements. • Press [◄] [►] to shift a space to the left or right of
3. Ensure that all operator devices are in the OFF a decimal point while editing a decimal
position. parameter value.
4. Close and securely fasten all covers and doors on • Press [OK] to accept the change.
the drive. • Press [Cancel] to disregard the change and exit
5. Apply power to the unit, but do not start the edit mode.
drive. For units with a disconnect switch, turn the • Press [Back] twice to show the status view.
switch to the ON position to apply power to the
drive. • Press [Main Menu] once to go back to the main
menu.
1. Press [Hand On]. The procedure in this section requires user-wiring and
2. Move the left cursor to the left of the decimal application programming to be completed. The following
point by using the left arrow key, and enter an procedure is recommended after application set-up is
RPM that slowly rotates the motor. completed.
3. Press [OK].
1. Press [Auto On].
4. If the motor rotation is wrong, set
2. Apply an external run command.
parameter 1-06 Clockwise Direction to [1] Inverse.
Examples of external run commands are a switch,
key, or programmable logic controller (PLC).
7.3.2 Encoder Rotation
3. Adjust the speed reference throughout the speed
range.
If encoder feedback is used, perform the following steps:
1. Select [0] Open Loop in parameter 1-00 Configu- 4. Ensure that the system is working as intended by
ration Mode. checking sound and vibration level of the motor.
2. Select [1] 24 V encoder in parameter 7-00 Speed 5. Remove the external run command.
PID Feedback Source. If warnings or alarms occur, see chapter 9.5 List of Warnings
3. Press [Hand On]. and Alarms.
4. Press [►] for positive speed reference
(parameter 1-06 Clockwise Direction at [0] Normal).
5. In parameter 16-57 Feedback [RPM], check that the
feedback is positive.
For more information on the encoder option, refer to the
option manual.
NOTICE NOTICE
REGIONAL SETTINGS LOSS OF DATA
Some parameters have different default settings for Loss of programming, motor data, localization, and
international or North America. For a list of the different monitoring records occurs when restoring default
default values, see chapter 11.2 International/North settings. To create a back-up, upload data to the LCP
American Default Parameter Settings. before initialization. Refer to chapter 7.5.1 Uploading and
Downloading Parameter Settings.
Establishing the correct programming for applications
requires setting several parameter functions. Details for Restore the default parameter settings by initializing the
parameters are provided in the programming guide. unit. Initialization is carried out through
parameter 14-22 Operation Mode or manually.
Parameter settings are stored internally in the drive,
allowing the following advantages: Parameter 14-22 Operation Mode does not reset settings
• Parameter settings can be uploaded into the LCP such as the following:
memory and stored as a back-up. • Running hours.
• Multiple units can be programmed quickly by • Serial communication options. 7 7
connecting the LCP to the unit and downloading
the stored parameter settings. • Personal menu settings.
• Settings that are stored in the LCP are not • Fault log, alarm log, and other monitoring
changed when restoring factory default settings. functions.
Recommended initialization
• Changes made to default settings as well as any
1. Press [Main Menu] twice to access parameters.
programming entered into parameters are stored
and available for viewing in the quick menu. See 2. Go to parameter 14-22 Operation Mode and
chapter 3.8 LCP Menus. press [OK].
3. Scroll to Initialization and press [OK].
7.5.1 Uploading and Downloading
4. Remove power to the unit and wait for the
Parameter Settings
display to turn off.
The drive operates using parameters stored on the control 5. Apply power to the unit. Default parameter
card, which is located within the drive. The upload and settings are restored during start-up. Start-up
download functions move the parameters between the takes slightly longer than normal.
control card and the LCP. 6. After alarm 80, Drive initialized to default value
appears, press [Reset].
1. Press [Off]. Manual initialization
2. Go to parameter 0-50 LCP Copy and press [OK]. Manual initialization resets all factory settings except for
the following:
3. Select 1 of the following:
• Parameter 15-00 Operating hours.
3a To upload data from the control card to
the LCP, select [1] All to LCP. • Parameter 15-03 Power Up's.
3b To download data from the LCP to the • Parameter 15-04 Over Temp's.
control card, select [2] All from LCP. • Parameter 15-05 Over Volt's.
4. Press [OK]. A progress bar shows the uploading or To perform manual initialization:
downloading process. 1. Remove power to the unit and wait for the
display to turn off.
5. Press [Hand On] or [Auto On].
2. Press and hold [Status], [Main Menu], and [OK]
simultaneously while applying power to the unit
(approximately 5 s or until an audible click
sounds and the fan starts). Start-up takes slightly
longer than normal.
130BB930.10
FC
The examples in this section are intended as a quick Parameter 1-29 [1] Enable
+24 V 12
reference for common applications. +24 V 13 Automatic complete AMA
D IN 18 Motor
• Parameter settings are the regional default values D IN 19 Adaptation
unless otherwise indicated (selected in COM 20 (AMA)
parameter 0-03 Regional Settings). D IN 27 Parameter 5-12 [0] No
D IN 29
• Parameters associated with the terminals and
D IN 32
Terminal 27 operation
their settings are shown next to the drawings. Digital Input
D IN 33
*=Default value
• Switch settings for analog terminals A53 or A54 D IN 37
Notes/comments: Set
are shown where required.
+10 V 50
parameter group 1-2* Motor
• For STO, a jumper wire may be required between A IN 53 Data according to motor
terminal 12 and terminal 37 when using factory A IN 54 nameplate.
default programming values. COM 55
A OUT
8.2 Wiring Configurations for Automatic 42
Parameters
Function Setting
130BB929.10
FC
+24 V 12 Parameter 1-29 [1] Enable
Automatic Motor complete AMA Table 8.2 Wiring Configuration for AMA without
+24 V 13
D IN 18 Adaptation T27 Connected
D IN 19 (AMA)
COM 20 Parameter 5-12 T [2]* Coast 8.3 Wiring Configurations for Analog Speed
D IN 27 erminal 27 inverse Reference
D IN 29 Digital Input
D IN 32
*=Default value Parameters
D IN 33 Function Setting
Notes/comments: Set
e30bb926.11
D IN FC
37
parameter group 1-2* Motor Parameter 6-10 0.07 V*
Data according to motor Terminal 53
+10 V 50
nameplate. Low Voltage
A IN 53
A IN Parameter 6-11 10 V*
54 +10 V 50
+ Terminal 53
COM 55 A IN 53
A OUT 42 A IN 54 High Voltage
COM 39 COM 55 Parameter 6-14 0 RPM
-
A OUT 42 Terminal 53
0 – 10 V
COM 39 Low Ref./Feedb.
Value
U-I
Parameter 6-15 1500 RPM
Table 8.1 Wiring Configuration for AMA with T27 Connected Terminal 53
A53 High Ref./Feedb.
Value
*=Default value
Notes/comments:
Parameters
130BB805.12
Speed
Function Setting
e30bb927.11
FC
Parameter 6-12 4 mA*
Terminal 53 Low
Current
Parameter 6-13 20 mA*
+10 V 50
+ Terminal 53
A IN 53 Start/Stop (18)
A IN 54 High Current
Illustration 8.1 Start/Stop with Safe Torque Off
COM 55 Parameter 6-14 0 RPM
-
A OUT 42 4 - 20mA Terminal 53 Low
COM 39 Ref./Feedb.
Value Parameters
U-I
Parameter 6-15 1500 RPM Function Setting
FC
Terminal 53 Parameter 5-10 [9] Latched
+24 V 12
A53 High Ref./Feedb. Terminal 18 Start
+24 V 13
Value Digital Input
D IN 18
*=Default value D IN 19 Parameter 5-12 [6] Stop Inverse
Notes/comments: COM 20 Terminal 27
D IN 27 Digital Input
D IN 29 *=Default value
Notes/comments:
8 8
D IN 32
Table 8.4 Wiring Configuration for Analog Speed Reference D IN 33 If parameter 5-12 Terminal 27
(Current) D IN 37 Digital Input is set to [0] No
operation, a jumper wire to
8.4 Wiring Configurations for Start/Stop +10 V 50 terminal 27 is not needed.
A IN 53
Parameters A IN 54
COM 55
Function Setting
130BB802.10
FC
A OUT 42
+24 V 12 Parameter 5-10 T [8] Start*
130BB803.10
COM 39
+24 V 13 erminal 18
D IN 18 Digital Input
D IN 19 Parameter 5-12 T [0] No
COM 20 erminal 27 operation
D IN 27 Digital Input
D IN 29 Parameter 5-19 T [1] Safe
D IN 32 erminal 37 Safe Torque Off
D IN 33
Stop Alarm
D IN 37 Table 8.6 Wiring Configuration for Pulse Start/Stop
*=Default value
Notes/comments:
130BB806.10
+10 50 Speed
A IN If parameter 5-12 Terminal 27
53
A IN 54
Digital Input is set to [0] No
COM 55 operation, a jumper wire to
A OUT 42 terminal 27 is not needed.
COM 39
Table 8.5 Wiring Configuration for Start/Stop Command with Stop Inverse (27)
COM 39 A IN 54
Parameter 3-10
COM 55
Preset Reference
A OUT 42
Preset ref. 0 25%
8 8
130BB928.11
COM 39
Preset ref. 1 50%
Preset ref. 2 75%
Preset ref. 3 100%
*=Default value
Notes/comments:
Table 8.7 Wiring Configuration for Start/Stop with Reversing Table 8.8 Wiring Configuration for an External Alarm Reset
and 4 Preset Speeds
8.6 Wiring Configuration for Speed
Reference Using a Manual
Potentiometer
Parameters
Function Setting
e30bb683.11
FC
Parameter 6-10 0.07 V*
Terminal 53
Low Voltage
+10 V 50 Parameter 6-11 10 V*
A IN 53 ≈ 5kΩ
Terminal 53
A IN 54
High Voltage
COM 55
Parameter 6-14 0 RPM
A OUT 42
COM
Terminal 53
39
Low Ref./Feedb.
Value
U-I
Parameter 6-15 1500 RPM
Terminal 53
A53 High Ref./Feedb.
Value
*=Default value
Notes/comments:
130BB840.12
Reference
Parameters
Function Setting
e30bb683.11
FC
Parameter 6-10 0.07 V* Start (18)
Terminal 53 Freeze ref (27)
Low Voltage
Speed up (29)
+10 V 50 Parameter 6-11 10 V*
A IN 53 ≈ 5kΩ Speed down (32)
Terminal 53
A IN 54
High Voltage
COM 55 Illustration 8.3 Speed Up/Speed Down
Parameter 6-14 0 RPM
A OUT 42
COM
Terminal 53
39
Low Ref./Feedb.
Value
8.8 Wiring Configuration for RS485 Network
U-I
Parameter 6-15 1500 RPM Connection
Terminal 53
Parameters
A53 High Ref./Feedb.
Function Setting
Value
130BB685.10
FC
Parameter 8-30 FC*
*=Default value +24 V 12
+24 V 13 Protocol
Notes/comments:
D IN 18 Parameter 8-31 1*
D IN
COM
19
20
Address
Parameter 8-32 9600*
8 8
Table 8.10 Wiring Configuration for Speed Reference
D IN 27 Baud Rate
D IN 29 *=Default value
(Using a Manual Potentiometer)
D IN 32
D IN 33
Notes/comments:
8.7 Wiring Configuration for Speed Up/ D IN 37 Select protocol, address, and
Speed Down baud rate in the parameters.
+10 V 50
Parameters A IN 53
Function Setting A IN 54
FC
Parameter 5-10 [8] Start* COM 55
+24 V 12
A OUT 42
+24 V 13 Terminal 18
COM 39
D IN 18 Digital Input
D IN 19 Parameter 5-12 [19] Freeze
01
COM 20 Terminal 27 Reference
02
R1
D IN 27 Digital Input
03
D IN 29 Parameter 5-13 [21] Speed Up
D IN 32 Terminal 29 04
D IN 33 Digital Input 05
R2
e30bb804.12
D IN 37 RS-485
Parameter 5-14 [22] Speed 06
Terminal 32 Down
61
Digital Input 68
+
*=Default value 69
-
Notes/comments:
8.9 Wiring Configuration for a Motor 8.10 Wiring Configuration for a Cascade
Thermistor Controller
NOTICE Illustration 8.4 shows an example with the built-in basic
Thermistors must use reinforced or double insulation to cascade controller with 1 variable-speed pump (lead) and 2
meet PELV insulation requirements. fixed-speed pumps, a 4–20 mA transmitter, and system
safety interlock.
Parameters
Function Setting
VLT
Parameter 1-90 [2] Thermistor
+24 V 12
Motor Thermal trip
+24 V 13
Protection
D IN 18
D IN 19 Parameter 1-93 [1] analog
COM 20 Thermistor input 53
D IN 27 Source
D IN 29 *=Default value
D IN 32
D IN 33 Notes/comments:
D IN 37 If only a warning is wanted, set
parameter 1-90 Motor Thermal
8 8 +10 V
A IN
50
53
Protection to [1] Thermistor
warning.
A IN 54
COM 55
A OUT 42
COM 39
130BB686.12
U-I
A53
130BA378.10
Power Card Control Card
(Safety Interlock)
(Feedback 1 res.)
pump 1.)
pump 2.)
(cascade
(cascade
RELAY 1
RELAY 2
D IN1/D OUT
D IN1/D OUT
COM A OUT
+ 24V OUT
+ 10V OUT
+24V OUT
COM D IN
COM A IN
A OUT1
(Start)
D IN 1
D IN 1
D IN 1
D IN1
A IN1
A IN2
MOTOR MAINS
96 97 98 91 92 93
PE 01 02 03 04 05 06 12 13 18 19 27 29 32 33 20 39 42 50 53 54 55
U V W L1 L2 L3
System System
Start/ Safety
Stop Interlock
L1
L2
L3
PE
8 8
M M M
8.11 Wiring Configuration for Relay Set-up 8.12 Wiring Configuration for a Fixed
with Smart Logic Control Variable Speed Pump
Parameters L1/L2/L3 L1/L2/L3 L1/L2/L3
130BA376.10
Function Setting
130BB839.10
FC
+24 V 12 Parameter 4-30 [1] Warning
+24 V 13 Motor Feedback
Power Section
D IN 18 Loss Function
D IN 19 Parameter 4-31 100 RPM
RELAY 1
RELAY 2
COM 20 Motor Feedback
D IN 27 Speed Error
D IN 29
Parameter 4-32 5s
D IN 32
Motor Feedback
D IN 33
Loss Timeout
D IN 37
Parameter 7-00 S [2] MCB 102
+10 V 50
peed PID
A IN 53 Feedback Source
A IN 54 Parameter 17-11 1024*
COM 55 Resolution (PPR)
A OUT 42 Parameter 13-00 [1] On
8 8
COM 39 SL Controller
Illustration 8.5 Fixed Variable Speed Pump Wiring Diagram
Mode
01
Parameter 13-01 [19] Warning
02
R1
Start Event
03
Parameter 13-02 [44] Reset key
8.13 Wiring Configuration for Lead Pump
Stop Event Alternation
04
05 Parameter 13-10 [21] Warning
R2
130BA377.13
06 Comparator no.
Operand FC
Parameter 13-11 [1] ≈ (equal)*
Comparator
Operator
R1
R2
Parameter 13-12 90
Comparator
Value
Parameter 13-51 [22]
k3 k3 K1 K1
SL Controller Comparator 0
Event k2 k1 K4 K3
K1 K2 K3 K4
Parameter 13-52 [32] Set digital
SL Controller out A low
Action
Parameter 5-40 F [80] SL digital
unction Relay output A Illustration 8.6 Lead Pump Alternation Wiring Diagram
*=Default value
Notes/comments:
If the limit in the feedback monitor is exceeded, warning 90, Every pump must be connected to 2 contactors (K1/K2 and
Feedback Mon. is issued. The SLC monitors warning 90, Feedback K3/K4) with a mechanical interlock. Thermal relays or other
Mon. and if the warning becomes true, relay 1 is triggered. motor overload protection devices must be applied
External equipment may require service. If the feedback error according to local regulation and/or individual demands.
goes below the limit again within 5 s, the drive continues and
the warning disappears. Reset relay 1 by pressing [Reset] on the • Relay 1 (R1) and relay 2 (R2) are the built-in relays
LCP. in the drive.
Table 8.14 Wiring Configuration for a Relay Set-up with • When all relays are de-energized, the 1st built-in
Smart Logic Control relay that is energized cuts in the contactor
corresponding to the pump controlled by the
8 8
130BD430.10
• Maintenance and service guidelines.
• Status messages.
• Warnings and alarms.
• Basic troubleshooting.
WARNING
UNINTENDED START
When the drive is connected to AC mains, DC supply, or
9 9 load sharing, the motor can start at any time. Illustration 9.1 Heat Sink Access Panel
Unintended start during programming, service, or repair
work can result in death, serious injury, or property
damage. The motor can start with an external switch, a
fieldbus command, an input reference signal from the NOTICE
LCP or LOP, via remote operation using MCT 10 Set-up DAMAGE TO HEAT SINK
Software, or after a cleared fault condition. Using fasteners that are longer than those originally
supplied with the heat sink panel can damage the heat
To prevent unintended motor start:
sink cooling fins.
• Press [Off/Reset] on the LCP before
programming parameters.
1. Remove power from the drive and wait 20
• Disconnect the drive from the mains.
minutes for the capacitors to discharge
• Completely wire and assemble the drive, motor, completely. Refer to chapter 2 Safety.
and any driven equipment before connecting
2. Position the drive so that the back of the drive is
the drive to AC mains, DC supply, or load
accessible.
sharing.
3. Remove the screws (3 mm [0.12 in] internal hex)
connecting the access panel to the back of the
9.2 Heat Sink Access Panel enclosure. There are 5 or 9 screws depending on
the size of the drive.
9.2.1 Removing the Heat Sink Access Panel
4. Inspect the heat sink for damage or dust buildup.
The drive can be ordered with an optional access panel in 5. Remove dust and debris with a vacuum.
the back of the unit. This panel provides access to the heat 6. Replace the panel and secure it to the back of
sink and allows the heat sink to be cleaned of any dust the enclosure with the screws previously
buildup. removed. Tighten the fasteners according to
chapter 10.8 Fastener Tightening Torques.
9.3 Status Messages AC brake AC brake was selected in parameter 2-10 Brake
Function. The AC brake overmagnetizes the
When the drive is in status mode, status messages motor to achieve a controlled slow-down.
automatically appear in the lowest line of the LCP display. AMA finish OK Automatic motor adaptation (AMA) was
Refer to Illustration 9.2. Status messages are defined in carried out successfully.
Table 9.1 – Table 9.3. AMA ready AMA is ready to start. To start, press [Hand
On].
AMA running AMA process is in progress.
130BB037.11
Status 1(1)
799RPM 7.83A 36.4kW
Braking The brake chopper is in operation. The brake
resistor absorbs the generative energy.
0.000
53.2% Braking max. The brake chopper is in operation. The power
limit for the brake resistor defined in
parameter 2-12 Brake Power Limit (kW) has
been reached.
Current high The drive output current is above the limit set
NOTICE in parameter 4-51 Warning Current High.
In auto/remote mode, the drive requires external Current low The drive output current is below the limit set
commands to execute functions. in parameter 4-52 Warning Speed Low.
DC hold DC hold is selected in parameter 1-80 Function
Table 9.1 to Table 9.3 define the meaning of the shown at Stop and a stop command is active. The
status messages. motor is held by a DC current set in
parameter 2-00 DC Hold Current.
Off The drive does not react to any control signal DC stop The motor is held with a DC current
until [Auto On] or [Hand On] is pressed. (parameter 2-01 DC Brake Current) for a
Auto The start/stop commands are sent via the specified time (parameter 2-02 DC Braking
control terminals and/or the serial communi- Time).
cation. • DC brake is activated in parameter 2-03 DC
Hand The navigation keys on the LCP can be used Brake Cut In Speed [RPM] and a stop
to control the drive. Stop commands, reset, command is active.
reversing, DC brake, and other signals applied • DC brake (inverse) is selected as a function
to the control terminals override local control. for a digital input (parameter group 5-1*
Digital Inputs). The corresponding terminal
Table 9.1 Operating Mode
is not active.
Remote The speed reference is given from: • The DC brake is activated via serial
• External signals. communication.
• Serial communication. Feedback high The sum of all active feedbacks is above the
feedback limit set in parameter 4-57 Warning
• Internal preset references.
Feedback High.
Local The drive uses reference values from the LCP. Feedback low The sum of all active feedbacks is below the
feedback limit set in parameter 4-56 Warning
Table 9.2 Reference Site
Feedback Low.
Freeze output The remote reference, which holds the present Protection md Protection mode is active. The unit has
speed, is active. detected a critical status (an overcurrent or
• [20] Freeze Output was selected as a overvoltage).
function for a digital input (parameter • To avoid tripping, the switching frequency
group 5-1* Digital Inputs). The is reduced to 1500 kHz if
corresponding terminal is active. Speed parameter 14-55 Output Filter is set to [2]
control is only possible via the terminal Sine-Wave Filter Fixed. Otherwise, the
functions speed up and speed down. switching frequency is reduced to 1000 Hz.
• Hold ramp is activated via serial communi- • If possible, protection mode ends after
cation. approximately 10 s.
Freeze output A freeze output command has been given, but • Protection mode can be restricted in
request the motor remains stopped until a run parameter 14-26 Trip Delay at Inverter Fault.
permissive signal is received.
QStop The motor is decelerating using
Freeze ref. [19] Freeze Reference was selected as a parameter 3-81 Quick Stop Ramp Time.
function for a digital input (parameter group
• [4] Quick stop inverse was selected as a
5-1* Digital Inputs). The corresponding terminal function for a digital input (parameter
is active. The drive saves the actual reference. group 5-1* Digital Inputs). The
Changing the reference is now only possible corresponding terminal is not active.
via terminal functions speed up and speed
down. • The quick stop function was activated via
serial communication.
Jog request A jog command has been given, but the
motor is stopped until a run permissive signal Ramping The motor is accelerating/decelerating using
is received via a digital input. the active ramp up/down. The reference, a
Start fwd/rev [12] Enable Start Forward and [13] Enable Start Trip
Reverse were selected as functions for 2 When tripping, the drive suspends operation to prevent
different digital inputs (parameter group 5-1* damage to the drive and other equipment. When a trip
Digital Inputs). The motor starts in forward or occurs, the motor coasts to a stop. The drive logic
reverse depending on which corresponding continues to operate and monitor the drive status. After
terminal is activated. the fault condition is remedied, the drive is ready for a
Stop The drive has received a stop command from reset.
1 of the following: Trip lock
• LCP. When trip locking, the drive suspends operation to prevent
• Digital input. damage to the drive and other equipment. When a trip
lock occurs, the motor coasts to a stop. The drive logic
• Serial communication.
continues to operate and monitor the drive status. The
Trip An alarm occurred and the motor is stopped. drive starts a trip lock only when serious faults occur that
Once the cause of the alarm is cleared, reset can damage the drive or other equipment. After the faults
the drive using 1 of the following: are fixed, cycle the input power before resetting the drive.
• Pressing [Reset].
Warning and alarm displays
• Remotely by control terminals.
• A warning is shown in the LCP along with the
• Via serial communication.
warning number.
Pressing [Reset] or remotely by control
terminals or via serial communication.
• An alarm flashes along with the alarm number.
130BP086.12
Once the cause of the alarm is cleared, cycle Status 1(1)
power to the drive. Reset the drive manually 0.0Hz 0.000kW 0.00A
by 1 of the following: 0.0Hz
0
9 9
• Pressing [Reset].
• Remotely by control terminals.
nc
Ba
resolved.
Alarm On
Info
OK
An alarm indicates a fault that requires immediate
attention. The fault always triggers a trip or trip lock. Reset Warn.
WARNING/ALARM 11, Motor thermistor overtemp • Check that the motor size matches the drive. 9 9
Check whether the thermistor is disconnected. Select • Check that the motor data is correct in
whether the drive issues a warning or an alarm in parameters 1-20 to 1-25.
parameter 1-90 Motor Thermal Protection.
ALARM 14, Earth (ground) fault
Troubleshooting There is current from the output phase to ground, either in
• Check for motor overheating. the cable between the drive and the motor, or in the
• Check if the motor is mechanically overloaded. motor itself. The current transducers detect the ground
fault by measuring current going out from the drive and
• When using terminal 53 or 54, check that the
current going into the drive from the motor. Ground fault
thermistor is connected correctly between either
is issued if the deviation of the 2 currents is too large. The
terminal 53 or 54 (analog voltage input) and
current going out of the drive must be the same as the
terminal 50 (+10 V supply). Also check that the
current going into the drive.
terminal switch for 53 or 54 is set for voltage.
Check that parameter 1-93 Thermistor Resource Troubleshooting
selects terminal 53 or 54. • Remove power to the drive and repair the ground
fault.
• When using terminal 18, 19, 31, 32, or 33 (digital
inputs), check that the thermistor is connected • Check for ground faults in the motor by
correctly between the digital input terminal used measuring the resistance to ground of the motor
(digital input PNP only) and terminal 50. Select cables and the motor with a megohmmeter.
the terminal to use in parameter 1-93 Thermistor • Reset any potential individual offset in the 3
Resource. current transducers in the drive. Perform the
WARNING/ALARM 12, Torque limit manual initialization or perform a complete AMA.
The torque has exceeded the value in This method is most relevant after changing the
parameter 4-16 Torque Limit Motor Mode or the value in power card.
parameter 4-17 Torque Limit Generator Mode. ALARM 15, Hardware mismatch
Parameter 14-25 Trip Delay at Torque Limit can change this A fitted option is not operational with the present control
warning from a warning-only condition to a warning card hardware or software.
followed by an alarm.
Record the value of the following parameters and contact
Danfoss.
• Parameter 15-40 FC Type.
• Parameter 15-41 Power Section.
• Parameter 15-42 Voltage. 0 = The torque reference was not reached before timeout
(parameter 2-27 Torque Ramp Time).
• Parameter 15-43 Software Version.
1 = Expected brake feedback was not received before
• Parameter 15-45 Actual Typecode String. timeout (parameter 2-23 Activate Brake Delay,
• Parameter 15-49 SW ID Control Card. parameter 2-25 Brake Release Time).
parameter 1-86 Trip Speed Low [RPM] (except when starting WARNING 62, Output frequency at maximum limit
or stopping), the drive trips. If the output frequency reaches the value set in
parameter 4-19 Max Output Frequency, the drive issues a
ALARM 50, AMA calibration failed
warning. The warning ceases when the output drops
Contact the Danfoss supplier or Danfoss service
below the maximum limit. If the drive is unable to limit
department.
the frequency, it trips and issues an alarm. The latter may
ALARM 51, AMA check Unom and Inom happen in the flux mode if the drive loses control of the
The settings for motor voltage, motor current, and motor motor.
power are wrong.
Troubleshooting
Troubleshooting • Check the application for possible causes.
• Check the settings in parameters 1-20 to 1-25.
• Increase the output frequency limit. Ensure that
ALARM 52, AMA low Inom the system can operate safely at a higher output
The motor current is too low. frequency.
Troubleshooting ALARM 63, Mechanical brake low
• Check the settings in parameter 1-24 Motor The actual motor current has not exceeded the release
Current. brake current within the start delay time window.
ALARM 53, AMA motor too big WARNING 64, Voltage Limit
The motor is too large for the AMA to operate. The load and speed combination demands a motor
ALARM 54, AMA motor too small voltage higher than the actual DC-link voltage.
The motor is too small for the AMA to operate. WARNING/ALARM 65, Control card over temperature
ALARM 55, AMA parameter out of range The cutout temperature of the control card is 85 °C
The AMA cannot run because the parameter values of the (185 °F).
WARNING 76, Power unit setup • To apply the change, enable option layout
The required number of power units does not match the changes in parameter 14-89 Option Detection.
detected number of active power units. When replacing an • Alternatively, restore the correct option configu-
enclosure size F module, this warning occurs if the power- ration.
specific data in the module power card does not match
WARNING 89, Mechanical brake sliding
the rest of the drive. If the power card connection is lost,
The hoist brake monitor detects a motor speed exceeding
the unit also triggers this warning.
10 RPM.
Troubleshooting
ALARM 90, Feedback monitor
• Confirm that the spare part and its power card Check the connection to encoder/resolver option and, if
are the correct part number.
necessary, replace VLT® Encoder Input MCB 102 or VLT®
• Ensure that the 44-pin cables between the MDCIC Resolver Input MCB 103.
and power cards are mounted properly.
ALARM 91, Analog input 54 wrong settings
WARNING 77, Reduced power mode Set switch S202 in position OFF (voltage input) when a
This alarm applies to only multi-drive systems. The system KTY sensor is connected to analog input terminal 54.
is operating in reduced power mode (fewer than the
allowed number of drive modules). This warning is
generated on power cycle when the system is set to run
with fewer drive modules and remains on.
The report value in the alarm log indicates which drive ALARM 247, Power card temperature
module generated the alarm: This alarm is only for multi-drive systems. It is equivalent to
alarm 69, Power card temperature. The report value in the
1 = Left drive module.
alarm log indicates which drive module generated the
2 = Second drive module from left. alarm:
3 = Third drive module from left (in 4-module 1 = Left drive module.
module systems).
2 = Second drive module from left.
4 = Fourth drive module from left (in 4-module
3 = Third drive module from left (in 4-module
module systems).
module systems).
ALARM 245, Heat sink sensor
4 = Fourth drive module from left (in 4-module
No feedback from the heat sink temperature sensor. The
module systems).
signal from the IGBT thermal sensor is not available on the
power card. This alarm is equivalent to alarm 39, Heat sink ALARM 248, Illegal power section configuration
sensor. The report value in the alarm log indicates which This alarm is only for multi-drive systems. It is equivalent to
drive module generated the alarm: alarm 79, Illegal power section configuration. The report
value in the alarm log indicates which drive module
1 = Left drive module.
generated the alarm:
2 = Second drive module from left.
1 = Left drive module.
3 = Third drive module from left (in 4-module
2 = Second drive module from left.
module systems).
3 = Third drive module from left (in 4-module
4 = Fourth drive module from left (in 4-module
module systems).
module systems).
4 = Fourth drive module from left (in 4-module
Troubleshooting
Check the following: module systems). 9 9
Troubleshooting
• Power card.
Check the following:
• Gatedrive card.
• The current scaling cards on the MDCIC.
• Ribbon cable between the power card and the
WARNING 250, New spare part
gatedrive card.
The power or switch mode supply has been exchanged.
ALARM 246, Power card supply Restore the drive type code in the EEPROM. Select the
This alarm is only for multi-drive systems. It is equivalent to correct type code in parameter 14-23 Typecode Setting
alarm 46, Power card supply. The report value in the alarm according to the label on the drive. Remember to select
log indicates which drive module generated the alarm: Save to EEPROM at the end.
1 = Left drive module. WARNING 251, New type code
2 = Second drive module from left. The power card or other components have been replaced
and the type code has been changed.
3 = Third drive module from left (in 4-module
module systems). Troubleshooting
9.6 Troubleshooting
Symptom Possible cause Test Solution
Display Missing input power. See Table 6.1. Check the input power source.
dark/No Missing or open fuses. See Open power fuses in this table for possible Follow the recommendations provided.
function causes.
No power to the LCP. Check the LCP cable for proper connection or Replace the faulty LCP or connection
damage. cable.
Shortcut on control voltage Check the 24 V control voltage supply for Wire the terminals properly.
(terminal 12 or 50) or at control terminal 12/13 to 20–39, or 10 V supply for
terminals. terminals 50–55.
Incompatible LCP (LCP from – Use only LCP 101 (P/N 130B1124) or LCP
VLT® 2800 or 5000/6000/8000/ 102 (P/N 130B1107).
FCD or FCM).
Wrong contrast setting. – Press [Status] + [▲]/[▼] to adjust the
contrast.
Display (LCP) is defective. Test using a different LCP. Replace the faulty LCP or connection
cable.
Internal voltage supply fault or – Contact supplier.
SMPS is defective.
Intermittent Overloaded supply (SMPS) due To rule out a problem in the control wiring, If the display stays lit, the problem is in
display to improper control wiring or a disconnect all control wiring by removing the the control wiring. Check the wiring for
fault within the AC drive. terminal blocks. shorts or incorrect connections. If the
Motor Motor rotation limit. Check that parameter 4-10 Motor Speed Program correct settings.
running in Direction is programmed correctly.
wrong Active reversing signal. Check if a reversing command is programmed Deactivate reversing signal.
direction for the terminal in parameter group 5-1*
Digital inputs.
Wrong motor phase – See chapter 7.3.1 Warning - Motor Start.
connection.
10 Specifications
Table 10.1 Electrical Data for Enclosures D1h/D3h, Mains Supply 3x200–240 V AC
1) For fuse ratings, see chapter 10.7 Fuses and Circuit Breakers.
2) Typical power loss is at normal conditions and expected to be within ±15% (tolerance relates to variety in voltage and cable conditions). These
values are based on a typical motor efficiency (IE/IE3 border line). Lower efficiency motors add to the power loss in the drive. Applies to
dimensioning of drive cooling. If the switching frequency is higher than the default setting, the power losses can increase. LCP and typical control
card power consumptions are included. For power loss data according to EN 50598-2, refer to www.danfoss.com/vltenergyefficiency. Options and
customer load can add up to 30 W to the losses, though usually a fully loaded control card and options for slots A and B each add only 4 W.
3) Measured using 5 m (16.4 ft) shielded motor cables at rated load and rated frequency. Efficiency measured at nominal current. For energy
efficiency class, see chapter 10.4 Ambient Conditions. For part load losses, see www.danfoss.com/vltenergyefficiency.
Table 10.2 Electrical Data for Enclosures D2h/D4h, Mains Supply 3x200–240 V AC
1) For fuse ratings, see chapter 10.7 Fuses and Circuit Breakers.
2) Typical power loss is at normal conditions and expected to be within ±15% (tolerance relates to variety in voltage and cable conditions). These
values are based on a typical motor efficiency (IE/IE3 border line). Lower efficiency motors add to the power loss in the drive. Applies to
dimensioning of drive cooling. If the switching frequency is higher than the default setting, the power losses can increase. LCP and typical control 10 10
card power consumptions are included. For power loss data according to EN 50598-2, refer to www.danfoss.com/vltenergyefficiency. Options and
customer load can add up to 30 W to the losses, though usually a fully loaded control card and options for slots A and B each add only 4 W.
3) Measured using 5 m (16.4 ft) shielded motor cables at rated load and rated frequency. Efficiency measured at nominal current. For energy
efficiency class, see chapter 10.4 Ambient Conditions. For part load losses, see www.danfoss.com/vltenergyefficiency.
10 10 Efficiency3)
Output frequency [Hz]
0.98
0–590
0.98
0–590
0.98
0–590
Heat sink overtemperature trip [°C (°F)] 110 (230) 110 (230) 110 (230)
Control card overtemperature trip [°C (°F)] 75 (167) 75 (167) 75 (167)
Table 10.3 Electrical Data for Enclosures D1h/D3h/D5h/D6h, Mains Supply 3x380–480 V AC
1) For fuse ratings, see chapter 10.7 Fuses and Circuit Breakers.
2) Typical power loss is at normal conditions and expected to be within ±15% (tolerance relates to variety in voltage and cable conditions). These
values are based on a typical motor efficiency (IE/IE3 border line). Lower efficiency motors add to the power loss in the drive. Applies to
dimensioning of drive cooling. If the switching frequency is higher than the default setting, the power losses can increase. LCP and typical control
card power consumptions are included. For power loss data according to EN 50598-2, refer to www.danfoss.com/vltenergyefficiency. Options and
customer load can add up to 30 W to the losses, though usually a fully loaded control card and options for slots A and B each add only 4 W.
3) Measured using 5 m (16.4 ft) shielded motor cables at rated load and rated frequency. Efficiency measured at nominal current. For energy
efficiency class, see chapter 10.4 Ambient Conditions. For part load losses, see www.danfoss.com/vltenergyefficiency.
10 10 Efficiency3)
Output frequency [Hz]
0.98
0–590
0.98
0–590
0.98
0–590
0.98
0–590
0.98
0–590
Heat sink overtemperature trip [°C (°F)] 110 (230) 110 (230) 110 (230) 110 (230) 110 (230)
Control card overtemperature trip [°C (°F)] 75 (167) 75 (167) 75 (167) 75 (167) 75 (167)
Table 10.5 Electrical Data for Enclosures D1h/D3h/D5h/D6h, Mains Supply 3x525–690 V AC
1) For fuse ratings, see chapter 10.7 Fuses and Circuit Breakers.
2) Typical power loss is at normal conditions and expected to be within ±15% (tolerance relates to variety in voltage and cable conditions). These
values are based on a typical motor efficiency (IE/IE3 border line). Lower efficiency motors add to the power loss in the drive. Applies to
dimensioning of drive cooling. If the switching frequency is higher than the default setting, the power losses can increase. LCP and typical control
card power consumptions are included. For power loss data according to EN 50598-2, refer to www.danfoss.com/vltenergyefficiency. Options and
customer load can add up to 30 W to the losses, though usually a fully loaded control card and options for slots A and B each add only 4 W.
3) Measured using 5 m (16.4 ft) shielded motor cables at rated load and rated frequency. Efficiency measured at nominal current. For energy
efficiency class, see chapter 10.4 Ambient Conditions. For part load losses, see www.danfoss.com/vltenergyefficiency.
Torque characteristics
Starting torque (constant torque) Maximum 150% for 60 s1), 2)
Overload torque (constant torque) Maximum 150% for 60 s1), 2)
1) Percentage relates to the nominal current of the drive.
2) Once every 10 minutes.
Analog inputs
Number of analog inputs 2
Terminal number 53, 54
Modes Voltage or current
Mode select Switches A53 and A54
Voltage mode Switch A53/A54=(U) 10 10
Voltage level -10 V to +10 V (scaleable)
Input resistance, Ri Approximately 10 kΩ
Maximum voltage ±20 V
Current mode Switch A53/A54=(I)
Current level 0/4 to 20 mA (scaleable)
Input resistance, Ri Approximately 200 Ω
Maximum current 30 mA
Resolution for analog inputs 10 bit (+ sign)
Accuracy of analog inputs Maximum error 0.5% of full scale
Bandwidth 100 Hz
The analog inputs are galvanically isolated from the supply voltage (PELV) and other high-voltage terminals.
PELV isolation
130BA117.10
+24 V
Control Mains
18
High
voltage Motor
37
Functional
isolation
RS485 DC-bus
Pulse inputs
Programmable pulse inputs 2
Terminal number pulse 29, 33
Maximum frequency at terminal 29, 33 (push-pull driven) 110 kHz
Maximum frequency at terminal 29, 33 (open collector) 5 kHz
Analog output
Number of programmable analog outputs 1
Terminal number 42
Current range at analog output 0/4–20 mA
Maximum resistor load to common at analog output 500 Ω
Accuracy on analog output Maximum error: 0.8% of full scale
Resolution on analog output 8 bit
The analog output is galvanically isolated from the supply voltage (PELV) and other high-voltage terminals.
Digital output
Programmable digital/pulse outputs 2
Terminal number 27, 291)
Voltage level at digital/frequency output 0–24 V
Maximum output current (sink or source) 40 mA
Maximum load at frequency output 1 kΩ
10 10 Maximum capacitive load at frequency output 10 nF
Minimum output frequency at frequency output 0 Hz
Maximum output frequency at frequency output 32 kHz
Accuracy of frequency output Maximum error: 0.1% of full scale
Resolution of frequency outputs 12 bit
1) Terminals 27 and 29 can also be programmed as inputs.
The digital output is galvanically isolated from the supply voltage (PELV) and other high-voltage terminals.
Relay outputs
Programmable relay outputs 2
Maximum cross-section to relay terminals 2.5 mm2 (12 AWG)
Minimum cross-section to relay terminals 0.2 mm2 (30 AWG)
Length of stripped wire 8 mm (0.3 in)
Relay 01 terminal number 1–3 (break), 1–2 (make)
Maximum terminal load (AC-1)1) on 1–2 (NO) (Resistive load)2), 3) 400 V AC, 2 A
Maximum terminal load (AC-15)1) on 1–2 (NO) (Inductive load @ cosφ 0.4) 240 V AC, 0.2 A
Maximum terminal load (DC-1)1) on 1–2 (NO) (Resistive load) 80 V DC, 2 A
Maximum terminal load (DC-13)1) on 1–2 (NO) (Inductive load) 24 V DC, 0.1 A
Maximum terminal load (AC-1)1) on 1–3 (NC) (Resistive load) 240 V AC, 2 A
Maximum terminal load (AC-15)1) on 1–3 (NC) (Inductive load @ cosφ 0.4) 240 V AC, 0.2 A
Maximum terminal load (DC-1)1) on 1–3 (NC) (Resistive load) 50 V DC, 2 A
Maximum terminal load (DC-13)1) on 1–3 (NC) (Inductive load) 24 V DC, 0.1 A
Minimum terminal load on 1–3 (NC), 1–2 (NO) 24 V DC 10 mA, 24 V AC 2 mA
Control characteristics
Resolution of output frequency at 0–1000 Hz ±0.003 Hz
System response time (terminals 18, 19, 27, 29, 32, 33) ≤2 m/s
Speed control range (open loop) 1:100 of synchronous speed 10 10
Speed accuracy (open loop) 30–4000 RPM: Maximum error of ±8 RPM
All control characteristics are based on a 4-pole asynchronous motor.
NOTICE
Connection to PC is carried out via a standard host/device USB cable.
The USB connection is galvanically isolated from the supply voltage (PELV) and other high-voltage terminals.
The USB connection is not galvanically isolated from ground. Use only isolated laptop/PC as connection to the USB
connector on the drive or an isolated USB cable/converter.
Installing fuses on the supply side ensures that potential damage is contained inside the drive enclosure if a component
breakdown (first fault) occurs inside the drive. Use the recommended fuses to ensure compliance with EN 50178, refer to
Table 10.7, Table 10.8, and Table 10.9.
NOTICE
Use of fuses on the supply side is mandatory for IEC 60364 (CE) and NEC 2009 (UL) compliant installations.
10 10 N132
N160
170M2621
170M4015
N200 170M4016
N250 170M4018
Type aR fuses are recommended for drives in enclosure sizes D3h–D4h. See Table 10.10.
Bussmann Rating
LPJ-21/2SP 2.5 A, 600 V
For UL compliance, use the Bussmann 170M series fuses for units supplied without a disconnect, contactor, or circuit breaker
option. If a disconnect, contactor, or circuit breaker option is supplied with the drive, see Table 10.12 to Table 10.15 for SCCR
ratings and UL fuse criteria.
The short-circuit current rating (SCCR) represents the maximum level of short-circuit current that the drive can safely
10 10
withstand. If the drive is not supplied with a mains disconnect, contactor, or circuit breaker, the SCCR of the drive is 100000
A at all voltages (200–690 V).
If the drive is supplied with a mains disconnect only, the SCCR of the drive is 100000 amps at all voltages (200–600 V). See
Table 10.12. If the drive is supplied with a contactor only, refer to Table 10.13 for the SCCR. If the drive contains both a
contactor and disconnect, see Table 10.14.
If the drive is supplied with a circuit breaker only, the SCCR depends on the voltage. Refer to Table 10.15.
Table 10.12 D5h and D7h Drives Supplied with a Disconnect Only
1) With an upstream branch protection Class J fuse with maximum rating of 600 A.
2) With an upstream branch protection Class J fuse with maximum rating of 800 A.
Table 10.13 D6h and D8h Drives Supplied with a Contactor Only
1) With gL/gG fuses: 425 A maximum fuse size for D6h, and 630 A maximum fuse size for D8h.
2) With external upstream Class J fuses: 450 A maximum fuse size for D6h, and 600 A maximum fuse size for D8h.
Table 10.14 D6h and D8h Drives Supplied with a Disconnect and Contactor
1) With gL/gG fuses: 425A maximum fuse size for D6h, and 630A maximum fuse size for D8h.
2) With external upstream Class J fuses: 450 A maximum fuse size for D6h, and 600 A maximum fuse size for D8h.
130BE982.10
99 (3.9)
164 (6.5)
667 (26.3)
500 (19.7) 10 10
130BF797.10
378 (14.9)
82 (3.2)
18 (0.7)
20 (0.8)
148 (5.8)
844 (33.2)
10 10 561 (22.1)
130BF798.10
325 (12.8)
A
33
(1.3)
246 (9.7)
180 (7.1) 25
(1.0)
A 11 (0.4)
123
(4.8)
130 (5.1)
78
(3.1)
200 (7.9)
893
(35.2)
844
(33.2)
10 10
656
(25.8)
63 (2.5)
11
(0.4)
20
(0.8)
24
B 9 (0.9)
(0.3)
200 (7.9)
130BF669.10
298 (11.7)
105
404 (15.9)
130BF607.10
137 (5.4)
1 2
138 (5.4)
205 (8.1)
130BF321.10
96 (3.8)
211 (8.3)
871 (34.3)
10 10
602 (23.7)
378 (14.9)
130BF799.10
142 (5.6)
18 (0.7)
20 (0.8)
148 (5.8)
1050 (41.3)
10 10 718 (28.3)
130BF800.10
420 (16.5)
346 (13.6)
A
130 (5.1)
11 (0.4)
107
(4.2)
213 (8.4)
1099
(43.3)
320 (12.6)
1051
(41.4)
10 10
857 (33.7) 75 (2.9)
B
11 (0.4)
20 (0.8)
24 (0.9)
9 (0.3)
B
271 (10.7)
130BF670.10
395 (15.6)
105
523 (20.6)
130BF608.10
369 (14.5)
27 (1.0) 185 (7.3)
1 2
145 (5.7)
196 (7.7)
130BF322.10
61 (2.4)
128 (5.0)
10 10
660 (26.0)
495 (19.5)
130BF801.10
375 (14.8)
82 (3.2)
39 (1.5)
18 (0.7)
20 (0.8)
130BF802.10
250 (9.8)
A
180 (7.1)
A
33 (1.3)
123 M10
(4.8)
130 (5.1)
25 (1.0)
78 (3.1)
200 (7.9)
889 (35.0)
844 (33.2)
656 (25.8)
10 10
25 (1.0)
11 (0.4)
M10
20 (0.8)
24
200 (7.9) (0.9)
9 (0.3)
130BF323.10
59 (2.3)
176 (6.9)
10 10
868 (34.2)
611 (24.1)
39 (1.5)
130BF803.10
375 (14.8)
18 (0.7)
142 (5.6)
20 (0.8)
148 (5.8)
10 10
1050 (41.3)
130BF804.10
350 (13.8)
280 (11.0)
A
A
33 (1.3)
107
(4.2)
1122 (44.2)
213 (8.4)
320 (12.6)
1096 (43.1)
1051 (41.4)
10 10
857 (33.7)
B
40
(1.6)
11 (0.4)
24 (0.9)
20 (0.8)
B
9 (0.3)
271 (10.7)
130BF324.10
149 (5.9)
1107 (43.6)
10 10
733 (28.9)
381 (15.0)
130BF805.10
115 (4.5)
23 (0.9)
161 (6.3)
1277 (50.3)
10 10
130BF806.10
325 (12.8)
306 (12.1)
276 (10.9)
180 (7.1)
A
A
63 (2.5)
123 15 (0.6)
(4.8)
M10
130
(5.1)
78
25
(3.1)
(1)
200 4X 11 (0.4)
(7.9)
1324
(52.1)
10 10
1276
(50.2)
1111
(43.7)
123
(4.8)
B
64
130 (5.1) (2.5)
11 (0.4)
78
(3.1 M10
200 (7.9)
130BF828.10
433 (17.0)
218 (8.6)
10 10 670 (26.4)
130BF669.10
298 (11.7)
105
404 (15.9)
10 10
130BF609.10
242 (9.5)
121 (4.8)
43 (1.7)
1 2
224 (8.8)
111 (4.4)
130BF325.10
159 (6.3)
1447 (57.0)
10 10
909 (35.8)
130BF807.10
381 (15.0)
115 (4.5)
23 (0.9)
181 (7.1)
1617 (63.7)
10 10
130BF808.10
325 (12.8)
306 (12.1)
276 (10.9)
A
180 (7.1) 63 (2.5)
A
130 M10
15 (0.6)
(5.1)
123
(4.8)
25 (1)
78
(3.1)
200 4X 11 (0.4)
(7.9)
1663
(65.5)
1615
(63.6)
1452
(57.2)
10 10 123
(4.8)
130 (5.1)
78
(3.1)
200 B
(7.9)
11 (0.4)
64 (3.0)
559 (22.0)
M10
24 (0.9)
20 (0.8) 9 (0.1)
B
200 (7.9)
130BF829.10
433 (17.0)
218 (8.6)
1009 (39.7)
10 10
130BF669.10
298 (11.7)
105
404 (15.9)
10 10
130BF609.10
242 (9.5)
121 (4.8)
43 (1.7)
1 2
224 (8.8)
111 (4.4)
130BF326.10
209 (8.2)
1754 (69.1)
1282 (50.5)
10 10
130BF809.10
386 (15.2)
156 (6.2)
23 (0.9)
25 (1.0)
161 (6.3)
193 (76.0)
10 10
130BF810.10
420 (16.5)
411 (16.2)
374 (14.7)
A
A 280 (11.0)
70 (2.8)
23
(0.9)
213
(8.4)
320
(12.6)
M10
1953
(76.9)
978
(77.9) 10 10
1760
(69.3)
B
130 (5.1)
71 385 (15.2)
107 (2.8)
(4.2)
213
(8.4)
320 235
(12.6) 25 (1.0)
668 (9.3)
(26.3)
14 (0.6)
130BF830.10
591 (23.3)
316
(12.4)
10 10 1168 (46.0)
130BF832.10
1731 (68.1)
1537 (60.5)
10 10
468
(18.4)
271
(10.7) 2X 11 (0.4)
23 (0.9)
130BF670.10
395 (15.6)
105
523 (20.6)
130BF610.10
337 (13.3)
1 2
169 (6.6)
43 (1.7)
-A-
222 (8.7)
115 (4.5)
130BF327.10
215 (8.5)
1699 (66.9)
10 10
767
(30.2) 1400 (55.1)
112
(4.4)
130BF811.10
406 (16.0)
156 (6.2)
23 (0.9)
25 (1.0)
162 (6.4)
10 10
2236 (88.0)
130BF812.10
420 (16.5)
411 (16.2)
374 (14.7)
A 280 (11.0)
130 (5.1) A
70 (2.8)
107
23
(4.2)
(0.9)
213 4X 11 (0.4)
(8.4)
25 (1.0)
320
(12.6)
M10
2259
(88.9)
130 (5.1)
2284
(89.9)
2065
10 10
(81.3)
107
(4.2)
213 B
(8.4)
973 235 25
(38.3) (9.3) (1.0)
14 (0.6)
130BF831.10
591 (23.3)
316
(12.4)
10 10
1473 (58.0)
130BF670.10
395 (15.6)
105
523 (20.6)
130BF610.10
337 (13.3)
1 2
169 (6.6)
43 (1.7)
-A-
222 (8.7)
115 (4.5)
11 Appendix
11 11 IINV
IM,N
Rated inverter output current
Nominal motor current
STO
TLIM
Safe Torque Off
Torque limit
IVLT,MAX Maximum output current UM,N Nominal motor voltage
IVLT,N Rated output current supplied by the drive V Volt
IEC International electrotechnical commission VVC Voltage vector control
IGBT Insulated-gate bipolar transistor Xh Motor main reactance
I/O Input/output
Table 11.1 Abbreviations, Acronyms, and Symbols
IP Ingress protection
kHz Kilohertz
Conventions
kW Kilowatt
• Numbered lists indicate procedures.
Ld Motor d-axis inductance
Lq Motor q-axis inductance • Bullet lists indicate other information and
description of illustrations.
LC Inductor-capacitor
LCP Local control panel • Italicized text indicates:
LED Light-emitting diode - Cross reference
LOP Local operation pad
- Link
mA Milliamp
MCB Miniature circuit breakers - Footnote
MCO Motion control option - Parameter name
MCP Motor control processor
- Parameter group name
MCT Motion control tool
MDCIC Multi-drive control interface card
- Parameter option
• All dimensions are in mm (inch).
Parameter International default parameter value North American default parameter value
Parameter 0-03 Regional Settings International North America
Parameter 0-71 Date Format DD-MM-YYYY MM/DD/YYYY
Parameter 0-72 Time Format 24 h 12 h
Parameter 1-20 Motor Power [kW] 1) 1)
Parameter 1-22 Motor Voltage 230 V/400 V/575 V 208 V/460 V/575 V
Parameter 1-23 Motor Frequency 50 Hz 60 Hz
Parameter 3-03 Maximum Reference 50 Hz 60 Hz
Parameter 3-04 Reference Function Sum External/Preset
Parameter 4-13 Motor Speed High Limit 1500 RPM 1800 RPM
[RPM]3)
Parameter 4-14 Motor Speed High Limit [Hz]4) 50 Hz 60 Hz
Parameter 4-19 Max Output Frequency 100 Hz 120 Hz
Parameter 4-53 Warning Speed High 1500 RPM 1800 RPM
Parameter 5-12 Terminal 27 Digital Input Coast inverse External interlock
Parameter 5-40 Function Relay Alarm No alarm
Parameter 6-15 Terminal 53 High Ref./Feedb. 50 60
Value
Parameter 6-50 Terminal 42 Output Speed 0-HighLim Speed 4-20 mA
Parameter 14-20 Reset Mode Manual reset Infinite auto reset
Parameter 22-85 Speed at Design Point 1500 RPM 1800 RPM
[RPM]3)
Parameter 22-86 Speed at Design Point [Hz] 50 Hz 60 Hz 11 11
Parameter 24-04 Fire Mode Max Reference 50 Hz 60 Hz
146
0-85 Summer Time Start for Fieldbus 1-72 Start Function 3-8* Other Ramps 5-24 Terminal X46/9 Digital Input
0-86 Summer Time End for Fieldbus 1-73 Flying Start 3-80 Jog Ramp Time 5-25 Terminal X46/11 Digital Input
0-** Operation / Display 0-89 Date and Time Readout 1-77 Compressor Start Max Speed [RPM] 3-81 Quick Stop Ramp Time 5-26 Terminal X46/13 Digital Input
0-0* Basic Settings
Appendix
0-9* Varia 1-78 Compressor Start Max Speed [Hz] 3-82 Starting Ramp Up Time 5-3* Digital Outputs
0-01 Language 0-95 Warning LED blinking 1-79 Compressor Start Max Time to Trip 3-9* Digital Pot.Meter 5-30 Terminal 27 Digital Output
0-02 Motor Speed Unit 1-** Load and Motor 1-8* Stop Adjustments 3-90 Step Size 5-31 Terminal 29 Digital Output
0-03 Regional Settings 1-0* General Settings 1-80 Function at Stop 3-91 Ramp Time 5-32 Term X30/6 Digi Out (MCB 101)
0-04 Operating State at Power-up 1-00 Configuration Mode 1-81 Min Speed for Function at Stop [RPM] 3-92 Power Restore 5-33 Term X30/7 Digi Out (MCB 101)
0-05 Local Mode Unit 1-03 Torque Characteristics 1-82 Min Speed for Function at Stop [Hz] 3-93 Maximum Limit 5-4* Relays
0-1* Set-up Operations 1-06 Clockwise Direction 1-86 Trip Speed Low [RPM] 3-94 Minimum Limit 5-40 Function Relay
0-10 Active Set-up 1-1* Motor Selection 1-87 Trip Speed Low [Hz] 3-95 Ramp Delay 5-41 On Delay, Relay
0-11 Programming Set-up 1-10 Motor Construction 1-9* Motor Temperature 4-** Limits / Warnings 5-42 Off Delay, Relay
0-12 This Set-up Linked to 1-1* VVC+ PM/SYN RM 1-90 Motor Thermal Protection 4-1* Motor Limits 5-5* Pulse Input
0-13 Readout: Linked Set-ups 1-14 Damping Gain 1-91 Motor External Fan 4-10 Motor Speed Direction 5-50 Term. 29 Low Frequency
0-14 Readout: Prog. Set-ups / Channel 1-15 Low Speed Filter Time Const. 1-93 Thermistor Source 4-11 Motor Speed Low Limit [RPM] 5-51 Term. 29 High Frequency
0-15 Readout: actual setup 1-16 High Speed Filter Time Const. 1-94 ATEX ETR cur.lim. speed reduction 4-12 Motor Speed Low Limit [Hz] 5-52 Term. 29 Low Ref./Feedb. Value
0-2* LCP Display 1-17 Voltage filter time const. 1-95 Thermistor Sensor Type 4-13 Motor Speed High Limit [RPM] 5-53 Term. 29 High Ref./Feedb. Value
0-20 Display Line 1.1 Small 1-2* Motor Data 1-96 Thermistor Sensor Source 4-14 Motor Speed High Limit [Hz] 5-54 Pulse Filter Time Constant #29
0-21 Display Line 1.2 Small 1-20 Motor Power [kW] 1-97 Thermistor Threshold level 4-16 Torque Limit Motor Mode 5-55 Term. 33 Low Frequency
0-22 Display Line 1.3 Small 1-21 Motor Power [HP] 1-98 ATEX ETR interpol. points freq. 4-17 Torque Limit Generator Mode 5-56 Term. 33 High Frequency
0-23 Display Line 2 Large 1-22 Motor Voltage 1-99 ATEX ETR interpol points current 4-18 Current Limit 5-57 Term. 33 Low Ref./Feedb. Value
0-24 Display Line 3 Large 1-23 Motor Frequency 2-** Brakes 4-19 Max Output Frequency 5-58 Term. 33 High Ref./Feedb. Value
0-25 My Personal Menu 1-24 Motor Current 2-0* DC-Brake 4-5* Adj. Warnings 5-59 Pulse Filter Time Constant #33
0-3* LCP Custom Readout 1-25 Motor Nominal Speed 2-00 DC Hold/Preheat Current 4-50 Warning Current Low 5-6* Pulse Output
0-30 Custom Readout Unit 1-26 Motor Cont. Rated Torque 2-01 DC Brake Current 4-51 Warning Current High 5-60 Terminal 27 Pulse Output Variable
0-31 Custom Readout Min Value 1-28 Motor Rotation Check 2-02 DC Braking Time 4-52 Warning Speed Low 5-62 Pulse Output Max Freq #27
0-32 Custom Readout Max Value 1-29 Automatic Motor Adaptation (AMA) 2-03 DC Brake Cut In Speed [RPM] 4-53 Warning Speed High 5-63 Terminal 29 Pulse Output Variable
0-37 Display Text 1 1-3* Adv. Motor Data 2-04 DC Brake Cut In Speed [Hz] 4-54 Warning Reference Low 5-65 Pulse Output Max Freq #29
0-38 Display Text 2 1-30 Stator Resistance (Rs) 2-06 Parking Current 4-55 Warning Reference High 5-66 Terminal X30/6 Pulse Output Variable
0-39 Display Text 3 1-31 Rotor Resistance (Rr) 2-07 Parking Time 4-56 Warning Feedback Low 5-68 Pulse Output Max Freq #X30/6
0-4* LCP Keypad 1-35 Main Reactance (Xh) 2-1* Brake Energy Funct. 4-57 Warning Feedback High 5-8* I/O Options
0-40 [Hand on] Key on LCP
VLT® HVAC Drive FC 102
1-36 Iron Loss Resistance (Rfe) 2-10 Brake Function 4-58 Missing Motor Phase Function 5-80 AHF Cap Reconnect Delay
0-41 [Off] Key on LCP 1-37 d-axis Inductance (Ld) 2-11 Brake Resistor (ohm) 4-59 Motor Check At Start 5-9* Bus Controlled
0-42 [Auto on] Key on LCP 1-38 q-axis Inductance (Lq) 2-12 Brake Power Limit (kW) 4-6* Speed Bypass 5-90 Digital & Relay Bus Control
0-43 [Reset] Key on LCP 1-39 Motor Poles 2-13 Brake Power Monitoring 4-60 Bypass Speed From [RPM] 5-93 Pulse Out #27 Bus Control
0-44 [Off/Reset] Key on LCP 1-40 Back EMF at 1000 RPM 2-15 Brake Check 4-61 Bypass Speed From [Hz] 5-94 Pulse Out #27 Timeout Preset
MG16D502
6-23 Terminal 54 High Current 8-30 Protocol 9-68 Status Word 1 12-03 Default Gateway 12-96 Port Config
6-24 Terminal 54 Low Ref./Feedb. Value 8-31 Address 9-70 Programming Set-up 12-04 DHCP Server 12-97 QoS Priority
6-25 Terminal 54 High Ref./Feedb. Value 8-32 Baud Rate 9-71 Profibus Save Data Values 12-05 Lease Expires 12-98 Interface Counters
6-26 Terminal 54 Filter Time Constant 8-33 Parity / Stop Bits 9-72 ProfibusDriveReset 12-06 Name Servers 12-99 Media Counters
MG16D502
Appendix
6-27 Terminal 54 Live Zero 8-34 Estimated cycle time 9-75 DO Identification 12-07 Domain Name 13-** Smart Logic
6-3* Analog Input X30/11 8-35 Minimum Response Delay 9-80 Defined Parameters (1) 12-08 Host Name 13-0* SLC Settings
6-30 Terminal X30/11 Low Voltage 8-36 Maximum Response Delay 9-81 Defined Parameters (2) 12-09 Physical Address 13-00 SL Controller Mode
6-31 Terminal X30/11 High Voltage 8-37 Maximum Inter-Char Delay 9-82 Defined Parameters (3) 12-1* Ethernet Link Parameters 13-01 Start Event
6-34 Term. X30/11 Low Ref./Feedb. Value 8-39 Protocol Firmware version 9-83 Defined Parameters (4) 12-10 Link Status 13-02 Stop Event
6-35 Term. X30/11 High Ref./Feedb. Value 8-4* FC MC protocol set 9-84 Defined Parameters (5) 12-11 Link Duration 13-03 Reset SLC
6-36 Term. X30/11 Filter Time Constant 8-40 Telegram Selection 9-85 Defined Parameters (6) 12-12 Auto Negotiation 13-1* Comparators
6-37 Term. X30/11 Live Zero 8-42 PCD Write Configuration 9-90 Changed Parameters (1) 12-13 Link Speed 13-10 Comparator Operand
6-4* Analog Input X30/12 8-43 PCD Read Configuration 9-91 Changed Parameters (2) 12-14 Link Duplex 13-11 Comparator Operator
6-40 Terminal X30/12 Low Voltage 8-5* Digital/Bus 9-92 Changed Parameters (3) 12-18 Supervisor MAC 13-12 Comparator Value
6-41 Terminal X30/12 High Voltage 8-50 Coasting Select 9-93 Changed Parameters (4) 12-19 Supervisor IP Addr. 13-1* RS Flip Flops
6-44 Term. X30/12 Low Ref./Feedb. Value 8-52 DC Brake Select 9-94 Changed Parameters (5) 12-2* Process Data 13-15 RS-FF Operand S
6-45 Term. X30/12 High Ref./Feedb. Value 8-53 Start Select 9-99 Profibus Revision Counter 12-20 Control Instance 13-16 RS-FF Operand R
6-46 Term. X30/12 Filter Time Constant 8-54 Reversing Select 10-** CAN Fieldbus 12-21 Process Data Config Write 13-2* Timers
6-47 Term. X30/12 Live Zero 8-55 Set-up Select 10-0* Common Settings 12-22 Process Data Config Read 13-20 SL Controller Timer
6-5* Analog Output 42 8-56 Preset Reference Select 10-00 CAN Protocol 12-27 Primary Master 13-4* Logic Rules
6-50 Terminal 42 Output 8-7* BACnet 10-01 Baud Rate Select 12-28 Store Data Values 13-40 Logic Rule Boolean 1
6-51 Terminal 42 Output Min Scale 8-70 BACnet Device Instance 10-02 MAC ID 12-29 Store Always 13-41 Logic Rule Operator 1
6-52 Terminal 42 Output Max Scale 8-72 MS/TP Max Masters 10-05 Readout Transmit Error Counter 12-3* EtherNet/IP 13-42 Logic Rule Boolean 2
6-53 Terminal 42 Output Bus Control 8-73 MS/TP Max Info Frames 10-06 Readout Receive Error Counter 12-30 Warning Parameter 13-43 Logic Rule Operator 2
6-54 Terminal 42 Output Timeout Preset 8-74 "I-Am" Service 10-07 Readout Bus Off Counter 12-31 Net Reference 13-44 Logic Rule Boolean 3
6-55 Analog Output Filter 8-75 Initialisation Password 10-1* DeviceNet 12-32 Net Control 13-5* States
6-6* Analog Output X30/8 8-8* FC Port Diagnostics 10-10 Process Data Type Selection 12-33 CIP Revision 13-51 SL Controller Event
6-60 Terminal X30/8 Output 8-80 Bus Message Count 10-11 Process Data Config Write 12-34 CIP Product Code 13-52 SL Controller Action
6-61 Terminal X30/8 Min. Scale 8-81 Bus Error Count 10-12 Process Data Config Read 12-35 EDS Parameter 13-9* User Defined Alerts
Operating Guide
6-62 Terminal X30/8 Max. Scale 8-82 Slave Messages Rcvd 10-13 Warning Parameter 12-37 COS Inhibit Timer 13-90 Alert Trigger
6-63 Terminal X30/8 Output Bus Control 8-83 Slave Error Count 10-14 Net Reference 12-38 COS Filter 13-91 Alert Action
6-64 Terminal X30/8 Output Timeout Preset 8-84 Slave Messages Sent 10-15 Net Control 12-4* Modbus TCP 13-92 Alert Text
6-7* Analog Output X45/1 8-85 Slave Timeout Errors 10-2* COS Filters 12-40 Status Parameter 13-9* User Defined Readouts
6-70 Terminal X45/1 Output 8-89 Diagnostics Count 10-20 COS Filter 1 12-41 Slave Message Count 13-97 Alert Alarm Word
6-71 Terminal X45/1 Min. Scale 8-9* Bus Jog / Feedback 10-21 COS Filter 2 12-42 Slave Exception Message Count 13-98 Alert Warning Word
6-72 Terminal X45/1 Max. Scale 8-90 Bus Jog 1 Speed 10-22 COS Filter 3 12-7* BACnet 13-99 Alert Status Word
6-73 Terminal X45/1 Bus Control 8-91 Bus Jog 2 Speed 10-23 COS Filter 4 12-70 BACnet Status 14-** Special Functions
6-74 Terminal X45/1 Output Timeout Preset 8-94 Bus Feedback 1 10-3* Parameter Access 12-71 BACnet Datalink 14-0* Inverter Switching
6-8* Analog Output X45/3 8-95 Bus Feedback 2 10-30 Array Index 12-72 BACnet UDP Port 14-00 Switching Pattern
6-80 Terminal X45/3 Output 8-96 Bus Feedback 3 10-31 Store Data Values 12-75 BBMD IP Address 14-01 Switching Frequency
147
11 11
11 11
14-32 Current Lim Ctrl, Filter Time 15-46 Frequency Converter Ordering No 16-3* Drive Status 16-94 Ext. Status Word 20-22 Setpoint 2
148
14-4* Energy Optimising 15-47 Power Card Ordering No 16-30 DC Link Voltage 16-95 Ext. Status Word 2 20-23 Setpoint 3
14-40 VT Level 15-48 LCP Id No 16-31 System Temp. 16-96 Maintenance Word 20-3* Feedb. Adv. Conv.
14-41 AEO Minimum Magnetisation 15-49 SW ID Control Card 16-32 Brake Energy /s 18-** Info & Readouts 20-30 Refrigerant
Appendix
14-42 Minimum AEO Frequency 15-50 SW ID Power Card 16-33 Brake Energy Average 18-0* Maintenance Log 20-31 User Defined Refrigerant A1
14-43 Motor Cosphi 15-51 Frequency Converter Serial Number 16-34 Heatsink Temp. 18-00 Maintenance Log: Item 20-32 User Defined Refrigerant A2
14-5* Environment 15-53 Power Card Serial Number 16-35 Inverter Thermal 18-01 Maintenance Log: Action 20-33 User Defined Refrigerant A3
14-50 RFI Filter 15-54 Config File Name 16-36 Inv. Nom. Current 18-02 Maintenance Log: Time 20-34 Duct 1 Area [m2]
14-51 DC-Link Compensation 15-55 Vendor URL 16-37 Inv. Max. Current 18-03 Maintenance Log: Date and Time 20-35 Duct 1 Area [in2]
14-52 Fan Control 15-56 Vendor Name 16-38 SL Controller State 18-1* Fire Mode Log 20-36 Duct 2 Area [m2]
14-53 Fan Monitor 15-58 Smart Setup Filename 16-39 Control Card Temp. 18-10 FireMode Log:Event 20-37 Duct 2 Area [in2]
14-55 Output Filter 15-59 Filename 16-40 Logging Buffer Full 18-11 Fire Mode Log: Time 20-38 Air Density Factor [%]
14-56 Capacitance Output Filter 15-6* Option Ident 16-41 Performance Measurements 18-12 Fire Mode Log: Date and Time 20-6* Sensorless
14-57 Inductance Output Filter 15-60 Option Mounted 16-42 Service Log Counter 18-3* Inputs & Outputs 20-60 Sensorless Unit
14-59 Actual Number of Inverter Units 15-61 Option SW Version 16-43 Timed Actions Status 18-30 Analog Input X42/1 20-69 Sensorless Information
14-6* Auto Derate 15-62 Option Ordering No 16-45 Motor Phase U Current 18-31 Analog Input X42/3 20-7* PID Autotuning
14-60 Function at Over Temperature 15-63 Option Serial No 16-46 Motor Phase V Current 18-32 Analog Input X42/5 20-70 Closed Loop Type
14-61 Function at Inverter Overload 15-64 Application Version 16-47 Motor Phase W Current 18-33 Analog Out X42/7 [V] 20-71 PID Performance
14-62 Inv. Overload Derate Current 15-70 Option in Slot A 16-49 Current Fault Source 18-34 Analog Out X42/9 [V] 20-72 PID Output Change
14-8* Options 15-71 Slot A Option SW Version 16-5* Ref. & Feedb. 18-35 Analog Out X42/11 [V] 20-73 Minimum Feedback Level
14-80 Option Supplied by External 24VDC 15-72 Option in Slot B 16-50 External Reference 18-36 Analog Input X48/2 [mA] 20-74 Maximum Feedback Level
14-88 Option Data Storage 15-73 Slot B Option SW Version 16-52 Feedback[Unit] 18-37 Temp. Input X48/4 20-79 PID Autotuning
14-89 Option Detection 15-74 Option in Slot C0/E0 16-53 Digi Pot Reference 18-38 Temp. Input X48/7 20-8* PID Basic Settings
14-9* Fault Settings 15-75 Slot C0/E0 Option SW Version 16-54 Feedback 1 [Unit] 18-39 Temp. Input X48/10 20-81 PID Normal/ Inverse Control
14-90 Fault Level 15-76 Option in Slot C1/E1 16-55 Feedback 2 [Unit] 18-4* PGIO Data Readouts 20-82 PID Start Speed [RPM]
15-** Drive Information 15-77 Slot C1/E1 Option SW Version 16-56 Feedback 3 [Unit] 18-40 Analog Input X49/1 20-83 PID Start Speed [Hz]
15-0* Operating Data 15-8* Operating Data II 16-58 PID Output [%] 18-41 Analog Input X49/3 20-84 On Reference Bandwidth
15-00 Operating hours 15-80 Fan Running Hours 16-59 Adjusted Setpoint 18-42 Analog Input X49/5 20-9* PID Controller
15-01 Running Hours 15-81 Preset Fan Running Hours 16-6* Inputs & Outputs 18-43 Analog Out X49/7 20-91 PID Anti Windup
15-02 kWh Counter 15-9* Parameter Info 16-60 Digital Input 18-44 Analog Out X49/9 20-93 PID Proportional Gain
15-03 Power Up's 15-92 Defined Parameters 16-61 Terminal 53 Switch Setting 18-45 Analog Out X49/11 20-94 PID Integral Time
15-04 Over Temp's 15-93 Modified Parameters 16-62 Analog Input 53 18-46 X49 Digital Output [bin] 20-95 PID Differentiation Time
VLT® HVAC Drive FC 102
15-05 Over Volt's 15-98 Drive Identification 16-63 Terminal 54 Switch Setting 18-5* Ref. & Feedb. 20-96 PID Diff. Gain Limit
15-06 Reset kWh Counter 15-99 Parameter Metadata 16-64 Analog Input 54 18-50 Sensorless Readout [unit] 21-** Ext. Closed Loop
15-07 Reset Running Hours Counter 16-** Data Readouts 16-65 Analog Output 42 [mA] 18-57 Air Pressure to Flow Air Flow 21-0* Ext. CL Autotuning
15-08 Number of Starts 16-0* General Status 16-66 Digital Output [bin] 18-6* Inputs & Outputs 2 21-00 Closed Loop Type
15-1* Data Log Settings 16-00 Control Word 16-67 Pulse Input #29 [Hz] 18-60 Digital Input 2 21-01 PID Performance
MG16D502
21-3* Ext. CL 2 Ref./Fb. 22-37 High Speed [Hz] 23-53 Energy Log 25-27 Stage Function 26-37 Term. X42/5 Live Zero
21-30 Ext. 2 Ref./Feedback Unit 22-38 High Speed Power [kW] 23-54 Reset Energy Log 25-28 Stage Function Time 26-4* Analog Out X42/7
21-31 Ext. 2 Minimum Reference 22-39 High Speed Power [HP] 23-6* Trending 25-29 Destage Function 26-40 Terminal X42/7 Output
21-32 Ext. 2 Maximum Reference 22-4* Sleep Mode 23-60 Trend Variable 25-30 Destage Function Time 26-41 Terminal X42/7 Min. Scale
MG16D502
Appendix
21-33 Ext. 2 Reference Source 22-40 Minimum Run Time 23-61 Continuous Bin Data 25-4* Staging Settings 26-42 Terminal X42/7 Max. Scale
21-34 Ext. 2 Feedback Source 22-41 Minimum Sleep Time 23-62 Timed Bin Data 25-40 Ramp Down Delay 26-43 Terminal X42/7 Bus Control
21-35 Ext. 2 Setpoint 22-42 Wake-up Speed [RPM] 23-63 Timed Period Start 25-41 Ramp Up Delay 26-44 Terminal X42/7 Timeout Preset
21-37 Ext. 2 Reference [Unit] 22-43 Wake-up Speed [Hz] 23-64 Timed Period Stop 25-42 Staging Threshold 26-5* Analog Out X42/9
21-38 Ext. 2 Feedback [Unit] 22-44 Wake-up Ref./FB Difference 23-65 Minimum Bin Value 25-43 Destaging Threshold 26-50 Terminal X42/9 Output
21-39 Ext. 2 Output [%] 22-45 Setpoint Boost 23-66 Reset Continuous Bin Data 25-44 Staging Speed [RPM] 26-51 Terminal X42/9 Min. Scale
21-4* Ext. CL 2 PID 22-46 Maximum Boost Time 23-67 Reset Timed Bin Data 25-45 Staging Speed [Hz] 26-52 Terminal X42/9 Max. Scale
21-40 Ext. 2 Normal/Inverse Control 22-5* End of Curve 23-8* Payback Counter 25-46 Destaging Speed [RPM] 26-53 Terminal X42/9 Bus Control
21-41 Ext. 2 Proportional Gain 22-50 End of Curve Function 23-80 Power Reference Factor 25-47 Destaging Speed [Hz] 26-54 Terminal X42/9 Timeout Preset
21-42 Ext. 2 Integral Time 22-51 End of Curve Delay 23-81 Energy Cost 25-5* Alternation Settings 26-6* Analog Out X42/11
21-43 Ext. 2 Differentation Time 22-52 End of Curve Tolerance 23-82 Investment 25-50 Lead Pump Alternation 26-60 Terminal X42/11 Output
21-44 Ext. 2 Dif. Gain Limit 22-6* Broken Belt Detection 23-83 Energy Savings 25-51 Alternation Event 26-61 Terminal X42/11 Min. Scale
21-46 Ext. 2 On Reference Bandwidth 22-60 Broken Belt Function 23-84 Cost Savings 25-52 Alternation Time Interval 26-62 Terminal X42/11 Max. Scale
21-5* Ext. CL 3 Ref./Fb. 22-61 Broken Belt Torque 23-85 CO2 Conversion Factor 25-53 Alternation Timer Value 26-63 Terminal X42/11 Bus Control
21-50 Ext. 3 Ref./Feedback Unit 22-62 Broken Belt Delay 23-86 CO2 Reduction 25-54 Alternation Predefined Time 26-64 Terminal X42/11 Timeout Preset
21-51 Ext. 3 Minimum Reference 22-7* Short Cycle Protection 24-** Appl. Functions 2 25-55 Alternate if Load < 50% 30-** Special Features
21-52 Ext. 3 Maximum Reference 22-75 Short Cycle Protection 24-0* Fire Mode 25-56 Staging Mode at Alternation 30-2* Adv. Start Adjust
21-53 Ext. 3 Reference Source 22-76 Interval between Starts 24-00 Fire Mode Function 25-58 Run Next Pump Delay 30-22 Locked Rotor Detection
21-54 Ext. 3 Feedback Source 22-77 Minimum Run Time 24-01 Fire Mode Configuration 25-59 Run on Mains Delay 30-23 Locked Rotor Detection Time [s]
21-55 Ext. 3 Setpoint 22-78 Minimum Run Time Override 24-02 Fire Mode Unit 25-8* Status 30-5* Unit Configuration
21-57 Ext. 3 Reference [Unit] 22-79 Minimum Run Time Override Value 24-03 Fire Mode Min Reference 25-80 Cascade Status 30-50 Heat Sink Fan Mode
21-58 Ext. 3 Feedback [Unit] 22-8* Flow Compensation 24-04 Fire Mode Max Reference 25-81 Pump Status 30-9* Wifi LCP
21-59 Ext. 3 Output [%] 22-80 Flow Compensation 24-05 Fire Mode Preset Reference 25-82 Lead Pump 30-90 SSID
21-6* Ext. CL 3 PID 22-81 Square-linear Curve Approximation 24-06 Fire Mode Reference Source 25-83 Relay Status 30-91 Channel
21-60 Ext. 3 Normal/Inverse Control 22-82 Work Point Calculation 24-07 Fire Mode Feedback Source 25-84 Pump ON Time 30-92 Password
Operating Guide
21-61 Ext. 3 Proportional Gain 22-83 Speed at No-Flow [RPM] 24-09 Fire Mode Alarm Handling 25-85 Relay ON Time 30-93 Security type
21-62 Ext. 3 Integral Time 22-84 Speed at No-Flow [Hz] 24-1* Drive Bypass 25-86 Reset Relay Counters 30-94 IP address
21-63 Ext. 3 Differentation Time 22-85 Speed at Design Point [RPM] 24-10 Drive Bypass Function 25-9* Service 30-95 Submask
21-64 Ext. 3 Dif. Gain Limit 22-86 Speed at Design Point [Hz] 24-11 Drive Bypass Delay Time 25-90 Pump Interlock 30-96 Port
21-66 Ext. 3 On Reference Bandwidth 22-87 Pressure at No-Flow Speed 24-9* Multi-Motor Funct. 25-91 Manual Alternation 30-97 Wifi Timeout Action
22-** Appl. Functions 22-88 Pressure at Rated Speed 24-90 Missing Motor Function 26-** Analog I/O Option 31-** Bypass Option
22-0* Miscellaneous 22-89 Flow at Design Point 24-91 Missing Motor Coefficient 1 26-0* Analog I/O Mode 31-00 Bypass Mode
22-00 External Interlock Delay 22-90 Flow at Rated Speed 24-92 Missing Motor Coefficient 2 26-00 Terminal X42/1 Mode 31-01 Bypass Start Time Delay
22-01 Power Filter Time 23-** Time-based Functions 24-93 Missing Motor Coefficient 3 26-01 Terminal X42/3 Mode 31-02 Bypass Trip Time Delay
22-1* Air Pres. to Flow 23-0* Timed Actions 24-94 Missing Motor Coefficient 4 26-02 Terminal X42/5 Mode 31-03 Test Mode Activation
22-10 Air Pressure to Flow Signal source 23-00 ON Time 24-95 Locked Rotor Function 26-1* Analog Input X42/1 31-10 Bypass Status Word
149
11 11
11 11
32-** MCO Basic Settings 36-00 Terminal X49/1 Mode 40-43 Alarm Log: Voltage 99-55 PC Debug Array
150
32-9* Development 36-01 Terminal X49/3 Mode 40-44 Alarm Log: DC Link Voltage 99-6* Fan Power Card Dev
32-90 Debug Source 36-02 Terminal X49/5 Mode 40-45 Alarm Log: Control Word 99-60 FPC Debug Selection
34-** MCO Data Readouts 36-03 Terminal X49/7 Mode 40-46 Alarm Log: Status Word 99-61 FPC Debug 0
Appendix
34-0* PCD Write Par. 36-04 Terminal X49/9 Mode 43-** Unit Readouts 99-62 FPC Debug 1
34-01 PCD 1 Write to MCO 36-05 Terminal X49/11 Mode 43-0* Component Status 99-63 FPC Debug 2
34-02 PCD 2 Write to MCO 36-1* Analog Input X49/1 43-00 Component Temp. 99-64 FPC Debug 3
34-03 PCD 3 Write to MCO 36-10 Terminal X49/1 Low Voltage 43-01 Auxiliary Temp. 99-65 FPC Debug 4
34-04 PCD 4 Write to MCO 36-11 Terminal X49/1 Low Current 43-02 Component SW ID 99-66 FPC Backdoor
34-05 PCD 5 Write to MCO 36-12 Terminal X49/1 High Voltage 43-1* Power Card Status 99-9* Internal Values
34-06 PCD 6 Write to MCO 36-13 Terminal X49/1 High Current 43-10 HS Temp. ph.U 99-90 Options present
34-07 PCD 7 Write to MCO 36-14 Term. X49/1 Low Ref./Feedb. Value 43-11 HS Temp. ph.V 99-91 Motor Power Internal
34-08 PCD 8 Write to MCO 36-15 Term. X49/1 High Ref./Feedb. Value 43-12 HS Temp. ph.W 99-92 Motor Voltage Internal
34-09 PCD 9 Write to MCO 36-16 Term. X49/1 Filter Time Constant 43-13 PC Fan A Speed 99-93 Motor Frequency Internal
34-10 PCD 10 Write to MCO 36-17 Term. X49/1 Live Zero 43-14 PC Fan B Speed 99-94 Imbalance derate [%]
34-2* PCD Read Par. 36-2* Analog Input X49/3 43-15 PC Fan C Speed 99-95 Temperature derate [%]
34-21 PCD 1 Read from MCO 36-20 Terminal X49/3 Low Voltage 43-2* Fan Pow.Card Status 99-96 Overload derate [%]
34-22 PCD 2 Read from MCO 36-21 Terminal X49/3 Low Current 43-20 FPC Fan A Speed
34-23 PCD 3 Read from MCO 36-22 Terminal X49/3 High Voltage 43-21 FPC Fan B Speed
34-24 PCD 4 Read from MCO 36-23 Terminal X49/3 High Current 43-22 FPC Fan C Speed
34-25 PCD 5 Read from MCO 36-24 Term. X49/3 Low Ref./Feedb. Value 43-23 FPC Fan D Speed
34-26 PCD 6 Read from MCO 36-25 Term. X49/3 High Ref./Feedb. Value 43-24 FPC Fan E Speed
34-27 PCD 7 Read from MCO 36-26 Term. X49/3 Filter Time Constant 43-25 FPC Fan F Speed
34-28 PCD 8 Read from MCO 36-27 Term. X49/3 Live Zero 99-* Devel support
34-29 PCD 9 Read from MCO 36-3* Analog Input X49/5 99-0* DSP Debug
34-30 PCD 10 Read from MCO 36-30 Terminal X49/5 Low Voltage 99-00 DAC 1 selection
35-** Sensor Input Option 36-31 Terminal X49/5 Low Current 99-01 DAC 2 selection
35-0* Temp. Input Mode 36-32 Terminal X49/5 High Voltage 99-02 DAC 3 selection
35-00 Term. X48/4 Temperature Unit 36-33 Terminal X49/5 High Current 99-03 DAC 4 selection
35-01 Term. X48/4 Input Type 36-34 Term. X49/5 Low Ref./Feedb. Value 99-04 DAC 1 scale
35-02 Term. X48/7 Temperature Unit 36-35 Term. X49/5 High Ref./Feedb. Value 99-05 DAC 2 scale
35-03 Term. X48/7 Input Type 36-36 Term. X49/5 Filter Time Constant 99-06 DAC 3 scale
VLT® HVAC Drive FC 102
35-04 Term. X48/10 Temperature Unit 36-37 Term. X49/5 Live Zero 99-07 DAC 4 scale
35-05 Term. X48/10 Input Type 36-4* Output X49/7 99-08 Test param 1
35-06 Temperature Sensor Alarm Function 36-40 Terminal X49/7 Analogue Output 99-09 Test param 2
35-1* Temp. Input X48/4 36-41 Terminal X49/7 Digital Output 99-10 DAC Option Slot
35-14 Term. X48/4 Filter Time Constant 36-42 Terminal X49/7 Min. Scale 99-1* Hardware Control
MG16D502
Index Operating Guide
A Circuit breakers...................................................................................... 67
AC mains.................................................................................................. 31 Condensation......................................................................................... 17
see also Mains Control
Additional resources.............................................................................. 4 Characteristics................................................................................ 105
Wiring................................................................................................... 27
ADN compliance..................................................................................... 4
Control card
Alarms Overtemperature trip point.................................................. 96, 98
List of............................................................................................. 14, 84 RS485 specifications..................................................................... 104
Log.................................................................................................. 14, 92 Specifications.................................................................................. 105
Types of................................................................................................ 83 Warning............................................................................................... 90
Ambient conditions Control input/output
Specifications.................................................................................. 102 Descriptions and default settings.............................................. 63
Analog Control shelf........................................................................................... 11
Input specifications...................................................................... 103
Output specifications................................................................... 104 Control wiring.......................................................................... 63, 64, 67
Wiring configuration for speed reference............................... 72 Cooling
Analog input/output Check list............................................................................................. 67
Descriptions and default settings.............................................. 64 Dust warning..................................................................................... 17
Brake Derating
Resistor................................................................................................ 84 Specifications.................................................................................. 102
Status message................................................................................. 81 Digital
Terminal torque rating................................................................. 108 Input specifications...................................................................... 103
Brake resistor Output specifications................................................................... 104
Warning............................................................................................... 87 Digital input/output
Wiring................................................................................................... 66 Descriptions and default settings.............................................. 64
Wiring schematic............................................................................. 26
Dimensions
Burst transient....................................................................................... 27 D1h exterior..................................................................................... 109
Bus termination switch....................................................................... 65 D1h terminal...................................................................................... 35
D2h exterior..................................................................................... 113
D2h terminal...................................................................................... 37
C D3h exterior..................................................................................... 117
D3h terminal...................................................................................... 39
Cables
D4h exterior..................................................................................... 120
Cable length and cross-section................................................ 102
D4h terminal...................................................................................... 41
Installation warning........................................................................ 23
D5h exterior..................................................................................... 123
Maximum number and size per phase.............................. 96, 98
D5h terminal...................................................................................... 43
Opening............................................. 109, 113, 123, 128, 133, 139
D6h exterior..................................................................................... 128
Routing......................................................................................... 63, 67
D6h terminal...................................................................................... 47
Shielded............................................................................................... 23
D7h exterior..................................................................................... 133
Specifications.......................................................... 96, 98, 100, 102
D7h terminal...................................................................................... 53
Capacitor storage................................................................................. 17 D8h exterior..................................................................................... 139
D8h terminal...................................................................................... 57
Dimensions shipping............................................................................. 7
Discharge time......................................................................................... 5 G
Disconnect.............................................................................................. 66 Galvanic isolation............................................................................... 104
Disconnect switch................................................................................ 68 Gases......................................................................................................... 17
Disposal instruction............................................................................... 4 Gland plate
D1h dimensions............................................................................. 112
Door clearance..................................... 112, 116, 127, 132, 138, 143 D2h dimensions............................................................................. 116
Door/panel cover D5h dimensions............................................................................. 127
Torque rating................................................................................... 108 D6h dimensions............................................................................. 132
D7h dimensions............................................................................. 138
Drive
D8h dimensions............................................................................. 143
Definition............................................................................................... 7
Torque rating................................................................................... 108
Initialization....................................................................................... 71
Lifting................................................................................................... 19 Ground
Status.................................................................................................... 81 Check list............................................................................................. 67
Floating delta.................................................................................... 31
Grounded delta................................................................................ 31
E Grounding.......................................................................................... 29
Efficiency Isolated main..................................................................................... 31
Specifications.................................................................... 96, 98, 100 Terminal torque rating................................................................. 108
Warning............................................................................................... 89
Electrical specifications 200–240 V................................................ 97
Ground wire............................................................................................ 27
Electrical specifications 380–480 V................................................ 99
Electrical Specifications 525–690 V............................................. 100
H
Electronic thermal relay (ETR).......................................................... 23
Hand on............................................................................................. 14, 81
EMC.............................................................................................. 23, 24, 25
Heat sink
Encoder.................................................................................................... 70 Access.................................................................... 126, 131, 136, 142
Energy efficiency class...................................................................... 102 Access panel torque rating........................................................ 108
Alarm.................................................................................................... 89
Environment........................................................................................ 102
Cleaning.............................................................................................. 17
Explosive atmosphere......................................................................... 18 Overtemperature trip point.................................................. 96, 98
Exterior dimensions Warning............................................................................................... 90
D1h..................................................................................................... 109 Heater
D2h..................................................................................................... 113 Usage.................................................................................................... 17
D3h..................................................................................................... 117 Wiring of.............................................................................................. 65
D4h..................................................................................................... 120 Wiring schematic............................................................................. 26
D5h..................................................................................................... 123
High voltage.................................................................................... 87, 88
D6h..................................................................................................... 128
D7h..................................................................................................... 133 High voltage warning............................................................................ 5
D8h..................................................................................................... 139 Humidity.................................................................................................. 17
External alarm reset wiring configuration................................... 74
I
F Indicator lights....................................................................................... 83
Factory default settings...................................................................... 71 Input
Fans Power.................................................................................................... 27
Servicing.............................................................................................. 17 Voltage................................................................................................. 68
Warning............................................................................................... 92 Input specifications........................................................................... 103
Fault log................................................................................................... 14 Installation
Fieldbus.................................................................................................... 63 Check list............................................................................................. 67
Electrical.............................................................................................. 23
Filter........................................................................................................... 17
EMC-compliant................................................................................. 25
Fire mode................................................................................................. 92 Initialization....................................................................................... 71
Fuses Qualified personnel........................................................................... 5
Overcurrent protection.................................................................. 23 Quick set-up....................................................................................... 69
Pre-start check list........................................................................... 67 Start up................................................................................................ 70
Specifications.................................................................................. 106 Tools needed..................................................................................... 16
Troubleshooting............................................................................... 95 Installation................................................................................ 18, 20, 22
Installation environment................................................................... 17
Interference
EMC....................................................................................................... 24 N
Radio....................................................................................................... 7
Nameplate............................................................................................... 16
Interlock device..................................................................................... 65
Navigation keys.............................................................................. 14, 68
L
O
LCP
Display................................................................................................. 13 Optional equipment..................................................................... 65, 68
Indicator lights.................................................................................. 14 Output
Menu..................................................................................................... 15 Specifications.................................................................................. 104
Troubleshooting............................................................................... 94
Overcurrent protection...................................................................... 23
Leakage current................................................................................ 5, 27
Overvoltage............................................................................................ 95
Lifting................................................................................................. 16, 19
Load share P
Terminal dimensions....................................................................... 34
Terminal torque rating................................................................. 108 Parameters.............................................................................. 15, 71, 145
Terminals...................................................................................... 12, 33 Pedestal.................................................................................................... 20
Warning........................................................................................... 5, 88
PELV......................................................................................................... 104
Wiring schematic............................................................................. 26
Periodic forming................................................................................... 17
Load share............................................................................................... 33
Phase loss................................................................................................ 84
Load sharing............................................................................................. 7
Pigtails...................................................................................................... 23
Local control panel (LCP)................................................................... 13
Potential equalization......................................................................... 27
M Potentiometer................................................................................. 64, 75
Danfoss A/S
Ulsnaes 1
DK-6300 Graasten
vlt-drives.danfoss.com
*MG16D502*