Diesel Fire Pump Equipment Manual
Diesel Fire Pump Equipment Manual
MAINTENACE MANUAL
DIESEL ENGINE FIRE PUMP GROUP
DIESEL ENGINE PUMP GROUP INSTALLATION, OPERATION AND MAINTENANCE MANUAL
Content
1. Introduction.......................................................................................................................................................................................... 1
2. Safety/Caution/Warnings...................................................................................................................................................................1
2.1 General..................................................................................................................................................................................... 1
2.2 Installation, Moving and Transportation...............................................................................................................................1
2.3 Fire Proofing and Explosion Protection...............................................................................................................................1
2.4 Safety Guard............................................................................................................................................................................2
2.5 Chemical................................................................................................................................................................................... 2
2.6 Noise......................................................................................................................................................................................... 2
3. Diesel Engine Pump Group Structure.............................................................................................................................................3
3.1 Description............................................................................................................................................................................... 3
3.2 Diesel Engine...........................................................................................................................................................................3
3.3 Electric Power System of Diesel Engine.............................................................................................................................3
3.4 Cooling System.......................................................................................................................................................................3
3.5 Preheating................................................................................................................................................................................ 6
3.6 Fuel Tank and Common Base...............................................................................................................................................6
3.7 Coupling.................................................................................................................................................................................... 6
3.8 Silencer and Exhaust System...............................................................................................................................................6
3.9 Control system.........................................................................................................................................................................6
4. Moving, Towing and Storage.............................................................................................................................................................6
4.1 Moving....................................................................................................................................................................................... 6
4.2 Lifting Position.........................................................................................................................................................................6
4.3 Open Packing and Keep........................................................................................................................................................7
4.4 Storage..................................................................................................................................................................................... 7
4.5 Pumps Storage........................................................................................................................................................................8
5. Installation............................................................................................................................................................................................ 8
5.1 Foundation............................................................................................................................................................................... 8
5.2 Installation Process.................................................................................................................................................................8
5.3 Common Base Assembly.......................................................................................................................................................9
5.4 Grouting.................................................................................................................................................................................... 9
5.5 Coupling Alignment.................................................................................................................................................................9
5.6 Whole Group Installation......................................................................................................................................................10
5.7 Outlet and Inlet pipes............................................................................................................................................................10
5.8 Pump Installation...................................................................................................................................................................11
5.9 Location for Pump Installation.............................................................................................................................................11
5.10 Pipe for Pump Suction and Discharge.............................................................................................................................11
6. Air Intake............................................................................................................................................................................................ 11
6.1 Ventilation for Pump Room..................................................................................................................................................12
6.2 Exhaust and installation of exhaust pipe...........................................................................................................................12
6.3 Fuel System...........................................................................................................................................................................14
6.4 Fire precautions.....................................................................................................................................................................15
6.5 Batteries..................................................................................................................................................................................16
6.6 ReduceNoise.........................................................................................................................................................................16
7. Operation Principle........................................................................................................................................................................... 16
8. Operation........................................................................................................................................................................................... 16
8.1 General................................................................................................................................................................................... 16
DIESEL ENGINE PUMP GROUP INSTALLATION, OPERATION AND MAINTENANCE MANUAL
1. Introduction
This diesel pump unit is designed for fire-fighting system. It is easy to being operated by only placing and adding
water/cooling liquid, fuel, lubricating oil and battery electrolyte. It is efficient emergency capacity.
This manual is for maintenance and operation. If the diesel engine manual and pump manual can be referred to at
the same time, it will help to ensure that the pump group keeps operating at maximum performance and efficiency for a
long life. If in dirty or dusty environments more attention, it must be serviced more frequent to keep the set running
properly.
Make sure that the installation, adjustment and maintenance must be operated by the qualified people.
2. Safety/Caution/Warnings
2.1 General
Please note the follows during the installation, operation and maintenance to avoid the accidents. The diesel engine
pump group must be operated by the professional person.
Warning
Read and understand all safety precautions and warnings before operating or performing maintenance. Fail to
follow the instructions, procedures, and safety precautions in this manual may increase the possibility of accidents
injuries.
Start the pump set only in safe condition.
Only start the equipment when it is in safe condition. If not sure that the diesel fire pump set is safe or not, do not
start the engine.
If the diesel fire pump set is unsafe, stick the danger notices and disconnect the main switch of battery so that it
cannot be started and reconnect it when the pump set is in normal condition.
Cut the main switch of battery and disconnect the battery negative (-) lead before repairing or cleaning inside the
equipment if necessary.
Install and operate this pump group must completely comply with relevant national or local environmental emission
codes, standards or other requirements.
Page 1 of 37
DIESEL ENGINE PUMP GROUP INSTALLATION, OPERATION AND MAINTENANCE MANUAL
Warning
Ensure that the pump room is properly ventilated.
Keep the room, floor and diesel pump group clean. When there is spills of fuel, oil, battery electrolyte or coolant
occur, they should be cleaned up immediately.
Never store flammable liquids near the engine.
Oily rags should be stored in containers which covered with metal.
Do not smoke or allow sparks flames or other sources of ignition around the fuel or batteries, fuel vapor can be
explosive. Hydrogen gas generated by charging batteries is also explosive.
Turn off the power of the battery charger before connecting or disconnecting with battery.
Keep electrically conductive object, such as tools, away from exposed electrical parts such as terminals to avoid
arcing or sparks, the arcing might ignite fuel or vapor.
Do not refill the fuel tank when the equipment is running.
Do not attempt to operate the pump group when there is fuel leakage.
If the engine fail to start many times. There will create excessive unburned fuel gas in the exhaust system which
can create a potentially explosive condition. Exhaust the gas and then start the engine.
2.5 Chemical
Fuels, oils, coolants lubricants and battery electrolyte used in this diesel pump group must be treated properly, if not, it
will be harmful to the people.
Warning
Do not swallow or have skin contacted with fuel, oil, coolant, lubricants or battery electrolyte. If swallowed, take the
medical treatment immediately and do not induce vomiting. For skin contact, wash the skin with soap and water.
Do not wear clothing with fuel or lube oil.
Wear an acid resistant apron, face shield or goggles when handling the battery. If the skin is splashed with the
electrolyte, flush it immediately with much of water.
2.6 Noise
The unit shall produce 105dBA noise if the unit is without the shell. Continuous exposure under more than 85dBA noise
will damage hearing.
Warning!
Ear protection must be worn when working around the engine.
Page 2 of 37
DIESEL ENGINE PUMP GROUP INSTALLATION, OPERATION AND MAINTENANCE MANUAL
Page 3 of 37
DIESEL ENGINE PUMP GROUP INSTALLATION, OPERATION AND MAINTENANCE MANUAL
Standard:NFPA20
3.1 Description
The diesel engine pump group includes: Diesel Engine, Water Pump, Main Control Panel and Engine Conrol Panel,
Fuel Tank, Coupling, Coupling Guard, Exhaust pipe, Cooling Loop, Heat Exchanger, Expansion Water Box, Battery etc.
Page 4 of 37
DIESEL ENGINE PUMP GROUP INSTALLATION, OPERATION AND MAINTENANCE MANUAL
Cooling System
Page 5 of 37
DIESEL ENGINE PUMP GROUP INSTALLATION, OPERATION AND MAINTENANCE MANUAL
Cooling Loop:
Page 6 of 37
DIESEL ENGINE PUMP GROUP INSTALLATION, OPERATION AND MAINTENANCE MANUAL
3.5 Preheating
There is a Preheating device which keeps the engine easy to be started. When the engine is standby, the preheater is
operating and cut off when the engine is started.
3.7 Coupling
The universal coupling is used for the diesel pump group. This coupling not only can transfer the power but also can
adjust the shaft alignment; it is a perfect capacity of angular compensation, compact structure, high transmission
efficiency, even can reduce the vibration.
Page 7 of 37
DIESEL ENGINE PUMP GROUP INSTALLATION, OPERATION AND MAINTENANCE MANUAL
Fig.6 Lifting
4.4 Storage
When diesel engine pumps group arrival, if they can not be installed immediately, it should be stored in a place where a
clean, dry and slow change in ambient temperature is. For long time storage, It must be protected against water vapor,
dust and other objects, and the tarpaulin or other suitable cover can be used.
Storage preparation:Long - term storage will have the decisive impact. Proper storage preparations can minimize
the impact.
Diesel engine Storage: storing diesel engines for over eight months must follow the below steps: mix the 2% 5th
composite rust inhibitor with diesel to run for 10 minutes, the fuel system and combustion chamber will full of
archive oil, in order to avoid the corrosion of parts. Provisional decision to change the storage time, please read
diesel engine manual for the correct steps.
Page 8 of 37
DIESEL ENGINE PUMP GROUP INSTALLATION, OPERATION AND MAINTENANCE MANUAL
Battery Storage: Battery storage, if using maintenance-free batteries: required charging every eight weeks time (4
weeks for tropical regions), fully charged. If it is open type lead acid battery, charge it every four weeks (2 weeks for
tropical regions), it must be fully charged.
5. Installation
If unit must be taken outside the building temporary, do not unpack the package.
Don't let the machine exposed to air pollution, for example, the dust, metal dust, fiber dust, smoke, lampblack,
evaporation gas or other pollution of the construction site;
Keep enough space for installation. Do not let any part of the unit as support point for other equipments;
Non-equipment construction workers can not go into the room;
During the whole process of the installation, unit must have jacket protection to avoid from raining, snow, wind and
sand, collision, welding burns, artificial trample. If installing other device over pump set, protective measures must
be prepared and cover the pump group to prevent equipment from damaging or dirt entering. The staff mustn’t
stand on the device for operation; the pump set can not hold the scaffolding and platform load force.
Warning!
Prohibit connecting, start battery and run the equipment without authorization.
5.1 Foundation
Diesel engine and pump have one common base; the whole group can be fixed on the good foundation by the ground
bolts. During installing this unit, only need bolt to fit on a good foundation。
Foundation: The best foundation is an independent reinforced concrete, the strength is up to C20, and dimension is
200mm than the group size. The foundation can provide a rigid support to the unit and prevent the wobble and vibration,
foundation thickness can be determined according to different models, but the area can not be smaller than the common
base (considering dynamic load, the common base must be withstand more than 5 times of unit weight, ensure that
bellowing concrete is fulfilling with backfill gravel soil and steel bar). If the unit is going to install on the building which is
higher than floor, the building structure must be able to withstand the dynamic weight of pump group. Calculate pump
running frequency and check whether there is resonance with the building, also take the stored fuel and accessories
weight into consideration.
Buildings must comply with local building regulations, if the floor is usually wet, the foundation would be higher than the
floor, or design the drainage ditches. So that there is a dry place where is convenient for repair / maintenance, and also
minimize the corrosion metal common base.
Page 9 of 37
DIESEL ENGINE PUMP GROUP INSTALLATION, OPERATION AND MAINTENANCE MANUAL
The foundation must fully meet the vibration requirements, and be strong enough to prevent the unit from being
distorted or misplaced.
Do not interrupt until the completion of the entire height of 150mm when casting the foundation. The scratches and
slot of the common base surface should be prepared before the concrete dries, ensure the bonding layer of grout
surface, the anchor bolt placement in the concrete should meet the length of it, as shown in Figure 7 going through
the common base and tighten the nut and washer. Leave a few days for concrete maintenance before the common
base wedge iron grouting. Holes for secondary grout strength should be one class higher than the foundation and
use the non-shrink concrete.
5.4 Grouting
The grout fills the concrete foundation, so as to uniform the
bearing of unit weight and prevent loose. After leveling unit,
follow the below steps to grout correctly (See Figure 7). Around
scratches and slotted concrete foundation format the solid
portion of the grout.
Fully floating on the concrete foundation, remove the
water of surface.
Fully fill the concrete foundation with grouting, if
necessary, exclude the internal air.
Check the anchor bolt is loose or not after the grout dries,
tighten the nut and check.
Tighten the nut and check the concentricity of the unit.
Brush the undercoat when 14 days after grouting or
completely dry to prevent air and moisture from entering.
Fig.7 Lifting
5.5 Coupling Alignment
Universal coupling is used for this diesel engine pump group, it include whole fork and intermediate, in order to keep the
angular velocity of driving shaft and driven shaft (ω1=ω2 ), must be Satisfy the following three conditions
1. The dip angle of the intermediate and the driven shaft must be equal : β1=β2
2. The shaft fork head at the two ends of the intermediate must be on the same plane
3. The centerline of driving shaft, driven shaft and the intermediate must be on the same plane.
Page 10 of 37
DIESEL ENGINE PUMP GROUP INSTALLATION, OPERATION AND MAINTENANCE MANUAL
Page 11 of 37
DIESEL ENGINE PUMP GROUP INSTALLATION, OPERATION AND MAINTENANCE MANUAL
√ × ×
Fig.9 Diameter Changes
6. Air Intake
Air for engine combustion must be clean and as cool as possible. Normally this air can be drawn from the area
surrounding the pump set via the engine mounted air filter. However, in some cases due to dust, dirt, or heat, the air
around the set is unsuitable. In these cases an inlet duct should be fitted. This duct should run from the source of clean
air (outside the building, another room, etc.) to the engine mounted air filter. Do not remove the air filter and mount it at a
remote location as this can increase the possibility of dirt leaking through the ductwork and into the engine inlet. To
ensure that this type of installation will not have a detrimental effect on the operation of the pump set, the design of the
inlet duct should be approved by the factory.
Page 12 of 37
DIESEL ENGINE PUMP GROUP INSTALLATION, OPERATION AND MAINTENANCE MANUAL
The air inlet and exit openings should be large enough to ensure free flow of air into and out of the room.
Both the inlet and exit openings should have louvers for weather protection. These may be fixed but preferably
should be movable in cold climates so that while the pump set is not operating the louvers can be closed. It can
keep the room warm. For automatic starting pump sets, the louvers must be movable they can automatic open or
close. They should be programmed to open immediately upon starting the engine. The force of radiator air should
not be depended upon to open the louvers vanes unless the system has been specifically designed.
This diesel engine pump group use the heat exchanger cooling system, the radiated heat from the pump set must
still be removed from the room.
Page 13 of 37
DIESEL ENGINE PUMP GROUP INSTALLATION, OPERATION AND MAINTENANCE MANUAL
Page 14 of 37
DIESEL ENGINE PUMP GROUP INSTALLATION, OPERATION AND MAINTENANCE MANUAL
The outer end of the exhaust pipe, if horizontal, should be cut at 60°. A rain hood or cap is needed if there is
vertical pipe to prevent the rain or snow from entering the exhaust system. (See Fig.12).
The exhaust pipe must not be connected to other smoke tube or other such as :boiler smoke tube or smoke
pipe of canteen.
Exhaust pipe installation should be as short as possible and to reduce elbow, in particular to avoid the 90 °
bend with small radius. Piping should increase the diameter of the exhaust pipe and large bending radius
fittings or 45 ° bend when installing long pipes and more turns.
Note: Non - professional design muffler (especially low-noise muffler) may affect the output power of the engine and
even lead to abnormal running of equipment. The lifting of the exhaust pipe, muffler and the construction process of the
building:
Caution
Do not use galvanized pipe or fittings for the fuel system.
Fuel delivery and return lines should be at least as large as the fitting sizes on the pump set, and overflow piping
should be one size larger. For longer runs of piping or low ambient temperature, the size of these lines should be
increased to ensure adequate flow. Flexible piping should be used to connect to the engine to avoid damage or
Page 15 of 37
DIESEL ENGINE PUMP GROUP INSTALLATION, OPERATION AND MAINTENANCE MANUAL
Warning!
Non-ferrous metal parts(such as galvanized pipe , aluminum pipe, copper pipe, copper valves , etc.) are prohibiting
using in the oil containers, oil pipelines, fittings, valves.
Engine room tank can not be too small in principle. If the fuel tank is too small is not conducive to the heat
dissipation of the engine temperature oil return, especially the units continuous running several hours. The
proposed design of the fuel tank for more than four hours.
Float / the pointer instrument or transparent polycarbonate resin tube are used in for directions of fuel level, the
ordinary glass tube level gauge for level indication of the tank must not be used, as potential safety hazards maybe
exist.
Return pipe diameter must be not less than the diameter of the oil supply line, laying maximum height can not
exceed one meter the engine back oil exports, or back oil pressure will be too high and affect the normal working of
the engine, seriously may cause security incidents. In addition: prohibiting the installation valve in the oil return
pipe.
Warning!
Ensure adequate ventilation of the pump roon.
Ensure the cleaning of the pump room, the floor and the unit. If have any leakage of fuel, electrolyte, or coolant,
clean them immediately.
Never store flammable liquids near the diesel engine.
Rags with oil should be stored in covered metal containers.
It is not permitted to smoke or sparking near the battery and fuel, or other behaviors may cause fire. Because an
explosion may caused by the volatile gas fuel and hydrogen during battery charging (may some reasons the battery
leaks).
Before connecting or disconnecting the battery, power off the battery charger.
Conductive objects, such as tools, should stay away from exposed electrification parts, such as the output
electrodes, in order to prevent the electric arc or spark to cause an explosion because of the fuel or gas.
Do not inject fuel into the fuel tank in the case of the running of the machine or site unclean.
Do not try to start when known to have a fuel leak.
Excessive unburned gas in the exhaust system will be accumulating when multiple starts unsuccessful. You must
especially careful, because there are potential explosion hazard. Drain away the gas first, and then start.
Page 16 of 37
DIESEL ENGINE PUMP GROUP INSTALLATION, OPERATION AND MAINTENANCE MANUAL
6.5 Batteries
Warning
No smoking! No spark near the battery, the spark may cause explode because of hydrogen during charging the
battery.
The battery should be located as close as possible to the pump set and also accessible for maintain. If may affect
the starting capability if the wire is too long.
6.6 ReduceNoise
It is important to control noise during installation. There are many methods to control the noise.
Warning
Ear protection must be worn during operating or working around an operating diesel fire pump set.
Exhaust Silencer: it reduces noise with different model, normally including: industrial environment, the home
environment, high demand, top demand.
Shell: it can water-proof and reduce the noise, these shells are specially designed for special noise level
requirements.
Other way to reduce noise: when the unit is installed within the building, there is a variety of noise-reducing
equipment such as anechoic chamber, separated ventilation fan mufflers and walls of sound-absorbing materials
can reduce noise.
7. Operation Principle
Diesel engine fire pump group is as a standby device, when the unit receives effective signals or when motor pump is
power off or lack of phase, the pump unit can automatically start. At the same time, the control cabinet can monitor the
running state, the condition of pump room etc, to realize the control, alarm and display functions, ultimately acheve the
purpose of in automatic put out the fire or control the fire.
8. Operation
8.1 General
The diesel pump set is equipped with an advanced electronic control system. It allows the operator manually or
automatically control of the diesel pump set. It has protection circuits to sound an optional alarm and even shutdown the
set if problems occur.
The following shows the detail about start and stop. There is manual, automatic, remote control.
Page 17 of 37
DIESEL ENGINE PUMP GROUP INSTALLATION, OPERATION AND MAINTENANCE MANUAL
Check all hoses for loose connections and tighten or replace if necessary.
Check the battery terminals for corrosion – clean if necessary.
Warning
! When working with the batteries do not smoke or use an open flame in the vicinity. Hydrogen gas from batteries is
explosive.
! Do not short circuit battery output electrode.
Check the battery electrolyte level – fill with distilled water if necessary. If the battery is new and has never been
charged, fill with suitable premixed electrolyte and charge.
Check the control panel and the diesel pump set for heavy accumulation of dust and dirt – clean if necessary.
These can pose an electrical hazard or give rise to cooling problems.
Check the air filter blockage indicator, change a new filter if it is blocked.
Clear the area around the diesel pump set of any insecure items that could inhibit operation or cause injury. Ensure
cooling air ventilation screens are clear, not blocked.
Visually checks the entire diesel pump set for signs of leaks from the fuel system, cooling system, lubrication oil and
oil seal.
Regularly drain exhaust system condensate traps, if equipped.
Before commission, must open the pump discharger valve.
Page 18 of 37
DIESEL ENGINE PUMP GROUP INSTALLATION, OPERATION AND MAINTENANCE MANUAL
Note:
Except over speed shut down is automatic, all of the stop is by manual。
When you push the “Stop”Buttion, for starting the engine again, need reset first and and solve the problem
firstly and then can start again.
Page 19 of 37
DIESEL ENGINE PUMP GROUP INSTALLATION, OPERATION AND MAINTENANCE MANUAL
9. Control System
Page 20 of 37
DIESEL ENGINE PUMP GROUP INSTALLATION, OPERATION AND MAINTENANCE MANUAL
This diesel engine fire-pump group can achieve the auto, remote or manual control (including the monitory, alarm etc.)
operated by two control panels. One is main control panel and another is the engine control panel. Both of them can not
operation together to control, only when the main control panel can’t work, the engine control panel can achieve its
control function and vice verse), at the same times When the 2 control panel can’t operate, the engine can be started by
Emergency Starter for emergency start.
9.1 References
Regulated in accordance with N.F.P.A Standards
NF C15 100 – Installations électriques BT (Low voltage electrical installations)
NF EN60 439.1 – Ensembles appareillage BT (Low voltage equipment assemblies)
NF EN60 259 – Degré de protection des enveloppes (casing protection levels)
NF EN60 947 – Appareillage BT (Low voltage equipment)
NF EN60 269 – Fusibles (Fuses)
89/392/CEE (with amendments 91/368, 93/44 and 93/68) - Machines Directive
73/23/CEE (with amendment 93/68) - Low Voltage Directive
89/336/CEE (with amendment 92/31 and 93/68) – Electromagnetic compatibility Directive
Page 21 of 37
DIESEL ENGINE PUMP GROUP INSTALLATION, OPERATION AND MAINTENANCE MANUAL
If the information 'System started' is displayed during an attempt, the control panel stops the starter, cancels the
subsequent start attempts and activates the 'System running' indicator.
If the 'System started' information has not been displayed after six attempted starts, the control panel activates the
'Fail to start' alarm, displays the corresponding information and blocks the automatic system.
If the battery 1 or 2 error information is displayed during a start sequence, starting is done using only the battery
that is not signalling an error.
The control panel detects a speed signal from a magnetic pick-up fixed on the motor's housing opposite the crown
gear. Exceeding a minimum threshold provokes the 'System started' information. Exceeding a maximum threshold
blocks the automatic system and displays an overspeed information (visual and sound alarm, alarm display).
Digital voltmeters are displayed on the LCD screen and are used to check the voltage of each battery when the
starter is used by isolating it from its linked charger. This means that it is possible to check that the voltage is
sufficient for starting which requires at least 80% of the nominal voltage.
If a battery is out of action or is not sufficiently charged, this does not compromise starting or the various functions
of the control panel.
There is a Pressure controller, It can show the pressure and set the pressure data.
Page 22 of 37
DIESEL ENGINE PUMP GROUP INSTALLATION, OPERATION AND MAINTENANCE MANUAL
Moving the selector switch to the Stop position to isolate the pressure switch and pressure transducer.
Moving the selector switch to the Stop position prevents manual or automatic starting .
The mode is displayed on the LCD screen as follows:
Manual mode if the selector switch is on Manu.
Auto mode if the selector switch is on Auto.
Off mode if the selector switch is on stop.
WARNING!
The system can be stopped when operating by pressing the push “Stop”button on the front of the control panel. The
selector switch must be put in the “Off”position to stop the engine before using the STOP push button to avoid the
system immediately restarting if a start request is still operational.
9.3.3.2 Chargers
The chargers are adjusted with a 12V or 24V DC output depending on the nominal voltage of the battery connected
to them. They operate normally with an input voltage that varies between + 15% and - 10% around a nominal value
of 230V AC (60Hz).
If changes to the mains voltage (+/– 10%) and frequency (+/– 2%) are slow and cumulative, the charger output
voltage remains stable around the set value with the following tolerances:
With batteries connected: +/– 1%
Without batteries connected: +/– 4%
The charging current is highest when the battery voltage is equal to its nominal voltage. There is no significant charge
when the battery floating voltage is 115% of the nominal voltage.
Page 23 of 37
DIESEL ENGINE PUMP GROUP INSTALLATION, OPERATION AND MAINTENANCE MANUAL
ensure staff safety. The K19 relay is fitted to a plate and slaved to a thermostat fitted to the engine's cylinder head
and the 'System started' display. This means that the heater coils are not powered when the engine temperature is
greater than a set threshold or when the power pump is operating.
An 'On Off' selector switch located on the front of the control panel turns the preheater off at any time.
‘
9.3.5 Monitoring
The control panel monitors the following:
Battery 1 and 2 voltage (digital voltmeter on the LCD screen)
Battery 1 charge rate (digital ammeter on the LCD screen)
Battery 2 charge rate (digital ammeter on the LCD screen)
Fuel level (analogical indicator on mechanical gauge)
Oil pressure (analogical manometer)
Oil Temperature (analogical thermometer)
Alternator Current (analogical amperemeter)
Water temperature (analogical thermometer)
Engine speed(Speed odometer)
Time counter (tachymeter)
The degree of error for the equipment is no more than +/- 5% except for the tachymeter where it is +/-25 rpm.
Page 24 of 37
DIESEL ENGINE PUMP GROUP INSTALLATION, OPERATION AND MAINTENANCE MANUAL
9.3.7.6 Overspeed
Diesel engine overspeed
Page 25 of 37
DIESEL ENGINE PUMP GROUP INSTALLATION, OPERATION AND MAINTENANCE MANUAL
9.4.3 Battery
9.4.3.1 Specifications
6 cell lead batteries are used (for starting purposes) providing a nominal voltage of 12V. For 24V applications, each direct
current source is fitted with two 12V batteries connected in series. These batteries do not need any special maintenance
other than checking the level of electrolyte and cleaning from time to time if necessary. The size of the batteries depends
on the diesel engine used based on the criteria described below.
9.4.3.2 Sizing
The battery size depends on the following criteria and assumes that the temperature in the premises is at least 10°C and
the diesel engines have been correctly preheated:
The equipment has been selected for its suitability for starting, especially its ability to meet the starter's needs as
specified by the diesel engine's manufacturer.
Each battery has enough capacity for 6 successive 15 second starting attempts.
The batteries have sufficient capacity to ensure the starting sequence, i.e. six attempts plus the 'Not started' error,
should it occur, after a mains power supply failure lasting 72 hours.
The system's consumption in stand-by is about 400 mA which requires deducting a capacity of about 29 Ah from the
nominal battery capacity for a 72 hour mains power supply cut before making the start attempts.
The voltage of a battery providing the direct current required by the starter must not be less than 80% of the battery's
nominal value.
9.4.4 Chargers
9.4.4.1 Specifications
Type Automatically adjusted
Rectification Double alternating
Primary voltage 230V – 50Hz
Insulation voltage 3750 V
Operating temperature range - 5°C to + 50°C
Overloading / short circuit protection yes
Nominal secondary voltage 12V DC 24V DC
Floating voltage 13.8V DC 27.2V DC
Secondary current 10A 10A
Consumption 150W 250W
9.4.5.2 Outputs
In addition to the five outputs for displaying information (two NO contacts and two NC contacts for each with the following
Page 26 of 37
DIESEL ENGINE PUMP GROUP INSTALLATION, OPERATION AND MAINTENANCE MANUAL
characteristics), the user has a 4A contact (closed when the power pump system is operating) to manage the ventilation
gate valves.
Permanent allowable current 2A
Maximum acceptable voltage 250V
Interrupting capacity 120W
9.6 Alarm
Mains Failure
When the mains power supply is cut off (180 seconds + 21 seconds time delay).
Charger 1 and 2 Error
When the mains power supply is cut off (180 seconds time delay) or when the downstream fuse is blown. (20 second
time delay)
Battery 1 and 2 Error:
When battery unable to be operated.
Disconnect a battery to obtain the alarm.
Starter Error
When the connection between the control panel and the starter has some problems. (15 second time delay).
Disconnect the starter coil supply.
Pressure Switch Not Automatic
Pressure switch and pressure sensor are no longer operating automatically.
Set the appropriate selector switch to Stop or Manu.
Fail to Start
When the engine fails to start after six attempts.
Hold the engine stop handle and lower the pressure, the alarm will occur after six start attempts.
Engine Temperature Alarm
When the engine is higher temperature.
Shunt the sensor to obtain the error.
Oil Pressure Alarm
When there is an oil pressure error during the engine is running.
Disconnect the sensor to obtain the error when the engine is not running.
Earth the sensor when the engine is running to obtain the error (5 second time delay).
Diesel Level Alarm
When the level of diesel is insufficient.
Disconnect the sensor from the fuel tank to obtain the error.
Diesel Leak Alarm
When diesel tank is leakage (presence of diesel in the run-off tank or the double skin).
Page 27 of 37
DIESEL ENGINE PUMP GROUP INSTALLATION, OPERATION AND MAINTENANCE MANUAL
Pre-Heating Alarm
When there is an engine preheating error.
Press the vigi 30 mA test button in the control panel or set the selector switch to stop to obtain the error.
Overspeed
Whena diesel engine is overspeed.Engine emergency stop.
Turn automatic starting off.Press the test button on the front of the control panel to obtain the error (the engine rpm must
be greater than 2,000 rpm or at 1,700 rpm to perform the test).An external input dry contact option is available for
triggering the alarm on terminals 0 and 9.
Water Tank High or Low Alarm
When there is a high or low level in the pump water tank.
Lower or raise the level bulbs in the tank to obtain the error
Sprinkler Room tTemperature Alarm
When there is a low temperature in the sprinkler room (4°C).
Lower the thermostat until the alarm is reached to obtain this error.
Ventilator gate valve error
When the gate valves have not been opened during the engine is running.
Press on the gate valve stops when the engine is running to obtain this error.
In stand-by, disconnect a stop to obtain the error.
Resetting alarms
Push the “Reset Fault’ button on the front of the control panel
Page 28 of 37
DIESEL ENGINE PUMP GROUP INSTALLATION, OPERATION AND MAINTENANCE MANUAL
Page 29 of 37
DIESEL ENGINE PUMP GROUP INSTALLATION, OPERATION AND MAINTENANCE MANUAL
Pump leakage
Seal leakage
-The operating point is not the - Re - adjustment of the operating
# # # # # # # #
design point point
Page 30 of 37
DIESEL ENGINE PUMP GROUP INSTALLATION, OPERATION AND MAINTENANCE MANUAL
- Check
- Tighten the bolt
- Connecting bolts loose - Replace the gasket
# - Improperly sealed - Check the pump tubing
connection , it is necessary to reduce
the piping layout
- Check the flushing and sealing
liquid pressure
- Cleaning the seal piping , if
possible, the sealing liquid use an
-Shaft seal wear external water supply or increase the
#
pressure
- Replace the shaft seal
- Replacement of worn parts
- Replace shaft sleeve
- Change the pipeline
- If the pipeline is too much
- The liquid flow of pump inlet resistance, it is necessary to change
# # # #
pipe is poor the inlet tube
- Check the piping distorted or
deformed, and correct.
- Adjust
-Gland, end caps, the seal - Replace
# # gland is installed wrong or - Corrected
fillers wrong - Replace the packing
- Replace of worn parts
- Check the flushing and sealing
liquid pressure
- Cleaning the seal piping , if
- Lack of coolant or cooling
# # possible with an external sealing
chamber contaminated
liquid water or increase the pressure
- Increased coolant flow
- Clean coolant
- Re-adjust
- Check piping connections and
-Pump improperly adjusted or pump installation, reduce the piping
# #
pipes have resonance layout if necessary
- Piping connections use damping
materials
Page 31 of 37
DIESEL ENGINE PUMP GROUP INSTALLATION, OPERATION AND MAINTENANCE MANUAL
- Increase or decrease , or
replacement of oil
-Check and adjust the operating
point
# -Axial force is too large
-Check the operation state
-Check the inlet flow
- Clean rotor
# # # -Rotor imbalance
- Rotor rebalance
- Check
- The solid of base is not
# # # - Reform
enough
- Correct
- Adjust
- Check the rotor
-Friction between impeller - Check the impeller position
# # # #
and pump shell - Check the pipe connections to
ensure that the pump is not under
stress
- Exhaust
The air bubbles is not allowed - Check the air tightness of the inlet
# # #
in the medium pipe, if necessary install gasket
- Install exhaust valve
Page 32 of 37
DIESEL ENGINE PUMP GROUP INSTALLATION, OPERATION AND MAINTENANCE MANUAL
Page 33 of 37