KCD2-STC-Ex1 2O ES
KCD2-STC-Ex1 2O ES
KCD2-STC-Ex1 2O ES
KCD2-STC-Ex1.2O.ES
< 1-channel isolated barrier
< 24 V DC supply (Power Rail)
< Input for 2-wire SMART transmitters and current sources
< Signal splitter (1 input and 2 outputs)
< Dual output 0/4 mA ... 20 mA or 0/1 V ... 5 V
< Terminal blocks with test sockets
< Up to SIL 3 acc. to IEC/EN 61508
Function
This isolated barrier is used for intrinsic safety applications.
The device supplies 2-wire transmitters in the hazardous area, and can also be used with current sources.
It transfers the analog input signal to the safe area as two isolated output signals.
Bi-directional communication is supported for SMART transmitters that use current modulation to transmit data and voltage modulation to receive
data.
The output is selected as a current source, current sink, or voltage source via switches.
Test sockets for the connection of HART communicators are integrated into the terminals of the device.
Application
The device supports the following SMART protocols:
l HART
l BRAIN
Connection
KCD2-STC-Ex1.2O.ES
- +
1+ 5 + V
HART
I
HART
HART
+ -
6
2-
3+
- +
HART
7
Release date: 2023-06-01 Date of issue: 2023-06-01 Filename: 286746_eng.pdf
mA + V
II
+ -
4- 8
9+
10-
24 V DC
Zone 0, 1, 2 24 V DC Zone 2
Div. 1, 2 Power Rail Div. 2
Technical Data
General specifications
Signal type Analog input
Functional safety related parameters
Safety Integrity Level (SIL) SIL 3
Systematic capability (SC) SC 3
Supply
Electromagnetic compatibility
Directive 2014/30/EU EN 61326-1:2013 (industrial locations)
Conformity
Electromagnetic compatibility NE 21:2012
EN 61326-3-2:2008
Degree of protection IEC 60529:2001
Protection against electrical shock UL 61010-1:2012
Ambient conditions
Ambient temperature -20 ... 60 °C (-4 ... 140 °F)
extended ambient temperature range up to 70 °C (158 °F), refer to manual for
necessary mounting conditions
Mechanical specifications
Degree of protection IP20
Connection screw terminals
Mass approx. 100 g
Dimensions 12.5 x 124 x 114 mm (0.5 x 4.9 x 4.5 inch) (W x H x D) , housing type A2
General information
Note Both output loads must be connected to ensure complete and correct operation within
the technical specification.
Supplementary information Observe the certificates, declarations of conformity, instruction manuals, and manuals
where applicable. For information see www.pepperl-fuchs.com.
Front view
Removable terminals
blue
1 2
3 4
LED green:
KCD2-STC-
Ex1.2O.ES
Power supply
PWR
S1
S2
S3
S4
I II
Removable terminals
green
UPR-03 Universal Power Rail with end caps and cover, 3 conductors, length: 2 m
UPR-03-M Universal Power Rail with end caps and cover, 3 conductors, length: 1,6 m
UPR-03-S Universal Power Rail with end caps and cover, 3 conductors, length: 0.8 m
K-DUCT-BU-UPR-03 Profile rail with UPR-03- * insert, 3 conductors, wiring comb field side, blue
Release date: 2023-06-01 Date of issue: 2023-06-01 Filename: 286746_eng.pdf
Accessories
KC-ST-5GN Terminal block for KC modules, 2-pin screw terminal, green
KC-STP-5GN Terminal block for KC modules, 2-pin screw terminal, with test sockets, green
KC-STP-5BU Terminal block for KC modules, 2-pin screw terminal, with test sockets, blue
Configuration
S1 ... S4
Output 1 S1 S2
Current source output I II
Current sink output II II
Voltage output I I
Not valid II I
Output 2 S3 S4
Current source output II I
Current sink output II II
Voltage output I I
Not valid I II
5
Pepperl+Fuchs Group USA: +1 330 486 0002 Germany: +49 621 776 2222 Singapore: +65 6779 9091
www.pepperl-fuchs.com [email protected] [email protected] [email protected]