Control & Protection
Control & Protection
WHAT IS PROTECTION
IT IS A KIND OF INSURANCE FOR COSTLY ELECTRICAL EQUIPMENT.
THE COST OF PROTECTION IS SIMILAR TO THE INSURANCE PREMIUM AND WORKS OUT
TO BETWEEN 1 TO 5 PER CENT OF THE COST OF THE PROTECTED EQUIPMENT.
PROTECTION
EXAMPLES:
A 100 MW GENERATOR MAY COST ABOUT RS 30 CRORES. THE COST OF COMPLETE
PROTECTION WITH PANELS MAY BE 30 LAKHS (i.e. ABOUT 1 PER CENT).
A 150 MVA POWER TRANSFORMER MAY COST ABOUT RS. 2.0 CRORES. THE COST
OF PROTECTION WILL BE AROUND RS. 10 LAKHS (5 PER CENT).
ASSOCIATED EQUIPMENT
CURRENT TRANSFORMERS
VOLTAGE TRANSFORMERS
AUXILIARY SUPPLIES (AC or DC)
CIRCUIT BREAKERS
CURRENT TRANSFORMERS
APPLICABLE INDIAN STANDARDS – IS 2705 BAR PRIMARY AND WOUND PRIMARY
METERING CURRENT TRANSFORMER
PROTECTIVE CURRENT TRANSFORMER
METERING CT
ACCURACY FROM 10 TO 125% RATED CURRENT
CLASSES OF ACCURACY – 0.1, 0.5, 1.0 & 1.5
Page 1 of 30
POWER SYSTEM PROTECTION
PROTECTIVE CT
ACCURACY IMPORTANT FROM 100% RATED CURRENT UPTO ACCURACY LIMIT FACTOR
WHICH CAN BE 5, 10, 15 OR 20
VOLTAGE TRANSFORMERS:
ELECTRO MAGNETIC TYPE (FOR BUS VTs)
CAPACITOR TYPE (FOR LINE VTs)
Page 2 of 30
POWER SYSTEM PROTECTION
USUALLY DUAL PURPOSE i.e. SUITABLE FOR BOTH METERING AND PROTECTION.
FOR METERING, ACCURACY IS IMPORTANT BETWEEN 0.9 TO 1.1 TIMES RATED
PRIMARY VOLTAGE, WITH 0.25 TO 1.0 TIMES RATED BURDEN.
FOR PROTECTION ACCURACY IS IMPORTANT BETWEEN 0.05 TO 0.9 TIMES RATED
PRIMARY VOLTAGE AND FROM 1.1 TO Vf TIMES RATED PRIMARY VOLTAGE, AT 0.25
TO 1.0 TIMES RATED BURDEN.
Vf IS 1.1 FOR SOLIDLY EARTHED SYSTEMS AND 1.9 FOR INSULATED SYSTEMS (FOR 30
SECONDS OR 8 HOURS)
CLASSES OF ACCURACY – 0.5, 1.0, 2.0 & 5.0 FOR METERING
CLASSES OF ACCURACY - 3 & 5 FOR PROTECTION.
CIRCUIT BREAKERS:
THE CONTACT OF THE PROTECTION RELAYS OPERATES ON THE TRIP COIL OF THE
CIRCUIT BREAKER EITHER DIRECTLY OR THROUGH HIGH SPEED TRIPPING RELAYS.
FOR EHV CIRCUIT BREAKERS GENERALLY TWO TRIP COILS ARE PROVIDED.
THE TRIP COILS OPERATE ON ONE OF THE AUXILIARY SUPPLIES NOTED ABOVE.
PROTECTION FUNDAMENTALS
CLASSIFICATION OF RELAYS BASED ON THE PRINCIPLES OF OPERATING MOVEMENT:
ELECTROMECHANICAL RELAYS:
ATTRACTED ARMATURE OR HINGED ARMATURE RELAYS
INDUCTION DISC RELAYS
INDUCTION CUP/VANE RELAYS
POLARISED MAGNET RELAYS
MOVING COIL RELAYS
THERMAL RELAYS (BI-METALLIC TYPE)
THERMAL RELAYS (HEAT SINK TYPE)
MECHANICAL RELAYS (BUCHHOLZ RELAY)
Page 3 of 30
POWER SYSTEM PROTECTION
ELECTROMAGNETIC RELAYS:
REED RELAYS
STATIC RELAYS:
RELAYS USING ANALOGUE TECHNIQUES (COMPARATORS, LEVEL DETECTORS, ETC)
RELAYS USING DIGITAL TECHNIQUES (MICROPROCESSORS, ICs ETC)
NOTE:
WE MUST UNDERSTAND THE DIFFERENCE BETWEEN ELECTROMECHANICAL AND
ELECTROMAGNETIC RELAYS. IN THE FORMER, THERE IS ALWAYS A MECHANICAL
LINKAGE BETWEEN THE OPERATING MOVEMENT AND THE CONTACT ASSEMBLY,
WHEREAS IN THE LATTER, THE CONTACTS CLOSE DUE TO IONIZATION BROUGHT
ABOUT BY MAGNETISATION OF THE RELAY.
Page 4 of 30
POWER SYSTEM PROTECTION
Page 5 of 30
POWER SYSTEM PROTECTION
OPERATION INDICATOR
MECHANICAL FLAG, SELF OR HAND RESET, USUALLY HAND RESET
OR
LED, RESET BY PUSH BUTTON
OUTPUT RELAYS
MEASURING ELEMENTS USUALLY HAVE LOW CONTACT RATINGS AND LIMITED
NUMBER OF CONTACTS AND HENCE DRIVE A FOLLOWER RELAY, WHICH IS AN
AUXILIARY RELAY HAVING SUFFICIENT No. OF CONTACTS WITH MUCH HIGHER
Page 6 of 30
POWER SYSTEM PROTECTION
ZONES OF PROTECTION
IDEALLY, THE VARIOUS ZONES OF PROTECTION SHOULD OVERLAP ACROSS THE
CIRCUIT BREAKERS AS SHOWN IN FIGURE. SO THAT THERE ARE NO BLIND SPOTS,
ESPECIALLY THOSE WHICH EXIST BETWEEN CTs AND CBs (E.G. POST MOUNTED CTs)
IF THE CTs ARE MOUNTED ON EITHER SIDE OF THE CIRCUIT BREAKER AS SHOWN
BELOW, OVER LAPPING OF THE ZONES OF PROTECTION IS EASY.
Page 7 of 30
POWER SYSTEM PROTECTION
IN THIS CASE, THE FEEDER PROTECTION WILL NOT BE ABLE TO SEE A FAULT AT ‘F’ AND
PROTECTION AT THE FARTHER END WILL HAVE TO BE USED TO ISOLATE THE FAULT.
Page 8 of 30
POWER SYSTEM PROTECTION
Page 9 of 30
POWER SYSTEM PROTECTION
IN THE TIME GRADING PRINCIPLE, THE OPERATING CURRENT SETTINGS OF THE RELAYS
AT VARIOUS LOCATIONS ARE MORE OR LESS THE SAME (SO THAT THEY PICK-UP FOR
ALL FAULTS), BUT THE FINAL TRIPPING IS DELAYED BY SUITABLE INTERVALS BY
MEANS OF DEFINITE TIME DELAY RELAYS. THIS ENSURES THAT THE RELAY NEAREST
TO FAULT TRIPS FIRST AND ISOLATES THE FAULTY SECTION. IF IT FAILS, THE RELAY IN
THE NEXT PREVIOUS SECTION TAKES OVER AND SO ON. ONCE THE FAULT IS CLEARED,
ALL THE CURRENT RELAYS RESET (THESE RELAYS ARE USUALLY DESIGNED TO HAVE
HIGH DROP-OFF / PICK-UP RATIO), TIME GRADING IS OBTAINED GENERALLY BY
DEFINITE TIME DELAY RELAYS BUT IT IS ALSO POSSIBLE TO USE INVERSE TIME
RELAYS.
Page 10 of 30
POWER SYSTEM PROTECTION
STATIC RELAYS
POWER SYSTEM RELAYS - DESIGN BASED ON ELECTRONIC COMPONENTS.
IS 8686 DEFINITION - “A PROTECTIVE RELAY IN WHICH THE DESIGNATED RESPONSE
IS DEVELOPED BY ELECTRONIC, MAGNETIC OR OTHER COMPONENTS WITHOUT
MECHANICAL MOTION”.
FIELD OF ELECTRONICS - LARGELY COMPRISES PROCESSING OF ELECTRICAL
SIGNALS FOR A DESIRED FUNCTIONAL OUTPUT.
ELECTRICAL SIGNALS - FROM CURRENT TRANSFORMERS AND POTENTIAL
TRANSFORMERS.
PROCESSING CIRCUITS - AMPLIFIERS, COMPARATORS, PHASE SHIFTING NETWORKS,
FILTERS ETC
SIGNALS IN ANALOG FORM DO NOT UNDERGO ANY CHANGE IN FORM.
SETTINGS OF OPERATING VALUE, OPERATING TIME, CHARACTERISTIC CURVE ETC.
WILL BE WITH POTENTIOMETERS (VARIABLE RESISTOR) OR FIXED RESISTOR
SELECTED BY DIP SWITCHES OR THUMB WHEEL SWITCHES (DIGITAL SWITCHES).
SETTINGS ARE OBTAINED BY HAVING TAPS ON THE BUILT-IN INSTRUMENT
TRANSFORMERS, CAUSING RELAY BURDENS TO VARY.
PROCESSOR RELAYS
AGAIN ELECTRONIC RELAYS.
SIGNALS FROM CT’S AND PT’S ARE CONVERTED TO DIGITAL SIGNALS (O’s AND I’s).
PROCESSING DONE BY THE DEVICE CALLED ‘MICROPROCESSOR’ OR
‘MICROCONTROLLER’.
TECHNIQUE COMPRISES OF STORING THE DIGITAL SIGNALS IN A CIRCUIT BLOCK
CALLED “REGISTER” AND CARRYING OUT THE SIGNAL PROCESSING BY A SERIES OF
INSTRUCTIONS (LOGICAL & ARITHMETIC).
TECHNIQUE POPULARLY CALLED BY THE NAME “SOFTWARE” (LOW LEVEL AND
HIGH LEVEL LANGUAGES).
SETTINGS BY DIP SWITCHES AS IN STATIC RELAYS.
SIGNALS CONVERTED FROM ANALOG TO DIGITAL FORM (O’s AND I’s).
WORD LENGTH OF 8, 16 OR 32 BITS FORM THE SIGNAL INFORMATION.
TECHNIQUE PROVIDES SUPERIOR PERFORMANCE AND FLEXIBILITY.
SETTINGS OBTAINED WITHOUT TAPS ON INSTRUMENT TRANSFORMERS - MAKES
BURDEN CONSTANT AT ALL SETTINGS.
Page 11 of 30
POWER SYSTEM PROTECTION
NUMERICAL RELAYS
TECHNIQUE OF PROCESSING THE SIGNALS WOULD REMAIN SAME AS IN PROCESSOR
RELAYS i.e., CONVERTING THE ANALOG SIGNALS TO DIGITAL AND PROCESSING BY A
SOFTWARE.
FEATURES ENHANCED BY HAVING THE SETTINGS DISPLAYED ON A SMALL LCD
SCREEN – SIMILAR TO THAT OF CALCULATOR OR DIGITAL POCKET DIARY.
SETTING DONE BY PUSH BUTTONS AND READ DIRECTLY ON THE SCREEN.
AVOIDS MANUAL COMPUTATION AS WOULD BE REQUIRED WHEN DONE BY DIP
SWITCHES.
DIGITAL SIGNALS STORED IN ANOTHER DEVICE TERMED “MEMORY”.
HELPS IN RECORD OF FAULT LEVEL FOR RETRIEVAL AND ANALYSIS.
SIGNALS CONVERTED TO A FORM (RS 232) SUITABLE FOR COMMUNICATING WITH
PCs.
FACILITATES IN MAKING THE SETTINGS FROM A REMOTE LOCATION SUCH AS A
CENTRALISED CONSOLE.
HELPS IN OBTAINING ALL THE DATA ON A PC FOR FURTHER PROCESSING.
Page 12 of 30
POWER SYSTEM PROTECTION
Page 13 of 30
POWER SYSTEM PROTECTION
2 INSULATION TESTS
TEST TYPE TEST VALUES REFERENCE
STANDARDS
3. INSULATION TESTS
TEST TYPE TEST VALUES REFERENCE
STANDARDS
Page 14 of 30
POWER SYSTEM PROTECTION
4. MECHANICAL TESTS
TEST TYPE TEST REFERENCE
VALUES SSTANDARDS
FAULT CALCULATIONS
COMPLEX QUANTITY REPRESENTATION:
CONVENTIONAL Z
RECTANGULAR x + jy
TRIGNOMETRIC Z (Cos + jsin)
EXPONENTIAL Z e^j
CIRCUIT PARAMETERS
RESISTANCE: R
REACTANC: X – INDUCTIVE / CAPACITIVE
IMPEDANCE : Z
Page 15 of 30
POWER SYSTEM PROTECTION
Page 16 of 30
POWER SYSTEM PROTECTION
Page 17 of 30
POWER SYSTEM PROTECTION
TRANSFORMER PROTECTION
DEPENDING ON THE CAPACITY OF TRANSFORMER (50 KVA OR 150 MVA), THE
FOLLOWING PROTECTIONS ARE PROVIDED.
BUCHHOLZ
DIFFERENTIAL
REF (RESTRICTED EARTH FAULT)
OVER FLUXING (V/F)
BACKUP OVER CURRENT AND EARTH FAULT WITH INSTANTANEOUS HIGH SET ON
THE HV SIDE
BACKUP OVER CURRENT AND EARTH FAULT WITH INSTANTANEOUS HIGHSET ON
THE LV SIDE
OIL TEMPERATURE, WINDING TEMPERATURE & OIL SURGE
THERMAL OVERLOAD
Page 18 of 30
POWER SYSTEM PROTECTION
Page 19 of 30
POWER SYSTEM PROTECTION
THE INSTANTANEOUS HIGHSET ELEMENTS ARE USUALLY SET IN SUCH A WAY THAT
THEY DO NOT OPERATE FOR FAULTS ON THE LV SIDE OF THE TRANSFORMER, WHEREAS
ALL FAULTS ON THE HV SIDE ARE CLEARED INSTANTANEOUSLY BY THESE RELAYS.
INVERSE TIME OVER CURRENT AND EARTH FAULT RELAYS ARE PROVIDED ON THE LV
SIDE OF THE TRANSFORMERS TO SERVE AS BACK-UP FOR FAULTS DOWN THE LINE ON
LV FEEDERS AS WELL AS ON BUSBARS.
WHEN TWO TRANSFORMERS ARE IN PARALLEL ON THE LV SIDE, IT IS NORMAL
PRACTICE TO PROVIDE DIRECTIONAL OVER CURRENT & EARTH FAULT RELAYS,
LOOKING TOWARDS THE TRANSFORMERS. THESE RELAYS ALSO SERVE AS BACK-UP
FOR INTERNAL FAULTS TO THE TRANSFORMERS.
Page 20 of 30
POWER SYSTEM PROTECTION
THERMAL OVERLOAD
THERMAL OVERLOAD RELAYS CAN BE PROVIDED TO MONITOR THE OVERLOAD
CONDITIONS ON THE TRANSFORMERS. THE NORMAL INVERSE TIME RELAYS ARE
UNABLE TO PROVIDE EFFECTIVE OVERLOAD PROTECTION BECAUSE THEIR
MINIMUM PICK-UP VALUE IS AROUND 110% TO 120% OF THE SETTING. THERMAL
OVERLOAD RELAYS FOR TRANSFORMERS HAVE TO DESIGNED WITH LARGE TIME
CONSTANTS SUCH AS 120. SOMETIMES, SIMPLE DEFINITE TIME OVER CURRENT
RELAYS HAVING A HIGH DROP-OFF / PICK-UP RATIO ARE USED FOR OVERLOAD
PROTECTION OF TRANSFORMERS. THESE RELAYS DO NOT CATER FOR THE ACTUAL
OVERLOAD CAPACITY OF THE TRANSFORMERS AS IS DONE BY THE THERMAL
OVERLOAD RELAYS.
Page 21 of 30
POWER SYSTEM PROTECTION
LINE PROTECTION:
MAIN I – DISTANCE PROTECTION (3 ZONE / 4 ZONE)
MAIN II – DISTANCE PROTECTION (3 ZONE / 4 ZONE) OR PHASE COMPARISON
CARRIER CURRENT PROTECTION OR WAVE DETECTION PROTECTION.
BACK-UP DIRECTIONAL O/C & E/F PROTECTION (DEFINITE TIME OR INVERSE TIME).
CHECK SYNCHRONISING / DEAD LINE CHARGING.
1/3 PHASE AUTO RECLOSING.
OVER VOLTAGE.
DISTANCE TO FAULT LOCATOR.
Page 22 of 30
POWER SYSTEM PROTECTION
MOTOR PROTECTION
THERMAL OVERLOAD
INSTANTANEOUS SHORT CIRCUIT
INSTANTANEOUS EARTH FAULT
SINGLE PHASING
LOCKED ROTOR PROTECTION
NUMBER OF HOT STARTS PER HOUR
UNBALANCED LOAD (NEGATIVE PHASE SEQUENCE PROTECTION)
IF THIS WITHSTAND TIME IS LESS THAN THE MOTOR STARTING TIME, IT BECOMES
NECESSARY TO PROVIDE SEPARATE LOCKED ROTOR PROTECTION COUPLED WITH A
CENTRIFUGAL SWITCH OPERATED BY THE ROTOR OR THE MOTOR.
WITH SOFTWARE BASED RELAYS, IT IS PPOSSIBLE TO GIVE A ‘BLOCK ON START’
FEATURE WHICH WILL TAKE CARE OF THE ABOVE CONDITION WITHOUT USING
CENTRIFUGAL SWITCH.
FEEDER PROTECTION
FOR LT FEEDERS, IF AIR CIRCUIT BREAKERS ARE PROVIDED FOR CONTROLLING THEM,
INVERSE DEFINTE MINIMUM TIME LAG (IDMTL) OVER CURRENT AND EARTH FAULT
RELAYS ARE USED.
IF THE PROTECTION AT THE BACK OF THESE FEEDERS IS PROVIDED BY MEANS OF HRC
(HIGH RUPTURING CAPACITY) FUSES, IT IS PREFERABLE TO USE EXTREMELY INVERSE
TIME CHARACTERISTICS ON THE RELAYS SO THAT THEY CAN GRADE WITH THESE
FUSES.
Page 23 of 30
POWER SYSTEM PROTECTION
Page 24 of 30
POWER SYSTEM PROTECTION
CAPACITOR:
SHUNT CAPACITORS
SHUNT CAPACITORS ARE USED IN SUB-STATIONS TO IMPROVE POWER FACTOR AND
VOLTAGE OF THE SYSTEM.
SHUNT CAPACITOR BANKS ARE MADE UP OF A NUMBER OF SERIES – PARALLEL
UNITS MAKING UP THE TOTAL MVAR REQUIREMENT FOR THE SYSTEM.
HV CAPACITORS ARE GENERALLY RATED FOR 11 KV TO 33 KV.
IN MAJOR SUB-STATIONS, HV CAPACITORS ARE CONNECTED TO THE TERTIARY
WINDING OF THE POWER TRANSFORMERS WHERE THE VECTOR GROUP OF THE
POWER TRANSFORMERS IS GENERALLY YY0 WITH DELTA TERTIARY WINDING.
SHUNT CAPACITORS ARE ALSO USED AT INDUSTRIAL SUB-STATIONS IN ORDER TO
IMPROVE THE POWER FACTOR OF THE LOAD DRAWN BY INDUSTRIES.
CAPACITOR PROTECTION
INVERSE TIME OVER CURRENT AND EARTH FAULT
OVER VOLTAGE
UNDER VOLTAGE
UNBALANCE CURRENT (FOR DOUBLE STAR BANKS WITH FLOATING NEUTRAL).
NEUTRAL DISPLACEMENT (FOR SINGLE STAR BANKS USING RVTs WHOSE
SECONDARY IS CONNECTED IN OPEN DELTA).
Page 25 of 30
POWER SYSTEM PROTECTION
Page 26 of 30
POWER SYSTEM PROTECTION
ix. FINAL TEST ON LOAD CURRENT / VOLTAGE FOR CONFIRMING THE DIRECTION OF
RELAYS (DISTANCE, DIRECTIONAL ETC) AND CORRRECTNESS OF CT POLARITIES
FOR DIFFERENTIAL SCHEMES.
TEST EQUIPMENT:-
i. OVER CURRENT TEST SET
FOR CARRYING OUT SECONDARY INJECTION TESTS ON CURRENT OPERATED
RELAYS, ESPECIALLY IDMT AND DEFINITE TIME, A COMPACT TEST KIT
INCORPORATING VARIABLE CURRENT FACILITY AND A TIMER IS AVAILABLE.
THE MAGNITUDE OF CURRENT CAN BE VARIED IN THE RANGE 0 – 200AMPS. THIS
ENABLES TESTING OF EVEN 5A RATED RELAYS AT 20 TIMES THE MAXIMUM
SETTING OF 200%. THE TIMER IS DIGITAL WITH A RESOLUTION OF 1
MILLISECOND SO THAT EVEN INSTANTANEOUS, HIGH SPEED RELAY OPERATING
TIMES CAN BE MEASURED.
GENERALLY, THIS TEST KIT INCORPORATES LOW REACTANCE TRANSFORMERS,
VARIACS, CHOKES, CAPACITORS ETC. SO THAT THE OUTPUT CURRNET (TEST
CURRENT) WAVE FORM IS AS SINUSOIDAL AS POSSIBLE. THIS IS ESSENTIAL
ESPECIALLY FOR TESTING IDMT ELECTROMECHANICAL RELAYS AS THE
OPERATING TIMES OF THESE RELAYS ARE AFFECTED BY VARIATION IN THE
FREQUENCY OF THE TEST CURRENT AS WELL AS BY THE HARMONICS PRESENT IN
THE TEST CURRENT. OVER TEST KITS CAN ALSO INCLUDE VARIABLE AC & DC
VOLTAGE FACILITY FOR TESTING AUXILIARY AND HIGH SPEED TRIPPING
RELAYS.
Page 27 of 30
POWER SYSTEM PROTECTION
Page 28 of 30
POWER SYSTEM PROTECTION
Page 29 of 30
POWER SYSTEM PROTECTION
95 - 99. USED FOR SPECIFIC APPLICATIONS ON INDIVIDUAL INSTALLATIONS WHERE NONE OF THE
ASSIGNED NUMBERING FUNCTIONS FROM 1 TO 94 ARE USED.
Page 30 of 30