HVAC-Chapter 3 - Moist Air Properties (Psychrometry)
HVAC-Chapter 3 - Moist Air Properties (Psychrometry)
• Even Though it is a mixture of gases ( N2,O2 , Ar and CO2 ) , yet for the purpose of Psychrometry , it is
considered to be a mixture of dry air and water vapor only.
The atmospheric air can be treated as an ideal-gas mixture whose pressure is the
sum of the partial pressure of dry air Pa and that of the water vapor Pv, Partial
Pressure of water vapor (vapor pressure):
P = Pa + Pv
The pressure of water vapor would exert if it existed alone at the temperature and
volume of atmospheric air
Important Psychometric Properties:
1-Dry Bulb Temperature (DBT): Is the temperature of the moist air as it
measured by a standard thermometer or other temperature measuring
instruments.
2-Saturated Vapor Pressure (Psat): Is the saturated partial pressure of
water vapor at the dry bulb temperature. This is readily available in
thermodynamic tables and charts.
3-Humidity ratio (ω): The humidity ratio (or specific humidity) ω is the
ratio of mass of water (ma) associated with each kilogram of dry air
(m𝑣)
𝒎𝒗
ω= (kg water vapor/kg dry air)
𝒎𝒂
Important Psychometric Properties
Assuming both water vapour and dry air to be perfect gases, the
humidity ratio is given by:
𝑚𝑣
ω =
𝑀𝑎
Using perfect gas law: PV=mRT
𝑃𝑣𝑉 𝑃𝑣𝑉𝑀𝑣 𝑃𝑎𝑉 𝑃𝑎𝑉𝑀𝑎
Where 𝑚𝑣 = = ത & 𝑚𝑎 = = ത
𝑅𝑣𝑇 𝑅𝑇 𝑅𝑎𝑇 𝑅𝑇
• Substituting the values of gas constants of water vapour and air Rv and Ra in the
above equation; the humidity ratio is given by:
Important Psychometric Properties:
𝟏𝟖.𝟎𝟏𝟓 𝑷𝒗 𝑷𝒗
• (Humidity Ratio) ω = = 0.6219 (1)
𝟐𝟖.𝟗𝟔𝟓 𝑷𝒂 𝑷𝒂
•
• It is to be noted that, ω is a function of both total barometric pressure and vapor
pressure of water. P= Pt=Pa+PV
4- Relative humidity (Φ) or RH: Is defined as the ratio of actual mass of
water vapor in a given volume to the mass of water vapor in the same
volume of saturated air at the same temperature and pressure.
𝑷𝒗ൗ 𝑷𝒗 𝑷𝒗ൗ 𝝆𝒗
𝑹𝒗𝑻
𝜱= 𝑷
= = = (2)
𝑷𝒔ൗ
𝑷 𝑷𝒔 𝑷𝒔ൗ
𝑹𝒗𝑻 𝝆𝒔 T,P
The ratio of the amount of moisture air holds (mv) to the maximum amount of moisture air
can hold at the same temperature (mg) is called the relative humidity,
where Pg = Psat @ T
The relative and specific humidifies can also be expressed as
(3)
Relative humidity ranges from 0% for dry air to 100% for saturated air.
Important Psychometric Properties:
• At a given temperature and pressure the dry air can only hold a
certain maximum amount of moisture. When the moisture content is
maximum, then the air is known as saturated air, which is established
by a neutral equilibrium between the moist air and the liquid or solid
phases of water.
• For calculation purposes, the molecular weight of water vapour is
taken as Mv=18.015 and its gas constant is Rv=461.52 J/kg.K.
Important Psychometric Properties:
• For a given barometric pressure pt, given the DBT, we can find the
saturated vapour pressure psat from the thermodynamic property
tables on steam.
5-Dew-Point Temperature (DPT): If unsaturated moist air is cooled at
constant pressure, then the temperature at which the moisture in the
air begins to condense is known as dew-point temperature (DPT) of air.
An approximate equation for dew-point temperature is given by:
13-27
(4) (4)
(4)
• It can be obtained from steam tables
(6)
7- Enthalpy (h): : The enthalpy of moist air is the sum of the enthalpy
of the dry air and the enthalpy of the water vapour.
Enthalpy values are always based on some reference value. For moist
air, the enthalpy of dry air is given a zero value at 0oC, and for water
vapour the enthalpy of saturated water is taken as zero at 0oC.
13-5
The enthalpy of moist air is expressed per unit mass of dry air,
not per unit mass of moist air
The enthalpy of water vapor in the air can be taken to be equal to the enthalpy of the
saturated vapor at the same temperature:
𝒉 = 𝒄𝒑𝒂𝑻 + 𝝎𝒉𝒈
hg=2500.9 +cpvT
𝒉 = 𝟏. 𝟎𝟎𝟓𝑻 + 𝝎(𝟐𝟓𝟎𝟎. 𝟗 + 𝟏. 𝟖𝟖𝑻) kJ/kg (7)
• Where; cpa = specific heat of dry air, kJ/kg.K
• cpv = specific heat of water vapor, kJ/kg
• ω = humidity ratio, kg of water vapor/kg of dry air
• T = Dry-bulb temperature of air-vapor mixture, oC
• ha = enthalpy of dry air at temperature t, kJ/kg
• hg = enthalpy of water vapor at temperature T, kJ/kg
• hfg= latent heat of vaporization at 0oC, kJ/kg =2500 kJ/kg.
Important Psychometric Properties:
8- Specific volume(ѵ): The specific volume is defined as the number of
cubic meters of moist air per kilogram of dry air. From perfect gas
equation since the volumes occupied by the individual substances are
the same, the specific volume is also equal to the number of cubic
meters of dry air per kilogram of dry air,
Important Psychometric Properties:
where,
Sensible cooling
Psychrometric Processes
B) Sensible Heating or Simple Heating (O-B): During this process, the
moisture content ω of air remains constant and its temperature
increases as it flows over a heating coil. The heat transfer rate during
this process is given by:
Sensible Heating
Psychrometric Processes
C) Cooling and Dehumidification (Process O-C): When moist air is cooled
below its dew-point by bringing it in contact with a cold surface ,some of the water
vapor in the air condenses and leaves the air stream as liquid, as a result both the
temperature and humidity ratio of air decreases .This is the process air undergoes
in a typical air conditioning system. The heat and mass transfer rates can be
expressed in terms of the initial and final conditions by applying the conservation
of mass and conservation of energy equations as given below:
• By applying mass balance for the water:
Psychrometric Processes
Cooling with Dehumidification
• By applying energy balance:
• from the above two equations, the load on the cooling coil, Q is given
by:
• From the above equation, one can deduce that a SHF of 1.0
corresponds to no latent heat transfer and a SHF of 0 corresponds to
no sensible heat transfer. A SHF of 0.75 to 0.80 is quite common in air
conditioning systems in a normal dry-climate. A
• lower value of SHF, say 0.6, implies a high latent heat load such as
that occurs in a humid climate.
The sensible heat factor(SHF) is defined as qs/q. This parameter is shown on the
semicircular scale of Fig. 3-5. Note that the SHF can be negative. If we use the standard
sign convention that sensible or latent heat transfer to the system is positive and
transfer from the system is negative, the proper sign will result.
For example, with the cooling and dehumidifying process above, both sensible and
latent heat transfer are away from the air, qs and ql are both negative, and the SHF is
positive. In a situation where air is being cooled sensibly but a large latent heat gain is
present, the SHF will be negative if the absolute value of ql is greater than qs .
See problem 56
Sensible Heat Factor
The Sensible Heat Factor (SHF) is defined as 𝒒ሶ s/𝒒ሶ𝒕
A SHF of 0.75 to 0.80 is quite common in air conditioning systems in a normal dry-
climate.
A lower value of SHF, say 0.6, implies a high latent heat load such as that occurs in a
humid climate.
The slope of the cooling and dehumidification line is purely a function of the SHF.
Hence, we can draw the cooling and dehumidification line on psychrometric chart if
the initial state and the SHF are known.
Psychrometric Processes
D) Heating and Humidification (Process O-D): During winter it is
essential to heat and humidify the room air for comfort, this is normally
done by first sensibly heating the air and then adding water vapour to
the air stream through steam nozzles.
Mass balance of water vapor for the control volume yields the rate at
which steam has to be added,
• where Qh is the heat supplied through the heating coil and hw is the
enthalpy of steam.
• Since this process also involves simultaneous heat and mass
transfer, we can define a sensible heat factor for the process in a
way similar to that of a cooling and dehumidification process.
Psychrometric Processes
Heating and Humidifying Moist Air
Heating with Humidification
Example2:An air-conditioning system is to take in outdoor air
at 10°C and 30 % relative humidity at a steady rate of 45 m3/min
and to condition it to 25°C and 60 % relative humidity. The
outdoor air is first heated to 22°C in the heating section and then
humidified by the injection of hot steam in the humidifying
section.
Assuming the entire process takes place at a pressure of 100 kPa,
determine,
(a) the rate of heat supply in the heating section
(b) the mass flow rate of the steam required in the humidifying
section
Example3:Air enters a window air conditioner at 1
atm, 30°C, and 80 % relative humidity at a rate of
10 m3/min, and it leaves as saturated air at 14°C.
Part of the moisture in the air that condenses
during the process is also removed at 14°C.
Determine the rates of heat and moisture
removal from the air.
Evaporative Cooling