MG90V302
MG90V302
Operating Instructions
VLT® Active Filter AAF006
www.danfoss.com/drives
Contents Operating Instructions
Contents
1 Introduction 4
1.1 Purpose of the Manual 4
1.2 Additional Resources 4
1.3 Product Overview 4
1.3.1 Working Principle 4
1.3.2 IEEE519 Compliance 5
1.4 Ordering Information 6
1.4.1 Filter Configurator 6
1.4.2 Ordering Form Type Code 6
2 Safety 7
2.1 Safety Symbols 7
2.2 Qualified Personnel 7
2.3 Safety Precautions 7
3 Mechanical Installation 8
3.1 Pre-installation 8
3.1.1 Planning the Installation Site 8
3.1.2 Receiving the Active Filter 8
3.1.3 Transportation and Unpacking 8
3.1.4 Lifting 8
3.1.5 Mechanical Dimensions 9
3.2 Mechanical Installation 11
3.2.1 Tools Needed 11
3.2.2 Clearance Requirements 11
3.2.3 Power Terminal Locations 12
3.2.4 Cooling and Airflow 13
3.2.5 Gland/Conduit Entry - IP21 (NEMA 1) and IP54 (NEMA12) 14
4 Electrical Installation 15
4.1 Safety Instructions 15
4.2 Electrical Installation 15
4.2.1 Power Connections 15
4.2.2 Grounding 16
4.2.3 EMC Interference 17
4.2.4 Extra Protection (RCD) 18
4.2.5 RFI Switch 18
4.2.6 Torque 18
4.2.7 Current Transformer (CT) 18
4.2.8 Auto CT Detection 22
5 User Interface 30
5.1 Local Control Panel Operation 30
5.1.1 Modes of Operation 30
5.1.2 How to Operate Graphical LCP (GLCP) 30
5.1.3 Changing Data 33
5.1.4 Changing a Text Value 33
5.1.5 Changing a Group of Numeric Data Values 33
5.1.6 Changing of Data Value, Step-by-Step 33
5.1.7 Readout and Programming of Indexed Parameters 33
5.1.8 Quick Transfer of Parameter Settings with the LCP 34
5.1.9 Initialisation to Default Settings 34
5.1.10 RS485 Bus Connection 35
5.1.11 Connection to a PC 35
9 Specifications 81
9.1 Power Rating 81
9.2 Derating for Altitude and Ambient Temperature 84
9.3 Acoustic Noise 84
10 Appendix 85
10.1 Abbreviations and Conventions 85
Index 86
1 1 1 Introduction
130BB717.10
These operating instructions provide information for safe
installation and commissioning of the filter.
130BB718.10
The VLT® Advanced Active Filter is used for harmonic
current mitigation and reactive current compensation. The
unit can integrate with various systems and applications as
a centrally installed filter or be combined with a VLT®
frequency converter as a packaged low harmonic drive
solution.
130BB719.10
Control Manual
Disconnect
Fuse
Option
Soft charge
circuit
The active filter has an optional RFI filter for Class A1 equal
to category C2.
Use the ordering number system to design an active filter according to the application requirements. For the VLT® Active
Filter AAF 006 Series, it is possible to order standard filters and filters with integral options by sending a type code string
describing the product to the local Danfoss sales office. For example: AAF006A190T4E21HXXGCXXXSXXXXAXBXCFXXXDX
This section describes each character in the type code. In the example, a standard 190 A active filter in an enclosure with
IP21 protection rating is selected for a 380–480 V net. The internet-based configurator configures the right filter for the right
application and generates a type code string. The configurator automatically generates an 8-digit sales number to be
delivered to the local sales office. It is also possible to establish a project list with several products and send it to a Danfoss
sales representative. The configurator can be found at www.danfoss.com/BusinessAreas/DrivesSolutions/.
1.4.2 Ordering Form Type Code
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39
130BB504.10
A A F 0 0 x A T 4 E H x G C x x S x x x x A x B x C x x x x D x
2 Safety
2 2
2.1 Safety Symbols Voltage Output Current
Minimum waiting
time
[V] [A]
The following symbols are used in this document: (minutes)
380–480 190–400 20
WARNING High voltage can be present even when the warning indicator
lights are off.
Indicates a potentially hazardous situation that could
result in death or serious injury. Table 2.1 Discharge Time
CAUTION WARNING
Indicates a potentially hazardous situation that could LEAKAGE CURRENT HAZARD
result in minor or moderate injury. It can also be used to Leakage currents exceed 3.5 mA. Failure to ground the
alert against unsafe practices. filter properly can result in death or serious injury.
Qualified personnel is defined as trained staff, who are • Ensure that electrical work conforms to national
authorised to install, commission, and maintain equipment, and local electrical codes.
systems and circuits in accordance with pertinent laws and • Follow the procedures in this document.
regulations. Additionally, the personnel must be familiar
with the instructions and safety measures described in this
document. CAUTION
2.3 Safety Precautions INTERNAL FAILURE HAZARD
An internal failure in the filter can result in serious injury
WARNING when the filter is not properly closed.
WARNING
DISCHARGE TIME
The active filter contains DC-link capacitors, which can
remain charged even when the filter is not powered.
Failure to wait the specified time after power has been
removed before performing service or repair work can
result in death or serious injury.
3 Mechanical Installation
3 3 3.1.1 Planning the Installation Site Always lift the unit in the dedicated lifting eyes. Use a bar
to avoid bending the lifting holes.
NOTICE
Due to the size and clearance requirements of the active
130BB642.10
filter, it is important to pre-plan installation. Failure to
do so may result in additional work during and after
installation.
• Cooling.
NOTICE
Damaged packaging can indicate rough transportation NOTICE
which may have caused interior failures in the unit.
The lifting bar must be able to handle the weight of the
Claim damages even if the exterior of the unit seems
unit. See chapter 3.1.5 Mechanical Dimensions for
intact.
weights. Maximum diameter for the bar is 25 mm (1
inch). The angle from the top of the unit to the lifting
3.1.3 Transportation and Unpacking cable should be > 60°.
130BC632.10
1 304.0
[12.0]
148.0
[5.8]
[225.0]
[8.9]
2X 27.0 2X 13.0
[1.1] [.5]
3 3
1755.5
1780.5 [69.1]
[70.1]
1552.8
[61.1]
1394.0
[54.9]
1020.1
[40.2]
2 160.0
[6.3]
555.9
[21.9]
199.5
[7.9] 221.0 251.0
[8.7] [9.9]
74.1
[2.9] 221.6
[8.7] 184.5
273.2 [7.3]
[10.8] 377.8
369.0 117.4
414.1 [14.9]
[14.5] [4.6]
[16.3]
603.8
[23.8]
130BC633.10
1 225.0
[8.9]
2X 27.0
[1.1]
3 3
2001.0
[78.8]
1544.5
[60.8]
1394.1
[54.9]
1230.0
[48.4]
730.7
[28.8]
2 160.0
[6.3]
198.2
[7.8]
249.1
[9.8]
72.2 270.9
[2.8] [11]
283.3
[11.2] 493.5 184.5
389.0 [19.4] [7.3]
[15.3] 369.0
600.0 [14.5]
[23.6] 553.5 23.3
[21.8] [.9]
Enclosure D14 E1
IP 21/54 21/54
Enclosure protection
NEMA Type 1/12 Type 1/12
Nominal current rate 190 A 250 A, 310 A, 400 A
Shipping dimensions Height
750/29.5 864/34
(mm/in.)
Width
737/29 737/29
(mm/in.)
Depth
1943/76.5 2203/86.7
(mm/in.)
Weight (kg/
283/623.9 500/1102.3
lbs.)
Unit dimensions Height
1780/70 2000/78.7
(mm/in.)
Width
600/23.6 600/23.6
(mm/in.)
Depth
380/14.9 494/19.4
(mm/in.)
Maximum-
Weight (kg/ 238/524.7 453/998.7
lbs.)
130BC635.10
[22.7]
• Screw driver.
576.7
• Wrench with 7–17 mm metric sockets. [22.7]
• Wrench extensions.
575.9
[22.7] terminal bus bar.
67.3
[2.7]
574.2
[22.6]
130BC638.10
Consider the position of the terminals when designing for
cable access. See Illustration 3.6, Illustration 3.7,
Illustration 3.8, and Illustration 3.9
3 3 19.6
130BC636.10
[.8]
29.0
[1.1] 730.7 719.1
[28.8] [28.3] 628.7
[24.8]
75.0
[3.0]
476.0 65.0
[18.7] [2.6]
130.0
[5.1]
389.0
[15.3]
194.0 343.0
88.0 [7.6] [13.5]
[3.5]
Illustration 3.8 Terminal Location of E1 with Disconnect
204.0
[8.0]
266.2 259.7
[10.5] [10.2]
130BC639.10
289.7
[11.4]
719.1
[28.3] 605.6 609.1
[23.8] [24.0]
75.0
[3.0]
505.0
486.0 [19.9] 188.0 112.0
[19.1] [7.4] [4.4]
224.0
[8.8]
537.0
[21.1]
83.7
[3.3] Illustration 3.9 Terminal Location of E1 without Disconnect
167.2
[6.6]
241.9
[9.5]
NOTICE
284.1 271.9
[11.2] [10.7] Each terminal allows up to 4 cables with cable lugs or
Illustration 3.7 Terminal Location of D14 without Disconnect use of a standard box lug. Ground is connected to the
relevant termination point in the unit.
130BB932.10
• Take air into the back of the unit 90
Back cooling 60
Filter Derating
The active filter has a back channel cooling system where 50
components. 10
0
The back channel air is normally ventilated via the plinth 0 0.5 4.9 13 27.3 45.9 66 89.3 115.7 147
inlet and ducted out the top of the enclosure. The design Pressure Increase (Pa)
of the back channel can also take air from the control Illustration 3.10 Enclosure Size D, Derating vs. Pressure
room and duct it back out again. This is supported to ease Change
stress on the control room air conditioner and conserve Air Flow: 450 cfm (765 m3/h)
energy. To support a backwall inlet, the unit air inlet has to
be blocked via an optional cover and the air outlet ducted
via an optional top duct. (%)
130BB933.10
NOTICE 90
80
The active filter fan runs for the following reasons: 70
Once the fan is started, it runs for a minimum of 10 Illustration 3.11 Enclosure Size E, Derating vs. Pressure Change
minutes. Air Flow: 725 cfm (1230 m3/h)
130BB736.11
and IP54 (NEMA12)
NOTICE
The gland plate ensures the specified protection degree,
and enables proper cooling of the unit. If the gland plate
is not mounted, the unit may trip on Alarm 69, Pwr. Card
Temp.
130BC640.10
560.0 21.9
[22.0] [.9] 55.9
[2.2]
110.6
[4.4]
257.0
182.8
[10.1]
[7.2]
350.0 181.9
[13.8] [7.2]
Illustration 3.12 Enclosure Size D14, Bottom View Illustration 3.14 Mounting of Base Plate, E1
361.7
257.6 [14.2]
[10.1]
520.0 40.0
[20.5] [1.6]
4 Electrical Installation
130BA026.10
When a residual current-operated protective
device (RCD) is used for protection against
3 Phase
electrical shock, only an RCD of Type B is 91 (L1)
permitted on the supply side. power
92 (L2)
input
Failure to follow the recommendation means the RCD 93 (L3)
may not provide the intended protection. 95 PE
The power cable connections are situated as shown in • The proximity factor depends on the number of
conductors, diameters and distance between the
Illustration 4.1. The mains connection is fitted to the mains
individual cables.
switch if this is included. Dimension the cable cross-section
in accordance with the filter current rating, including skin The proximity effect is depending on the number of
and proximity effects, derating, and local legislation. conductors, diameters and distance between the individual
cables.
Connect mains to terminals 91, 92 and 93. Connect ground
to the terminal on the immediate right of terminal 93. The optimised mains cable is:
• Copper wires.
Terminal number Function • Single conductors.
91, 92, 93 Mains R/L1, S/L2, T/L3
94 Ground
• Bus bars.
Copper affects skin less than aluminum, and bus bars have a larger surface area than cables, reducing the skin effect factor.
Proximity effects of single conductors are negligible.
The cable specifications in Table 4.2 take both skin and proximity effects into account:
Filter Minimum CU wire Equivalent RMS Minimum ALU wire Equivalent RMS Maximum wire
mm2 (AWG) cable for CU mm2 (AWG) current for ALU mm2 (AWG)
190 A 70 mm2 (2/0) 225 A 95 mm2 (3/0) 240 A 2*150 mm2 (2*300 MCM)
250 A 120 mm2 (4/0) 295 A 150 mm2 (300 MCM) 315 A 4x240 mm2 (4x500 MCM)
4 4 310 A
400 A
240 mm2 (500 MCM)
2*95 mm2 (2*3/0)
365 A
470 A
2*95 mm2 (2*3/0)
2*150 mm2 (2*300 MCM)
390 A
500 A
4x240 mm2 (4x500 MCM)
4x240 mm2 (8x900 MCM)
Table 4.2 Allowed Active Filter Mains Cable with Typical Cable Manufacturer Data
Due to the built-in LCL filter, the unit does not feed the main wire with high dU/dt signals. Doing so reduces the radiated
emission through the mains cable. Cable screen/shielding can thus be omitted allowing the mains cables to be connected
without considering EMC requirements.
The active filter can run at long cable runs. Cable length is limited by the voltage drop. It is advised to keep the cable
lengths to less then 200 m.
Active filters have either built-in or customer-supplied fuses. See chapter 4.2.11 Fuses for fuse recommendations. Always
ensure proper fusing according to local regulation.
4.2.2 Grounding
130BB739.11
Consider the following basic issues when installing an
active filter, to obtain electromagnetic compatibility (EMC):
• Safety grounding: The active filter has leakage
current and must be grounded appropriately for
safety reasons. Apply local safety regulations.
130BC643.10
A
4 4 4
1
10
8
9 7
8
NOTICE
EMC INTERFERENCE
Use screened cables for control wiring. Separate AAF mains input cable from other cables and control wiring. Minimum
200 mm (7.9 in) clearance between mains and control cables is required. Maximise this clearance to minimise EMC
emissions. Doing so reduces the risk of interference between the AAF and other electronic devices.
176FA247.12
ELCB, RCD, GFCI relays or multiple protective groundings
are often used as extra protection, or needed to provide
compliance with local safety regulations. In case of a
93
ground fault, a DC component may develop in the fault 92
T/L3
S/L2
current. Observe local regulations when using ELCB relays. R/L1
91
V/T2
97
W/T3
If the active filter is supplied from an isolated mains source Illustration 4.4 Use a Torque Wrench to Tighten the Bolts
(IT mains, floating delta and grounded delta) or TT/TN-S
mains with grounded leg, the RFI switch is recommended
to be turned off (OFF) 1) via 14-50 RFI Filter on the unit. 4.2.7 Current Transformer (CT)
For further reference, see IEC 364-3. In OFF mode, the
internal RFI capacities between the chassis and the The filter operates in close loop operation by receiving
intermediate circuit are cut off to avoid damage to the current signals for external current transformers. The
intermediate circuit. Refer to the application note VLT® on received signal is processed and the filter reacts according
IT mains. It is important to use isolation monitors that are to programmed actions.
capable for use together with power electronics (IEC
61557-8).
NOTICE CAUTION
Incorrect current transformer connection, installation or
Marine grids are typically IT type grids. configuration leads to unintended and uncontrollable
behaviour of the filter.
4.2.6 Torque
NOTICE
Correct torque is imperative for all electrical connections.
The current transformers are not part of the filter
Incorrect torque results in a bad electrical connection.
package and must be purchased separately.
Torque values are provided in Table 4.3.
CT specification
Enclosure size Torque Bolt size
The active filter supports most CTs. The CTs must have the
D 19 Nm (168 in.-lbs.) M10
following specifications:
E 19 Nm (168 in.-lbs.) M10
Technical specification of active filter, passive CT
Table 4.3 Correct Torque Values
RMS Maximum measured RMS current
Accuracy 0.5% or better (Class 0.5)
Use a torque wrench to ensure correct torque.
Secondary rated 1A or 5A (5A is recommended)
current Set-up via hardware
Rated frequency 50/60 Hz
Rated power/burden See Table 4.5 (AAF burden equals 2 mΩ)
Rated power/ 5 7.5 10 15 30 For a fixed CT burden, calculate the maximum allowed
burden [VA] wire length as:
Impedance of ≤ 0.15 ≤ 0.25 ≤ 0.35 ≤ 0.55 ≤ 1.15 [M]=([VA]-1.25)/(25*[Ω/M])
current CT [Ω]
Below the maximum wire length of CT with 2.5 mm2 wires
Table 4.5 Rated Power/Burden
and resistor value equal 8.2 Ω/km:
4 4
All other technical data such as dynamic rated current, [mm2/ AWG] [Ω/km] burden [VA] [meter/feet]
maximal permitted operating voltage, thermal 2.5/#14 8.2 5 <18/60
dimensioning of continuous current, thermal 2.5/#14 8.2 7.5 <30/100
dimensioning of short-time current, overcurrent limit,
2.5/#14 8.2 10 <42/140
isolation class, working temperature range etc. are
2.5/#14 8.2 15 <67/220
specific values of the system and have to be defined
2.5/#14 8.2 30 <140/460
during the project planning phase of the equipment.
Table 4.7 Maximum CT Wire Length
RMS specification
The minimum RMS is determined by the total current that Example
passes through the current transformer. It is important that Calculation example for correct current transformer for an
the current sensor is not too small, leading to saturation of application with:
the sensor. Add 10% margin and pick the next following RMS=653 A, Distance between filter and CTs of 30 m.
bigger standard RMS rate. Use current transformers that RMS=653*1.1=719 A, CT RMS=750 A. Burden: 30 m@2.5
have an RMS rating close to the maximum current flowing mm2 wire =>25*0.0082*30+1.25=7.4=>7.5 [VA].
through it to allow the highest possible accuracy of the
Current transformer installation
measurement and so an ideal compensation.
The unit only supports 3 CT installations. Install external
CT burden CTs on all 3 phases to detect the harmonic content of the
To ensure that the current transformer performs according grid. The flow direction of the sensor is indicated by an
to specifications, the rated burden should not be above arrow in most cases. The arrow points in the direction of
the true current requirement of the active filter. The the current flow and so towards the load. If the flow
burden of the CT depends on the wire type and the cable direction is programmed incorrectly, the polarity can be
length between the CT and the filter CT connection changed via active filter parameter 300-25 CT Polarity,
terminal. The filter itself contributes with 2 mΩ. which can program the polarity of the CTs in each of the 3
NOTICE phases individually.
1 or 5 A CT set-up
130BB511.11
To allow for possible reuse of already present CT
transformers, the active filter allows use of either 1 A or 5
A CTs. The filter is as standard set-up for 5 A CT feedback.
If the CTs are 1 A, redirect the CT terminal plug from slot
MK101, position 1, to MK108, position 2, on the AFC card.
See Illustration 4.6.
130BB950.10
5
4 4 3
4
PCC1
1
2
AAF
6 M M M
PCC2
130BB512.10
Individual or group compensation
The compensation of the filter depends on the signal that
is returned from the current transformers. The point of
installation for these sensors is to determine the loads that
are corrected.
Illustration 4.7 shows current transformers installed in front
of the entire installation with the filter compensating all
loads on the transformer. Illustration 4.8 shows current
transformers installed in front of distribution bus 2 and 1
frequency converter, so the filter only compensates for PCC1
those.
AAF
M M M
PCC2
130BB514.11
some of the loads, the filter does not compensate
unwanted current deformation of the frequency converter
and motor on the right hand side. If CTs are installed in
front of a single load, the filter only compensates the 1
load and so form individual load compensation.
130BB513.11
AAF
M M M
PCC1
If the current transformers are installed on the source
(PCC) side, the filter expects a sinusoidal (corrected) signal
feedback from the 3 sensors. If the sensors are installed on
the load side, the received signal is subtracted from the
ideal sine wave to calculate the necessary corrected
current.
AAF
NOTICE
M M M Erratic filter operation can be a result of incorrect current
transformers connection point programming
Illustration 4.9 Current Transformers Installed on Source (PCC) parameter 300-26 CT Placement.
Side for Group Compensation
The active filter performs an auto detection of the installed CT. The CT auto detection can be conducted both while the
system is running and when there is no load. The filter injects a prefixed current of known amplitude and phase angle and
measures the returned CT input. The performance is conducted on each phase individually for several frequencies to check
that phase sequence and RMS are set correctly.
600 750
1000 1250 1500 2000 2500 3000 3500 4000
Most restrictions on the CTs come from the installation, such as required cable length, temperature conditions, square
section of conductors, standard or split core layout, etc. A broad range of different current transformers can be used
independently of brand and type.
For specific CT requirements contact the local supplier or go to www.deif.com/
130BB516.11
Multiple current sources
Summation CTs are needed when the filter is to
compensate current from several sources. This is often the
case if a filter is installed in systems with generator back-
up or where the filter is only to compensate a limited
number of loads, for example, marine installations.
4 4
130BB515.11
PCC1
AAF
PCC1
M M M
• Polarity.
• Primary rating.
• RMS value.
• Accuracy (class 0.5).
• Location (PCC or load-side).
• Phase sequence.
NOTICE
Use summation CTs with great caution and always
ensure correct phase sequence, current direction,
primary and secondary rating. Incorrect installation
causes problems with filter operation.
130BB517.11
I5 I7 I11 I13 I17 I19 I23 I25
190 133 95 61 53 38 34 30 27
250 175 125 80 70 50 45 40 35
310 217 155 99 87 62 56 50 43
400 280 200 128 112 80 72 64 56
NOTICE
AAF
Always use de-tuned capacitor banks in installations with
frequency converters and active filters to avoid
resonance phenomena, unintended tripping or M M
component breakdown.
Illustration 4.13 Capacitor bank mounted upstream. CTs do
For de-tuned capacitors, the resonance frequency not measure capacitor current.
capacitors should be tuned for an inter-harmonic number
lower than the 3rd harmonic.
Illustration 4.13 shows recommended installation of the
active filter and CT placement in installations containing
NOTICE capacitor banks.
If installed with capacitor banks of any kind, the active
filter must operate in selective compensation mode.
130BB518.11
The capacitor bank should be installed upstream of the
filter toward the transformer. If this is not possible, install
the current transformers such that they do not measure
both needed current compensation and the capacitor
corrected current.
PCC1
AAF
M M
130BB520.11
130BB519.11
4 4
PCC1 PCC1
AAF AAF
M M M M
Illustration 4.15 CTs Do Not Measure Capacitor Current Illustration 4.16 Capacitor Bank Mounted on PCC with CTs
Ensuring that Capacitor Corrected Current is not Measured.
NOTICE
Use summation CTs with an accuracy of 0.5% of better.
Branch circuit protection Tie down all control wires to the designated control cable
To protect the installation against electrical and fire hazard, routing. Connect the shields properly to ensure optimum
all branch circuits in an installation, switch gear, machines electrical immunity.
etc., must be short-circuited and overcurrent protected
according to national/international regulations. CT connection
Short circuit protection Make connections on the terminal block below the active
130BA150.10
for overcurrent protection and comply with local and
national regulations.
Mains fuses 9 - 10 mm
(0.37 in)
130BT312.10
Table 4.11 Recommended Mains Fuses
Supplemental fuses
Enclosure
size Power & voltage Type
D A190 380–480 V ABB OETL-NF200A
E A250 380–480 V ABB OETL-NF400A
E A310 380–480 V ABB OETL-NF400A
E A400 380–480 V ABB OETL-NF800A
Table 4.13 Mains Disconnect Part Numbers Illustration 4.19 Removing the Screwdriver
+24 VDC
130BT107.11
0 VDC
mounted in the terminal. NPN (Sink)
Digital input wiring
To remove the cable from the terminal:
12 13 18 19 27 29 32 33 20 37
1. Insert a screwdriver (maximum 0.4x2.5 mm) in the
square hole.
2. Pull out the cable.
130BT340.10
PNP (Source)
130BT106.10
+24 VDC
12 13 18 19 27 29 32 33 20 37
130BC642.10
Relay 12
Control & AUX
Feedback
Soft-Charge
NC
4 4
Relay
Lc Is
Lac
92 (L2) Optional
Optional
Manual
Optional
Lm
Lc It
RFI Fuses
Disconnect Lac
Lm 3 3
93 (L3) Relay 12 Capacitor
AF Current
Lac Control & AUX Cef Current Sensors
Cef Cef Sensors
Feedback
Ref Ref Ref
Switch Mode
Power Supply
10Vdc 24Vdc
15mA 130/200mA
50 (+10 V OUT) + - + -
+10Vdc
S201
-10Vdc -
1 2
53 (A IN)
ON
+10Vdc relay1
ON/I=0-20mA
0/4-20 mA S202 03
OFF/U=0-10V
1 2
-10Vdc -
ON
54 (A IN) 240Vac, 2A
+10Vdc 02
0/4-20 mA
55 (COM A IN) 01
relay2
12 (+24V OUT) 06
240Vac, 2A
13 (+24V OUT) P 5-00 05
400Vac, 2A
24V (NPN)
18 (D IN) 04
0V (PNP)
24V (NPN)
19 (D IN) 0V (PNP) (COM A OUT) 39 Analog Output
0/4-20 mA
(A OUT) 42
20 (COM D IN)
24V (NPN)
27 (D IN/OUT) 0V (PNP) S801
24V ON=Terminated
1 2
ON
OFF=Open
0V 5V
* 24V (NPN)
29 (D IN/OUT) 0V (PNP)
24V
S801 0V
0V
RS-485
(N RS-485) 69 RS-485
24V (NPN) Interface
32 (D IN) 0V (PNP) (P RS-485) 68
24V (NPN)
33 (D IN) (COM RS-485) 61
0V (PNP)
(PNP) = Source
(NPN) = Sink
• Check function and installation of any sensors used for feedback to the active filter.
4 4
Cable routing • Ensure that power wiring and control wiring are separated, screened, or in 3 separate metallic conduits for
high-frequency interference isolation.
Control wiring • Check for broken or damaged wires and loose connections.
• Check that control wiring is isolated from power wiring for noise immunity.
• The use of shielded cable or twisted pair is recommended. Ensure that the shield is terminated correctly.
Cooling clearance • Measure that top and bottom clearance is adequate to ensure proper air flow for cooling, see
chapter 3.2.4 Cooling and Airflow .
Ambient conditions • Check that requirements for ambient conditions are met.
Grounding • Check for good ground connections that are tight and free of oxidation.
• Grounding to conduit, or mounting the back panel to a metal surface, is not a suitable grounding.
Panel interior • Inspect that the unit interior is free of dirt, metal chips, moisture, and corrosion.
Switches • Ensure that all switch and disconnect settings are in the proper positions.
Vibration • Check that the unit is mounted solidly, or that shock mounts are used, as necessary.
CAUTION
POTENTIAL HAZARD IN THE EVENT OF INTERNAL FAILURE
Risk of personal injury when the active filter is not properly closed.
• Before applying power, ensure all safety covers are in place and securely fastened.
5 User Interface
130BA018.13
5.1.1 Modes of Operation
Graphical display:
Ca
ck
n
The LCD display is backlit with a total of 6 alpha-numeric
Ba
ce
l
lines. All data is displayed on the LCP, which can show up
to 5 operating variables while in Status mode.
Illustration 5.1 shows an example of the frequency
Info
3 On OK
converter LCP. The filter LCP looks identical but displays
information related to the filter operation.
Warn.
1. Display:
Alarm
1a Status line: Status messages displaying
icons and graphics.
Hand Auto
1b Line 1–2: Operator data lines displaying 4 Off Reset
on on
data and variables the user defines. Add
an extra line by pressing the [Status]
key. Illustration 5.1 Example LCP
130BP074.10
Status ! 1(1)
measurements to be displayed via parameters 0-20, 0-21, Top section
43 RPM 5.44 A 25.3kW
0-22, 0-23, and 0-24.
Each value/measurement readout parameter selected in Middle section
1.4 Hz
parameters 0-20 to 0-24 has its own scale and number of 2.9%
digits after a possible decimal point. Larger numeric values
are displayed with few digits after the decimal point. ! Pwr.card temp (W29)
Bottom section
Example: Current readout Auto Remote Running
5.25 A; 15.2 A 105 A. Illustration 5.4 Bottom Section Status Mode 5 5
Status display I
This readout state is standard after start-up or initialisation.
Press [Info] to obtain information about the Display contrast adjustment
value/ measurement linked to the displayed operating Press [status] and [▲] for darker display
variables (1.1, 1.2, 1.3, 2, and 3). Press [Status] and [▼] for brighter display
See the operating variables shown in the display in
Indicator lights (LEDs):
Illustration 5.2. 1.1, 1.2 and 1.3 are shown in small size. 2
If certain threshold values are exceeded, the alarm and/or
and 3 are shown in medium size.
warning indicator lights are illuminated. A status and alarm
text appear on the control panel.
130BP041.10
Status 1 (1)
799 RPM 7.83 A 36.4 kw The On indicator light is activated when the active filter
1.1 receives power from:
0.000
• Mains voltage.
1.2
53.2 % • A 24 V external supply.
Auto Remote Ramping
2 Indicator lights (LEDs)
3 1.3
• Green LED/On: Control section is working.
Status display II On
See the operating variables (1.1, 1.2, 1.3, and 2) shown in
the display in Illustration 5.3. Warn.
In the example, speed, motor current, motor power, and
Alarm
frequency are selected as variables in the first and second Illustration 5.5 LED Status Indicator Lights
lines.
1.1, 1.2 and 1.3 are shown in small size. 2 is shown in large
size.
LCP keys
Menu keys
130BP062.10
Status 1 (1)
207RPM 5.25A 24.4 kW The menu keys are divided into functions. The keys below
1.1 the display and indicator lights are used for parameter set-
6.9 Hz
up, including option of display indication during normal
1.3 operation.
130BP045.10
1.2
Auto Remote Running
Quick Main Alarm
Status
Menu Menu Log
2
[Status] [Cancel]
Indicates the status of the active filter. Use [Status] for The last change or command is cancelled as long as the
selecting display mode or reverting to display mode from: display has not been changed.
• Quick menu.
• Q6: Loggings.
The active filter LCP displays information about operation
Navigation keys
such as THD of current, corrected current, injected current
The 4 navigation keys are used to navigate between the
or Cos ϕ, and true power factor. options available in [Quick Menu], [Main Menu], and [Alarm
Log]. Move the cursor with the navigation keys.
The Quick Menu parameters can be accessed immediately
[OK]
unless a password has been created via parameters 0-60,
The OK key is used for selecting a parameter marked by
0-61, 0-65 or 0-66.
the cursor and for enabling the change of a parameter.
It is possible to switch directly between Quick Menu mode
and Main Menu mode.
130BT117.10
Ca
[Main Menu]
ck
nc
Ba
el
The main menu is used for programming all parameters.
The Main Menu parameters can be accessed immediately
unless a password has been created via parameters 0-60,
0-61, 0-65 or 0-66.
It is possible to switch directly between Main Menu mode
Info
navigation structure.
Hand Auto
Off Reset
on on
Back
[Hand On] 6. Press [▲] and [▼] to select the correct parameter
Press [Hand On] to begin operation of the active filter via setting. Or, to move to digits within a number,
the LCP. The key can be [1] Enabled or [0] Disabled via use [◄] and [►]. The cursor indicates the digit
0-40 [Hand on] Key on LCP. selected to change. [▲] increases the value, [▼]
The following control signals are active when [Hand On] decreases the value.
is pressed: 7. Press [Cancel] to ignore the change, or press [OK]
• [Hand On] - [Off] - [Auto On]. to accept the change and enter a new setting.
• Reset.
5.1.8 Quick Transfer of Parameter Settings 14-22 Operation Mode initialises all except:
with the LCP • Parameter 14-50 RFI Filter.
Once the set-up is complete, store (back up) the parameter • 8-31 Address.
settings in the LCP or on a PC via MCT 10 set-up software • 8-32 Baud Rate
tool.
• 8-35 Minimum Response Delay
The LCP can now be connected to another active filter and NOTICE
the parameter settings copied to this active filter. When carrying out manual initialisation, serial communi-
cation, RFI filter settings, and fault log settings are reset.
Data transfer from LCP to the unit Manual initialisation removes parameters selected in
1. Go to 0-50 LCP Copy. 0-25 My Personal Menu.
2. Press [OK].
1. Disconnect from mains and wait until the display
3. Select [2] All from LCP.
turns off.
4. Press [OK].
2. Press [Status] - [Main Menu] - [OK] at the same
The parameter settings stored in the LCP are now time during power-up for graphical LCP .
transferred to the active filter indicated by the progress
3. Release the keys after 5 s.
bar. When 100% is reached, press [OK].
4. The unit is now programmed according to default
settings.
5.1.9 Initialisation to Default Settings
This parameter initialises all except:
There are 2 ways to initialise the unit to default: • Parameter 15-00 Operating hours
Recommended initialisation and manual initialisation.
Each method has a different impact. • Parameter 15-03 Power Up's
5.1.11 Connection to a PC
NOTICE
The USB connection is galvanically isolated from the
supply voltage (PELV) and other high-voltage terminals.
The USB connection is connected to protective ground
on the unit. Use only an isolated laptop as PC
connection to the USB connector.
The factory settings for the active filter are selected for 6.1.3 CT-wiring for Parallel Filter
optimal operation for most applications with a minimum Connection
of programming needed. The filter is set in overall
harmonic compensation mode with harmonic current VLT active filter is designed to allow up to 4 units to run in
priority. Selection of readouts and information to be parallel for a harmonic and reactive compensation
displayed on the LCP status lines can be customised. In a extension to 4 times the individual filter rating. The parallel
few cases, the filter must be tuned specially for the given installed filters use the same current input and so only one
6 6 grid and load conditions. external set of CTs have to be installed. In case additional
filtration is needed, additional filters have to use separate
The following steps are often sufficient to set up the filter current transformers installed up or down stream of the CT
and get proper operation: signal and injection point of the paralleled installation.
• Program the external CTs:
- Check that the CT location is correct in
130BB713.10
parameter 300-26 CT Placement.
- Activate the Auto CT Detection in
parameter 300-29 Start Auto CT Detection.
- Confirm the found CT ratio, polarity, and
sequence.
130BB714.10
Filter Run
PCC1
130BB716.11
M 42 F1 42 F2 42 F3 42
53 53 53 53
27 27 27 27
19 19 19 19
29 29 29 29
20 20 20 20
The parallel connected filters must have the CT input Table 6.1 shows the necessary connections when fewer
signal wired in serial according to Illustration 6.3: than 4 units are paralleled. The software set-up of digital
and analog input/output is done automatically according
to Table 6.1, based on software programming
130BB715.10
Terminal Terminal
connection at connection at
follower master
Follower 1 (F1) 27 27
M F1 F2 Follower 2 (F2) 27 19
12 12 12
Follower 3 (F3) 42 53
All (parallel) 29 29
All (parallel) 20 20
CAUTION malfunction.
andparameter 300-26 CT Placement on each unit. Program each follower unit at parameter 300-41 Follower ID
Alternatively, each follower unit can conduct an automatic with a unique ID.
CT detection after the master unit is turned off. Only run 1 Before starting the units by pushing [Auto On], check that
auto CT detection at a time. the following parameters all have been correctly
In addition to this CT setting, it is also necessary to set programmed and have similar values for all units sharing 1
each unit to have its respective role in the cascade set of CTs:
network. Parameter 300-40 Master Follower Selection is set
to master or follower for each unit. • Parameter 300-00 Harmonic Cancellation Mode.
300-40 Master Follower Selection • Parameter 300-20 CT Primary Rating.
Option: Function: • 300-22 CT Nominal Voltage.
[0] Master If operating active filters in parallel, select
whether this filter is a master or a follower
• Parameter 300-24 CT Sequence.
Ensure that only 1 master is set in each group of parallel 6.2 Programming
connected filters. Verify that no other unit is set to
master. 6.2.1 Quick Menu Mode
After changing this parameter, additional parameters are The LCP provides access to all parameters listed under the
accessible. For the master units, 300-42 Number of Follower Quick Menus. Press [Quick Menu] to display the list of
AFs has to be programmed for the number of followers options in the quick menu.
connected.
Efficient parameter set-up for most applications
300-41 Follower ID
The parameters for most the applications are set up via
Range: Function: the Quick Menu.
1* [1 - 3 ] Enter the unique ID of this follower. Verify that no
To set parameters through the [Quick Menu]:
other follower uses the same ID.
1. Select [2] Quick set-up for selecting language,
compensation mode, CT set-up, etc.
NOTICE
2. Select [1] My personal menu to set up the LCP
Parameter 300-41 Follower ID is not accessible unless
readout parameters. If preset display is
parameter 300-40 Master Follower Selection is set to
acceptable, this operation can be left out.
follower.
It is recommended to do the set-up in the order listed.
130BB473.10
0.0% 0.00 1(1)
Quick Menus
01 My Personal Menu
02 Quick Setup
The parameters in Q2 Quick Setup are the basic parameters
05 Changes Made that are always needed to set up the active filter.
06 Loggings
Q6 Loggings
0-20 Display Line 1.1 Small Power Factor
0-21 Display Line 1.2 Small THD of current
0-22 Display Line 1.3 Small Mains Current
0-23 Display Line 2 Large Output Current
0-24 Display Line 3 Large Mains Frequency
6.2.6 Main Menu Mode Each parameter has a name and number that remain the
same regardless of the programming mode. In the Main
The LCP provides access to the Main Menu mode. Select Menu mode, the parameters are divided into groups. The
the Main Menu mode by pressing the [Main Menu] key. first digit of the parameter number (from the left) indicates
The resulting readout appears on the display of the LCP. the parameter group number. All parameters can be
Lines 2 through 5 on the display show a list of parameter changed in the main menu. Option cards added to the
groups that can be selected via the ▲ and ▼ keys. unit enable additional parameters associated with the
option device.
6.2.7 Parameter Selection
6 6 0-** Operation/Display Parameters related to the fundamental functions of the filter, function of the LCP
keys and configuration of the LCP display.
5-** Digital In/Out Parameter group for configuring the digital inputs and outputs.
8-** Communication and Options Parameter group for configuring communications and options.
14-** Special Functions Parameter group for configuring special filter functions.
15-** Unit Information Parameter group containing filter information such as operating data, hardware
configuration, and software versions.
16-** Data Readouts Parameter group for data readouts, e.g. actual references, voltages, control, alarm,
warning, and status words.
300-** AF Settings Parameter group for setting the active filter.
301-** AF Readouts Parameter group for the filter readouts.
After selecting a parameter group, select a parameter with the navigation keys.
The middle section on the LCP display shows the parameter number and name as well as the selected parameter value.
The main menu includes all available parameters in the [47] Czech Part of Language package 3
VLT® Active Filter. All parameters are grouped by name
indicating the function of the parameter group. All [48] Polski Part of Language package 4
parameters are listed by name and number in this manual. [49] Russian Part of Language package 3
Parameters in this group are related to the fundamental [51] Bahasa Part of Language package 2
functions of the active filter, function of the LCP keys, and Indonesia
configuration of the LCP display. [52] Hrvatski
130BP075.10
link the set-ups together using parameter 0-12 This Set-up 0 RPM 0.00A 1(1)
Set-up Handling 0-1*
Linked to. Parameters which are not changeable during 0-12 This Set-up Linked to
operation are marked FALSE in the parameter lists in
chapter 6.12 Parameter Lists. [1] Setup 1
0-43 [Reset] Key on LCP 0-61 Access to Main Menu w/o Password
Option: Function: Option: Function:
[7] Enabled [0] * Full access Disables password defined in
without OFF parameter 0-60 Main Menu Password.
[8] Password
[1] LCP: Read Prevent unauthorised editing of Main Menu
without OFF
only parameters.
Copy parameters from and to the LCP. Use these [3] Bus: Read Read-only functions for parameters on
parameters for saving and copying set-ups from one unit only Fieldbus and/or FC standard bus.
to another. [4] Bus: No No access to parameters is allowed via
access Fieldbus and/or FC standard bus.
0-50 LCP Copy
6 6
Option: Function: [5] All: Read only Read-only function for parameters on LCP,
Fieldbus or FC standard bus.
[0] * No copy
[1] All to LCP [6] All: No access No access from LCP, Fieldbus or FC standard
[2] All from LCP Copies all parameters in all set-ups from bus is allowed.
the LCP memory to the filter memory.
[3] Size indep. Copy only the parameters that are If [0] Full access is selected, parameter 0-60 Main Menu
from LCP independent of the active filter size. The Password, 0-65 Personal Menu Password and 0-66 Access to
latter selection can be used to programme Personal Menu w/o Password are ignored.
several filters with the same function NOTICE
without disturbing size-dependent data.
A more complex password protection is available for
0-51 Set-up Copy OEMs upon request.
Option: Function:
[0] * No copy No function 0-65 Quick Menu Password
[3] Copy to set- Copies all parameters in the present 0-66 Access to Quick Menu w/o Password
up 3 programming set-up (defined in If 0-61 Access to Main Menu w/o Password is set to [0] Full access
0-11 Programming Set-up) to set-up 3. then this parameter is ignored.
[4] Copy to set- Copies all parameters in the present Option: Function:
up 4 programming set-up (defined in [0] * Full access Disables the password defined in
0-11 Programming Set-up) to set-up 4. parameter 0-65 Quick Menu Password.
[9] Copy to all Copies the parameters in the present set-up [1] LCP: Read only Prevents unauthorised editing of Quick
to each of the set-ups 1 to 4. Menu parameters.
[3] Bus: Read only Read only functions for Quick Menu
6.4.6 0-6* Password parameters on Fieldbus and/or FC standard
bus.
0-60 Main Menu Password [5] All: Read only Read only function for Quick Menu
Range: Function: parameters on LCP, Fieldbus or FC standard
100* [-9999 - Define the password for access to the Main bus.
9999 ] Menu via the [Main Menu] key. If
0-61 Access to Main Menu w/o Password is
set to [0] Full access, this parameter is
ignored.
6.5 5-** Digital I/O Mode Digital input function Select Terminal
No operation [0] All term 32, 33
6.5.1 5-0* Digital I/O Mode Reset [1] All
Stop inverse [6] All
Parameters for configuring the input and output using Start [8] All term 18
NPN and PNP. Latched start [9] All
5-00 Digital I/O Mode Set-up select bit 0 [23] All
Set-up select bit 1 [24] All
Option: Function:
Pulse input Time Based [32] 29, 33
This parameter cannot be adjusted while the unit is
Follower AF # 1 Run [99] All
running.
Feedback
Digital inputs and programmed digital outputs are Follower AF # 2 Run [100] All
pre-programmable for operation either in PNP or NPN Feedback
systems.
Sleep [101] T18, T19, T27, T29
[1] NPN Action on negative directional pulses (↕). NPN Functions dedicated to only one digital input are stated in
systems are pulled up to + 24 V, internally in the the associated parameter.
filter.
5-10 Terminal 18 Digital Input
NOTICE Option: Function:
Once this parameter has been changed, it must be [0] No No reaction to signals transmitted to the
activated by performing a power cycle. operation terminal.
Option: Function: [6] Stop inverse Stop Inverted function. Generates a stop
NOTICE function when the selected terminal goes
from logical level 1 to 0.
This parameter cannot be adjusted while
the unit is running. [8] * Start (Default Digital input 18): Select start for a
start/stop command. Logic 1=start, logic
0=stop.
[0] * Input Defines terminal 27 as a digital input.
[9] Latched The filter starts, if a pulse is applied for
[1] Output Defines terminal 27 as a digital output.
Start minimum 2 ms. The filter stops when stop
inverse is activated.
5-02 Terminal 29 Mode
Option: Function: [23] Set-up Select Set-up select bit 0 or Select Set-up
select bit 0 select bit 1 to select one of the 4 set-ups.
[0] * Input Defines terminal 29 as a digital input.
Set parameter 0-10 Active Set-up to [9] Multi
[1] Output Defines terminal 29 as a digital output. Set-up.
5-10 Terminal 18 Digital Input 29 Mode. These parameters cannot be adjusted while the
Option: Function: unit is running.
[100] Follower AF Do not program this setting. It is done 5-30 Terminal 27 Digital Output
#2 Run automatically for paralleling. See Option: Function:
Feedback parameter 300-40 Master Follower Selection
[0] No operation Default for all digital outputs and relay
and parameter 300-41 Follower ID for more
outputs.
information about paralleling.
[1] Control ready The control card is ready. E.g.: Feedback
[101] Sleep The filter goes into sleep mode at light duty
from a unit where the control is supplied
to save energy.
by an external 24 V (MCB 107) and the
main power to the unit is not detected.
5-11 Terminal 19 Digital Input
[2] Unit ready The unit is ready for operation and applies
Option: Function:
a supply signal on the control board.
[0] * No Operation Functions are described under 5-1* Digital
Inputs [4] Enable / no Ready for operation. No start or stop
Table 6.9 Overview of Functions, Alarms and Warnings 5-31 Terminal 29 Digital Output
Option: Function:
6.5.3 5-3* Digital Outputs [0] * No operation Functions are described under parameter
group 5-3* Digital Outputs
Parameters for configuring the output functions for the
output terminals. The 2 solid-state digital outputs are
common for terminals 27 and 29. Set the I/O function for
terminal 27 in parameter 5-01 Terminal 27 Mode, and set
the I/O function for terminal 29 in parameter 5-02 Terminal
[0] * Manual reset Select [0] Manual reset, to perform a [1] Control Select [1] Control card test to test the analog
reset via [RESET] or via the digital card test and digital inputs and outputs and the +10 V
inputs. control voltage. The test requires a test
connector with internal connections. Use the
[1] Automatic reset x 1 Select [1]-[12] Automatic reset x 1… following procedure for the control card test:
130BA097.12
12 13 18 19 27 29 32 33 20 37
FC 302
12 13 18 19 27 32 33 20
FC 301
39 42 50 53 54 55
FC 301 &
FC 302
6 6
Illustration 6.8 Terminal Connections
[3] Boot
mode
Status word
description.
Decimal value. See
6 6
• Digital input.
parameter 16-03 Status
• Digital outputs. Word for description after
Parameters for reporting the bus references and control 16-92 Warning Word
words. Range: Function:
16-80 Fieldbus CTW 1 0* [0 - 4294967295 ] View the warning word sent via the serial
communication port in hex code.
Range: Function:
0* [0 - View the 2-byte control word (CTW) received 16-93 Warning Word 2
65535 ] from the bus master. Interpretation of the
Range: Function:
control word depends on the fieldbus option
installed and the control word profile selected 0* [0 - 4294967295] View the warning word sent via the serial
in 8-10 Control Profile. communication port in hex code.
For more information, refer to the relevant
fieldbus manual. 16-94 Ext. Status Word
Range: Function:
16-84 Comm. Option STW 0* [0 - 4294967295] Returns the extended warning word sent
Range: Function: via the serial communication port in hex
0* [0 - 65535 ] View the extended fieldbus comm. option code.
status word.
For more information, refer to the relevant
fieldbus manual.
[1] Follower
triggered from external. 6 6
[2] * Not Paralleled
300-51 Sleep Mode Trig Source
NOTICE Option: Function:
Ensure that only 1 master is set in each group of parallel [0] * Mains The filter is active/inactive according to line
connected filters. Verify that no other unit is set to current current. Trigger values are set in
master. parameter 300-52 Sleep Mode Wake Up Trigger
and parameter 300-53 Sleep Mode Sleep Trigger
After changing this parameter, additional parameters are [1] Digital Filter sleep is triggered via an external signal
accessible. For the master units, 300-42 Number of Follower Input provided to filter terminal 18.
AFs has to be programmed for the number of followers
connected. 300-52 Sleep Mode Wake Up Trigger
300-41 Follower ID Range: Function:
Range: Function: Application [Application Only available when [0] Mains
1* [1 - 3 ] Enter the unique ID of this follower. Verify that no dependent* dependant] Current is selected in
other follower uses the same ID. parameter 300-51 Sleep Mode Trig
Source. The parameter sets the %
NOTICE
Parameter 300-42 Num. of Follower AFs is not accessible
unless parameter 300-40 Master Follower Selection is set
to master.
6.10.1 300-6*
301-13 Cosphi
Range: Function:
0.00* [-1.00 - View the displacement power factor, after
2.00 ] compensation by the active filter. Positive
numbers indicate a leading power factor,
while negative numbers indicate a lagging
power factor.
Conv. 100 75 74 70 67 6 5 4 3 2 1 0 -1 -2 -3 -4 -5 -6
index
Conv. 1 3600000 3600 60 1/60 1000000 100000 10000 1000 100 10 1 0.1 0.01 0.001 0.0001 0.00001 0.000001
factor
6 6 5-16
5-17
Terminal X30/2 digital input
Terminal X30/3 digital input
[0] No operation
[0] No operation
All set-ups
All set-ups
TRUE
TRUE
-
-
Uint8
Uint8
5-18 Terminal X30/4 digital input [0] No operation All set-ups TRUE - Uint8
5-19 Terminal 37 Safe stop [1] Safe Stop Alarm 1 set-up TRUE - Uint8
5-3* Digital Outputs
5-30 Terminal 27 Digital output [0] No operation All set-ups TRUE - Uint8
5-31 Terminal 29 Digital output [0] No operation All set-ups TRUE - Uint8
5-4* Relays
5-40 Function relay [0] No operation All set-ups TRUE - Uint8
5-41 On delay, relay 0.30 s All set-ups TRUE -2 Uint16
5-42 Off delay, relay 0.30 s All set-ups TRUE -2 Uint16
6 6 15-73
15-74
Slot B option SW version
Option in slot C0
0 N/A
0 N/A
All set-ups
All set-ups
FALSE
FALSE
0
0
VisStr[20]
VisStr[30]
15-75 Slot C0 option SW version 0 N/A All set-ups FALSE 0 VisStr[20]
15-76 Option in slot C1 0 N/A All set-ups FALSE 0 VisStr[30]
15-77 Slot C1 option SW version 0 N/A All set-ups FALSE 0 VisStr[20]
15-9* Parameter Info
15-92 Defined parameters 0 N/A All set-ups FALSE 0 Uint16
15-93 Modified parameters 0 N/A All set-ups FALSE 0 Uint16
15-98 Unit identification 0 N/A All set-ups FALSE 0 VisStr[40]
15-99 Parameter metadata 0 N/A All set-ups FALSE 0 Uint16
NOTICE
Except for parameter 300-10 Active Filter Nominal Voltage, it is not recommended to change the settings in this
parameter group.
Par. No. # Parameter description Default value 4-set-up Change Conver- Type
during sion index
operation
300-0* General Settings
300-00 Harmonic cancellation mode [0] Overall All set-ups TRUE - Uint8
300-01 Compensation priority [0] Harmonics All set-ups TRUE - Uint8
300-08 Lagging reactive current [0] Disabled All set-ups
300-1* Network Settings
6 6 300-10 Active filter nominal voltage ExpressionLimit 2 set-ups FALSE 0 Uint32
300-2* CT Settings
300-20 CT primary rating ExpressionLimit 2 set-ups FALSE 0 Uint32
300-22 CT nominal voltage 342 V 2 set-ups FALSE 0 Uint32
300-24 CT sequence [0] L1, L2, L3 2 set-ups FALSE - Uint8
300-25 CT polarity [0] Normal 2 set-ups FALSE - Uint8
300-26 CT placement [1] Load Current 2 set-ups FALSE - Uint8
300-29 Start auto CT detection [0] Off All set-ups FALSE - Uint8
300-3* Compensation
300-30 Compensation points 0.0 A All set-ups TRUE -1 Uint32
300-35 Cosphi reference 0.500 N/A All set-ups TRUE -3 Uint16
300-4* Paralleling
300-40 Master follower selection [2] Not Paralleled 2 set-ups FALSE - Uint8
300-41 Follower ID 1 N/A 2 set-ups FALSE 0 Uint32
300-42 Number of follower AFs 1 N/A 2 set-ups FALSE 0 Uint32
300-5* Sleep Mode
300-50 Enable sleep mode null 2 set-ups TRUE - Uint8
300-51 Sleep mode trig source [0] Mains current All set-ups TRUE - Uint8
300-52 Sleep mode wake up trigger ExpressionLimit All set-ups TRUE 0 Uint32
300-53 Sleep mode sleep trigger 80 % All set-ups TRUE 0 Uint32
Par. No. # Parameter description Default value 4-set-up Change Conver- Type
during sion index
operation
301-0* Output Currents
301-00 Output current [A] 0.00 A All set-ups TRUE -2 Int32
301-01 Output current [%] 0.0 % All set-ups TRUE -1 Int32
301-1* Unit Performance
301-10 THD of current [%] 0.0 % All set-ups TRUE -1 Uint16
301-11 Estimated THD of voltage [%] 0.0 % All set-ups Uint16
301-12 Power factor 0.00 N/A All set-ups TRUE -2 Uint16
301-13 Cosphi 0.00 N/A All set-ups TRUE -2 Int16
301-14 Leftover currents 0.0 A All set-ups TRUE -1 Uint32
301-2* Mains Status
301-20 Mains current [A] 0A All set-ups TRUE 0 Int32
301-21 Mains frequency 0 Hz All set-ups TRUE 0 Uint8
301-22 Fund. mains current [A] 0A All set-ups TRUE 0 Int32
130BB021.10
termination switch (S801) of the unit, or a biased 61 68 69 39 42 50 53 54 55
termination resistor network. Use screened twisted pair
(STP) cable for bus cabling, and follow good common
7 7
installation practice.
Low-impedance ground connection of the screen at every Remove jumper to enable Safe Stop
node is very important, including at high frequencies. This 12 13 18 19 27 29 32 33 20 37
can be achieved by connecting a large surface of the
screen-to-ground, for example with a cable clamp or a
conductive cable gland. It may be necessary to apply
potential-equalizing cables to maintain the same ground
potential throughout the network, particularly in instal-
lations where there are long lengths of cable.
To prevent impedance mismatch, use the same type of
cable throughout the entire network.
175ZA907.10
Set the parameters in Table 7.2 to enable the FC protocol
for the filter.
RS485
• Keep the RS485 communication cable away from Illustration 7.4 Telegram Structure
noisy cables such as power lines and motor
cables. Doing so reduces high frequency noise
7.3.3 Telegram Length (LGE) Bit 7=0 (address format 1–31 active).
Bit 6 is not used.
The telegram length is the number of data bytes plus the Bit 5=1: Broadcast, address bits (0–4) are not used.
address byte ADR and the data control byte BCC. Bit 5=0: No Broadcast.
Bit 0-4=Filter address 1–31.
4 data bytes LGE=4+1+1=6 bytes
12 data bytes LGE=12+1+1=14 bytes 2. Address format 1–126:
Telegrams containing texts 101)+n bytes
Bit 7=1 (address format 1–126 active).
Bit 0-6=Filter address 1–126.
Table 7.3 Length of Telegrams Bit 0-6=0 Broadcast.
1) The 10 represents the fixed characters, while the n is variable
(depending on the length of the text). The slave returns the address byte unchanged to the
master in the response telegram.
7.3.4 Filter Address (ADR)
7.3.5 Data Control Byte (BCC)
2 different address formats are used.
The address range of the filter is either 1–31 or 1–126. The checksum is calculated as an XOR-function. Before the
The structure of data blocks depends on the type of telegram. There are 3 telegram types, and the type applies for both
control telegrams (master⇒follower) and response telegrams (follower⇒master).
130BA269.10
STX LGE ADR PCD1 PCD2 BCC
Parameter block
The parameter block is used to transfer parameters between master and follower. The data block is made up of 12 bytes (6
words) and also contains the process block.
130BA271.10
STX LGE ADR PKE IND PWEhigh PWElow PCD1 PCD2 BCC
Text block
The text block is used to read or write texts via the data block.
130BA270.10
STX LGE ADR PKE IND Ch1 Ch2 Chn PCD1 PCD2 BCC
7 7 1 1 1 1 Text transferred
number
Bits 12–15 transfer parameter commands from master to 3 The sub index used does not exist.
slave and return processed slave responses to the master. 4 The parameter is not the array type.
5 The data type does not match the defined
parameter.
Parameter commands master⇒slave
11 Data change in the defined parameter is not
Bit no. Parameter command
possible in the unit's present mode. Certain
15 14 13 12
parameters can only be changed when the motor
0 0 0 0 No command
is turned off.
0 0 0 1 Read parameter value
82 There is no bus access to the defined parameter.
0 0 1 0 Write parameter value in RAM (word)
83 Data change is not possible because factory set-
0 0 1 1 Write parameter value in RAM (double
up is selected.
word)
1 1 0 1 Write parameter value in RAM and Table 7.6 Fault Definitions
EEprom (double word)
1 1 1 0 Write parameter value in RAM and
7.3.8 Parameter Number (PNU)
EEprom (word)
1 1 1 1 Read/write text
Bits 0–1 transfer parameter numbers. The function of the
Table 7.4 Parameter Commands from Master to Slave
relevant parameter is defined in the parameter description
in the Programming Guide.
The index is used with the parameter number to read/ Unsigned means that there is no operational sign in the
write-access parameters with an index, e.g. 15-30 Alarm telegram.
Log: Error Code. The index consists of 2 bytes, a low byte
and a high byte. Data types Description
3 Integer 16
Only the low byte is used as an index. 4 Integer 32
5 Unsigned 8
7.3.10 Parameter Value (PWE) 6 Unsigned 16
7 Unsigned 32
The parameter value block consists of 2 words (4 bytes), 9 Text string
and the value depends on the defined command (AK). The 10 Byte string
master prompts for a parameter value when the PWE block 13 Time difference
contains no value. To change a parameter value (write), 33 Reserved
write the new value in the PWE block and send from the 35 Bit sequence
master to the follower.
Read text Fx xx 04 00
Write text Fx xx 05 00
7 7
truncated. If the read request for a parameter is for fewer
-6 0.000001
characters than the parameter stores, the response is space
-7 0.0000001
filled.
Table 7.8 Conversion Table
7.4.5 Conversion Factor
7.3.13 Process Words (PCD)
A parameter value can only be transferred as a whole
The block of process words is divided into 2 blocks of 16 number. Use a conversion factor to transfer decimals.
bits, which always occur in the defined sequence.
7.4.6 Parameter Values
PCD 1 PCD 2
Control telegram (master⇒slave control Reference value Standard data types
word) Standard data types are int 16, int 32, uint 8, uint 16 and
Control telegram (slave⇒master) status word Present output uint 32. They are stored as 4x registers (40001–4FFFF). The
frequency parameters are read using function 03 hex Read Holding
Registers. Parameters are written using the function 6 hex
Table 7.9 Process Words (PCD) Preset Single Register for 1 register (16 bits), and the
function 10 hex Preset Multiple Registers for 2 registers (32
7.4 How to Access Parameters in Modbus bits). Readable sizes range from 1 register (16 bits) up to
10 registers (20 characters).
RTU
Non-standard data types
7.4.1 Parameter Handling Non-standard data types are text strings and are stored as
4x registers (40001–4FFFF). The parameters are read using
The PNU (Parameter Number) is translated from the function 03 hex Read Holding Registers and written using
register address contained in the Modbus read or write function 10 hex Preset Multiple Registers. Readable sizes
message. The parameter number is translated to Modbus range from 1 register (2 characters) up to 10 registers (20
as (10 x parameter number) DECIMAL. characters).
• Auto reset.
If an alarm cannot be reset, the reason may be that its cause has not been rectified, or the alarm is trip-locked (see also
Table 8.1).
Alarms that are trip-locked offer additional protection, meaning that the mains supply must be switched off before the
alarm can be reset. After being switched back on, the unit is no longer blocked and may be reset as described in
chapter 8.2.2 Alarm Trip once the cause has been rectified.
Alarms that are not trip-locked can also be reset using the automatic reset function in 14-20 Reset Mode. Automatic wake-up
is possible during this type of reset.
If a warning and alarm is marked against a code in Table 8.1, either a warning occurs before an alarm, or the display for a
given fault (warning or alarm) is configurable.
A trip is the action when an alarm has appeared. The trip disables the active filter and can be reset by pressing [Reset] or
resetting via a digital input (parameter group 5-1* Digital Inputs [1] Reset). The origin event that caused an alarm cannot
damage the active filter or cause dangerous conditions. A trip lock is an action when an alarm occurs, which may cause
damage to active filter or connected parts. A trip lock situation can only be reset by a power cycling.
Warning yellow
Alarm flashing red
Trip locked yellow and red
Table 8.3 Description of Alarm Word, Warning Word and Extended Status Word
The alarm words, warning words and extended status words can be read out via serial bus or optional fieldbus for
diagnosis. See also parameter 16-90 Alarm Word, parameter 16-92 Warning Word and 16-94 Ext. Status Word. Reserved means
that the bit is not guaranteed to be any particular value. Reserved bits should not be used for any purpose.
8.3.1 Fault Messages for Active Filter ALARM 29, Heat sink temp
The maximum temperature of the heat sink has been
WARNING 1, 10 volts low exceeded. The temperature fault is not reset until the
The control card voltage is below 10 V from terminal 50. temperature drops below a defined heat sink temperature.
Remove some of the load from terminal 50, as the 10 V ALARM 33, Inrush fault
supply is overloaded. Max. 15 mA or minimum 590 Ω. Check whether a 24 V external DC supply has been
WARNING/ALARM 2, Live zero error connected.
The signal on terminal 53 or 54 is less than 50% of the WARNING/ALARM 34, Fieldbus communication fault
value set in parameters 6-10 Terminal 53 Low Voltage, The fieldbus on the communication option card is not
6-12 Terminal 53 Low Current, 6-20 Terminal 54 Low Voltage, working.
6-22 Terminal 54 Low Current.
WARNING/ALARM 35, Option Fault:
WARNING 4, Mains phase loss Contact Danfoss or supplier.
A phase is missing on the supply side, or the mains
ALARM 38, Internal fault
voltage imbalance is too high.
Contact Danfoss or supplier.
WARNING 5, DC-link voltage high
ALARM 39, Heat sink sensor
The DC-link voltage (DC) is higher than the high-voltage
No feedback from the heat sink temperature sensor.
warning limit. The unit is still active.
WARNING 40, Overload of Digital Output Terminal 27
WARNING 6, DC-link voltage low
Check the load connected to terminal 27 or remove short
The DC-link voltage (DC) is below the low-voltage warning
circuit connection.
limit. The unit is still active.
WARNING/ALARM 7, DC overvoltage
WARNING 41, Overload of Digital Output Terminal 29 8 8
Check the load connected to terminal 29 or remove short
If the DC-link voltage exceeds the limit, the unit trips.
circuit connection.
WARNING/ALARM 8, DC under voltage
ALARM 46, Power card supply
If the DC-link voltage (DC) drops below the under voltage
The supply on the power card is out of range.
limit, the filter checks if a 24 V back-up supply is
connected. If not, the filter trips. Check that the mains WARNING 47, 24 V supply low
voltage matches the nameplate specification. Contact Danfoss or supplier.
WARNING/ALARM 13, Overcurrent WARNING 48, 1.8 V supply low
The unit current limit has been exceeded. Contact Danfoss or supplier.
ALARM 14, Ground fault WARNING/ALARM/TRIP 65, Control card overtemperature
The sum current of the IGBT CTs does not equal zero. Control card overtemperature: The cut-out temperature of
Check if the resistance of any phase-to-ground has a low the control card is 80 °C.
value. Check both before and after mains contactor. Ensure WARNING 66, Heat sink temperature low
IGBT current transducers, connection cables, and This warning is based on the temperature sensor in the
connectors are OK. IGBT module.
ALARM 15, Incomp. Hardware Troubleshooting
A mounted option is incompatible with the present control
card SW/HW. The heat sink temperature measured as 0 °C could indicate
that the temperature sensor is defective, causing the fan
ALARM 16, Short circuit speed to increase to the maximum. If the sensor wire
There is a short circuit in the output. Turn off the unit and between the IGBT and the gate drive card is disconnected,
correct the error. this warning would result. Also, check the IGBT thermal
WARNING/ALARM 17, Control word time-out sensor.
There is no communication to the unit. ALARM 67, Option module configuration has changed
The warning is only active when 8-04 Control Word Timeout One or more options have either been added or removed
Function is not set to off. since the last power-down.
Possible correction: Increase parameter 8-03 Control Word
Timeout Time. Change 8-04 Control Word Timeout Function ALARM 68, Safe Torque Off (STO) activated
Safe Torque Off (STO) has been activated. To resume
WARNING 23, Internal fan fault normal operation, apply 24 V DC to terminal 37, then send
Internal fans have failed due to defect hardware or fans a reset signal (via bus, digital I/O, or by pressing [Reset].
not mounted. See 5-19 Terminal 37 Safe Stop.
WARNING 24, External fan fault
External fans have failed due to defective hardware or fans
not mounted.
ALARM 69, Power card temperature ALARM 309, Mains Ground Fault
The temperature sensor on the power card is either too A ground fault was detected in the mains currents. Check
hot or too cold. the mains for shorts and leakage current.
ALARM 70, Illegal FC Configuration ALARM 310, RTDC Buffer Full
Actual combination of control board and power board is Contact Danfoss or supplier.
illegal.
ALARM 311, Switch. Freq. Limit
ALARM 79, Illegal power section configuration The average switching frequency of the unit exceeded the
The scaling card is the incorrect part number or not limit. Verify that parameter 300-10 Active Filter Nominal
installed. Also MK102 connector on the power card could Voltage and 300-22 CT Nominal Voltage are set correctly. If
not be installed. so, contact Danfoss or supplier.
ALARM 80, Unit initialised to default value ALARM 312, CT Range
Parameter settings are initialised to default settings after a Current transformer measurement limitation was detected.
manual reset. Verify that the CTs used are an appropriate ratio.
ALARM 247, Power card temperature ALARM 314, Auto CT Interrupt
Power card overtemperature. A report value indicates the Auto CT detection has been interrupted.
source of the alarm (from left):
ALARM 315, Auto CT Error
1–4 inverter
An error was detected while performing auto CT detection.
5–8 rectifier
Contact Danfoss or supplier.
ALARM 250, New spare part
WARNING 316, CT Location Error
8 8 The power or switch mode supply has been exchanged.
The filter type code must be restored in the EEPROM.
The auto CT function could not determine the correct
locations of the CTs.
Select the correct type code in 14-23 Typecode Setting
according to the label on the unit. Remember to select WARNING 317, CT Polarity Error
Save to EEPROM to complete. The auto CT function could not determine the correct
polarity of the CTs.
ALARM 251, New type code
The filter has a new type code. WARNING 318, CT Ratio Error
The auto CT function could not determine the correct
ALARM 300, Mains Cont. Fault primary rating of the CTs.
The feedback from the mains contactor did not match the
expected value within the allowed time frame. Contact
Danfoss or supplier.
ALARM 301, SC Cont. Fault
The feedback from the soft charge contactor did not
match the expected value within the allowed time frame.
Contact Danfoss or supplier.
ALARM 302, Cap. Overcurrent
Excessive current was detected through the AC capacitors.
Contact Danfoss or supplier.
ALARM 303, Cap. Ground Fault
A ground fault was detected through the AC capacitor
currents. Contact Danfoss or supplier.
ALARM 304, DC Overcurrent
Excessive current through the DC-link capacitor bank was
detected. Contact Danfoss or supplier.
ALARM 305, Mains Freq. Limit
The mains frequency was outside the limits. Verify that the
mains frequency is within product specification.
ALARM 306, Compensation Limit
The needed compensation current exceeds unit capability.
Unit is running at full compensation.
ALARM 308, Resistor temp
Excessive resistor heat sink temperature detected.
9 Specifications
CT terminals specification
CT number 3 (one for each phase)
The AAF burden equals 2 mΩ
Secondary current rating 1 A or 5 A (hardware set-up)
Accuracy Class 0.5 or better
Digital inputs
Programmable digital inputs 2 (4)
Terminal number 18, 19, 271), 291)
Logic PNP or NPN
Voltage level 0-24–V DC
Voltage level, logic 0 PNP <5 V DC
Voltage level, logic1 PNP >10 V DC
Voltage level, logic 0 NPN >19 V DC
Voltage level, logic 1 NPN <14 V DC
Maximum voltage on input 28 V DC
Input resistance, Ri approx. 4 kΩ
All digital inputs are galvanically isolated from the supply voltage (PELV) and other high-voltage terminals.
1) Terminals 27 and 29 can also be programmed as output.
9 9 The RS485 serial communication circuit is functionally separated from other central circuits and galvanically isolated from the
supply voltage (PELV).
Digital output
Programmable digital/pulse outputs 2
Terminal number 27, 291)
Voltage level at digital/frequency output 0–24 V
Maximum output current (sink or source) 40 mA
1) Terminal 27 and 29 can also be programmed as input.
Surroundings
Enclosure IP21, IP54
Vibration test 1.0 g
Relative humidity 5% - 95% (IEC 721-3-3; class 3K3 (non-condensing) during operation
Aggressive environment (IEC 60068-2-43) H2S test class kD
Test method according to IEC 60068-2-43 H2S (10 days)
Ambient temperature
- with derating maximum 50 °C
- at full continuous output current max. 40 °C
Minimum ambient temperature -10 °C
Temperature during storage/transport -25 to +65 °C
Maximum altitude above sea level without derating 1000 m
Maximum altitude above sea level with derating 3000 m
EMC standards, Emission EN 61800-3-4
EN 61000-6-1/2,
EMC standards, Immunity EN 61000-4-2, EN 61000-4-3, EN 61000-4-4, EN 61000-4-5, EN 61000-4-6
Generic specifications
Maximum parallel filters 4 on same CT set
Filter efficiency 97%
Typical average switching frequency 3.0–4.5 kHz
Response time (reactive and harmonic) <0.5 ms
Settling time - reactive current control <20 ms
Settling time - harmonic current control <20 ms
Overshoot – reactive current control <10%
Overshoot – Harmonic current control <10%
WARNING
Connection to PC is carried out via a standard host/device USB cable. The USB connection is galvanically isolated from
the supply voltage (PELV) and other high-voltage terminals. The USB connection is not galvanically isolated from
protective earth. Use only isolated laptop/PC as connection to the USB connector on the unit or an isolated USB cable/
converter.
• The active filter has a short circuit protection current rate of 100 kA if properly fused
• Monitoring of the DC-link voltage ensures that the filter trips if the DC-link voltage is too low or too high.
• The active filter monitors the mains current as well as internal currents to reassure that current levels do not reach
critical levels. If current exceeds a critical level, the filter trips.
Table 9.1
Note: Numbers are rounded to nearest amp
130BD937.10
Temperature 110
100
90
The cooling capability of air is decreased at lower air 80
pressure. 70
Iout (%)
60
50
Below 1000 m altitude no derating is necessary, but above 40
30
1000 m the ambient temperature (TAMB) or maximum 20
output current (Iout) should be derated in accordance with 10
0
Illustration 9.1. 0 5 10 15 20 25 30 35 40 45 50 55
Tamb (Max) Deg C
An alternative is to lower the ambient temperature at high Illustration 9.2 Input/Output vs. Maximum Ambient
altitudes and thereby ensure 100% output current at high Temperature
altitudes. As an example of how to read the graph, the
situation at 2000 m is elaborated. At a temperature of 45
°C (TAMB, MAX - 3.3 K), 91% of the rated output current is
available. At a temperature of 41.7 °C, 100% of the rated
output current is available.
IOUT(%)
130BB008.10
100
95
9 9 90
85
80
0 500 1000 1500 2000 2500 3000
Altitude (meters above sea level)*
Illustration 9.1 Altitude Derating
10 Appendix
Conventions
Numbered lists indicate procedures.
Bullet lists indicate other information and description of
illustrations.
Italicised text indicates:
10 10
• Cross-reference
• Link
• Footnote
Index DC link....................................................................................................... 79
Default settings.............................................................................. 34, 62
A Derating, altitude................................................................................. 84
Abbreviations......................................................................................... 85 Diagnosis Read-Outs, 16-9*.............................................................. 57
Additional resources.............................................................................. 4 Digital I/O Mode, 5-0*......................................................................... 46
AF Readouts............................................................................................ 68 Digital In/Out......................................................................................... 64
AF Settings.............................................................................................. 68 Dimensions, mechanical...................................................................... 9
Alarm log, 15-3*.................................................................................... 53 Discharge time......................................................................................... 7
Alarm/warning code list..................................................................... 76 Door clearance...................................................................................... 11
B E
Back cooling........................................................................................... 13 Efficient parameter set-up for most applications..................... 38
Electrical installation........................................................................... 27
C EMC precautions................................................................................... 70
Cable length, cross-section............................................................... 81
Cabling..................................................................................................... 15 F
Changing a group of numeric data values.................................. 33 Fault message, active filter................................................................ 79
Changing a text value......................................................................... 33 FC Information....................................................................................... 65
Changing data....................................................................................... 33 FC port setting, 8-3*............................................................................ 49
Changing of data value...................................................................... 33 Feedback................................................................................................. 29
Circuit breakers..................................................................................... 29 Filter configurator................................................................................... 6
Clearance requirements..................................................................... 11 Fuses................................................................................................... 26, 29
Comm. and Options............................................................................ 64 Fusing....................................................................................................... 15
Conduit..................................................................................................... 29
Configuration......................................................................................... 48 G
Configurator, filter.................................................................................. 6 General setting, 8-0*............................................................................ 48
Connecting to a PC.............................................................................. 35 Gland/Conduit Entry, IP21 (NEMA 1) and IP54 (NEMA12)..... 14
Control cable.......................................................................................... 27 Graphical display.................................................................................. 30
Control card, USB serial communication..................................... 83 Grid condition........................................................................................ 81
Control terminal, input polarity, PNP............................................ 27 Ground connections............................................................................ 29
Control wire installation..................................................................... 26 Grounding........................................................................................ 16, 29
Control wiring........................................................................................ 29
Conventions........................................................................................... 85
H
Cooling clearance................................................................................. 29 Hand On................................................................................................... 33
CT terminal, specification.................................................................. 82
I
Current transformer............................................................................. 18
Indexed parameters............................................................................ 33
M R
Main menu mode................................................................................. 32 Reactive current compensation...................................................... 81
Main Menu Mode................................................................................. 40 Receiving, active filter........................................................................... 8
Maintenance.......................................................................................... 75 Relay outputs......................................................................................... 47
MCT 10...................................................................................................... 34 Reset................................................................................................... 33, 75
Mechanical dimensions........................................................................ 9 RFI switch................................................................................................. 18
Mechanical installation...................................................................... 11 RS485................................................................................................. 35, 69
Motor cables........................................................................................... 15 RS485 bus connection........................................................................ 35
Motor wiring........................................................................................... 29
Mounting................................................................................................. 29 S
Multiple frequency converters........................................................ 15 Screened cable...................................................................................... 29
Serial communication......................................................................... 75
O Service...................................................................................................... 75
Operating Data, 15-0*......................................................................... 52 Space......................................................................................................... 11
Operating mode................................................................................... 41 Special Functions.................................................................................. 65
Operation/Display................................................................................ 63 Status........................................................................................................ 32
Option Ident. , 15*6*............................................................................ 54 Status messages.................................................................................... 30
Ordering form type code..................................................................... 6 Step-by-step........................................................................................... 33
Stop inverse............................................................................................ 33
P
Paralleling................................................................................................ 36 T
Parameter Info, 15-9*.......................................................................... 55 Telegram length (LGE)........................................................................ 71
Parameter selection............................................................................. 40 Torque...................................................................................................... 18
Parameter set-up.................................................................................. 36 Trip Reset, 14-2*.................................................................................... 50
Password, 0-6*....................................................................................... 45
PC............................................................................................................... 35 U
PC connection........................................................................................ 35 Unit Identification................................................................................ 54
Planning, installation site..................................................................... 8 USB............................................................................................................. 35
PNP............................................................................................................ 27
Power connections.............................................................................. 15
V
Power factor........................................................................................... 29 Voltage level........................................................................................... 82
Power terminals.................................................................................... 12
W
Wire access.............................................................................................. 11
Danfoss can accept no responsibility for possible errors in catalogues, brochures and other printed material. Danfoss reserves the right to alter its products without notice. This also applies to
products already on order provided that such alterations can be made without subsequential changes being necessary in specifications already agreed. All trademarks in this material are property
of the respective companies. Danfoss and the Danfoss logotype are trademarks of Danfoss A/S. All rights reserved.
Danfoss A/S
Ulsnaes 1
DK-6300 Graasten
www.danfoss.com/drives
*MG90V302*