Doc MG06A802 VLT Automation Drive FC 360 Quick Guide
Doc MG06A802 VLT Automation Drive FC 360 Quick Guide
Quick Guide
VLT® AutomationDrive FC 360
vlt-drives.danfoss.com
Contents Quick Guide
Contents
1 Introduction 3
1.1 Purpose of the Manual 3
1.2 Additional Resources 3
1.3 Document and Software Version 3
1.4 Approvals and Certifications 3
1.5 Disposal 3
1.6 Product Overview 3
2 Safety 8
2.1 Safety Symbols 8
2.2 Qualified Personnel 8
2.3 Safety Precautions 8
3 Mechanical Installation 10
3.1 Identification and Variants 10
3.2 Installation Environment 11
3.3 Mounting 11
4 Electrical Installation 13
4.1 General Requirements 13
4.2 EMC-compliant Installation 13
4.3 Grounding Requirements 14
4.4 Wiring Schematic 15
4.5 Mains, Motor, and Ground Connections 18
4.6 Control Wiring 19
4.7 Jumper Terminals 12 and 27 21
4.8 Serial Communication 21
5 Commissioning 22
5.1 Safety Instructions 22
5.2 Applying Power 22
5.3 Hand On/Auto On Mode 22
5.4 Local Control Panel (LCP) Operations 23
5.5 Basic Programming 33
5.6 Checking Motor Rotation 35
5.7 Checking Encoder Rotation 35
5.8 Local-control Test 36
5.9 System Start-up 36
5.10 PROFIBUS 36
5.11 PROFINET 38
6 Applications 40
6.1 Application Selections 40
6.2 Application Examples 48
8 Specifications 58
8.1 Mains Supply 3x380–480 V AC 58
8.2 General Technical Data 61
8.3 Fuses 65
8.4 Connection Tightening Torques 66
9 Appendix 67
9.1 Symbols, Abbreviations, and Conventions 67
9.2 Parameter Menu Structure 67
Index 79
1 Introduction 1 1
5 Capacitor bank
• Provides ride-through
Illustration 1.1 is a block diagram of the internal protection for short power
components of the frequency converter. losses.
130BF760.10
controlled PWM AC waveform
J1–J5 6 Inverter for a controlled variable
1 2 3 9 6
output to the motor.
4 7
5
• Regulated 3-phase output
M 7 Output to motor power to the motor.
130BC449.10
b
Dimensions
[mm (in)]
A
a
D
Height A 210 (8.3) 272.5 (10.7) 272.5 (10.7) 317.5 (12.5) 410 (16.1) 515 (20.3) 550 (21.7)
Width B 75 (3.0) 90 (3.5) 115 (4.5) 133 (5.2) 150 (5.9) 233 (9.2) 308 (12.1)
Depth C 168 (6.6) 168 (6.6) 168 (6.6) 245 (9.6) 245 (9.6) 241 (9.5) 323 (12.7)
Depth C with
173 (6.8) 173 (6.8) 173 (6.8) 250 (9.8) 250 (9.8) 241 (9.5) 323 (12.7)
option B
D 180 (7.1) 240 (9.4) 240 (9.4) 270 (10.6) 364.7 (14.4) 452 (17.8) 484.5 (19.0)
Mounting holes
a 198 (7.8) 260 (10.2) 260 (10.2) 297.5 (11.7) 390 (15.4) 495 (19.5) 521 (20.5)
b 60 (2.4) 70 (2.8) 90 (3.5) 105 (4.1) 120 (4.7) 200 (7.9) 270 (10.6)
Mounting screw M4 M5 M5 M6 M6 M8 M8
130BC439.11
1
17
16
15
14
4
13
12
05
11
04
03
20
01
10
9
8
7
6
5
Illustration 1.2 Exploded View, J1–J5 (0.37–22 kW/0.5–30 hp), IP20 (Taking J2 as an Example)
3 1 1
130BD647.10
2
1
5
10
11
18
13 12
16 15
14
17
Illustration 1.3 Exploded View, J6–J7 (30–75 kW/40–100 hp), IP20 (Taking J7 as an Example)
2 Safety
2 2
2.1 Safety Symbols WARNING
The following symbols are used in this document: UNINTENDED START
When the frequency converter is connected to AC mains,
DC supply, or load sharing, the motor may start at any
WARNING time. Unintended start during programming, service, or
Indicates a potentially hazardous situation that could repair work can result in death, serious injury, or
result in death or serious injury. property damage. Start the motor with an external
switch, a fieldbus command, an input reference signal
CAUTION from the local control panel (LCP), via remote operation
using MCT 10 software, or after a cleared fault condition.
Indicates a potentially hazardous situation that could
To prevent unintended motor start:
result in minor or moderate injury. It can also be used to
alert against unsafe practices. • Disconnect the frequency converter from the
mains.
Minimum waiting
Voltage Power range
time
[V] [kW (hp)]
2 2
(minutes)
0.37–7.5 kW
380–480 4
(0.5–10 hp)
11–75 kW
380–480 15
(15–100 hp)
WARNING
LEAKAGE CURRENT HAZARD
Leakage currents exceed 3.5 mA. Failure to ground the
frequency converter properly can result in death or
serious injury.
• Ensure the correct grounding of the equipment
by a certified electrical installer.
WARNING
EQUIPMENT HAZARD
Contact with rotating shafts and electrical equipment
can result in death or serious injury.
• Ensure that only trained and qualified personnel
perform installation, start-up, and maintenance.
• Ensure that electrical work conforms to national
and local electrical codes.
• Follow the procedures in this manual.
NOTICE
HIGH ALTITUDES
For installation at altitudes above 2000 m (6562 ft),
contact Danfoss regarding PELV.
CAUTION
INTERNAL FAILURE HAZARD
An internal failure in the frequency converter can result
in serious injury when the frequency converter is not
properly closed.
• Ensure that all safety covers are in place and
securely fastened before applying power.
NOTICE
USE ON ISOLATED MAINS
For details about the use of the frequency converter on
isolated mains, refer to the section RFI Switch in the
design guide.
Follow the recommendations regarding the installation
on IT mains. Use relevant monitoring devices for IT
mains to avoid damage.
3 Mechanical Installation
130BC435.13
11 K: 11 kW (15 hp)
1
VLT Automation Drive
www.danfoss.com 11–12: Voltage class T4: 380–480 V 3 phases
T/C: FC-360HK37T4E20H2BXCDXXSXXXXAXBX
2
13–15: IP class E20: IP20
P/N: 134F2970 S/N: 691950A240
Danfoss A/S
0.37 kW 0.5HP High Overload 6430 Nordborg 16–17: RFI H1: C2 Class3)
IN: 3x380-480V 50/60Hz 1.24/0.99A Denmark
H2: C3 Class
3 OUT: 3x0-Vin 0-500Hz 1.2/1.1A(Tamb. 45 C)
o
X: No
CHASSIS/IP20 MADE BY DANFOSS IN CHINA 18: Brake chopper
B: Built-in4)
19: LCP X: No
20: PCB coating C: 3C3
21: Mains terminals D: Load sharing
AX: No
CAUTION: 29–30: Embedded
SEE MANUAL A0: PROFIBUS
fieldbus
WARNING: AL: PROFINET
STORED CHARGE DO NOT TOUCH UNTIL 4 MIN. AFTER 31–32: Option B BX: No option
DISCONNECTION
RISK OF ELECTRIC SHOCK-DUAL SUPPLY DISCONNECT MAINS
AND LOADSHARING BEFORE SERVICE Table 3.1 Type Code: Selection of Different Features and Options
For options and accessories, refer to the section Options and
Accessories in the VLT® AutomationDrive FC 360 Design Guide.
1 Type code 1) Only 11–75 kW (15–100 hp) for normal duty variants. PROFIBUS
2 Ordering number and PROFINET are unavailable for normal duty.
3 Specifications 2) For all power sizes, see chapter 8.1.1 Mains Supply 3x380–480 V
AC.
Illustration 3.1 Nameplates 1 and 2 3) H1 RFI filter is available for 0.37–22 kW (0.5–30 hp).
4) 0.37–22 kW (0.5–30 hp) with built-in brake chopper. 30–75 kW
(40–100 hp) with external brake chopper only.
130BC437.11
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32
F C - 3 6 0 H T 4 E 2 0 H 1 X X C D X X S X X X X A X B X
Q H 2 B A 0
A L
All VLT® AutomationDrive FC 360 units can be installed Enclosure size J1–J5 of VLT® AutomationDrive FC 360 units
side by side in vertical position. The units do not require can be installed in horizontal position.
extra ventilation on the side.
3 3
130BF793.10
130BF792.10
G
130BF794.10
G
4 Electrical Installation
WARNING
GROUNDING HAZARD
For operator safety, a certified electrical installer should
ground the frequency converter in accordance with
national and local electrical codes and instructions
contained within this manual. Ground currents are higher
4 4 than 3.5 mA. Failure to ground the frequency converter
properly could result in death or serious injury.
FC 1 FC 2 FC 3
PE
FC 1 FC 2 FC 3
PE
130BC438.19
3)
RFI
91 (L1) (U) 96
3 phase 92 (L2) (V) 97
power
4 4
93 (L3) (W) 98
input (PE) 99
95 PE
Motor
Switch mode
power supply 1) (-UDC) 88
10 V DC 24 V DC (+UDC) 89 Brake
15 mA 100 mA
resistor
50 (+10 V OUT) + - + -
+10 V DC (BR) 81 5)
0-10 V DC 53 (A IN)
0/4-20 mA
0-10 V DC 54 (A IN)
0/4-20 mA
Relay 1
55 (COM A IN/OUT) 03
250 V AC, 3 A
02
Analog 42 (A OUT)
output
01
0/4-20 mA
45 (A OUT)
12 (+24 V OUT)
Relay 2 2)
P 5-00 06
250 V AC, 3 A
24 V (NPN) 05
18 (D IN) 0 V (PNP)
24 V (NPN) 04
19 (D IN) 0 V (PNP)
20 (COM D IN)
4)
24 V (NPN) ON=Terminated
1 2
ON
RS485
(N RS485) 69 RS485
0V Interface
24 V (NPN) (P RS485) 68
31 (D IN) 0 V (PNP)
0V (COM RS485) 61
24 V (NPN)
32 (D IN) 0 V (PNP) (PNP) = Source
24 V (NPN) (NPN) = Sink
33 (D IN) 0 V (PNP)
A=Analog, D=Digital
1) Built-in brake chopper available from J1–J5.
2) Relay 2 is 2-pole for J1–J3 and 3-pole for J4–J7. Relay 2 of J4–J7 with terminals 4, 5, and 6 has same NO/NC logic as relay 1.
Relays are pluggable in J1–J5 and fixed in J6–J7.
4 4
e30bf228.11
6
4 4
8
9
10
11
1 12
90
13
2 14
3
15
u
4
v 16
4
w
4 PE
L1 17
L2
L3
PE
18
130BC501.10
WARNING
INDUCED VOLTAGE
04 05
Run output motor cables from multiple frequency
converters separately. Induced voltage from output
01 02 03
motor cables run together can charge equipment
capacitors even when the equipment is turned off and
4 4 locked out. Failure to run output motor cables separately
could result in death or serious injury.
130BD648.11
(enclosure sizes J1–J5). When off, the internal RFI
filter capacitors between the chassis and the
intermediate circuit are isolated to avoid damage
to the intermediate circuit and reduce ground
capacity currents in accordance with IEC 61800-3.
• Do not install a switch between the frequency
converter and the motor in IT mains.
130BC504.11
output current is
100 mA for all
4 4
24 V loads.
Parameter 5-10 Ter
18 minal 18 Digital [8] Start
Input
Digital inputs.
Parameter 5-11 Ter
[10]
19 minal 19 Digital
Reversing
Input
Parameter 5-16 Ter
[0] No
31 minal 31 Digital Digital input.
operation
Illustration 4.6 Control Wiring Access for Enclosure Sizes J1–J7 Input
Parameter 5-14 Ter
[0] No Digital input, 24
32 minal 32 Digital
operation V encoder.
Control terminal types Input
Terminal 33 can
Illustration 4.7 shows the frequency converter control Parameter 5-15 Ter
terminals. Terminal functions and default settings are [16] Preset ref be used for
33 minal 33 Digital pulse input.
summarized in Table 4.1. bit 0
Input
Parameter 5-12 Ter
130BC505.12
See chapter 8.2 General Technical Data for terminal ratings Parameter 6-91 Ter Programmable
[0] No analog output.
details. 42 minal 42 Analog
operation The analog
Output
signal is 0–20
mA or 4–20 mA
Parameter 6-71 Ter at a maximum of
[0] No
45 minal 45 Analog 500 Ω. Can also
operation
Output be configured as
digital outputs.
130BB922.12
Parameter group RS485 interface.
68 (+) 8-3* FC Port – A control card
Settings switch is
PE PE <10 mm
Parameter group provided for PE PE
69 (-) 8-3* FC Port – termination 1
2
Settings resistance.
Relays 1 Minimum 16 mm2 (6 AWG)
Form C relay 2 Equalizing cable
output. These
relays are in Illustration 4.8 Shielding Clamps at Both Ends
01, 02, 03 5-40 [0] [9] Alarm various locations
depending on
the frequency
50/60 Hz ground loops
converter config-
With long control cables, ground loops could occur. To
uration and size.
eliminate ground loops, connect 1 end of the shield to the
Usable for AC or
ground with a 100 nF capacitor (keeping leads short).
DC voltage and
130BB609.12
resistive or PLC FC
inductive loads.
04, 05, 06 5–40 [1] [5] Running
RO2 in J1–J3 PE
100nF PE <10 mm
enclosure is 2-
Illustration 4.9 Connection with a 100 nF Capacitor
pole, only
terminals 04 and
05 are available
130BB923.12
69 69 recommended.
68 68
61 61 • See chapter 4.3.1 Grounding Requirements for
PE
PE
PE <10 mm
PE
proper grounding.
4 4
1
130BB489.10
2
RS485
69
Alternatively, the connection to terminal 61 can be
omitted.
FC FC
130BB924.12
PE PE <10 mm
PE PE
1 For basic serial communication set-up, select the following:
2 1. Protocol type in parameter 8-30 Protocol.
1 Minimum 16 mm2 (6 AWG) 2. Frequency converter address in
2 Equalizing cable parameter 8-31 Address.
3. Baud rate in parameter 8-32 Baud Rate.
Illustration 4.11 Twisted-pair Cables without Terminal 61
Two communication protocols are internal to the
frequency converter.
5 Commissioning
3. Ensure that input power to the unit is off and 5.3 Hand On/Auto On Mode
locked out. Do not rely on the frequency
converter disconnect switches for input power After installation, there are 2 simple ways to start up the
isolation. frequency converter:
• Hand-on mode.
4. Verify that there is no voltage on input terminals
L1 (91), L2 (92), and L3 (93), phase-to-phase, and • Auto-on mode.
phase-to-ground. At the first power-up, it is in auto-on mode.
5. Verify that there is no voltage on output
terminals 96 (U), 97 (V), and 98 (W), phase-to-
130BD062.10
phase, and phase-to-ground. On OK
6. Confirm continuity of the motor by measuring Ω
Warn
values on U–V (96–97), V–W (97–98), and W–U
(98–96). Alarm
130BC506.10
5.4 Local Control Panel (LCP) Operations
1
5 5
3
VLT® AutomationDrive FC 360 supports numerical local
control panel (NLCP) LCP 21, graphic local control panel A
Setup 1
(GLCP) LCP 102, and blind cover. This chapter describes the 5
operations with LCP 21 and LCP 102. 2
Back
130B1000 or downloaded from the Danfoss website: On OK
drives.danfoss.com/downloads/pctools/#/. 6
12
Warn
7
Alarm
8 10
Hand Off Auto
D
On Reset On
13 14 15
A. Numeric display
Key Function
The LCD display is backlit with 1 numeric line. All data is
shown in the LCP. For moving to the previous step or layer
9 [Back]
in the navigation structure.
1 The set-up number shows the active set-up and the edit For switching between parameter groups,
set-up. If the same set-up acts as both active and edit set- parameters, and within parameters, or
up, only that set-up number is shown (factory setting). 10 [▲] [▼] increasing/decreasing parameter values.
When active and edit set-ups differ, both numbers are Arrows can also be used for setting local
shown in the display (set-up 12). The number flashing reference.
indicates the edit set-up. Press to access parameter groups or to
2 Parameter number. 11 [OK]
enable a selection.
3 Parameter value. Press to move from left to right within
5 5 4 Motor direction is shown at the bottom left of the display.
A small arrow indicates the direction.
12 [►] the parameter value to change each digit
individually.
5 The triangle indicates whether the LCP is in Status, Quick
Menu, or Main Menu. Table 5.3 Legend to Illustration 5.2, Navigation Keys
Table 5.1 Legend to Illustration 5.2, Section A D. Operation keys and indicator lights (LEDs)
Key Function
130BD135.10
Press [►] to edit any of the 4 digits on the display The Quick Menu gives easy access to the most frequently
individually. When pressing [►] once, the cursor moves to used parameters.
the first digit and the digit starts flashing as shown in
Illustration 5.4. Press the [▲] [▼] to change the value. 1. To enter Quick Menu, press [Menu] until the
Pressing [►] does not change the value of the digits or indicator in the display is placed above Quick
move the decimal point. Menu.
2. Press [▲] [▼] to select either QM1 or QM2, then
press [OK].
130BC440.10
Setup 1
3. Press [▲] [▼] to browse through the parameters in
Quick Menu. 5 5
4. Press [OK] to select a parameter.
5. Press [▲] [▼] to change the value of a parameter
Setup 1
setting.
6. Press [OK] to accept the change.
7. To exit, press either [Back] twice (or 3 times if in
QM2 and QM3) to enter Status, or press [Menu]
Setup 1
once to enter Main Menu.
Setup 1
Setup 1
26
QM 1 QM 2 Changes made QM 3 QM 4 QM 5
Commissioning
130BC445.13
Motor
Motor control 1-39 XXXX Motor poles Terminal 32/33
nominal 1-25 XXXX RPM 1-22 XXXX V Motor voltage 1-01 [1] 5-71 [0]
principle encoder direction
speed
Motor cont. Motor thermal
rated torque
1-26 XXXX 1-23 XXXX Hz Motor frequency 1-90 [0] protection
Motor type 1-10 [0]
Stator PM motor Asynchronous motor
Resistance (Rs) 1-30 XXXX 1-24 XXXX A Motor current 2-10 [0] Brake function
Motor
Motor poles 1-39 XXXX Motor 1-24 XXXX A 1-20 XXXX kW Motor power
1-25 XXXX RPM nominal current 4-16 XXXX % Torque limit motor mode
speed
Motor
Back EMF at 1-40 XXXX 1-25 XXXX RPM
nominal 1-22 XXXX V Motor voltage
1000 RPM 4-17 XXXX % Torque limit generator mode
speed
Stator
MG06A802
Commissioning Quick Guide
After power-up, Status Menu is active. Press [Menu] to The Main Menu gives access to all parameters.
toggle between Status, Quick Menu, and Main Menu.
1. To enter Main Menu, press [Menu] until the
[▲] and [▼] toggle between the options in each menu. indicator in the display is placed above Main
Menu.
The display indicates the status mode with a small arrow 2. [▲] [▼]: Browse through the parameter groups.
above Status.
3. Press [OK] to select a parameter group.
4. [▲] [▼]: Browse through the parameters in the
130BA466.10
specific group.
5 5
5. Press [OK] to select the parameter.
6. [►] and [▲] [▼]: Set/change the parameter value.
7. Press [OK] to accept the value.
8. To exit, press either [Back] twice (or 3 times for
array parameters) to enter Main Menu, or press
[Menu] once to enter Status.
See Illustration 5.7, Illustration 5.8, and Illustration 5.9 for the
Illustration 5.6 Indicating Status Mode principles of changing the value of continuous,
enumerated, and array parameters, respectively. The
actions in the illustrations are described in Table 5.5,
The following 8 parameters can be accessed from the NLCP Table 5.6, and Table 5.7.
status menu in auto-on mode:
• Parameter 16-02 Reference [%].
• Parameter 16-09 Custom Readout.
• Parameter 16-10 Power [kW].
• Parameter 16-13 Frequency.
• Parameter 16-14 Motor current.
• Parameter 16-16 Torque [Nm].
• Parameter 16-30 DC Link Voltage.
• Parameter 16-52 Feedback[Unit].
The following 6 parameters can be accessed from the NLCP
status menu in [Hand On] mode:
• Parameter 16-09 Custom Readout.
• Parameter 16-10 Power [kW].
• Parameter 16-13 Frequency.
• Parameter 16-14 Motor current.
• Parameter 16-16 Torque [Nm].
• Parameter 16-30 DC Link Voltage.
130BC446.10
Setup 1
12 2 Press [▼] repeatedly to move down to the parameter.
3 Press [OK] to start editing.
OK 1 4 [►]: First digit flashing (can be edited).
Back
11
5 [►]: Second digit flashing (can be edited).
Setup 1
6 [►]: Third digit flashing (can be edited).
2x 10
7 [▼]: Decreases the parameter value, the decimal point
2 changes automatically.
+ OK Setup 1 8 [▲]: Increases the parameter value.
9 [Back]: Cancel changes, return to 2.
[OK]: Accept changes, return to 2.
5 5 OK 3
Setup 1
10 [▲][▼]: Select parameter within the group.
11 [Back]: Removes the value and shows the parameter group.
12 [▲][▼]: Select group.
4
Table 5.5 Changing Values in Continuous Parameters
Setup 1
130BC447.11
OK
Setup 1 Setup 1 7
Back
7 OK 1
Back
6
Setup 1
Setup 1
5
8 OK 2
Setup 1 Back
4 OK
Setup 1
130BC448.10
Setup 1 10 display area, which shows more information than LCP 21.
5x LCP 102 supports English, Chinese, and Portuguese
displays.
OK 1 9
Back
Setup 1 The GLCP is divided into 4 functional groups (see
8 Illustration 5.10).
%
INDEX
OK 2
A. Display area.
Setup 1
% 7 Back
B. Display menu keys. 5 5
INDEX C. Navigation keys and indicator lights (LEDs).
D. Operation keys and reset.
Setup 1 OK
130BD598.10
% 6
INDEX 1 3
Back
Status 1(1)
OK 4 799 RPM 7.83 A 36.4 kW
Setup 1 2
A
0.000
5
INDEX
% 5 53.2 %
nc
Ba
OK
7 [Back]: Cancels editing index, a new parameter can be 15
selected. Warn.
16 13
8 [▲][▼]: Select parameter within the group. Alarm
18 19 20 21
Table 5.7 Changing Values in Array Parameters
Illustration 5.10 Graphic Local Control Panel (GLCP)
Illustration 5.9 Main Menu Interactions - Array Parameters
5 5
3 0-22 [1610] Power [kW] text is shown.
4 0-23 [1613] Frequency
Table 5.11 Legend to Illustration 5.10, Indicator Lights (LEDs)
5 0-24 [1502] kWh Counter
Table 5.8 Legend to Illustration 5.10, Display Area D. Operation keys and reset
Operation keys are at the bottom of the LCP.
B. Display menu keys
Key Function
Menu keys are used for menu access for parameter set-up,
Starts the frequency converter in hand-on
toggling through status display modes during normal
mode.
operation, and viewing fault log data.
18 Hand On • An external stop signal by control input
Key Function or serial communication overrides the
6 Status Shows operational information. local hand on.
Allows access to programming parameters Stops the motor but does not remove power
Quick 19 Off
7 for initial set-up instructions and many to the frequency converter.
Menu
detailed application instructions. Puts the system in remote operational mode.
8 Main Menu
Allows access to all programming • Responds to an external start command
parameters. 20 Auto On by control terminals or serial communi-
Shows a list of current warnings, the last 10 cation.
9 Alarm Log
alarms, and the maintenance log.
Resets the frequency converter manually
21 Reset
after a fault has been cleared.
Table 5.9 Legend to Illustration 5.10, Display Menu Keys
Key Function
Reverts to the previous step or list in the
10 Back
menu structure.
Cancels the last change or command as long
11 Cancel
as the display mode has not changed.
Press for a definition of the function being
12 Info
shown.
Navigation To move between items in the menu, use the
13
keys 4 navigation keys.
Press to access parameter groups or to
14 OK
enable a selection.
130BD532.10
1. Press [Quick Menu] or [Main Menu] on the LCP.
2. Press [▲] [▼] to browse through the parameter
groups, press [OK] to select a parameter group.
3. Press [▲] [▼] to browse through the parameters,
press [OK] to select a parameter. 5 5
4. Press [▲] [▼] to change the value of a parameter
setting.
5. Press [◄] [►] to shift digit when a decimal
parameter is in the editing state.
6. Press [OK] to accept the change.
7. Press either [Back] twice to enter Status, or press
[Main Menu] once to enter the Main Menu.
View changes
Quick Menu Q5 - Changes Made lists all parameters
changed from default settings.
• The list only shows parameters which have been
changed in the current edit set-up.
• Parameters which have been reset to default
values are not listed.
Illustration 5.11 GLCP Adapter and Connecting Cable
• The message Empty indicates that no parameters
have been changed.
5.4.9 Backing Up/Downloading Parameters selections, fault log, alarm log, and other
with LCP monitoring functions.
• Manual initialization erases all motor,
Establishing the correct programming for applications programming, localization, and monitoring data,
often requires setting functions in several related and restores factory default settings.
parameters. Parameter details are provided in
Recommended initialization procedure, via
chapter 9.2 Parameter Menu Structure.
parameter 14-22 Operation Mode
1. Select parameter 14-22 Operation Mode and press
Programming data is stored internally in the frequency
[OK].
converter.
2. Select [2] Initialisation and press [OK].
5 5 • For back-up, upload data into the LCP memory. 3. Remove power to the unit and wait until the
display turns off.
• To download data to another frequency
converter, connect the LCP to that unit and 4. Apply power to the unit.
download the stored settings. Default parameter settings are restored during start-up.
• Restoring factory default settings does not This may take slightly longer than normal.
change data stored in the LCP memory.
Back-up/download process 5. Alarm 80, Drive initialized to default value is shown.
1. Press [Off] on the GLCP or [Off Reset] on the 6. Press [Reset] to return to operating mode.
NLCP to stop the motor before uploading or
Manual initialization procedure
downloading data.
1. Remove power to the unit and wait until the
2. Press [Main Menu] parameter 0-50 LCP Copy and display turns off.
press [OK].
2. Press and hold [Status], [Main Menu], and [OK] at
3. Select [1] All to LCP to upload data to the LCP, or the same time on the GLCP, or press [Menu] and
select [2] All from LCP to download data from the [OK] at the same time on the NLCP while
LCP, or select [3] Size indep. from LCP to download applying power to the unit (approximately 5 s or
motor size independent parameters from LCP. until a click is heard and the fan starts).
4. Press [OK]. A progress bar shows the uploading or Factory default parameter settings are restored during
downloading progress. start-up. This may take slightly longer than normal.
5. Press [Hand On] or [Auto On] to return to normal
operation. Manual initialization does not reset the following
frequency converter information:
5.4.10 Restoring Default Settings with LCP • Parameter 0-03 Regional Settings
• Parameter 1-06 Clockwise Direction
NOTICE • Parameter 15-00 Operating hours
Risk of losing programming, motor data, localization, and
monitoring records by restoration of default settings. To
• Parameter 15-03 Power Up's
provide a back-up, upload data to the LCP before initiali- • Parameter 15-04 Over Temp's
zation. • Parameter 15-05 Over Volt's
• Parameter 15-30 Alarm Log: Error Code
Restoring the default parameter settings is done by initiali-
zation of the frequency converter. Initialization is carried
out through parameter 14-22 Operation Mode
(recommended) or manually. Initialization does not reset
the settings for parameter 1-06 Clockwise Direction and
parameter 0-03 Regional Settings.
5.5 Basic Programming Program the following parameters in the listed order:
1. Parameter 1-24 Motor Current.
5.5.1 Asynchronous Motor Set-up 2. Parameter 1-26 Motor Cont. Rated Torque.
Enter the following motor data in the listed order. Find the 3. Parameter 1-25 Motor Nominal Speed.
information on the motor nameplate. 4. Parameter 1-39 Motor Poles.
5. Parameter 1-40 Back EMF at 1000 RPM.
1. Parameter 1-20 Motor Power.
6. Parameter 1-42 Motor Cable Length.
2. Parameter 1-22 Motor Voltage.
Run a complete AMA using parameter 1-29 Automatic
3. Parameter 1-23 Motor Frequency. Motor Adaption (AMA) and select [1] Enable Complete AMA.
5 5
4. Parameter 1-24 Motor Current. If a complete AMA is not performed successfully, configure
the following parameters manually.
5. Parameter 1-25 Motor Nominal Speed.
For optimum performance in VVC+ mode, extra motor data 1. Parameter 1-30 Stator Resistance (Rs).
is required to set up the following parameters. Enter phase common stator winding resistance
(Rs). If only phase-to-phase data is available,
6. Parameter 1-30 Stator Resistance (Rs). divide the phase-to-phase value by 2 to achieve
7. Parameter 1-31 Rotor Resistance (Rr). the phase value.
It is also possible to measure the value with an
8. Parameter 1-33 Stator Leakage Reactance (X1). ohmmeter, which also takes the resistance of the
9. Parameter 1-35 Main Reactance (Xh). cable into account. Divide the measured value by
2 and enter the result.
The data is found in the motor datasheet (this data is
typically not available on the motor nameplate). Run a 2. Parameter 1-37 d-axis Inductance (Ld).
complete AMA using parameter 1-29 Automatic Motor Enter direct axis inductance of the PM motor.
Adaption (AMA) [1] Enable Complete AMA or enter the If only phase-to-phase data is available, divide the
parameters manually. phase-to-phase value by 2 to achieve the phase
value.
Application-specific adjustment when running VVC+ It is also possible to measure the value with an
inductance meter, which also takes the
VVC+ is the most robust control mode. In most situations,
inductance of the cable into account. Divide the
it provides optimum performance without further
measured value by 2 and enter the result.
adjustments. Run a complete AMA for best performance.
3. Parameter 1-38 q-axis Inductance (Lq).
5.5.2 PM Motor Set-up in VVC+ This parameter is active only when
parameter 1-10 Motor Construction is set to [3] PM,
salient IPM.
Initial programming steps
Enter the quadrature axis inductance of the PM
1. Set parameter 1-10 Motor Construction to the
motor. If only phase-to-phase data is available,
following options to activate PM motor operation:
divide the phase-to-phase value by 2 to achieve
1a [1] PM, non salient SPM the phase value.
1b [3] PM, salient IPM It is also possible to measure the value with an
inductance meter, which also takes the
2. Select [0] Open Loop in parameter 1-00 Configu- inductance of the cable into account. Make 1
ration Mode. rotation of the motor’s rotor and find the
NOTICE maximum phase-to-phase inductance value.
Encoder feedback is not supported for PM motors. Divide the value by 2 and enter the result.
4. Parameter 1-44 d-axis Inductance Sat. (LdSat).
Programming motor data This parameter is active only when
When the initial programming steps are completed, the PM parameter 1-10 Motor Construction is set to [3] PM,
motor-related parameters in parameter groups 1-2* Motor salient IPM.
Data, 1-3* Adv. Motor Data, and 1-4* Adv. Motor Data II are This parameter corresponds to the saturation
active. inductance of d-axis. The default value is the
The information is on the motor nameplate and in the value set in parameter 1-37 d-axis Inductance (Ld).
motor datasheet. Do not change the default value in most cases. If
the motor supplier provides the saturation curve,
It is highly recommended to run AMA because it measures Before running the frequency converter, check the motor
the electrical characteristics of the motor to optimize rotation.
compatibility between the frequency converter and the
motor in VVC+ mode. 1. Press [Hand On].
2. Press [▲] for positive speed reference.
• The frequency converter builds a mathematical
3. Check that the speed shown is positive.
model of the motor for regulating output motor
current, thus enhancing motor performance. 4. Verify that the wiring between the frequency
converter and the motor is correct.
• Some motors are unable to run the complete
version of the test. In that case, select Enable
reduced AMA (not for PM).
5. Verify that the motor running direction matches
the setting in parameter 1-06 Clockwise Direction.
5 5
• If warnings or alarms occur, see 5a When parameter 1-06 Clockwise Direction
chapter 7.3 Warning and Alarm Code List. is set to [0] Normal (default clockwise):
• Run this procedure on a cold motor for best a. Verify that the motor turns
results. clockwise.
To run AMA using the numeric LCP b. Verify that the LCP direction
1. By default parameter setting, connect terminals arrow is clockwise.
12 and 27 before running AMA. 5b When parameter 1-06 Clockwise Direction
2. Enter the Main Menu. is set to [1] Inverse (counterclockwise):
3. Go to parameter group 1-** Load and Motor. a. Verify that the motor turns
counterclockwise.
4. Press [OK].
b. Verify that the LCP direction
5. Set motor parameters using nameplate data for
arrow is counterclockwise.
parameter group 1-2* Motor Data.
6. Set parameter 1-39 Motor Poles for IM and PM. 5.7 Checking Encoder Rotation
7. Set parameter 1-40 Back EMF at 1000 RPM for PM. Only check encoder rotation if encoder feedback is used.
8. Set motor cable length in parameter 1-42 Motor
Cable Length. 1. Select [0] Open Loop in parameter 1-00 Configu-
ration Mode.
9. Go to parameter 1-29 Automatic Motor Adaptation
(AMA). 2. Select [1] 24 V encoder in parameter 7-00 Speed
PID Feedback Source.
10. Press [OK].
3. Press [Hand On].
11. Select [1] Enable complete AMA.
4. Press [▲] for positive speed reference
12. Press [OK].
(parameter 1-06 Clockwise Direction at [0] Normal).
13. Press [Hand On] to activate AMA.
5. Check in parameter 16-57 Feedback [RPM] that the
14. The test runs automatically and indicates when it feedback is positive.
is complete.
NOTICE
Depending on the power size, AMA takes 3–10 minutes to
complete.
NEGATIVE FEEDBACK
If the feedback is negative, the encoder connection is
wrong. Use parameter 5-71 Term 32/33 Encoder Direction
NOTICE to inverse the direction, or reverse the encoder cables.
The AMA function does not cause the motor to run, and
it does not harm the motor.
130BD650.10
The procedure in this section requires user-wiring and
application programming to be completed. The following
procedure is recommended after application set-up is 1
completed.
The functions of the LEDs and switches on the front panel The PROFIBUS decoupling kit contains parts that are
are introduced in Table 5.14. required for PROFIBUS to work. Install the kit after the
control cassette with PROFIBUS is installed. Illustration 5.13
LED/Switch Description and Illustration 5.14 show how to install the decoupling kit
NS2 Not used for PROFIBUS. on a frequency converter.
NS1 Indicates the network status when communi-
cating with the PROFIBUS master. When this
130BD616.10
indicator light shows constant green, data
exchange between the master and the frequency
converter is active.
MS Indicates the module status, which is acyclic DP
V1 communication from either a PROFIBUS
master class 1 (PLC) or a master class 2 (MCT-10
1 5 5
Set-up Software, FDT tool). When this indicator
light shows constant green, DP V1 communi-
cation from master classes 1 and 2 is active.
COM Communication status for RS485. Not used for
PROFIBUS.
Termination When the switch is turned on, the termination
resistor resistor is in effect.
switch
PROFIBUS Use the switches in the selector to set the
address PROFIBUS address. The address change comes
selector into effect at the next power-up.
NOTICE
Switch off the power supply before
changing the switches.
1 Screws
5.11 PROFINET
130BD617.10
VLT® AutomationDrive FC 360 frequency converters
1
130BE332.10
1
1 Screws
130BE308.10
5 5
6 Applications
130BC430.11
FC 360
When an application is selected, relevant parameters are
+24V 12
automatically set. Customer-specific configuration of all
DI1 18
parameters based on specific requirements is still
6 6
Start
DI2 19
possible.
DI3 27
NOTICE
DI4 29 Coast inverse
DI5 31
It is recommended to initialize the frequency converter DI6 32
via parameter 14-22 Operation Mode or 2-finger reset Jog
DI7 33
before setting parameter 0-16 Application Selection.
COM 20
+10V 50
NOTICE AI1 53 - +
4-20
If any of the applications are selected, relay 1 is set to AI2 54 mA
[Running] and relay 2 is set to [Alarm] automatically. COM 55
AO1 42
AO2 45
1
R1 2
3
4
R2 5
6
Parameter settings
Parameter Option/value
Parameter 1-00 Configuration Mode [3] Process Closed
Loop
Parameter 1-03 Torque Characteristics [1] Variable Torque
Parameter 3-00 Reference Range [0] Min- Max
Parameter 3-15 Reference 1 Source [0] No Function
Parameter 4-12 Motor Speed Low Limit [Hz] 30.0 Hz
Parameter 4-14 Motor Speed High Limit 50.0 Hz
[Hz]
Parameter 5-10 Terminal 18 Digital Input [8] Start
Parameter 5-12 Terminal 27 Digital Input [2] Coast Inverse
Parameter 5-14 Terminal 32 Digital Input [14] Jog
Parameter 5-40 Function Relay [5] Running
(Relay 1 Selection)
Parameter 5-40 Function Relay [9] Alarm
(Relay 2 Selection)
Parameter 6-22 Terminal 54 Low Current 4.0 mA
Parameter 6-23 Terminal 54 High Current 20.0 mA
Parameter 6-29 Terminal 54 mode [0] Current Mode
Parameter 6-70 Terminal 45 Mode [0] 0–20 mA
Parameter 6-71 Terminal 45 Analog Output [100] Output Parameter 5-10 Terminal 18 [8] Start [8] Start
frequency Digital Input
Parameter 6-90 Terminal 42 Mode [0] 0–20 mA Parameter 5-12 Terminal 27 [2] Coast Inverse [2] Coast
Parameter 6-91 Terminal 42 Analog Output [103] Motor Current Digital Input Inverse
Parameter 7-20 Process CL Feedback 1 [2] Analog input 54 Parameter 5-14 Terminal 32 [23] Set-up select [23] Set-up
Resource Digital Input select
Parameter 5-40 Function [5] Running [5] Running
Table 6.1 Process Closed Loop Relay (Relay 1 Selection)
Parameter 5-40 Function [9] Alarm [9] Alarm
Application Relay (Relay 2 Selection)
Local/remote.
Parameter 6-10 Terminal 53 0.07 V
Parameter 0-16 Application Selection is set to [2] Local/Remote.
Low Voltage
Description
Parameter 6-11 Terminal 53 10 V
For applications where the speed reference can be switched
High Voltage
between local potentiometer and remote current signal.
Parameter 6-19 Terminal 53 [1] Voltage Mode
6 6
130BC431.11
FC 360
mode
Parameter 6-22 Terminal 54 4.0 mA
+24V 12
Low Current
DI1 18 Start
Parameter 6-23 Terminal 54 20.0 mA
DI2 19
High Current
DI3 27
Parameter 6-29 Terminal 54 [0] Current
DI4 29 Coast inverse
mode Mode
DI5 31
Parameter 6-70 Terminal 45 [0] 0–20 mA [0] 0–20 mA
DI6 32
Setup select Mode
DI7 33
Parameter 6-71 Terminal 45 [100] Output [100] Output
COM 20
Analog Output frequency frequency
+10V 50
Parameter 6-90 Terminal 42 [0] 0–20 mA [0] 0–20 mA
AI1 53
4-20 Mode
AI2 54
- mA + Parameter 6-91 Terminal 42 [103] Motor Current [103] Motor
COM 55
Analog Output Current
AO1 4 2
AO2 45 Table 6.2 Local/Remote
1
R1 2
3
4
R2 5
6
Application Application
Conveyors, extruders. Machine tools, texturizers.
Parameter 0-16 Application Selection is set to [3] Speed Open Loop. Parameter 0-16 Application Selection is set to [4] Simple Speed
Description Closed Loop.
For running at a stable speed by a voltage reference signal. Description
For precise speed applications with 24 V encoder feedback.
FC 360 130BC432.11
130BC433.13
+24V 12 FC 360
6 6
DI7 33 DI6 32 B
COM 20 DI7 33 A
+10V 50 COM 20
AI1 53 +10 V 50
AI2 54 AI1 53
COM 55 AI2 54
AO1 42 COM 55
AO2 45 AO1 42
1 AO2 45
R1 2 1
3 R1 2
4 3
R2 5 4
6 R2 5
6
Parameter settings
Parameter Option/value Parameter settings
Parameter 1-00 Configuration Mode [0] Speed Open Loop Parameter Option/value
Parameter 3-00 Reference Range [0] Min–Max Parameter 1-00 Configuration Mode [1] Speed Close Loop
Parameter 3-15 Reference 1 Source [1] AI 53 Parameter 3-00 Reference Range [0] Min–Max
Parameter 4-12 Motor Speed Low Limit 25.0 Hz Parameter 3-15 Reference 1 Source [1] AI 53
[Hz] Parameter 3-16 Reference 2 Source [11] Local Bus Ref
Parameter 4-14 Motor Speed High Limit 50.0 Hz Parameter 4-12 Motor Speed Low Limit 20.0 Hz
[Hz] [Hz]
Parameter 5-10 Terminal 18 Digital Input [8] Start Parameter 4-14 Motor Speed High Limit 50.0 Hz
Parameter 5-12 Terminal 27 Digital Input [2] Coast Inverse [Hz]
Parameter 5-40 Function Relay (Relay 1 [5] Running Parameter 5-10 Terminal 18 Digital Input [8] Start
Selection) Parameter 5-12 Terminal 27 Digital Input [2] Coast Inverse
Parameter 5-40 Function Relay (Relay 2 [9] Alarm Parameter 5-14 Terminal 32 Digital Input [82] Encoder input B
Selection) Parameter 5-15 Terminal 33 Digital Input [81] Encoder input A
Parameter 6-10 Terminal 53 Low Voltage 0.07 V Parameter 5-40 Function Relay (Relay 1 [5] Running
Parameter 6-11 Terminal 53 High Voltage 10 V Selection)
Parameter 6-19 Terminal 53 mode [1] Voltage Mode Parameter 5-40 Function Relay (Relay 2 [9] Alarm
Parameter 6-70 Terminal 45 Mode [0] 0–20 mA Selection)
Parameter 6-71 Terminal 45 Analog [100] Output frequency Parameter 6-10 Terminal 53 Low Voltage 0.07 V
Output Parameter 6-11 Terminal 53 High Voltage 10 V
Parameter 6-90 Terminal 42 Mode [0] 0–20 mA Parameter 6-19 Terminal 53 mode [1] Voltage Mode
Parameter 6-91 Terminal 42 Analog [103] Motor Current Parameter 6-70 Terminal 45 Mode [0] 0–20 mA
Output Parameter 6-71 Terminal 45 Analog [100] Output frequency
Output
Table 6.3 Speed Open Loop
Parameter 6-90 Terminal 42 Mode [0] 0–20 mA
130BC434.11
FC 360
+24V 12
DI1 18 Start
DI2 19
Coast inverse
DI3 27
DI4 29 Pre set ref bit 0
DI5 31
6 6
DI6 32 Pre set ref bit 1
DI7 33 Pre set ref bit 2
COM 20
+10V 50
AI1 53
AI2 54
COM 55
AO1 42
AO2 45
1
R1 2
3
4
R2 5
6
Parameter settings
Parameter Option/value
Parameter 1-00 Configuration Mode [0] Speed Open Loop
Parameter 3-00 Reference Range [0] Min–Max
Parameter 3-15 Reference 1 Source [0] No Function
Parameter 4-14 Motor Speed High Limit 50.0 Hz
[Hz]
Parameter 5-10 Terminal 18 Digital Input [8] Start
Parameter 5-12 Terminal 27 Digital Input [2] Coast Inverse
Parameter 5-13 Terminal 29 Digital Input [16] Preset ref bit 0
Parameter 5-14 Terminal 32 Digital Input [17] Preset ref bit 1
Parameter 5-15 Terminal 33 Digital Input [18] Preset ref bit 2
Parameter 6-70 Terminal 45 Mode [0] 0–20 mA
Parameter 6-71 Terminal 45 Analog [100] Output frequency
Output
Parameter 6-90 Terminal 42 Mode [0] 0–20 mA
Parameter 6-91 Terminal 42 Analog [103] Motor Current
Output
6 6 DI6
DI7
32
33
Parameter 6-10 Terminal 53 Low Voltage
Parameter 6-11 Terminal 53 High Voltage
4.0 mA
20.0 mA
COM 20
Parameter 6-14 Terminal 53 Low Ref./ 0
+10V 50
4-20 Feedb. Value
AI1 53
- mA + Parameter 6-15 Terminal 53 High Ref./ 250
AI2 54
Feedb. Value
COM 55
Parameter 6-19 Terminal 53 mode [0] Current Mode
AO1 42
Parameter 14-01 Switching Frequency 10.0 kHz
AO2 45
Parameter 14-07 Dead Time Compen- 65
1
sation Level
R1 2
Parameter 14-64 Dead Time Compen- [0] Disabled
3
sation Zero Current Level
4
Parameter 14-65 Speed Derate Dead Time 250
R2 5
Compensation
6
Parameter 14-51 DC-Link Voltage Compen- [0] Off
Parameter settings sation
Parameter Option/value Parameter 30-20 High Starting Torque 0
Parameter 1-00 Configuration Mode [0] Open Loop Time [s]
Parameter 1-01 Motor Control Principle [1] VVC+ Parameter 30-21 High Starting Torque 100
Current [%]
Parameter 1-08 Motor Control Bandwidth High
Parameter 30-22 Locked Rotor Protection [0] Off
Parameter 1-10 Motor Construction [1] PM, non-salient SPM
Parameter 30-23 Locked Rotor Detection 1
Parameter 1-14 Damping Gain 120
Time [s]
Parameter 1-15 Low Speed Filter Time 0.175
Const.
Table 6.6 One Gear Drive (OGD) LA10
Parameter 1-16 High Speed Filter Time 0.175
Const.
Parameter 1-17 Voltage filter time const. 0.035
Parameter 1-24 Motor Current 7.2
Parameter 1-25 Motor Nominal Speed 3000
Parameter 1-26 Motor Cont. Rated Torque 12.6
Parameter 1-29 Automatic Motor [0] Off
Adaptation (AMA)
Parameter 1-30 Stator Resistance (Rs) 0.5
Parameter 1-37 d-axis Inductance (Ld) 5
Parameter 1-39 Motor Poles 10
Parameter 1-40 Back EMF at 1000 RPM 120
Parameter 1-42 Motor Cable Length 50 m
Parameter 1-66 Min. Current at Low Speed 50
Parameter 1-73 Flying Start [2] Enable always
Parameter 2-06 Parking Current 80
Parameter 1-01 Motor Control Principle [1] VVC+ Parameter 30-21 High Starting Torque 100
Current [%]
Parameter 1-08 Motor Control Bandwidth High
Parameter 30-22 Locked Rotor Protection [0] Off
Parameter 1-10 Motor Construction [1] PM, non-salient SPM
Parameter 30-23 Locked Rotor Detection 1
Parameter 1-14 Damping Gain 120
Time [s]
Parameter 1-15 Low Speed Filter Time 0.175
Const.
Table 6.7 One Gear Drive (OGD) V210
Parameter 1-16 High Speed Filter Time 0.175
Const.
Parameter 1-17 Voltage filter time const. 0.035
Parameter 1-24 Motor Current 5.50
Parameter 1-25 Motor Nominal Speed 3000
Parameter 1-26 Motor Cont. Rated Torque 13.0
Parameter 1-29 Automatic Motor [0] Off
Adaptation (AMA)
Parameter 1-30 Stator Resistance (Rs) 1.000
Parameter 1-37 d-axis Inductance (Ld) 13.800
Parameter 1-39 Motor Poles 10
Parameter 1-40 Back EMF at 1000 RPM 155
Parameter 1-42 Motor Cable Length 50 m
Parameter 1-66 Min. Current at Low Speed 50
Parameter 1-73 Flying Start [2] Enable always
Parameter 2-06 Parking Current 10
6 6 DI7
COM 20
33
+10V 50
AI1 53
AI2 54
COM 55
AO1 42
AO2 45
1
R1 2
Mechanical brake
3
control
4
R2 5
6
Parameter settings
Parameter Option/value
Parameter 1-01 Motor Control Principle [1] VVC+
Parameter 1-71 Start Delay 0.2
Parameter 1-72 Start Function [4] Horizontal operation
Parameter 1-73 Flying Start [0] Disabled
Parameter 1-76 Start Current 50% of
parameter 1-24 Motor
Current
Parameter 2-00 DC Hold/Motor Preheat 50%
Current
Parameter 2-10 Brake Function [1] Resistor brake
Parameter 2-17 Over-voltage Control [0] Disabled
Parameter 2-20 Release Brake Current 0
Parameter 2-22 Activate Brake Speed [Hz] Parameter 1-23 Motor
Frequency -
parameter 1-25 Motor
Nominal Speed x
parameter 1-39 Motor
Poles/120
Parameter 2-23 Activate Brake Delay 0.1
Parameter 2-39 Mech. Brake w/ dir. [1] On
Change
Parameter 3-41 Ramp 1 Ramp Up Time 1
Parameter 3-42 Ramp 1 Ramp Down Time 1
Parameter 3-51 Ramp 2 Ramp Up Time 1
6 6
DI6 32
Parameter 4-30 Motor Feedback Loss [2] Trip
DI7 33
Function
COM 20
Parameter 4-31 Motor Feedback Speed 5
+10V 50
Error
AI1 53
Parameter 5-13 Terminal 29 Digital Input [0] No operation
AI2 54
Parameter 5-40 Function Relay [32] Mech brake ctrl
COM 55
Parameter 14-24 Trip Delay at Current 2
AO1 42
Limit
AO2 45
Parameter 14-25 Trip Delay at Torque 2
1
Limit
R1 2
Mechanical brake
3 Table 6.9 Hoist Speed Close Loop
control
4
R2 5
6
Parameter settings
Parameter Option/value
Parameter 1-00 Configuration Mode [1] Speed closed loop
Parameter 1-01 Motor Control Principle [1] VVC+
Parameter 1-71 Start Delay 0.2
Parameter 1-72 Start Function [3] Start speed cw
Parameter 1-73 Flying Start [0] Disabled
Parameter 1-75 Start Speed [Hz] 90% of nominal slip
frequency
Parameter 1-76 Start Current 80% of
parameter 1-24 Motor
Current
Parameter 2-10 Brake Function [1] Resistor brake
Parameter 2-17 Over-voltage Control [0] Disabled
Parameter 2-20 Release Brake Current 0
Parameter 2-22 Activate Brake Speed [Hz] Parameter 1-23 Motor
Frequency -
parameter 1-25 Motor
Nominal Speed x
parameter 1-39 Motor
Poles/120
Parameter 2-23 Activate Brake Delay 0.3
Parameter 2-24 Stop Delay 0.2
Parameter 2-25 Brake Release Time 0.5
Parameter 2-31 Speed PID Start Propor- 0.15
tional Gain
130BF818.10
The examples in this section are intended as a quick FC
Parameter 6-10 T
reference for common applications. +24 V 12 erminal 53 Low *0.07 V
D IN 18 Voltage
• Parameter settings are the regional default values D IN 19 Parameter 6-11 T
unless otherwise indicated (selected in D IN 27
erminal 53 High *10 V
D IN 29
parameter 0-03 Regional Settings). Voltage
D IN 31
• Parameters associated with the terminals and D IN 32
Parameter 6-14 T
their settings are shown next to the drawings. 33
erminal 53 Low *0
D IN
Ref./Feedb. Value
• Required switch settings for analog terminals 53
Parameter 6-15 T
or 54 are also shown.
6 6 +10 V
A IN
50
53
+
erminal 53 High 50 Hz
Ref./Feedb. Value
6.2.2 AMA A IN 54 Parameter 6-19 T
*[1] Voltage
COM 55 erminal 53 mode
Parameters -
A OUT 42 *=Default value
0 ~10 V
Function Setting Notes/comments:
130BF817.10
FC
Parameter 1-29 A
+24 V 12 [1] Enable
utomatic Motor
D IN 18 complete
Adaptation
D IN 19 AMA
(AMA) Table 6.11 Analog Speed Reference (Voltage)
D IN 27
D IN 29
Parameter 5-12 T
*[2] Coast
D IN 31 erminal 27 Parameters
inverse
D IN 32 Digital Input 130BF819.10 Function Setting
D IN 33 *=Default value FC Parameter 6-22 T
Notes/comments: Set +24 V 12 erminal 54 Low *4 mA
parameter group 1-2* Motor D IN 18 Current
Data according to motor D IN 19
+10 V 50 Parameter 6-23 T
D IN 27
A IN 53 specifications. erminal 54 High *20 mA
NOTICE D IN 29
A IN 54 Current
D IN 31
COM 55 Parameter 6-24 T
If terminals 12 and 27 are D IN 32
A OUT 42 erminal 54 Low *0
not connected, set D IN 33
parameter 5-12 Terminal 27 Ref./Feedb. Value
Digital Input to [0] No Parameter 6-25 T
operation. erminal 54 High 50 Hz
+10 V 50
A IN
+ Ref./Feedb. Value
53
A IN 54 Parameter 6-29 T
[0] Current
Table 6.10 AMA with T27 Connected COM 55 erminal 54 mode
-
A OUT 42 *=Default value
4 - 20mA
Notes/comments:
Parameters Speed
130BB840.12
Function Setting Reference
130BF820.10
FC
Parameter 6-10 T
+24 V 12
erminal 53 Low *0.07 V
D IN 18
Voltage Start (18)
D IN 19
D IN 27 Parameter 6-11 T Freeze ref (27)
6 6
A IN 54 Parameter 6-19 T
*[1] Voltage Parameters
COM 55 erminal 53 mode
Function Setting
130BF822.10
A OUT 42 *=Default value FC
+24 V 12 Parameter 5-10 Ter
Notes/comments:
D IN 18 minal 18 Digital *[8] Start
D IN 19 Input
D IN 27 Parameter 5-11 Ter
D IN 29 *[10]
Table 6.13 Speed Reference (Using a Manual Potentiometer) minal 19 Digital
D IN 31 Reversing
Input
D IN 32
Parameters Parameter 5-12 Ter [0] No
D IN 33
Function Setting minal 27 Digital operation
130BF821.10
FC
Parameter 5-10 T Input
+24 V 12
erminal 18 *[8] Start Parameter 5-14 Ter [16] Preset
D IN 18 +10 V 50
Digital Input A IN minal 32 Digital ref bit 0
D IN 19 53
D IN 27 Parameter 5-12 T [19] Freeze A IN 54 Input
D IN 29 erminal 27 Reference COM 55 Parameter 5-15 Ter [17] Preset
D IN 31 Digital Input A OUT 42 minal 33 Digital ref bit 1
D IN 32 Parameter 5-13 T [21] Speed Up Input
D IN 33 erminal 29 Parameter 3-10 Pre
Digital Input set Reference
Parameter 5-14 T [22] Speed Preset ref. 0 25%
+10 V 50 erminal 32 Down Preset ref. 1 50%
A IN 53 Digital Input Preset ref. 2 75%
A IN 54 *=Default value Preset ref. 3 100%
COM 55 Notes/comments: *=Default value
A OUT 42 Notes/comments:
Parameters
Function Setting
130BF823.10
FC
Parameter 5-11 T
+24 V 12
erminal 19 [1] Reset
D IN 18
19
Digital Input
D IN
D IN 27 *=Default value
D IN 29 Notes/comments:
D IN 31
D IN 32
D IN 33
6 6 +10 V
A IN
50
53
A IN 54
COM 55
A OUT 42
NOTICE
To meet PELV insulation requirements, use reinforced or
double insulation on the thermistors.
Parameters
Function Setting
130BF824.10
FC
Parameter 1-90 [2] Thermistor
+24 V 12
Motor Thermal trip
D IN 18
Protection
D IN 19
Parameter 1-93 T [1] Analog
D IN 27
hermistor Source input 53
D IN 29
D IN 31 Parameter 6-19 T
D IN 32 erminal 53 mode *[1] Voltage
D IN 33
* = Default value
+10 V 50 Notes/comments:
A IN 53 If only a warning is needed, set
A IN 54 parameter 1-90 Motor Thermal
COM 55 Protection to [1] Thermistor
A OUT 42 warning.
7.1 Warning and Alarm Types 7.2 Warning and Alarm Displays
Warning/ Description
Setup 1
130BD111.10
alarm type
Warning A warning indicates an abnormal operating
condition that might lead to an alarm. A warning
stops when the abnormal condition is removed.
Alarm An alarm indicates a fault that requires Status Quick Main
Menu Menu
immediate attention. The fault always triggers a
Illustration 7.1 Warning Display
trip or trip lock. Reset the frequency converter
after an alarm.
Reset the frequency converter in any of 4 ways:
An alarm or trip lock alarm shows in the display along with
• Press [Reset]/[Off/Reset].
the alarm number.
• Digital reset input command.
130BD112.10
• Auto reset.
Trip
When tripping, the frequency converter suspends Status Quick Main
operation to prevent damage to the frequency converter Menu Menu
and other equipment. When a trip occurs, the motor coasts Illustration 7.2 Alarm/Trip Lock Alarm
to a stop. The frequency converter logic continues to
operate and monitor the frequency converter status. After
the fault condition is remedied, the frequency converter is In addition to the text and alarm code on the frequency
ready for a reset. converter display, there are 3 status indicator lights. The
Trip lock warning indicator light is yellow during a warning. The
When trip locking, the frequency converter suspends alarm indicator light is red and flashing during an alarm.
operation to prevent damage to the frequency converter
and other equipment. When a trip lock occurs, the motor
130BD062.10
coasts to a stop. The frequency converter logic continues On OK
to operate and monitor the frequency converter status.
The frequency converter starts a trip lock only when Warn
serious faults occur that can damage the frequency Alarm
converter or other equipment. After the faults are fixed,
cycle the input power before resetting the frequency
D Hand Auto
converter. On Reset On
Num-
Description Warning Alarm Trip lock Cause
ber
Signal on terminal 53 or 54 is less than 50% of value set
in parameter 6-10 Terminal 53 Low Voltage,
2 Live zero error X X – parameter 6-12 Terminal 53 Low Current,
parameter 6-20 Terminal 54 Low Voltage, and
parameter 6-22 Terminal 54 Low Current.
No motor has been connected to the output of the
3 No motor X – –
frequency converter, or 1 motor phase is missing.
Missing phase on supply side, or the voltage imbalance is
4 Mains phase loss1) X X X
too high. Check the supply voltage.
7 DC overvoltage1) X X – Intermediate circuit voltage exceeds limit.
Intermediate circuit voltage drops below the voltage
8 DC undervoltage1) X X –
7 7 9 Inverter overloaded X X –
warning low limit.
More than 100% load for too long.
Motor is too hot due to more than 100% load for too
10 Motor ETR overtemperature X X –
long.
Motor thermistor overtem-
11 X X – Thermistor or thermistor connection is disconnected.
perature
Torque exceeds value set in either parameter 4-16 Torque
12 Torque limit X X – Limit Motor Mode or parameter 4-17 Torque Limit Generator
Mode.
Inverter peak current limit is exceeded. For J1–J6 units, if
13 Overcurrent X X X this alarm occurs on power-up, check whether power
cables are mistakenly connected to the motor terminals.
14 Earth fault – X X Discharge from output phases to ground.
Short circuit in motor or on motor terminals. For J7 units,
16 Short circuit – X X if this alarm occurs on power-up, check whether power
cables are mistakenly connected to the motor terminals.
17 Control word timeout X X – No communication to frequency converter.
18 Start failed – X – –
Brake resistor is short-circuited, thus the brake function is
25 Brake resistor short-circuited – X X
disconnected.
The power transmitted to the brake resistor over the last
26 Brake overload X X – 120 s exceeds the limit. Possible corrections: Decrease
brake energy via lower speed or longer ramp time.
Brake IGBT/Brake chopper short- Brake transistor is short-circuited, thus brake function is
27 – X X
circuited disconnected.
28 Brake check – X – Brake resistor is not connected/working.
30 U phase loss – X X Motor phase U is missing. Check the phase.
31 V phase loss – X X Motor phase V is missing. Check the phase.
32 W phase loss – X X Motor phase W is missing. Check the phase.
34 Fieldbus fault X X – PROFIBUS communication issues have occurred.
35 Option fault – X – Fieldbus or option B detects internal faults.
This warning/alarm is only active if the supply voltage to
36 Mains failure X X – the frequency converter is lost and parameter 14-10 Mains
Failure is NOT set to [0] No Function.
38 Internal fault – X X Contact the local Danfoss supplier.
Check the load connected to terminal 27 or remove
40 Overload T27 X – –
short-circuit connection.
Num-
Description Warning Alarm Trip lock Cause
ber
Check the load connected to terminal 29 or remove
41 Overload T29 X – –
short-circuit connection.
46 Gate drive voltage fault – X X –
47 24 V supply low X X X 24 V DC may be overloaded.
50 AMA calibration – X – –
51 AMA check Unom and Inom – X – Wrong setting for motor voltage and/or motor current.
52 AMA low Inom – X – Motor current is too low. Check the settings.
The power size of the motor is too large for the AMA to
53 AMA big motor – X –
operate.
The power size of the motor is too small for the AMA to
54 AMA small motor – X –
operate.
The parameter values of the motor are outside of the
55 AMA parameter range – X –
acceptable range. AMA does not run.
56 AMA interrupt – X – The AMA is interrupted.
57 AMA timeout – X – –
58 AMA internal – X – Contact Danfoss.
7 7
59 Current limit X X – Frequency converter overload.
60 External Interlock – X – –
61 Encoder loss X X – –
Actual motor current has not exceeded release brake
63 Mechanical brake low – X –
current within start delay time window.
The cutout temperature of the control card is 80 °C
65 Control card temp X X X
(176 °F).
69 Power card temp X X X –
70 Illegal FC config – X X –
Frequency converter initialized
80 – X – All parameter settings are initialized to default settings.
to default value
Occurs in IT mains when the frequency converter coasts
and the DC voltage is higher than 830 V. Energy on DC-
87 Auto DC brake X – –
link is consumed by the motor. This function can be
enabled/disabled in parameter 0-07 Auto DC Braking.
90 Feedback monitor X X – A feedback fault is detected by option B.
95 Broken belt X X – –
99 Locked rotor – X – –
Flow/pressure information
101 – X X –
missing
120 Position control fault – X – –
124 Tension limit – X – –
126 Motor rotating – X – –
Try to start PM motor which is rotating in an abnormal
127 Back EMF too high2) X – –
high speed.
250 New spare part – X X –
251 New type code – X X –
For diagnosis, read out the alarm words, warning words, and extended status words.
000000
0 1 Brake check Reserved Reserved Reserved Reserved Ramping Off
01
000000 Pwr. card Gate drive Pwr. card
1 2 Reserved Reserved AMA tuning Hand/Auto
02 temp voltage fault temp
000000 PROFIBUS OFF1
2 4 Earth fault Reserved Reserved Reserved Reserved Start CW/CCW
04 active
000000 Ctrl. card PROFIBUS OFF2
3 8 Reserved Reserved Ctrl. card temp Reserved Slowdown
08 temp active
000000 Ctrl. word Illegal FC PROFIBUS OFF3
4 16 Reserved Ctrl. word TO Reserved Catch up
7 7 5
10
000000
32
TO
Overcurrent
config
Reserved
20
000000
6 64 Torque limit Reserved Reserved Torque limit Reserved Feedback low Reserved
40
000000 Motor Th. Output current
7 128 Reserved Reserved Motor Th. over Reserved Control ready
80 over high
000001 Motor ETR Motor ETR Output current Frequency converter
8 256 Broken belt Reserved Broken belt
00 over over low ready
000002 Inverter Output freq.
9 512 Reserved Reserved Inverter overld. Reserved Quick stop
00 overld. high
000004 DC Output freq.
10 1024 Start failed Reserved DC undervolt. Reserved DC brake
00 undervolt. low
000008
11 2048 DC overvolt. Reserved Reserved DC overvolt. Reserved Brake check OK Stop
00
000010 External
12 4096 Short circuit Reserved Reserved Reserved Braking max Latched
00 interlock
000020
13 8192 Reserved Reserved Reserved Reserved Reserved Braking Reserved
00
000040 Mains ph.
14 16384 Reserved Reserved Mains ph. loss Reserved Reserved Freeze output
00 loss
000080
15 32768 AMA not OK Reserved Reserved No motor Auto DC brake OVC active Reserved
00
000100 Live zero
16 65536 Reserved Reserved Live zero error Reserved AC brake Jog
00 error
000200
17 131072 Internal fault Reserved Reserved Reserved Reserved Reserved Reserved
00
000400 Brake Brake resistor
18 262144 Reserved Reserved Reserved Reserved Start
00 overload power limit
000800
19 524288 U phase loss Reserved Reserved Reserved Reserved Reference high Reserved
00
001000 Option
20 1048576 V phase loss Reserved Reserved Overload T27 Reference low Start delay
00 detection
002000
21 2097152 W phase loss Option fault Reserved Reserved Reserved Reserved Sleep
00
004000 Fieldbus
22 4194304 Locked rotor Reserved Fieldbus fault Reserved Reserved Sleep boost
00 fault
7 7
27 Brake IGBT Reserved Reserved Reserved Reserved Reserved Reserved
00 8
100000 26843545 Option Feedback
28 Reserved Encoder loss Reserved Reserved FlyStart active
00 6 change fault
Frequency
200000 53687091 Back EMF too Heat sink clean
29 converter Encoder loss Reserved Reserved Reserved
00 2 high warning
initialized
400000 10737418
30 Reserved Reserved Reserved Reserved Reserved Reserved Reserved
00 24
800000 21474836 Mech. brake
31 Reserved Reserved Reserved Reserved Database busy Reserved
00 48 low
Table 7.2 Description of Alarm Word, Warning Word, and Extended Status Word
7 7 Err 93
donE
The LCP copy operation cannot be conducted when the frequency converter is running.
A notification that the LCP Copy process is finished.
NWrun The parameter cannot be changed while the frequency converter is running.
Err. The password that is input via the LCP is incorrect.
7.5 Troubleshooting
Symptom Possible cause Test Solution
Press [Auto On] or [Hand On]
LCP stop Check if [Off] has been pressed. (depending on operating mode) to
run the motor.
Check parameter 5-10 Terminal 18
Apply a valid start signal to start the
Missing start signal (standby) Digital Input of correct setting for
motor.
terminal 18 (use default setting).
Check parameter 5-12 Terminal 27 Apply 24 V on terminal 27 or
Motor coast signal active (coasting) Digital Input for correct setting of program this terminal to [0] No
Motor not running terminal 27 (use default setting). operation.
Check the following:
• Is the reference signal local,
remote, or bus reference? Program correct settings. Set preset
reference active in parameter group
Wrong reference signal source
• Is preset reference active?
3-1* References. Check for correct
• Is terminal connection correct? wiring. Check scaling of terminals.
• Is the scaling of terminals correct? Check reference signal.
8 Specifications
Frequency converter typical H11K H15K H18K H22K H30K H37K H45K H55K H75K
shaft output [kW (hp)] 11 15 18.5 22 30 37 45 55 75
(15) (20) (25) (30) (40) (50) (60) (75) (100)
Enclosure protection rating
J4 J4 J5 J5 J6 J6 J6 J7 J7
IP20
Output current
Continuous (3x380–440 V) [A] 23 31 37 42.5 61 73 90 106 147
Continuous (3x441–480 V) [A] 21 27 34 40 52 65 77 96 124
Intermittent (60 s overload) [A] 34.5 46.5 55.5 63.8 91.5 109.5 135 159 220.5
Continuous kVA (400 V AC)
15.94 21.48 25.64 29.45 42.3 50.6 62.4 73.4 101.8
[kVA]
Continuous kVA (480 V AC)
17.5 22.4 28.3 33.3 43.2 54.0 64.0 79.8 103.1
[kVA]
Maximum input current
Continuous (3x380–440 V) [A] 22.1 29.9 35.2 41.5 57 70.3 84.2 102.9 140.3
Continuous (3x441–480 V) [A] 18.4 24.7 29.3 34.6 49.3 60.8 72.7 88.8 121.1
Intermittent (60 s overload) [A] 33.2 44.9 52.8 62.3 85.5 105.5 126.3 154.4 210.5
Additional specifications
Maximum cable size (mains,
16 (6) 50 (1/0) 95 (3/0)
motor, brake) [mm2 (AWG)]
Estimated power loss at rated
maximum load [W]2)
289.53 393.36 402.83 467.52 630 848 1175 1250 1507 8 8
Weight [kg (lb)], enclosure 12.3 12.5 22.4 22.5
9.4 (20.7) 9.5 (20.9) 22.6 (49.8) 37.3 (82.2) 38.7 (85.3)
protection rating IP20 (27.1) (27.6) (49.4) (49.6)
Efficiency [%]3) 97.8 97.8 98.1 97.9 98.1 98.0 97.7 98.0 98.2
Frequency converter typical Q11K Q15K Q18K Q22K Q30K Q37K Q45K Q55K Q75K
shaft output [kW (hp)] 11 15 18.5 22 30 37 45 55 75
(15) (20) (25) (30) (40) (50) (60) (75) (100)
Enclosure protection rating
J4 J4 J5 J5 J6 J6 J6 J7 J7
IP20
Output current
Continuous (3x380–440 V)
23 31 37 42.5 61 73 90 106 147
[A]
Continuous (3x441–480 V)
21 27 34 40 52 65 77 96 124
[A]
Intermittent (60 s overload)
25.3 34.1 40.7 46.8 67.1 80.3 99 116.6 161.7
[A]
Continuous kVA (400 V AC)
15.94 21.48 25.64 29.45 42.3 50.6 62.4 73.4 101.8
[kVA]
Continuous kVA (480 V AC)
17.5 22.4 28.3 33.3 43.2 54.0 64.0 79.8 103.1
[kVA]
Maximum input current
Continuous (3x380–440 V)
22.1 29.9 35.2 41.5 57 70.3 84.2 102.9 140.3
[A]
Continuous (3x441–480 V)
18.4 24.7 29.3 34.6 49.3 60.8 72.7 88.8 121.1
8 8 [A]
Intermittent (60 s overload)
24.3 32.9 38.7 45.7 62.7 77.3 92.6 113.2 154.3
[A]
Additional specifications
Maximum cable size (mains,
16 (6) 50 (1/0) 95 (3/0)
motor, brake) [mm2 (AWG)]
Estimated power loss at
289.53 393.36 402.83 467.52 630 848 1175 1250 1507
rated maximum load [W]2)
Weight [kg (lb)], enclosure 22.5 22.6 37.3
9.4 (20.7) 9.5 (20.9) 12.3 (27.1) 12.5 (27.6) 22.4 (49.4) 38.7 (85.3)
protection rating IP20 (49.6) (49.8) (82.2)
Efficiency [%]3) 97.8 97.8 98.1 97.9 98.1 98.0 97.7 98.0 98.2
2) The typical power loss is at nominal load conditions and expected to be within ±15% (tolerance relates to variety in voltage and
cable conditions).
Values are based on a typical motor efficiency (IE2/IE3 border line). Motors with lower efficiency add to the power loss in the frequency
converter and motors with high efficiency reduce power loss.
Applies to dimensioning of frequency converter cooling. If the switching frequency is higher than the default setting, the power losses
may rise. LCP and typical control card power consumptions are included. Further options and customer load may add up to 30 W to the
losses (though typically only 4 W extra for a fully loaded control card, fieldbus, or options for slot B).
For power loss data according to EN 50598-2, refer to www.danfoss.com/vltenergyefficiency.
3) Measured using 5 m shielded motor cables at rated load and rated frequency for enclosure sizes J1–J5, and using 33 m shielded
motor cables at rated load and rated frequency for enclosure sizes J6 and J7. For energy efficiency class, see the Ambient Conditions
section in chapter 8 Specifications. For part load losses, see www.danfoss.com/vltenergyefficiency.
Torque characteristics
Starting torque (high overload) Maximum 160% for 60 s1)2)
Overload torque (high overload) Maximum 160% for 60 s1)2)
Starting torque (normal overload) Maximum 110% for 60 s1)2)
Overload torque (normal overload) Maximum 110% for 60 s1)2)
Starting current Maximum 200% for 1 s
Torque rise time in VVC+ (independent of fsw) Maximum 50 ms
1) Percentage relates to the nominal torque. It is 150% for 11–75 kW (15–100 hp) frequency converters.
2) Once every 10 minutes.
Digital inputs
Programmable digital inputs 7
Terminal number 18, 19, 271), 291),31, 32, 33
Logic PNP or NPN
Voltage level 0–24 V DC
Voltage level, logic 0 PNP < 5 V DC
Voltage level, logic 1 PNP > 10 V DC
Voltage level, logic 0 NPN > 19 V DC
Voltage level, logic 1 NPN < 14 V DC
Maximum voltage on input 28 V DC
Pulse frequency range 4 Hz–32 kHz
(Duty cycle) minimum pulse width 4.5 ms
Analog inputs
Number of analog inputs 2
Terminal number 53, 54
Modes Voltage or current
Mode select Software
Voltage level 0–10 V
Input resistance, Ri Approximately 10 kΩ
Maximum voltage -15 to +20 V
Current level 0/4 to 20 mA (scaleable)
Input resistance, Ri Approximately 200 Ω
Maximum current 30 mA
Resolution for analog inputs 11 bit
Accuracy of analog inputs Maximum error 0.5% of full scale
Bandwidth 100 Hz
The analog inputs are galvanically isolated from the supply voltage (PELV) and other high-voltage terminals.
130BD310.10
PELV isolation
8 8 +24 V
18
Control Mains
High
voltage Motor
31
Functional
isolation
RS-485 DC Bus
NOTICE
HIGH ALTITUDE
For installation at altitudes above 2000 m (6562 ft), contact Danfoss hotline regarding PELV.
Pulse inputs
Programmable pulse inputs 2
Terminal number pulse 29, 33
Maximum frequency at terminal 29, 33 32 kHz (push-pull driven)
Maximum frequency at terminal 29, 33 5 kHz (open collector)
Minimum frequency at terminal 29, 33 4 Hz
Voltage level See the section on digital input
Maximum voltage on input 28 V DC
Input resistance, Ri Approximately 4 kΩ
Pulse input accuracy Maximum error: 0.1% of full scale
Analog outputs
Number of programmable analog outputs 2
Terminal number 45, 42
Current range at analog output 0/4–20 mA
Maximum resistor load to common at analog output 500 Ω
Accuracy on analog output Maximum error: 0.8% of full scale
Resolution on analog output 10 bit
The analog output is galvanically isolated from the supply voltage (PELV) and other high-voltage terminals.
Digital outputs
Programmable digital/pulse outputs 2
Terminal number 27, 291)
Voltage level at digital/frequency output 0–24 V
Maximum output current (sink or source) 40 mA
Maximum load at frequency output 1 kΩ
Maximum capacitive load at frequency output 10 nF
Minimum output frequency at frequency output 4 Hz
Maximum output frequency at frequency output 32 kHz
Accuracy of frequency output Maximum error: 0.1% of full scale
Resolution of frequency output 10 bit
1) Terminal 27 and 29 can also be programmed as input.
The digital output is galvanically isolated from the supply voltage (PELV) and other high-voltage terminals.
Relay outputs
Programmable relay outputs 2
Relay 01 and 02 01–03 (NC), 01–02 (NO), 04–06 (NC), 04–05 (NO)
Maximum terminal load (AC-1)1) on 01–02/04–05 (NO) (Resistive load) 250 V AC, 3 A
Maximum terminal load (AC-15)1) on 01–02/04–05 (NO) (Inductive load @ cosφ 0.4) 250 V AC, 0.2 A
Maximum terminal load (DC-1)1) on 01–02/04–05 (NO) (Resistive load) 30 V DC, 2 A
1)
Maximum terminal load (DC-13) on 01–02/04–05 (NO) (Inductive load) 24 V DC, 0.1 A
Maximum terminal load (AC-1)1) on 01–03/04–06 (NC) (Resistive load) 250 V AC, 3 A
Maximum terminal load (AC-15)1)on 01–03/04–06 (NC) (Inductive load @ cosφ 0.4) 250 V AC, 0.2 A
Maximum terminal load (DC-1)1) on 01–03/04–06 (NC) (Resistive load) 30 V DC, 2 A
Minimum terminal load on 01–03 (NC), 01–02 (NO) 24 V DC 10 mA, 24 V AC 20 mA
1) IEC 60947 t 4 and 5.
The relay contacts are galvanically isolated from the rest of the circuit by reinforced isolation.
The relays can be used on different loads (resistive load or inductive load) with different life cycles. The life cycle depends on the
configuration of the specific load.
Control characteristics
Resolution of output frequency at 0–500 Hz ±0.003 Hz
System response time (terminals 18, 19, 27, 29, 32, and 33) ≤2 ms
Speed control range (open loop) 1:100 of synchronous speed
Speed accuracy (open loop) ±0.5% of nominal speed
Speed accuracy (closed loop) ±0.1% of nominal speed
All control characteristics are based on a 4-pole asynchronous motor.
Ambient conditions
Enclosure sizes J1–J7 IP20
Vibration test, all enclosure sizes 1.0 g
Relative humidity 5–95% (IEC 721-3-3); Class 3K3 (non-condensing) during operation
Aggressive environment (IEC 60068-2-43) H2S test Class Kd
Test method according to IEC 60068-2-43 H2S (10 days)
Ambient temperature (at 60 AVM switching mode)
- with derating Maximum 55 °C (131 °F) 1)2)
- at full continuous output current with some power size Maximum 50 °C (122 °F)
- at full continuous output current Maximum 45 °C (113 °F)
Minimum ambient temperature during full-scale operation 0 °C (32 °F)
Minimum ambient temperature at reduced performance -10 °C (14 °F)
Temperature during storage/transport -25 to +65/70 °C (-13 to +149/158 °F)
Maximum altitude above sea level without derating 1000 m (3281 ft)
Maximum altitude above sea level with derating 3000 m (9843 ft)
EN 61800-3, EN 61000-3-2, EN 61000-3-3, EN 61000-3-11,
EMC standards, emission EN 61000-3-12, EN 61000-6-3/4, EN 55011, IEC 61800-3
EN 61800-3, EN 61000-6-1/2, EN 61000-4-2,
EMC standards, immunity EN 61000-4-3, EN 61000-4-4, EN 61000-4-5, EN 61000-4-6
Energy efficiency class3) IE2
NOTICE
Using fuses or circuit breakers is mandatory to ensure
compliance with IEC 60364 for CE.
8 8 J7 75 (100) 14 (123.9) 14 (123.9) 14 (123.9) – 1.6 (14.2) 0.44 (3.89) 0.5 (4.4)
9 Appendix
Conventions
• For illustrations, all dimensions are in [mm (in)].
• An asterisk (*) indicates the default setting of a parameter.
• Numbered lists indicate procedures.
• Bullet lists indicate other information.
• Italicized text indicates:
- Cross-reference.
- Link.
- Parameter name.
68
0-0* Basic Settings [748] PCD Feed Forward [1890] Process PID Error [34] t/h 0-6* Password
0-01 Language [953] Profibus Warning Word [1891] Process PID Output [40] m/s 0-60 Main Menu Password
*[0] English [1501] Running Hours [1892] Process PID Clamped Output [41] m/min 0 - 999 *0
Appendix
[10] Chinese [1502] kWh Counter [1893] Process PID Gain Scaled Output [45] m 1-** Load and Motor
[28] Bras.port [1600] Control Word [2117] Ext. 1 Reference [Unit] [60] °C 1-0* General Settings
0-03 Regional Settings [1601] Reference [Unit] [2118] Ext. 1 Feedback [Unit] [70] mbar 1-00 Configuration Mode
*[0] International *[1602]Reference [%] [2119] Ext. 1 Output [%] [71] bar *[0] Open Loop
[1] North America [1603] Status Word [3401] PCD 1 Write For Application [72] Pa [1] Speed closed loop
0-04 Operating State at Power-up [1605] Main Actual Value [%] [3402] PCD 2 Write For Application [73] kPa [2] Torque closed loop
[0] Resume [1609] Custom Readout [3403] PCD 3 Write For Application [74] m WG [3] Process Closed Loop
*[1] Forced stop, ref=old [1610] Power [kW] [3404] PCD 4 Write For Application [80] kW [4] Torque open loop
[2] Forced stop, ref=0 [1611] Power [hp] [3405] PCD 5 Write For Application [120] GPM [6] Surface Winder
0-06 GridType [1612] Motor Voltage [3406] PCD 6 Write For Application [121] gal/s [7] Extended PID Speed OL
[10] 380-440V/50Hz/IT-grid [1613] Frequency [3407] PCD 7 Write For Application [122] gal/min 1-01 Motor Control Principle
[11] 380-440V/50Hz/Delta [1614] Motor current [3408] PCD 8 Write For Application [123] gal/h [0] U/f
[12] 380-440V/50Hz [1615] Frequency [%] [3409] PCD 9 Write For Application [124] CFM *[1] VVC+
[20] 440-480V/50Hz/IT-grid [1616] Torque [Nm] [3410] PCD 10 Write For Application [127] ft³/h 1-03 Torque Characteristics
[21] 440-480V/50Hz/Delta [1617] Speed [RPM] [3421] PCD 1 Read For Application [140] ft/s *[0] Constant torque
[22] 440-480V/50Hz [1618] Motor Thermal [3422] PCD 2 Read For Application [141] ft/min [1] Variable Torque
[110] 380-440V/60Hz/IT-grid [1622] Torque [%] [3423] PCD 3 Read For Application [160] °F [2] Auto Energy Optim. CT
[111] 380-440V/60Hz/Delta [1630] DC Link Voltage [3424] PCD 4 Read For Application [170] psi 1-06 Clockwise Direction
[112] 380-440V/60Hz [1633] Brake Energy /2 min [3425] PCD 5 Read For Application [171] lb/in2 *[0] Normal
[120] 440-480V/60Hz/IT-grid [1634] Heatsink Temp. [3426] PCD 6 Read For Application [172] in WG [1] Inverse
[121] 440-480V/60Hz/Delta [1635] Inverter Thermal [3427] PCD 7 Read For Application [173] ft WG 1-08 Motor Control Bandwidth
[122] 440-480V/60Hz [1636] Inv. Nom. Current [3428] PCD 8 Read For Application [180] HP [0] High
0-07 Auto DC Braking [1637] Inv. Max. Current [3429] PCD 9 Read For Application 0-31 Custom Readout Min Value [1] Medium
[0] Off [1638] SL Controller State [3430] PCD 10 Read For Application 0 - 999999.99 CustomReadoutUnit *0 [2] Low
*[1] On [1639] Control Card Temp. [3450] Actual Position CustomReadoutUnit [3] Adaptive 1
0-1* Set-up Operations [1650] External Reference [3456] Track Error 0-32 Custom Readout Max Value [4] Adaptive 2
0-10 Active Set-up [1652] Feedback[Unit] 0-21 Display Line 1.2 Small 0.0 - 999999.99 CustomReadoutUnit 1-1* Motor Selection
*[1] Set-up 1 [1653] Digi Pot Reference Same choices with 0-20 *100 CustomReadoutUnit 1-10 Motor Construction
[2] Set-up 2 [1657] Feedback [RPM] *[1614]Motor current 0-37 Display Text 1 *[0] Asynchron
[9] Multi Set-up [1660] Digital Input 0-22 Display Line 1.3 Small 0-0* [1] PM, non salient SPM
0-11 Programming Set-up [1661] Terminal 53 Setting Same choices with 0-20 0-38 Display Text 2 [3] PM, salient IPM
VLT® AutomationDrive FC 360
[1] Set-up 1 [1662] Analog input 53 *[1610]Power [kW] 0-0* 1-14 Damping Gain
[2] Set-up 2 [1663] Terminal 54 Setting 0-23 Display Line 2 Large 0-39 Display Text 3 0 - 250 % *120 %
MG06A802
[16] 11 kW - 15 hp 1-52 Min Speed Normal Magnetising [Hz] *[0] No protection 2-31 Speed PID Start Proportional Gain [150] lb ft
[17] 15 kW - 20 hp 0.1 - 10.0 Hz *1 Hz [1] Thermistor warning 0.000 - 1.000 *0.015 [160] °F
[18] 18.5 kW - 25 hp 1-55 U/f Characteristic - U [2] Thermistor trip 2-32 Speed PID Start Integral Time [170] psi
[19] 22 kW - 30 hp 0 - 1000 V *Size related [3] ETR warning 1 1.0 - 20000.0 ms *200.0 ms [171] lb/in2
MG06A802
Appendix
[20] 30 kW - 40 hp 1-56 U/f Characteristic - F [4] ETR trip 1 2-33 Speed PID Start Lowpass Filter Time [172] in WG
[21] 37 kW - 50 hp 0 - 500.0 Hz *Size related [22] ETR Trip - Extended Detection 0.1 - 100.0 ms *10.0 ms [173] ft WG
[22] 45 kW - 60 hp 1-6* Load Depen. Setting 1-93 Thermistor Source 2-39 Mech. Brake w/ dir. Change [180] HP
[23] 55 kW - 75 hp 1-60 Low Speed Load Compensation *[0] None *[0] OFF 3-02 Minimum Reference
[24] 75 kW - 100 hp 0 - 300 % *100 % [1] Analog Input 53 [1] ON -4999.0 - 4999 ReferenceFeedbackUnit
[25] 90 kW - 120 hp 1-61 High Speed Load Compensation [2] Analog Input 54 [2] ON with start delay *0 ReferenceFeedbackUnit
1-22 Motor Voltage 0 - 300 % *100 % [3] Digital input 18 3-** Reference / Ramps 3-03 Maximum Reference
50 - 1000 V *Size related 1-62 Slip Compensation [4] Digital input 19 3-0* Reference Limits -4999.0 - 4999 ReferenceFeedbackUnit
1-23 Motor Frequency -400 - 400.0 % *Size related [5] Digital input 32 3-00 Reference Range *Size related
20 - 500 Hz *Size related 1-63 Slip Compensation Time Constant [6] Digital input 33 *[0] Min - Max 3-04 Reference Function
1-24 Motor Current 0.05 - 5 s *0.1 s [7] Digital input 31 [1] -Max - +Max *[0] Sum
0.01 - 1000.00 A *Size related 1-64 Resonance Dampening 2-** Brakes 3-01 Reference/Feedback Unit [1] External/Preset
1-25 Motor Nominal Speed 0 - 500 % *100 % 2-0* DC-Brake [0] None 3-1* References
50 - 60000 RPM *Size related 1-65 Resonance Dampening Time Constant 2-00 DC Hold/Motor Preheat Current [1] % 3-10 Preset Reference
1-26 Motor Cont. Rated Torque 0.001 - 0.05 s *0.005 s 0 - 160 % *50 % [2] RPM -100 - 100 % *0 %
0.1 - 10000.0 Nm *Size related 1-66 Min. Current at Low Speed 2-01 DC Brake Current [3] Hz 3-11 Jog Speed [Hz]
1-29 Automatic Motor Adaption (AMA) 0 - 120 % *50 % 0 - 150 % *50 % [4] Nm 0 - 500.0 Hz *5 Hz
*[0] Off 1-7* Start Adjustments 2-02 DC Braking Time [5] PPM 3-12 Catch up/slow Down Value
[1] Enable Complete AMA 1-70 Start Mode 0 - 60 s *10 s [10] 1/min 0 - 100 % *0 %
[2] Enable Reduced AMA *[0] Rotor Detection 2-04 DC Brake Cut In Speed [12] Pulse/s 3-13 Reference Site
1-3* Adv. Motor Data I [1] Parking 0 - 500 Hz *0 Hz [20] l/s *[0] Linked to Hand / Auto
1-30 Stator Resistance (Rs) [3] Rotor Last Position 2-06 Parking Current [21] l/min [1] Remote
0.0 - 9999.000 Ohm *Size related 1-71 Start Delay 0 - 150 % *100 % [22] l/h [2] Local
Quick Guide
1-31 Rotor Resistance (Rr) 0 - 10 s *0 s 2-07 Parking Time [23] m³/s 3-14 Preset Relative Reference
0 - 9999.000 Ohm *Size related 1-72 Start Function 0.1 - 60 s *3 s [24] m³/min -100 - 100 % *0 %
1-33 Stator Leakage Reactance (X1) [0] DC Hold/delay time 2-1* Brake Energy Funct. [25] m³/h 3-15 Reference 1 Source
0.0 - 9999.000 Ohm *Size related *[2] Coast/delay time 2-10 Brake Function [30] kg/s [0] No function
1-35 Main Reactance (Xh) [3] Start speed cw *[0] Off [31] kg/min *[1] Analog Input 53
0.0 - 9999.00 Ohm *Size related [4] Horizontal operation [1] Resistor brake [32] kg/h [2] Analog Input 54
1-37 d-axis Inductance (Ld) [5] VVC+ clockwise [2] AC brake [33] t/min [7] Frequency input 29
0 - 65535 mH *Size related 1-73 Flying Start 2-11 Brake Resistor (ohm) [34] t/h [8] Frequency input 33
1-38 q-axis Inductance (Lq) *[0] Disabled 0 - 6200 Ohm *Size related [40] m/s [11] Local bus reference
0.000 - 65535 mH *Size related [1] Enabled 2-12 Brake Power Limit (kW) [41] m/min [20] Digital pot.meter
1-39 Motor Poles [2] Enabled Always 0.001 - 2000 kW *Size related [45] m [32] Bus PCD
2 - 100 *Size related [3] Enabled Ref. Dir. 2-14 Brake voltage reduce [60] °C 3-16 Reference 2 Source
1-4* Adv. Motor Data II [4] Enab. Always Ref. Dir. 0 - 500 V *0 V [70] mbar Same choices with 3-15
69
9 9
9 9
3-5* Ramp 2 0 - 16384 *0 [0] No operation [183] Sync. Hold [31] Relay 123
70
Same content with 3-4* 4-28 Speed Limit Bus Control [1] Reset [184] Sync. Latch Preset Factor Index [32] Mech brake ctrl
3-6* Ramp 3 0 - 16384 *0 [2] Coast inverse [185] Sync. Preset Factor Idx0 [36] Control word bit 11
Same content with 3-4* 4-3* Motor Fb Monitor [3] Coast and reset inverse [186] Sync. Preset Factor Idx1 [37] Control word bit 12
Appendix
3-7* Ramp 4 4-30 Motor Feedback Loss Function [4] Quick stop inverse 5-11 Terminal 19 Digital Input [40] Out of ref range
Same content with 3-4* [0] Disabled [5] DC-brake inverse Same choices with 5-10 [41] Below reference, low
3-8* Other Ramps [1] Warning [6] Stop inverse *[10] Reversing [42] Above ref, high
3-80 Jog Ramp Time *[2] Trip *[8] Start 5-12 Terminal 27 Digital Input [43] Extended PID Limit
0.01 - 3600 s *Size related [3] Jog [9] Latched start Same choices with 5-10 [45] Bus ctrl.
3-81 Quick Stop Ramp Time [4] Freeze Output [10] Reversing *[2] Coast inverse [46] Bus control, timeout: On
0.01 - 3600 s *Size related [5] Max Speed [11] Start reversing 5-13 Terminal 29 Digital Input [47] Bus control, timeout: Off
3-9* Digital Pot.Meter [6] Switch to Open Loop [12] Enable start forward Same choices with 5-10 [55] Pulse output
3-90 Step Size 4-31 Motor Feedback Speed Error [13] Enable start reverse *[14] Jog [56] Heat sink cleaning warning, high
0.01 - 200 % *0.10 % 0 - 50 Hz *20 Hz [14] Jog [32] Pulse input [60] Comparator 0
3-92 Power Restore 4-32 Motor Feedback Loss Timeout [15] Preset reference on 5-14 Terminal 32 Digital Input [61] Comparator 1
*[0] Off 0 - 60 s *0.05 s [16] Preset ref bit 0 Same choices with 5-10 [62] Comparator 2
[1] On 4-4* Adj. Warnings 2 [17] Preset ref bit 1 *[0] No operation [63] Comparator 3
3-93 Maximum Limit 4-40 Warning Freq. Low [18] Preset ref bit 2 [82] Encoder input B [64] Comparator 4
-200 - 200 % *100 % 0 - 500 Hz *Size related [19] Freeze reference 5-15 Terminal 33 Digital Input [65] Comparator 5
3-94 Minimum Limit 4-41 Warning Freq. High [20] Freeze output Same choices with 5-10 [70] Logic rule 0
-200 - 200 % *-100 % 0 - 500 Hz *Size related [21] Speed up *[16] Preset ref bit 0 [71] Logic rule 1
3-95 Ramp Delay 4-42 Adjustable Temperature Warning [22] Speed down [32] Pulse input [72] Logic rule 2
0 - 3600000 ms *1000 ms 0 - 200 *0 [23] Set-up select bit 0 [81] Encoder input A [73] Logic rule 3
4-** Limits / Warnings 4-5* Adj. Warnings [28] Catch up 5-16 Terminal 31 Digital Input [74] Logic rule 4
4-1* Motor Limits 4-50 Warning Current Low [29] Slow down Same choices with 5-10 [75] Logic rule 5
4-10 Motor Speed Direction 0 - 500 A *0 A [34] Ramp bit 0 *[0] No operation [80] SL digital output A
[0] Clockwise 4-51 Warning Current High [35] Ramp bit 1 5-3* Digital Outputs [81] SL digital output B
*[2] Both directions 0 - 500.00 A *Size related [45] Latched start reverse 5-30 Terminal 27 Digital Output [82] SL digital output C
4-12 Motor Speed Low Limit [Hz] 4-54 Warning Reference Low [51] External Interlock *[0] No operation [83] SL digital output D
0 - 400.0 Hz *0 Hz -4999 - 4999 *-4999 [55] DigiPot increase [1] Control Ready [91] Encoder emulate output A
4-14 Motor Speed High Limit [Hz] 4-55 Warning Reference High [56] DigiPot decrease [2] Drive ready [160] No alarm
0.1 - 500 Hz *65 Hz -4999 - 4999 *4999 [57] DigiPot clear [3] Drive rdy/rem ctrl [161] Running reverse
4-16 Torque Limit Motor Mode 4-56 Warning Feedback Low [60] Counter A (up) [4] Stand-by / no warning [165] Local ref active
0 - 1000 % *Size related -4999 - 4999 ProcessCtrlUnit *-4999 [61] Counter A (down) [5] Running [166] Remote ref active
4-17 Torque Limit Generator Mode ProcessCtrlUnit [62] Reset Counter A [6] Running / no warning [167] Start command activ
VLT® AutomationDrive FC 360
0 - 1000 % *100 % 4-57 Warning Feedback High [63] Counter B (up) [7] Run in range/no warn [168] Drive in hand mode
4-18 Current Limit -4999 - 4999 ProcessCtrlUnit *4999 [64] Counter B (down) [8] Run on ref/no warn [169] Drive in auto mode
MG06A802
[3] Drive rdy/rem ctrl [167] Start command activ [1] Counter clockwise 6-7* Analog/Digital Output 45 [42] Above ref, high
[4] Stand-by / no warning [168] Drive in hand mode 5-9* Bus Controlled 6-70 Terminal 45 Mode [45] Bus ctrl.
[5] Running [169] Drive in auto mode 5-90 Digital & Relay Bus Control *[0] 0-20 mA [46] Bus control, timeout: On
[6] Running / no warning [170] Homing Completed 0 - 0xFFFFFFFF *0 [1] 4-20 mA [47] Bus control, timeout: Off
MG06A802
Appendix
[7] Run in range/no warn [171] Target Position Reached 5-93 Pulse Out 27 Bus Control [2] Digital Output [56] Heat sink cleaning warning, high
[8] Run on ref/no warn [172] Position Control Fault 0 - 100 % *0 % 6-71 Terminal 45 Analog Output [60] Comparator 0
[9] Alarm [173] Position Mech Brake 5-94 Pulse Out 27 Timeout Preset *[0] No operation [61] Comparator 1
[10] Alarm or warning [175] Running on tension 0 - 100 % *0 % [100] Output frequency [62] Comparator 2
[11] At torque limit [176] Ready to run 5-95 Pulse Out 29 Bus Control [101] Reference [63] Comparator 3
[12] Out of current range [193] Sleep Mode 0 - 100 % *0 % [102] Process Feedback [64] Comparator 4
[13] Below current, low [194] Broken Belt Function 5-96 Pulse Out 29 Timeout Preset [103] Motor Current [65] Comparator 5
[14] Above current, high 5-41 On Delay, Relay 0 - 100 % *0 % [104] Torque rel to limit [70] Logic rule 0
[15] Out of frequency range 0 - 600 s *0.01 s 6-** Analog In/Out [105] Torq relate to rated [71] Logic rule 1
[16] Below frequency, low 5-42 Off Delay, Relay 6-0* Analog I/O Mode [106] Power [72] Logic rule 2
[17] Above frequency, high 0 - 600 s *0.01 s 6-00 Live Zero Timeout Time [107] Speed [73] Logic rule 3
[18] Out of feedb. range 5-5* Pulse Input 1 - 99 s *10 s [111] Speed Feedback [74] Logic rule 4
[19] Below feedback, low 5-50 Term. 29 Low Frequency 6-01 Live Zero Timeout Function [113] PID Clamped Output [75] Logic rule 5
[20] Above feedback, high 4 - 31999 Hz *4 Hz *[0] Off [139] Bus Control [80] SL digital output A
[21] Thermal warning 5-51 Term. 29 High Frequency [1] Freeze output [143] Ext. CL 1 [81] SL digital output B
[22] Ready, no thermal warning 5 - 32000 Hz *32000 Hz [2] Stop [162] Tapered tension set point [82] SL digital output C
[23] Remote,ready,no TW 5-52 Term. 29 Low Ref./Feedb. Value [3] Jogging [254] DC Link Voltage [83] SL digital output D
[24] Ready, no over-/ under voltage -4999 - 4999 *0 [4] Max. speed 6-72 Terminal 45 Digital Output [160] No alarm
[25] Reverse 5-53 Term. 29 High Ref./Feedb. Value [5] Stop and trip *[0] No operation [161] Running reverse
[26] Bus OK -4999 - 4999 *Size related 6-1* Analog Input 53 [1] Control Ready [165] Local ref active
[27] Torque limit & stop 5-55 Term. 33 Low Frequency 6-10 Terminal 53 Low Voltage [2] Drive ready [166] Remote ref active
[28] Brake, no brake warning 4 - 31999 Hz *4 Hz 0 - 10 V *0.07 V [3] Drive rdy/rem ctrl [167] Start command activ
[29] Brake ready, no fault 5-56 Term. 33 High Frequency 6-11 Terminal 53 High Voltage [4] Stand-by / no warning [168] Drive in hand mode
Quick Guide
[30] Brake fault (IGBT) 5 - 32000 Hz *32000 Hz 0 - 10 V *10 V [5] Running [169] Drive in auto mode
[31] Relay 123 5-57 Term. 33 Low Ref./Feedb. Value 6-12 Terminal 53 Low Current [6] Running / no warning [170] Homing Completed
[32] Mech brake ctrl -4999 - 4999 *0 0 - 20 mA *4 mA [7] Run in range/no warn [171] Target Position Reached
[36] Control word bit 11 5-58 Term. 33 High Ref./Feedb. Value 6-13 Terminal 53 High Current [8] Run on ref/no warn [172] Position Control Fault
[37] Control word bit 12 -4999 - 4999 *Size related 0 - 20 mA *20 mA [9] Alarm [173] Position Mech Brake
[40] Out of ref range 5-6* Pulse Output 6-14 Terminal 53 Low Ref./Feedb. Value [10] Alarm or warning [174] TLD indicator
[41] Below reference, low 5-60 Terminal 27 Pulse Output Variable -4999 - 4999 *0 [11] At torque limit [175] Running on tension
[42] Above ref, high *[0] No operation 6-15 Terminal 53 High Ref./Feedb. Value [12] Out of current range [176] Ready to run
[45] Bus ctrl. [45] Bus ctrl. -4999 - 4999 *Size related [13] Below current, low [177] End of roll
[46] Bus control, timeout: On [48] Bus ctrl., timeout 6-16 Terminal 53 Filter Time Constant [14] Above current, high [193] Sleep Mode
[47] Bus control, timeout: Off [100] Output frequency 0.01 - 10 s *0.01 s [15] Out of frequency range [194] Broken Belt Function
[56] Heat sink cleaning warning, high [101] Reference 6-19 Terminal 53 mode [16] Below frequency, low [198] Drive Bypass
[60] Comparator 0 [102] Process Feedback [0] Current mode [17] Above frequency, high 6-73 Terminal 45 Output Min Scale
71
9 9
9 9
[107] Speed [73] Logic rule 3 7-13 Torque PID Integration Time [1] Inverse *[1] Profile default
72
[111] Speed Feedback [74] Logic rule 4 0.002 - 2 s *0.020 s 7-48 PCD Feed Forward [2] CTW Valid, active low
[113] PID Clamped Output [75] Logic rule 5 7-2* Process Ctrl. Feedb 0 - 65535 *0 [4] PID error inverse
[139] Bus Control [80] SL digital output A 7-20 Process CL Feedback 1 Resource 7-49 Process PID Output Normal/ Inv. Ctrl. [5] PID reset I part
Appendix
[143] Ext. CL 1 [81] SL digital output B *[0] No function *[0] Normal [6] PID enable
[162] Tapered tension set point [82] SL digital output C [1] Analog Input 53 [1] Inverse 8-19 Product Code
[254] DC Link Voltage [83] SL digital output D [2] Analog Input 54 7-5* Adv. Process PID II 0 - 2147483647 *Size related
6-92 Terminal 42 Digital Output [160] No alarm [3] Frequency input 29 7-50 Process PID Extended PID 8-3* FC Port Settings
*[0] No operation [161] Running reverse [4] Frequency input 33 [0] Disabled 8-30 Protocol
[1] Control Ready [165] Local ref active 7-22 Process CL Feedback 2 Resource *[1] Enabled *[0] FC
[2] Drive ready [166] Remote ref active *[0] No function 7-51 Process PID Feed Fwd Gain [2] Modbus RTU
[3] Drive rdy/rem ctrl [167] Start command activ [1] Analog Input 53 0 - 100 *1 8-31 Address
[4] Stand-by / no warning [168] Drive in hand mode [2] Analog Input 54 7-52 Process PID Feed Fwd Ramp up 0.0 - 247 *1
[5] Running [169] Drive in auto mode [3] Frequency input 29 0.01 - 100 s *0.01 s 8-32 Baud Rate
[6] Running / no warning [170] Homing Completed [4] Frequency input 33 7-53 Process PID Feed Fwd Ramp down [0] 2400 Baud
[7] Run in range/no warn [171] Target Position Reached 7-3* Process PID Ctrl. 0.01 - 100 s *0.01 s [1] 4800 Baud
[8] Run on ref/no warn [172] Position Control Fault 7-30 Process PID Normal/ Inverse Control 7-56 Process PID Ref. Filter Time [2] 9600 Baud
[9] Alarm [173] Position Mech Brake *[0] Normal 0.001 - 1 s *0.001 s [3] 19200 Baud
[10] Alarm or warning [174] TLD indicator [1] Inverse 7-57 Process PID Fb. Filter Time [4] 38400 Baud
[11] At torque limit [175] Running on tension 7-31 Process PID Anti Windup 0.001 - 1 s *0.001 s [5] 57600 Baud
[12] Out of current range [176] Ready to run [0] Off 7-6* Feedback Conversion [6] 76800 Baud
[13] Below current, low [177] End of roll *[1] On 7-60 Feedback 1 Conversion [7] 115200 Baud
[14] Above current, high [193] Sleep Mode 7-32 Process PID Start Speed *[0] Linear 8-33 Parity / Stop Bits
[15] Out of frequency range [194] Broken Belt Function 0 - 6000 RPM *0 RPM [1] Square root [0] Even Parity, 1 Stop Bit
[16] Below frequency, low [198] Drive Bypass 7-33 Process PID Proportional Gain 7-62 Feedback 2 Conversion [1] Odd Parity, 1 Stop Bit
[17] Above frequency, high 6-93 Terminal 42 Output Min Scale 0 - 10 *0.01 *[0] Linear [2] No Parity, 1 Stop Bit
[18] Out of feedb. range 0 - 200 % *0 % 7-34 Process PID Integral Time [1] Square root [3] No Parity, 2 Stop Bits
[19] Below feedback, low 6-94 Terminal 42 Output Max Scale 0.10 - 9999 s *9999 s 8-** Comm. and Options 8-35 Minimum Response Delay
[20] Above feedback, high 0 - 200 % *100 % 7-35 Process PID Differentiation Time 8-0* General Settings 0.0010 - 0.5 s *0.01 s
[21] Thermal warning 6-96 Terminal 42 Output Bus Control 0 - 20 s *0 s 8-00 Option A warning control 8-36 Maximum Response Delay
[22] Ready, no thermal warning 0 - 16384 *0 7-36 Process PID Diff. Gain Limit *[0] None 0.1 - 10.0 s *Size related
[23] Remote,ready,no TW 7-** Controllers 1 - 50 *5 [1] Disable Warning 8-4* FC MC protocol set
[24] Ready, no over-/ under voltage 7-0* Speed PID Ctrl. 7-38 Process PID Feed Forward Factor 8-01 Control Site 8-42 PCD Write Configuration
[25] Reverse 7-00 Speed PID Feedback Source 0 - 200 % *0 % *[0] Digital and ctrl.word [0] None
[26] Bus OK [1] 24V encoder 7-39 On Reference Bandwidth [1] Digital only [1] [302] Minimum Reference
VLT® AutomationDrive FC 360
[27] Torque limit & stop [2] MCB 102 0 - 200 % *5 % [2] Controlword only [2] [303] Maximum Reference
[28] Brake, no brake warning [3] MCB 103 7-4* Adv. Process PID I 8-02 Control Source [3] [341] Ramp 1 Ramp up time
MG06A802
[6] [1602] Reference % [2] Logic AND [412] Motor Speed Low Limit [Hz] [1639] Control Card Temp. [302] Minimum Reference
[7] [1603] Status Word *[3] Logic OR [414] Motor Speed High Limit [Hz] [1650] External Reference [303] Maximum Reference
[8] [1605] Main Actual Value [%] 8-55 Set-up Select [416] Torque Limit Motor Mode [1652] Feedback[Unit] [311] Jog Speed [Hz]
[9] [1609] Custom Readout [0] Digital input [417] Torque Limit Generator Mode [1653] Digi Pot Reference [312] Catch up/slow Down Value
MG06A802
Appendix
[10] [1610] Power [kW] [1] Bus [427] Torque Limit Bus Control [1657] Feedback [RPM] [341] Ramp 1 Ramp Up Time
[11] [1611] Power [hp] [2] Logic AND [428] Speed Limit Bus Control [1660] Digital Input [342] Ramp 1 Ramp Down Time
[12] [1612] Motor Voltage *[3] Logic OR [553] Term. 29 High Ref./Feedb. Value [1661] Terminal 53 Setting [351] Ramp 2 Ramp Up Time
[13] [1613] Frequency 8-56 Preset Reference Select [558] Term. 33 High Ref./Feedb. Value [1662] Analog input 53 [352] Ramp 2 Ramp Down Time
[14] [1614] Motor Current [0] Digital input [590] Digital & Relay Bus Control [1663] Terminal 54 Setting [380] Jog Ramp Time
[15] [1615] Frequency [%] [1] Bus [593] Pulse Out 27 Bus Control [1664] Analog input 54 [381] Quick Stop Ramp Time
[16] [1616] Torque [Nm] [2] Logic AND [595] Pulse Out 29 Bus Control [1665] Analog output 42 [mA] [412] Motor Speed Low Limit [Hz]
[17] [1618] Motor Thermal *[3] Logic OR [615] Terminal 53 High Ref./Feedb. Value [1666] Digital Output [414] Motor Speed High Limit [Hz]
[18] [1630] DC Link Voltage 8-57 Profidrive OFF2 Select [625] Terminal 54 High Ref./Feedb. Value [1667] Pulse input 29 [Hz] [416] Torque Limit Motor Mode
[19] [1634] Heatsink Temp. [0] Digital input [676] Terminal 45 Output Bus Control [1668] Pulse input 33 [Hz] [417] Torque Limit Generator Mode
[20] [1635] Inverter Thermal [1] Bus [696] Terminal 42 Output Bus Control [1669] Pulse output 27 [Hz] [553] Term. 29 High Ref./Feedb. Value
[21] [1638] SL Controller State [2] Logic AND [733] Process PID Proportional Gain [1670] Pulse output 29 [Hz] [558] Term. 33 High Ref./Feedb. Value
[22] [1650] External Reference *[3] Logic OR [734] Process PID Integral Time [1671] Relay output [590] Digital & Relay Bus Control
[23] [1652] Feedback [Unit] 8-58 Profidrive OFF3 Select [735] Process PID Differentiation Time [1672] Counter A [593] Pulse Out 27 Bus Control
[24] [1660] Digital Input 18,19,27,33 [0] Digital input [748] PCD Feed Forward [1673] Counter B [595] Pulse Out 29 Bus Control
[25] [1661] Terminal 53 Switch Setting [1] Bus [890] Bus Jog 1 Speed [1679] Analog output 45 [mA] [615] Terminal 53 High Ref./Feedb. Value
[26] [1662] Analog input 53 [2] Logic AND [891] Bus Jog 2 Speed [1684] Comm. Option STW [625] Terminal 54 High Ref./Feedb. Value
[27] [1663] Terminal 54 Switch Setting *[3] Logic OR [1680] Fieldbus CTW 1 [1685] FC Port CTW 1 [676] Terminal 45 Output Bus Control
[28] [1664] Analog input 54 8-7* Protocol SW Version [1682] Fieldbus REF 1 [1690] Alarm Word [696] Terminal 42 Output Bus Control
[29] [1665] Analog output 42 [mA] 8-79 Protocol Firmware version [3401] PCD 1 Write For Application [1691] Alarm Word 2 [733] Process PID Proportional Gain
[30] [1671] Relay output 0 - 65535 *Size related [3402] PCD 2 Write For Application [1692] Warning Word [734] Process PID Integral Time
[31] [1672] Counter A 8-8* FC Port Diagnostics [3403] PCD 3 Write For Application [1693] Warning Word 2 [735] Process PID Differentiation Time
[32] [1673] Counter B 8-80 Bus Message Count [3404] PCD 4 Write For Application [1694] Ext. Status Word [748] PCD Feed Forward
Quick Guide
[33] [1690] Alarm Word 0 - 4294967295 *0 [3405] PCD 5 Write For Application [1695] Ext. Status Word 2 [890] Bus Jog 1 Speed
[34] [1692] Warning Word 8-81 Bus Error Count [3406] PCD 6 Write For Application [1697] Alarm Word 3 [891] Bus Jog 2 Speed
[35] [1694] Ext. Status Word 0 - 4294967295 *0 [3407] PCD 7 Write For Application [3421] PCD 1 Read For Application [1500] Operating hours
[38] [1622] Torque [%] 8-82 Slave Messages Rcvd [3408] PCD 8 Write For Application [3422] PCD 2 Read For Application [1501] Running Hours
[41] [1657] Feedback [RPM] 0 - 4294967295 *0 [3409] PCD 9 Write For Application [3423] PCD 3 Read For Application [1502] kWh Counter
[42] [1679] Analog Output 45 [mA] 8-83 Slave Error Count [3410] PCD 10 Write For Application [3424] PCD 4 Read For Application [1600] Control Word
[43] [1617] Speed [RPM] 0 - 4294967295 *0 9-16 PCD Read Configuration [3425] PCD 5 Read For Application [1601] Reference [Unit]
[44] [1666] Digital Output 8-84 Slave Messages Sent [0] None [3426] PCD 6 Read For Application [1602] Reference [%]
8-5* Digital/Bus 0 - 4294967295 *0 [1500] Operating hours [3427] PCD 7 Read For Application [1603] Status Word
8-50 Coasting Select 8-85 Slave Timeout Errors [1501] Running Hours [3428] PCD 8 Read For Application [1605] Main Actual Value [%]
[0] Digital input 0 - 4294967295 *0 [1502] kWh Counter [3429] PCD 9 Read For Application [1609] Custom Readout
[1] Bus 8-88 Reset FC port Diagnostics [1600] Control Word [3430] PCD 10 Read For Application [1610] Power [kW]
[2] Logic AND *[0] Do not reset [1601] Reference [Unit] [3450] Actual Position [1611] Power [hp]
73
9 9
9 9
[1661] Terminal 53 Setting [0] 9,6 kbit/s 0 - 4294967295 *0 [1] Broadcast & Multicast 13-1* Comparators
74
[1662] Analog input 53 [1] 19,2 kbit/s 12-03 Default Gateway 12-96 Port Config 13-10 Comparator Operand
[1663] Terminal 54 Setting [2] 93,75 kbit/s 0 - 4294967295 *0 [0] Normal *[0] Disabled
[1664] Analog input 54 [3] 187,5 kbit/s 12-04 DHCP Server [1] Mirror Port 1 to 2 [1] Reference %
Appendix
[1665] Analog output 42 [mA] [4] 500 kbit/s 0 - 2147483647 *0 [2] Mirror Port 2 to 1 [2] Feedback %
[1667] Pulse input 29 [Hz] [6] 1500 kbit/s 12-05 Lease Expires [10] Port 1 disabled [3] Motor speed
[1668] Pulse input 33 [Hz] [7] 3000 kbit/s 0 - 4294967295 *0 [11] Port 2 disabled [4] Motor Current
[1669] Pulse output 27 [Hz] [8] 6000 kbit/s 12-06 Name Servers [254] Mirror Int. Port to 1 [6] Motor power
[1670] Pulse output 29 [Hz] [9] 12000 kbit/s 0 - 4294967295 *0 [255] Mirror Int. Port to 2 [7] Motor voltage
[1671] Relay output [10] 31,25 kbit/s 12-07 Domain Name 12-98 Interface Counters [8] DC-link voltage
[1672] Counter A [11] 45,45 kbit/s 1 - 48 *0 0 - 4294967295 *4000 [12] Analog input AI53
[1673] Counter B *[255] No baudrate found 12-08 Host Name 12-99 Media Counters [13] Analog input AI54
[1679] Analog output 45 [mA] 9-65 Profile Number 1 - 48 *0 0 - 4294967295 *0 [18] Pulse input FI29
[1680] Fieldbus CTW 1 0 - 0 *0 12-09 Physical Address 13-** Smart Logic [19] Pulse input FI33
[1682] Fieldbus REF 1 9-70 Edit Set-up 0 - 17 *0 13-0* SLC Settings [20] Alarm number
[1684] Comm. Option STW [1] Set-up 1 12-1* Ethernet Link Parameters 13-00 SL Controller Mode [30] Counter A
[1685] FC Port CTW 1 [2] Set-up 2 12-10 Link Status *[0] Off [31] Counter B
[1690] Alarm Word *[9] Active Set-up *[0] No Link [1] On 13-11 Comparator Operator
[1691] Alarm Word 2 9-71 Profibus Save Data Values [1] Link 13-01 Start Event [0] Less Than (<)
[1692] Warning Word *[0] Off 12-11 Link Duration [0] False *[1] Approx.Equal (~)
[1693] Warning Word 2 [1] Store all setups 0 - 0 *Size related [1] True [2] Greater Than (>)
[1694] Ext. Status Word 9-72 ProfibusDriveReset 12-12 Auto Negotiation [2] Running 13-12 Comparator Value
[1695] Ext. Status Word 2 *[0] No action [0] Off [3] In range -9999 - 9999 *0
[1697] Alarm Word 3 [1] Power-on reset *[1] On [4] On reference 13-2* Timers
[3401] PCD 1 Write For Application [2] Power-on reset prep 12-13 Link Speed [7] Out of current range 13-20 SL Controller Timer
[3402] PCD 2 Write For Application [3] Comm option reset *[0] None [8] Below I low 0 - 3600 s *0 s
[3403] PCD 3 Write For Application 9-80 Defined Parameters (1) [1] 10 Mbps [9] Above I high 13-4* Logic Rules
[3404] PCD 4 Write For Application 0 - 9999 *0 [2] 100 Mbps [16] Thermal warning 13-40 Logic Rule Boolean 1
[3405] PCD 5 Write For Application 9-81 Defined Parameters (2) 12-14 Link Duplex [17] Mains out of range *[0] False
[3406] PCD 6 Write For Application 0 - 9999 *0 [0] Half Duplex [18] Reversing [1] True
[3407] PCD 7 Write For Application 9-82 Defined Parameters (3) *[1] Full Duplex [19] Warning [2] Running
[3408] PCD 8 Write For Application 0 - 9999 *0 12-8* Other Ethernet Services [20] Alarm (trip) [3] In range
[3409] PCD 9 Write For Application 9-83 Defined Parameters (4) 12-80 FTP Server [21] Alarm (trip lock) [4] On reference
[3410] PCD 10 Write For Application 0 - 9999 *0 *[0] Disabled [22] Comparator 0 [7] Out of current range
[3421] PCD 1 Read For Application 9-84 Defined Parameters (5) [1] Enabled [23] Comparator 1 [8] Below I low
VLT® AutomationDrive FC 360
[3422] PCD 2 Read For Application 0 - 9999 *0 12-81 HTTP Server [24] Comparator 2 [9] Above I high
[3423] PCD 3 Read For Application 9-85 Defined Parameters (6) *[0] Disabled [25] Comparator 3 [16] Thermal warning
MG06A802
[42] Auto Reset Trip [35] Digital input DI27 [1] Ran5 [12] Automatic reset x 20 [9] 12.0 kHz
[50] Comparator 4 [36] Digital input DI29 [2] 2.0 kHz [13] Infinite auto reset [10] 16.0 kHz
[51] Comparator 5 [39] Start command [3] 3.0 kHz [14] Reset at power-up 14-64 Dead Time Compensation Zero Current
[60] Logic rule 4 [40] Drive stopped [4] 4.0 kHz 14-21 Automatic Restart Time Level
MG06A802
Appendix
[61] Logic rule 5 [42] Auto Reset Trip [5] 5.0 kHz 0 - 600 s *10 s *[0] Disabled
[70] SL Time-out 3 [50] Comparator 4 [6] 6.0 kHz 14-22 Operation Mode [1] Enabled
[71] SL Time-out 4 [51] Comparator 5 [7] 8.0 kHz *[0] Normal operation 14-65 Speed Derate Dead Time Compen-
[72] SL Time-out 5 [60] Logic rule 4 [8] 10.0 kHz [2] Initialisation sation
[73] SL Time-out 6 [61] Logic rule 5 [9] 12.0 kHz 14-24 Trip Delay at Current Limit 20 - 1000 Hz *Size related
[74] SL Time-out 7 [70] SL Time-out 3 [10] 16.0 kHz 0 - 60 s *60 s 14-8* Options
[83] Broken Belt [71] SL Time-out 4 14-03 Overmodulation 14-25 Trip Delay at Torque Limit 14-89 Option Detection
13-41 Logic Rule Operator 1 [72] SL Time-out 5 [0] Off 0 - 60 s *60 s *[0] Protect Option Config.
*[0] Disabled [73] SL Time-out 6 *[1] On 14-27 Action At Inverter Fault [1] Enable Option Change
[1] AND [74] SL Time-out 7 14-07 Dead Time Compensation Level [0] Trip 14-9* Fault Settings
[2] OR [83] Broken Belt 0 - 100 *Size related *[1] Warning 14-90 Fault Level
[3] AND NOT 13-52 SL Controller Action 14-08 Damping Gain Factor 14-29 Service Code [0] Off
[4] OR NOT *[0] Disabled 0 - 100 % *Size related 0 - 0x7FFFFFFF *0 *[3] Trip Lock
[5] NOT AND [1] No action 14-09 Dead Time Bias Current Level 14-3* Current Limit Ctrl. [4] Trip w. delayed reset
[6] NOT OR [2] Select set-up 1 0 - 100 % *Size related 14-30 Current Lim Ctrl, Proportional Gain [5] Flystart
[7] NOT AND NOT [3] Select set-up 2 14-1* Mains On/Off 0 - 500 % *100 % 15-** Drive Information
[8] NOT OR NOT [10] Select preset ref 0 14-10 Mains Failure 14-31 Current Lim Ctrl, Integration Time 15-0* Operating Data
13-42 Logic Rule Boolean 2 [11] Select preset ref 1 *[0] No function 0.002 - 2 s *0.020 s 15-00 Operating hours
Same choices with 13-40 [12] Select preset ref 2 [1] Ctrl. ramp-down 14-32 Current Lim Ctrl, Filter Time 0 - 0x7fffffff. h *0 h
*[0] False [13] Select preset ref 3 [2] Ctrl. ramp-down, trip 1 - 100 ms *5 ms 15-01 Running Hours
13-43 Logic Rule Operator 2 [14] Select preset ref 4 [3] Coasting 14-4* Energy Optimising 0 - 0x7fffffff. h *0 h
Same choices with 13-41 [15] Select preset ref 5 [4] Kinetic back-up 14-40 VT Level 15-02 kWh Counter
*[0] Disabled [16] Select preset ref 6 [5] Kinetic back-up, trip 40 - 90 % *66 % 0 - 2147483647 kWh *0 kWh
Quick Guide
13-44 Logic Rule Boolean 3 [17] Select preset ref 7 [6] Alarm 14-41 AEO Minimum Magnetisation 15-03 Power Up's
Same choices with 13-40 [18] Select ramp 1 [7] Kin. back-up, trip w recovery 40 - 75 % *66 % 0 - 2147483647 *0
*[0] False [19] Select ramp 2 14-11 Mains Fault Voltage Level 14-44 d-axis current optimization for IPM 15-04 Over Temp's
13-5* States [22] Run 100 - 800 V *342 V 0 - 200 % *100 % 0 - 65535 *0
13-51 SL Controller Event [23] Run reverse 14-12 Response to Mains Imbalance 14-5* Environment 15-05 Over Volt's
*[0] False [24] Stop *[0] Trip 14-50 RFI Filter 0 - 65535 *0
[1] True [25] Qstop [1] Warning [0] Off 15-06 Reset kWh Counter
[2] Running [26] DC Brake [2] Disabled [1] On *[0] Do not reset
[3] In range [27] Coast [3] Derate *[2] Grid Type [1] Reset counter
[4] On reference [28] Freeze output [4] Fast Trip 14-51 DC-Link Voltage Compensation 15-07 Reset Running Hours Counter
[7] Out of current range [29] Start timer 0 [5] Fast Warning [0] Off *[0] Do not reset
[8] Below I low [30] Start timer 1 14-15 Kin. Back-up Trip Recovery Level *[1] On [1] Reset counter
[9] Above I high [31] Start timer 2 0 - 500.000 ReferenceFeedbackUnit 14-52 Fan Control 15-3* Alarm Log
75
9 9
9 9
15-48 LCP Id No 16-15 Frequency [%] 0 - 40000 *0 [4] 4096 [1] Analog Input 53
76
0 - 0 *0 0 - 6553.5 % *0 % 16-70 Pulse output 29 [Hz] 17-59 Resolver Interface [2] Analog Input 54
15-49 SW ID Control Card 16-16 Torque [Nm] 0 - 40000 *0 *[0] Disabled [3] Frequency input 29
0 - 0 *0 -30000 - 30000 Nm *0 Nm 16-71 Relay output [1] Enabled [4] Frequency input 33
Appendix
15-50 SW ID Power Card 16-17 Speed [RPM] 0 - 65535 *0 17-6* Monitoring and App. 21-15 Ext. 1 Setpoint
0 - 0 *0 -30000 - 30000 RPM *0 RPM 16-72 Counter A 17-60 Feedback Direction -999999.999 - 999999.999 ExtPID1Unit
15-51 Drive Serial Number 16-18 Motor Thermal -32768 - 32767 *0 *[0] Clockwise *0 ExtPID1Unit
0 - 0 *0 0 - 100 % *0 % 16-73 Counter B [1] Counter clockwise 21-17 Ext. 1 Reference [Unit]
15-53 Power Card Serial Number 16-22 Torque [%] -32768 - 32767 *0 17-61 Feedback Signal Monitoring -999999.999 - 999999.999 ExtPID1Unit
0 - 0 *0 -200 - 200 % *0 % 16-79 Analog output 45 [mA] [0] Disabled *0 ExtPID1Unit
15-6* Option Ident 16-3* Drive Status 0 - 20 mA *0 mA *[1] Warning 21-18 Ext. 1 Feedback [Unit]
15-60 Option Mounted 16-30 DC Link Voltage 16-8* Fieldbus & FC Port [2] Trip -999999.999 - 999999.999 ExtPID1Unit
0 - 30 *Size related 0 - 65535 V *0 V 16-80 Fieldbus CTW 1 [3] Jog *0 ExtPID1Unit
15-61 Option SW Version 16-33 Brake Energy /2 min 0 - 65535 *0 [4] Freeze Output 21-19 Ext. 1 Output [%]
0 - 20 *Size related 0 - 10000 kW *0 kW 16-82 Fieldbus REF 1 [5] Max Speed 0 - 100 % *0 %
15-62 Option Ordering No 16-34 Heatsink Temp. -32768 - 32767 *0 [6] Switch to Open Loop 21-2* Ext. CL 1 PID
0 - 8 *Size related -128 - 127 °C *0 °C 16-84 Comm. Option STW 18-** Data Readouts 2 21-20 Ext. 1 Normal/Inverse Control
15-63 Option Serial No 16-35 Inverter Thermal 0 - 65535 *0 18-8* Center Winder Readout *[0] Normal
0 - 18 *Size related 0 - 255 % *0 % 16-85 FC Port CTW 1 18-81 Tension PID Output [1] Inverse
15-70 Option in Slot A 16-36 Inv. Nom. Current 0 - 65535 *1084 -5000 - 5000 Hz *0 Hz 21-21 Ext. 1 Proportional Gain
0 - 30 *0 0 - 655.35 A *0 A 16-86 FC Port REF 1 18-82 Center Winder Output 0 - 10 *0.01
15-71 Slot A Option SW Version 16-37 Inv. Max. Current -32768 - 32767 *0 -5000 - 5000 Hz *0 Hz 21-22 Ext. 1 Integral Time
0 - 20 *0 0 - 655.35 A *0 A 16-9* Diagnosis Readouts 18-83 Line Speed 0.01 - 10000 s *10000 s
15-9* Parameter Info 16-38 SL Controller State 16-90 Alarm Word -5000 - 5000 Hz *0 Hz 21-23 Ext. 1 Differentation Time
15-92 Defined Parameters 0 - 20 *0 0 - 0xFFFFFFFFUL *0 18-84 Diameter 0 - 10 s *0 s
0 - 2000 *0 16-39 Control Card Temp. 16-91 Alarm Word 2 0 - 100 % *0 % 21-24 Ext. 1 Dif. Gain Limit
15-97 Application Type 0 - 65535 °C *0 °C 0 - 0xFFFFFFFFUL *0 18-85 Tapered Tension Set Point 1 - 50 *5
0 - 0xFFFFFFFF *0 16-5* Ref. & Feedb. 16-92 Warning Word 0 - 100 % *0 % 22-** Appl. Functions
15-98 Drive Identification 16-50 External Reference 0 - 0xFFFFFFFFUL *0 18-86 Tension Feedback 22-0* Miscellaneous
0 - 56 *0 -200 - 200 % *0 % 16-93 Warning Word 2 0 - 100 % *0 % 22-02 Sleepmode CL Control Mode
15-99 Parameter Metadata 16-52 Feedback[Unit] 0 - 0xFFFFFFFFUL *0 18-9* PID Readouts *[0] Normal
0 - 9999 *0 -4999 - 4999 ProcessCtrlUnit *0 16-94 Ext. Status Word 18-90 Process PID Error [1] Simplified
16-** Data Readouts ProcessCtrlUnit 0 - 0xFFFFFFFFUL *0 -200 - 200 % *0 % 22-4* Sleep Mode
16-0* General Status 16-53 Digi Pot Reference 16-95 Ext. Status Word 2 18-91 Process PID Output 22-40 Minimum Run Time
16-00 Control Word -200 - 200 *0 0 - 0xFFFFFFFFUL *0 -200 - 200 % *0 % 0 - 600 s *10 s
VLT® AutomationDrive FC 360
0 - 65535 *0 16-57 Feedback [RPM] 16-97 Alarm Word 3 18-92 Process PID Clamped Output 22-41 Minimum Sleep Time
16-01 Reference [Unit] -30000 - 30000 RPM *0 RPM 0 - 0xFFFFFFFFUL *0 -200 - 200 % *0 % 0 - 600 s *10 s
MG06A802
0 - 600 s *10 s 32-80 Maximum Allowed Velocity 34-06 PCD 6 Write For Application -1073741824 - 1073741824 *0 37-23 Partial Roll Diameter Value
30-** Special Features 1 - 30000 RPM *1500 RPM 0 - 65535 *0 37-03 Pos. Type 5 - 100 % *5 %
30-2* Adv. Start Adjust 32-81 Motion Ctrl Quick Stop Ramp 34-07 PCD 7 Write For Application *[0] Absolute 37-24 Core1 Diameter
30-20 High Starting Torque Time [s] 50 - 3600000 ms *1000 ms 0 - 65535 *0 [1] Relative 5 - 100 % *5 %
MG06A802
Appendix
0 - 60 s *Size related 33-** Motion Control Adv. Settings 34-08 PCD 8 Write For Application 37-04 Pos. Velocity 37-25 Core2 Diameter
30-21 High Starting Torque Current [%] 33-0* Home Motion 0 - 65535 *0 1 - 30000 RPM *100 RPM 5 - 100 % *5 %
0 - 200.0 % *Size related 33-00 Homing Mode 34-09 PCD 9 Write For Application 37-05 Pos. Ramp Up Time 37-26 Winder Jog Speed
30-22 Locked Rotor Protection *[0] Not forced 0 - 65535 *0 50 - 100000 ms *5000 ms 0 - 100 % *0 %
*[0] Off [1] Forced manual homing 34-10 PCD 10 Write For Application 37-06 Pos. Ramp Down Time 37-27 TLD Low Limit
[1] On [2] Forced automated homing 0 - 65535 *0 50 - 100000 ms *5000 ms 0 - 100 % *0 %
30-23 Locked Rotor Detection Time [s] 33-01 Home Offset 34-2* PCD Read Par. 37-07 Pos. Auto Brake Ctrl 37-28 TLD High Limit
0.05 - 1 s *0.10 s -1073741824 - 1073741824 *0 34-21 PCD 1 Read For Application [0] Disable 0 - 100 % *0 %
32-** Motion Control Basic Settings 33-02 Home Ramp Time 0 - 65535 *0 *[1] Enable 37-29 TLD Timer
32-1* User Unit 1 - 1000 ms *10 ms 34-22 PCD 2 Read For Application 37-08 Pos. Hold Delay 0.001 - 5 s *0.001 s
32-11 User Unit Denominator 33-03 Homing Velocity 0 - 65535 *0 0 - 10000 ms *0 ms 37-30 TLDOnDelay
1 - 65535 *1 -1500 - 1500 RPM *100 RPM 34-23 PCD 3 Read For Application 37-09 Pos. Coast Delay [0] Disabled
32-12 User Unit Numerator 33-04 Homing Behaviour 0 - 65535 *0 0 - 1000 ms *200 ms *[1] Enabled
1 - 65535 *1 *[1] Reverse no index 34-24 PCD 4 Read For Application 37-10 Pos. Brake Delay 37-31 Diameter Limit Detector
32-5* Feadback Source [3] Forward no index 0 - 65535 *0 0 - 1000 ms *200 ms 0 - 100 % *100 %
32-50 Source Slave 33-1* Synchronization 34-25 PCD 5 Read For Application 37-11 Pos. Brake Wear Limit 37-32 Initial Diameter Measurement
*[0] 24V-Encoder 33-13 Accuracy Window 0 - 65535 *0 0 - 1073741824 *0 *[0] Set diameter when diameter reset
[1] MCB102 -1073741824 - 1073741823 *1000 34-26 PCD 6 Read For Application 37-12 Pos. PID Anti Windup [1] Set diameter based on analog signal
[2] MCB103 33-14 Relative Slave Velocity Limit[%] 0 - 65535 *0 [0] Disable 37-33 Diameter Measurement Input
32-52 Source Master 0 - 100 % *50 % 34-27 PCD 7 Read For Application *[1] Enable *[0] No Function
[0] 24V-Encoder 33-27 Offset Filter Time 0 - 65535 *0 37-13 Pos. PID Output Clamp [1] Input53(0~10 VDC or 0~20 mA )
*[1] MCB102 0 - 1073741823 ms *0 ms 34-28 PCD 8 Read For Application 1 - 10000 *1000 [2] Input54(0~10 VDC or 0~20 mA )
[2] MCB103 33-4* Limit Handling 0 - 65535 *0 37-14 Pos. Ctrl. Source 37-34 Reading at Core
Quick Guide
[3] VM 33-41 Negative Software Limit 34-29 PCD 9 Read For Application *[0] DI 0 - 10 *0
32-6* PID -1073741824 - 1073741824 *-500000 0 - 65535 *0 [1] FieldBus 37-35 Reading at Full Roll
32-60 Proportional factor 33-42 Positive Software Limit 34-30 PCD 10 Read For Application 37-15 Pos. Direction Block 0 - 10 V *0 V
0.000 - 1000.000 *1.000 -1073741824 - 1073741824 *500000 0 - 65535 *0 *[0] No Blocking 37-36 Tension Set Point Input
32-61 Derivative factor 33-43 Negative Software Limit Active 34-5* Process Data [1] Block Reverse *[0] Par.3721
0.000 - 1000.000 *0.000 *[0] Inactive 34-50 Actual Position [2] Block Forward [1] Input53(0~10 VDC or 0~20 mA )
32-62 Integral factor [1] Active -1073741824 - 1073741824 *0 37-17 Pos. Ctrl Fault Behaviour [2] Input54(0~10 VDC or 0~20 mA )
0.0000 - 100.0000 *0.0000 33-44 Positive Software Limit Active 34-52 Actual Master Position *[0] Ramp Down&Brake 37-37 Taper Set Point Input
32-63 Limit Value for Integral Sum[%] *[0] Inactive -1073741824 - 1073741823 *0 [1] Brake Directly *[0] Par.3722
0.0 - 100.0 % *100.0 % [1] Active 34-56 Track Error 37-18 Pos. Ctrl Fault Reason [1] Input53(0~10 VDC or 0~20 mA )
32-64 PID Bandwidth[%] 33-45 Time in Target Window -2147483647 - 2147483647 *0 *[0] No Fault [2] Input54(0~10 VDC or 0~20 mA )
0.0 - 100.0 % *100.0 % 0 - 10 ms *0 ms 34-57 Synchronizing Error [1] Homing Needed 37-38 Tension Feedback Input
32-65 Velocity Feed-Forward 33-46 Target Window LimitValue -2147483647 - 2147483647 *0 [2] Pos. HW Limit *[0] No Function
77
9 9
9 9
*[0] No function
78
[1] 24V encoder
[2] MCB102
[3] MCB103
Appendix
*[0] Off
[1] On
MG06A802
Index Quick Guide
B
H
Branch circuit protection................................................................... 65
Hand on.................................................................................................... 30
High altitude............................................................................................. 9
C
High voltage...................................................................................... 8, 22
Cable length........................................................................................... 61
Horizontal mounting........................................................................... 12
Clearance requirement....................................................................... 11
Control
Characteristic..................................................................................... 63
I
cable..................................................................................................... 20 IEC 61800-3...................................................................................... 18, 64
system..................................................................................................... 3
Induced voltage.................................................................................... 13
terminal........................................................................................ 30, 53
wiring............................................................................................ 13, 14 Initialization
Manual procedure........................................................................... 32
Control card
Procedure............................................................................................ 32
+10 V DC output............................................................................... 63
Performance...................................................................................... 64 Input
RS485 serial communication....................................................... 63 Power............................................................................................. 13, 14
signal.................................................................................................... 20
Conventions........................................................................................... 67
voltage................................................................................................. 22
Cross-section.......................................................................................... 61 Power............................................................................................... 4, 22
Terminal............................................................................................... 22
D Inputs
Analog inputs.................................................................................... 62
DC current.................................................................................................. 4 Digital inputs.............................................................................. 21, 61
Default setting....................................................................................... 32 Pulse inputs........................................................................................ 62
Derating............................................................................................ 11, 64 Installation.............................................................................................. 11
Digital output......................................................................................... 63 Installation environment................................................................... 11
Discharge time......................................................................................... 8 Isolated mains........................................................................................ 18
Disconnect switch................................................................................ 22
L
E Leakage current....................................................................................... 9
Electrical noise....................................................................................... 14 Load sharing............................................................................................. 8
EMC............................................................................................................ 64 Local control........................................................................................... 30
EMC-compliant installation.............................................................. 13
Encoder rotation................................................................................... 35
Q W
Qualified personnel................................................................................ 8 Warning and alarm list........................................................................ 53
Quick menu..................................................................................... 25, 30 Wire size................................................................................................... 13
R
Reference................................................................................................. 30
Relay output........................................................................................... 63
Remote command.................................................................................. 3
Danfoss A/S
Ulsnaes 1
DK-6300 Graasten
vlt-drives.danfoss.com
*MG06A802*