Main
Range PowerLogic
Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
Product or component type Power meter
Complementary
Power quality analysis up to the 15th harmonic
Network frequency 50 Hz
60 Hz
type of network 1P + N
3P + N
3P
Number of inputs 0
Excluding VAT, FCA Jabal Ali & are subject to change – check with your local distributor.
25 Sep 2024 1
Measurement accuracy Active energy +/- 0.5 %
Reactive energy +/- 2 %
Active power +/- 0.5 %
Apparent power +/- 0.5 %
Frequency +/- 0.05 %
Power factor +/- 0.5
Current +/- 0.5 %
Voltage +/- 0.5 %
Apparent energy +/- 0.5 %
Reactive power +/- 2 %
Communication port protocol Modbus RTU and ASCII at 9.6, 19.2 and 38.4 kbauds even/odd or none - 2 wires,
insulation 2500 V
JBUS
Standards UL 61010-1
EN 50470-3
EN 50470-1
IEC 62053-22:2020
IEC 60529
IEC 62053-24
IEC 61557-12:2015
IEC 62053-23:2020
IEC 62052-11:2020
IEC 62052-31:2015
Width 96 mm
Depth 72 mm
Height 96 mm
Environment
Electromagnetic compatibility Voltage dips and interruptions immunity test class A conforming to IEC 61000-4-11
Limits for harmonic current emissions class A conforming to IEC 61000-3-2
Electrostatic discharge level 4 conforming to IEC 61000-4-2
Conducted RF disturbances level 3 conforming to IEC 61000-4-6
Magnetic field at power frequency level 4 conforming to IEC 61000-4-8
Conducted and radiated emissions - test level: 150 kHz...80 MHz class B conforming
to EN 55022
Immunity to conducted disturbances - test level: 150 kHz...80 MHz conforming to IEC
61000-4-6
Electrical fast transient/burst immunity test conforming to IEC 61000-4-4
Radiated radio-frequency electromagnetic field immunity test conforming to IEC
61000-4-3
Surge immunity test class B conforming to IEC 61000-4-5
Voltage dips and interruptions immunity test conforming to IEC 61000-4-11
Pollution degree 2
2 25 Sep 2024
Ambient air temperature for -25…70 °C meter
operation -20…70 °C display
-25…-20 °C (with reduced performance) display
Packing Units
Unit Type of Package 1 PCE
25 Sep 2024 3
Sustainability
Green PremiumTM label is Schneider Electric’s commitment to delivering products with best-in-
class environmental performance. Green Premium promises compliance with the latest regulations,
transparency on environmental impacts, as well as circular and low-CO2 products.
Guide to assessing product sustainability is a white paper that clarifies global eco-label
standards and how to interpret environmental declarations.
Learn more about Green Premium arrow2_right
Guide to assess a product’s sustainability arrow2_right
Transparency RoHS/REACh
Well-being performance
Mercury Free
Weee The product must be disposed on European Union markets following specific waste
collection and never end up in rubbish bins
4 25 Sep 2024