Fuel Gas Compressor System
Fuel Gas Compressor System
337/305 MW CCPP
O&M By:KEPCO-KPS
Gas Compressor
2. Cyclone Separator
-The cyclone separator unit is designed for 100% of flow.
- separates solid particles and moisture droplets from the
supplied gas by centrifugal action.
Major Equipments from Gas inlet to Compressor
Main Inlet
Header
from Titas
RMS
lled
n e u m atic Contro
P ff
cy Shut o
Emergen e Main
Valv
Inlet
Manual
Isolation
Valve
Major Equipments from Gas inlet to Compressor
shu ain
val off
M
ve
t
Gas detector
Air line
Vent
N2 charging point
Measuring instrument
Major Equipments from Gas inlet to Compressor
Manual
bypass
M isolation
iso anua valve of
la l
va tion cyclone
be lve separator
cy for
sep clon e
ara e
t or
con aining
Aut sate
Pressure relief
dr
d en
o
PI
Bypass valve
Cyclone
Level gauge separator
Major Equipments from Gas inlet to Compressor
Filter
Major Equipments from Gas inlet to Compressor
4. Metering unit
- The metering system is used to measure the total gas consumption of Gas
Turbine.
- consists of pressure compensation transmitter, temperature compensation
sensor, ultrasonic flow meter,chromotograph & flow computer etc. The
pressure compensation transmitter is used to measure the gas absolute
pressure in working condition, the temperature sensor is used to measure
the gas temperature in working condition and flow meter measure the flow
rate of gas and Chromatograph takes the online real time measurement of
gas heating value,density & wobbe index .
- The Flow computer calculates the gas volumetric flow rate & mass flow rate
by receiving all the data i.e. flow rate from flow meter, gas components &
density from chromatrograph,temperature & pressure from transmitter.
[Wobbe Index= LHV/(SG of gas X T)]
Flow computer
PT TE AT
Ultrasonic Flow
meter
Major Equipments from Gas inlet to Compressor
w
Flo ter
me pass
by alve
v
Flow
meter
inlet
valve
Sample line for
gas analyzer
Gas analyzer
Gas Booster
Compressor
GBC internal
structure
Gas Compressor
Initially the opening of the
valve is 5-10 degree. The
opening of this control valve
shall be gradually opened to
30 degree for operation
without load for two hours
after the speed of machine
train reaches the working
Instrument speed and running steadily.
air line
Compressor
Inlet
Compressor
outlet
Gas Compressor
Inlet
line
≥45 H
11 Temperature after Lube oil cooler (°C) 40
≤ 20 L
s N2
li n g ga sealing
a
Se from
line essor line
pr Vent
com tlet line
ou
after
sealing
Gas Compressor
Sealing lines
Gas
in
Gas Cooling
out water in
Lube oil
supply
Return
Lo tank
Lube Oil Skid Capacity 4500L
tor
x trac
o re
Local MCC Vap
Lube oil
pump
Suction
Delivery
Lo
Self cooler
pressure
control
valve Lo Filter
Gas Compressor
There are two screw pumps for
supplying oil to the compressor
bearings, motor bearings & gear box.
One pump is running & another one
in standby condition. When the
supply oil pressure drops below 0.11
MPa the standby oil pump come into
service automatically; after the
pressure returns to normal the spare
pump stops automatically.
If pressure dropped ≤0.08Mpa unit
will be tripped.
Suction strainer
Gas Compressor
Bypass manual
valve
These heaters will maintain
the lube oil tank
temperature from 20ᵒC-
25ᵒC.If tank temperature
goes down to 20ᵒC heater
vvee
tank surface.
PPrree
ers
aters
eerr
OOvv
ctric
Electr
Ele heat
ic he
Gas Compressor
Lube oil is cooled in the
er coolers.The oil
Ov sure e
es in temperature at outlet of
Lube pr ch l
Oil dis the cooler is regulated by
in controlling the cooling
water flow.It alarms when
oil temperature is above
45deg C. .Consumption of
cooling water is
35t/h*2(One working one
standby).Inlet cooling
water temperature is
32deg C.
Lube
oil
out
Cooling
water
Outlet
Cooling
Lube oil cooler water
inlet
Gas Compressor
Lube oil then runs into filter after
Lube oil filter
cooling. Filtering precession for lube oil
is 20μ. when the DP is more than
0.15Mpa, service filter should be
changed over. A self power pressure
Vent control valve is provided at the supply
header after the filter which will control
the supply header pressure.
Filter Filter
outlet inlet
Drain
Self
pressure
control
valve
Common
Com
m lube oil
lube on supply
o
retur il header
n
head
er
Gas Compressor
Emergency/Overhead lube oil tank:
Check valve
Bypass
Fil manual
De ling & valve
liv
lin ery
e
Common
lube oil
supply
header
Gas Compressor
Gearbox Parameters:
• Model: HSG836-1
• Transmitted power:
2240KW
• Service factor: 1.4
• Speed ratio: 13270/2981
• Oil Consumption: 150L/min
• Weight: 1100kg
Gas Compressor
Motor Parameters:
• Model: YBKS630-2
• Rated power: 2240KW
• Rated voltage: 6600V
• Rated current: 232A
• Rated speed: 2981r/min
• Cooling mode: Water cooling
• Weight:12000Kg
Gas Compressor
Cooling
water
Motor winding outlet
cooling
Cooling
water
outlet
Cooling
water
inlet
Cooling
water
inlet
Standby Gas Compressor
These are the
interconnection valves
after cooler of GBC-3 to
supply gas for both GBC-1
and GBC-2 delivery header.
By operating those valves
gas can be supplied at both
GBC’s delivery header. This
valves should be kept open
always for standby
To GBC -2
delivery operation.
header
To GBC-1
delivery
header
Gas Compressor
PLC System:
• PLC system is used to start/stop & control the Gas compressors & associated items.
• SMPCL GBC PLC system is provided by GE.
• Location: GBC MCC room.
Gas Compressor
Gas Compressor
Gas Compressor
Gas Compressor
Gas Compressor
Gas Compressor
Gas Compressor
Start up Interlock:
Gas Compressor
Compressor Trip logic:
Gas Compressor
Lube Oil Heater on/Off
Logic:
Gas Compressor
LO pump Logic:
Gas Compressor
Normal Operation: The suction adjusting valve of
compressor E-35 shall be gradually opened and the anti surge
valve shall be gradually closed so as to increase the gas volume
for pressurizing of the process system. The anti surge valve shall
be switched to automatic mode when the process system will
running steadily.
Normal shutdown: The load of compressor shall be firstly
reduced and the anti surge valve shall be opened and the
machine train shall be disconnected with the process system
before shutdown.
Condensate Tank & Vent Stack
Condensate
pump
Condensate
drain
Common vent for all vent point Condensate tank for all condensate
and pressure relief valve drain.
Gas Turbine Inlet Filtration & Heating System
Bypass
of heater
Gas Turbine Inlet Filtration & Heating System
Electric
heater
Inlet from
gas
conditioni
ng unit
Heater
control
panel
Heater parameters
Capacity:110KW
Design pressure:35bar
Design temperature:60DegC
Operating temperature:50-55DegC
Volume:0.25m3
Valve
before
entering
heater
Heater
bypass valve
Gas Turbine Inlet Filtration & Heating System
Gas fuel forwarding supply system:
Equipment Specifications
• Gas forwarding filter FLT101/102
• Gas pneumatic stop valve VS4-4
• Gas flow meter VM-1
• Gas total bleeding valve VA13-18
• Pressure switch of gas VSR stop valve 63FG-1/2
• Pressure transmitter of gas VSR stop valve 96FG-1
• Gas VSR stop valve VSR-1
• Pressure transmitter of gas VSR stop valve 96FG-2A/2B/2C
• Gas regulating control valve VGC-1
• Gas inter-valve bleeding solenoid valve 20VG-1
• Gas valve control hydraulic oil accumulator AH1-3
Gas Turbine Inlet Filtration & Heating System
Gas forwarding
filter
Vent
Manual v/v line
before entering
filter
Level
Condensate
gauges
drain
Gas Turbine Inlet Filtration & Heating System
Gas
pneumatic
stop valve Gas total
VS4-4 bleeding
valve VA-13-
18
Pressure
transmitter
of VSR 96FG1
Gas
regulating
Gas int control
er valve
valve
bleedin VGC-1
Gas g
solenoi
VSR d
valve
stop 20VG-1
valve
VSR1
Hydraulic
Hydraulic oil in oil
accumulat
or AH1-3 P & ID of the gas
module
Hydraulic oil out
Gas Turbine NG Skid
Hydrau
Return lic oil in
hydraulic
oil
Pressure
switch
63FG-1 &
2
Pressure
transmitter
96FG-1
Gas Turbine NG Skid
Control Valve.
The function of the fuel gas control valve
is to admit the proper amount of fuel
required by the turbine for a given load
or speed.
Control
valve
VGC-1
Hydrauli
c oil
Low gas pressure switch 63FG–1 & 63FG-2, installed in the gas piping
ahead of the gas stop/speed ratio and control valve assembly, provides
alarm protection and, on a dual–fuel unit, initiates a transfer to liquid fuel
should the supply gas pressure drop below the switch setting. An alarm will
be initiated and displayed on the turbine panel in the control center.
Gas Turbine NG Skid
Solenoid–operated valve 20VG–1 is installed in
the vent piping from the casing of the
combination gas stop/speed ratio and gas
control valve. When the turbine is at rest, any
20VG-1 fuel gas that might accumulate in the area
between the stop/speed ratio and control valve
vents to atmosphere through this valve.
Hydraulic
trip
Hydraulic relayVH5-2
trip
relayVH5-1
When trip oil pressure is normal, gas fuel trip relay VH5 is held in a position that allows hydraulic oil to flow
between control servo valve 90SR and hydraulic cylinder of VSR.In this condition, normal control of the
stop/speed ratio valve is allowed. In the event of a loss of trip oil pressure, the spring in the trip relay shifts the
spool to interrupt the flow path of hydraulic oil between the control servo valve and the hydraulic
cylinder.Simultaneously,the hydraulic oil in the VSR is dumped to drain and the stop/speed ratio valve
closes,shutting off fuel gas flow to the turbine.
Thank
You All!!