DV2 Installation Guide C2 A4
DV2 Installation Guide C2 A4
Solutions
Installation Guide
(APR/NPR Rectifiers)
Eaton Corporation
Telecommunications Power Solutions
www.eaton.com/telecompower
[email protected]
Eaton Corporation disclaims any liability for direct, indirect, incidental, special or
consequential damages arising out of the application or use of any information
contained in this document. The foregoing disclaimer applies to damages or personal
injury, property damage, loss of operation, loss of profits, loss of product or loss of time,
whether incurred by the purchaser, the purchaser’s employees or third party.
Information in this document does not constitute a warranty, representation or
guarantee concerning the suitability or performance of Eaton products. No such
warranty, representation or guarantee is expressed or implied.
Information contained in this document is subject to change without further notice.
Eaton, Powerware, Intergy, CellSure, SiteSure, PowerManagerII and DCTools are trade
names, trademarks, and/or service marks of Eaton Corporation or its subsidiaries and
affiliates. Unless otherwise noted, brands, product names, trademarks or registered
trademarks are the property of their respective holders.
Subject to the right to use its equipment, Eaton Corporation does not convey any right,
title or interest in its intellectual property, including, without limitation, its patents,
copyrights and know-how.
No part of this document may be reproduced or transmitted in any form, by any means
or for any purpose other than the Purchaser’s personal use, without the express written
permission of Eaton Corporation.
Copyright © 2005-2009 Eaton Corporation. All Rights Reserved.
About This Guide
About This Guide
Purpose
This guide provides instructions to correctly install, commission and operate Eaton Data-
Voice-Video Power Solutions .
Audience
This guide is intended for use by:
• DC power system installers competent in:
• installing and commissioning DC Power Systems
• safe working practices for AC and DC powered equipment
• the relevant local electrical safety regulations and wiring standards
• DC power system operators and maintenance staff competent in:
• operation of DC Power Systems
• safe working practices for AC and DC powered equipment
Scope
This guide covers installation, commissioning and maintenance of Eaton Data-Voice-Video
Power Solutions.
Related Information
• PowerManagerII Online Help
• DCTools Online Help
• Planning Guide – IPN 997-00012-15
• Eaton SM60 Supervisory Module Handbook – IPN 997-00012-27
• Eaton SM65 Supervisory Module Handbook – IPN 997-00012-35
• SiteSure Installation and Configuration Guide – IPN 997-00012-19
• CellSure Installation Guide – IPN 997-00012-20
Chapter 4 Commissioning
Overview ................................................................................................................................. 29
Inserting Rectifiers ................................................................................................................. 30
Pre-Power-Up Checklist ........................................................................................................ 31
Applying AC Power .............................................................................................................. 32
Configuring the DC Power System...................................................................................... 32
Using DCTools to configure the system ..................................................................................... 33
Using the Supervisory Module Keypad to Configure the System .......................................... 35
Testing Alarms at a Remote Location.................................................................................. 35
Applying DC Power to the Load.......................................................................................... 36
Chapter 5 Maintenance
Overview ................................................................................................................................. 37
Troubleshooting...................................................................................................................... 38
Replacing a Rectifier .............................................................................................................. 42
Monitoring and Replacing Transient Protective Devices ................................................. 44
Replacing the Supervisory Module ..................................................................................... 44
Battery Disposal and Recycling............................................................................................ 44
Appendix A Specifications
DC Power System using NPR Rectifiers ............................................................................. 45
DC Power System using APR/APU Rectifiers................................................................... 47
Appendix B System Components
Low Voltage Disconnect (LVD) Option .............................................................................. 49
LVD control by LVDCS controllers............................................................................................. 49
LVD selector switch and status LEDs ......................................................................................... 50
External Current Shunts/Sensors ........................................................................................ 51
Current shunts ............................................................................................................................... 51
CS04-A11 current sensor............................................................................................................... 51
Appendix C Magazine Addressing
NPR Rectifier Addressing ..................................................................................................... 57
APR/APU Rectifier Addressing .......................................................................................... 59
Equipment Incident Report
Worldwide Support
General Description
C h a p t e r 1
General Description
Overview
Topic Page
Other Features 5
2
2
# Supervisory module display (if fitted). See details on page 4. (For more details of the supervisory module refer to the relevant
supervisory module handbook listed under Related Information on page i.)
$ Rectifier magazine(s)* with either Access Power Rectifiers (APR/APU) or Network Power Rectifiers (NPR). See details of
rectifiers on page 3.
% Battery shelves with battery MCBs. (A battery shelf front cover is also supplied, but is not shown.)
These diagrams show typical layouts. Actual system configuration may vary from that shown.
* In some system configurations the AC distribution module may be installed in place of the top
rectifier magazine.
# Non-Urgent Alarm LED = (Yellow) ! Pull-out carry handle (NPR type rectifiers only)
# Keypad
$ Power On LED (green) – indicates that the ??? SM VARIABLE NOT SET ??? is powered
% Non-urgent Alarm LED (yellow) – indicates one or more active Non-urgent alarms
! Urgent/Critical Alarm LED (red) – indicates one or more active Urgent/Critical alarms
7 Scroll: Press to scroll through lists and menus and to increase or decrease
configuration file values.
6
: Information: Press to view status messages and a list of active alarms in Status View
Mode.
8 Enter: Press to go to Configuration Mode and Edit Mode, save configuration file
changes, clear alarms or toggle relay states.
For operation of the supervisory module refer to the supervisory module handbook. See Related
Information on page i.
Other Features
External communications
Eaton Data-Voice-Video Power Solutions have a number of methods of external
communication depending on the model of supervisory module fitted.
SM60 SM65
Communication with Eaton DCTools or PowerManagerII software
on a PC or Laptop via a serial cable.
Communication with Eaton DCTools or PowerManagerII software
on a PC or Laptop via an external PSTN or GSM modem. (Note 1)
Preparation
C h a p t e r 2
Preparation
Overview
Topic Page
Warnings 8
Warnings
This section contains important warnings. Read these warnings before installing or operating
an Eaton Data-Voice-Video Power Solutions DC power system.
Electrical Safety
• The DC earth/ground link must be rated to carry the combined fault current of battery strings.
See details on page 24.
• If the DC power system is to be installed in a location where the ambient temperature may rise
above 50ºC (122ºF), then V110 rated cable must be used for all connections.
• The DC power system is not compatible with IT (Impedance Terra) AC power distribution
topologies. For advice refer to Worldwide Support on page 63.
• A registered electrician (or suitably qualified person) must check the integrity of the installed
cabling, BEFORE the DC power system is powered up.
• Commissioning must be performed in the sequence documented in this guide.
Reverse Polarity
• Always check that the battery cables have been terminated to the correct system polarity
BEFORE connecting the batteries or closing the battery disconnect device. Connecting batteries
to the DC power system with incorrect system polarity will void all warranty claims.
Batteries
• The plastic cases of batteries installed in Eaton DC power system racks must have a flammability
rating of UL 94-V2 or better.
• Flooded cell lead acid batteries must be installed in a battery room. Do not install flooded lead
acid batteries in an Eaton DC power system rack.
• Flooded cell and VRLA lead acid batteries can emit explosive gases and must be installed with
adequate ventilation. Refer to the battery manufacturer or supplier for advice on minimum
ventilation levels.
• Do not wear a synthetic dust-coat or overalls. Synthetic fabrics can hold static electric charge that
create sparks during discharge.
• Remove rings, wristwatch and other metal jewelry that might be exposed to battery terminals,
before installing batteries.
• Batteries are powerful sources of energy and present a potential electrical shock and energy
hazard. The energy hazard is always present, even if the batteries are not connected. Avoid short
circuiting terminals of opposite polarity.
• Always use insulated tools.
• Do not place tools, loose cables or metal objects (such as interconnecting bars) on top of batteries.
• Do not drop tools, loose cables or metal objects onto intercell connections or terminals of
opposite polarity.
• Only terminate cables and interconnecting bars after confirming that the termination will not
create a short circuit.
• Always tighten battery terminal bolts according to the battery manufacturer’s specification.
Failing to do so can cause erratic battery performance, possible damage to the battery, and/or
personal injury.
• There is a risk of electric shock if a battery is replaced by an incorrect type.
• Dispose of batteries according to the instructions.
Rectifiers
•
•
Do not install the rectifiers until the room has been cleaned and is dust free.
To reduce the risk of electric shock and maintain optimum system cooling, always cover empty
rectifier slots with blanking panels.
• To avoid electrical shock, do not place hands inside the rectifier magazine.
• Rectifier cases may exceed 100ºC (212ºF), especially after prolonged operation. Use suitable
gloves when removing a rectifier from the magazine.
• Do not attempt to disassemble faulty rectifiers. Return them (in their original packaging) with a
copy of the Equipment Incident Report on page 61.
• Ensure that any upstream Residual Current Devices (RCDs) are appropriately rated for the
rectifiers' maximum earth leakage current (see Specifications on page 45 for value).
DC Distribution(s)
• The DC Common of the DC power system can be connected to earth (ground). If this connection
is made all of the following conditions must be met:
• Your equipment and the DC power system must be located within the same premises.
• No switching or disconnecting devices are allowed in the conductor between the DC
common line and the point of connection to the earth electrode conductor.
Refer to Connecting the DC Output to Earth on page 24 for further information.
Servicing
• The DC power system contains hazardous voltages. Do not attempt to disassemble or service
the unit if you are not qualified.
EMC Compliance
• Eaton Data-Voice-Video Power Solutions DC power systems may be used in close proximity to
other electronic equipment, provided installation is carried out according to instructions in this
guide. However, proper installation and compliance with EMC standards does not guarantee
that the DC power system will not respond to electromagnetic disturbances, or will not cause
interference to other equipment in a particular installation.
• In a domestic environment this product may cause radio interference in which case the user may
be required to take adequate measures.
• Changes or modifications to the DC power system not approved by Eaton Corporation could
void Federal Communications Commission (FCC) authority to operate that equipment.
• Data-Voice-Video Power Solutions DC power systems have been tested and found to comply
with the limits for a Class A digital device, pursuant to part 15 of the FCC Rules. These limits
are designed to provide reasonable protection against harmful interference in a commercial
installation.. This equipment generates, uses, and can radiate radio frequency energy and, if not
installed and used in accordance with the instructions, may cause harmful interference to radio
communications. However, there is no guarantee that the interference will not occur in a
particular installation. If this equipment does cause harmful interference to radio or television
reception, which can be determined by turning the equipment off and on, the user is encouraged
to try to correct the interference by one or more of the following measures:
• Reorient or relocate the receiving antenna.
• Increase the separation between the equipment and receiver.
• Connect the equipment into an outlet on a circuit different from that to which the receiver is
connected.
• Consult the dealer or an experienced radio/TV technician for help.
Keep the original packaging and use it if any equipment needs to be returned for replacement or
repair.
Installation
C h a p t e r 3
Installation
Overview
Topic Page
•
Access’. A key or tool is required to gain access to the power system. A sign must
also be displayed, warning that the power system metalwork may be hot.
The rack of the DC power system must meet the fire and electrical enclosure
requirements specified in AS/NZS 60950.1, EN 60950-1, IEC 60950-1 and UL
60950-1. To maintain compliance with these requirements, all covers must be fitted
(including the bottom cover plate, if bottom cable access is not required.)
• Lifting equipment and at least two people are required to safely move the DC
power system. Without lifting equipment four people are required to move the
power system safely.
Apart from the rectifiers and batteries, Eaton Data-Voice-Video Power Solutions are always
supplied completely assembled. Rectifiers and batteries are always shipped separately.
Clearance Requirements
The following minimum clearances are required:
• Front Clearance – 600mm (24“) from walls and other equipment required for access.
• Top Clearance – 200mm (8“) from ceilings or overhead cable trays/ducting, required for
optimum system cooling.
• Single Side or Back Clearance – 600mm (24“) from walls and other equipment
recommended to assist access.
• Back Clearance – 600mm (24“) from walls if the vented back panel is fitted.
Mounting
1 Before moving the power system into position, ensure that:
• Extra under floor support is in place, if required.
• The plastic dust cover is fitted and sealed to prevent dust and metal shavings from
entering the power system during drilling.
2 Move and align the rack and check the required clearance distances (see previous
section).
3 Drill the mounting holes and bolt down the rack.
4 Remove the plastic dust cover and vacuum clean around the rack to remove any metal
shavings and dust.
Earthing (Grounding)
The most important aspect of any power system installation at a site is the integrity of the
earthing systems. Effective earthing will significantly increase site protection. Most sites have
a number of earthing systems such as:
• AC Power earth
• DC Power earth
• Tower / building lightning protection earth
For optimum protection, all earths must be brought together at one "star" point. Otherwise,
surge currents can flow within the system creating large voltages. These can cause damage to
equipment that does not normally require surge protection, such as rectifier outputs and
communications interfaces.
If there is a tower on the site then use the tower earth as the "star" point. This is because it
conducts the majority of the surge to earth, especially if the site is lightning-prone. For other
sites, a 'direct-lightning' earth will not be available therefore a structural or power system
earth will be used. In multi-floor buildings, always try to use structural earths if the common
earth point cannot be found at ground level. For basements / single floor buildings, the AC
power earth is usually the most appropriate.
Installation
Install the transient protection according to the following diagram.
! Primary transient protection (refer to ' MOVs (3, phase-neutral, refer to text
text for rating) for rating)
Transient protective devices are fitted with alarm contacts and visual indicators. Monitor the
status of all externally installed transient protective devices either by:
• Connection of the alarm contacts to one of the Digital Inputs on the supervisory module
(preferred option) or to the building management system. Refer to the supervisory
module handbook for details of Digital Inputs.
• Regular inspection of the visual indicators
The alarm signal lines of the external transient protective devices must be isolated from the
AC supply (by voltage-free relay contacts) before connecting these signal lines to the
supervisory module.
For information on monitoring and replacing MOVs see details on page 44.
High AC Voltage Protection
If the AC voltage is expected to exceed 275V (L-N), then it is strongly recommended that an
external high voltage protection unit (HVPU) be installed. This will automatically disconnect
the AC at high voltage and reconnect it at normal voltage.
Install the HVPU as in the following diagram. Monitor the status of the HVPU by connecting
the High VAC alarm output to one of the Digital Inputs on the supervisory module. (Refer to
the supervisory module handbook for details of Digital Inputs.)
The High VAC alarm signal lines must be isolated from the AC supply (by a voltage-free relay
contact) before connecting these signal lines to the supervisory module.
% DC power system
•
rated for the rectifiers' maximum earth leakage current (see Specifications on page
45 for value).
If the DC power system is to be installed in a location where the ambient
temperature may rise above 50ºC (122ºF), then V110 rated cable must be used for
all connections.
• There must be adequate discrimination between the rectifier internal fuses, the
MCBs in the AC distribution of the DC Power System and the upstream AC
supply-disconnect devices. Failure to do this may result in the loss of AC power
to all rectifiers if a fault occurs in one rectifier. Refer to AC Discrimination on
page 18 for more information.
• Only use a three-phase (Δ) AC power source that is referenced to earth, or has a
protection system in place to prevent the phase-earth voltage exceeding the rating
of the rectifier.
AC Installation Practices
Read the following AC installation practices before connecting the AC supply:
• Ensure that each cable entry gland provides firm strain relief and adequate anchorage
for each AC supply cable.
• Prevent excessive strain on the AC wiring and terminal connections.
• Terminate the AC supply cable at the DC power system before terminating the AC
supply cable at the main AC switchboard or sub switchboard of the building.
• Label the main AC switchboard or sub switchboard.
• When all AC supply cabling is in place and terminated, perform electrical insulation and
continuity tests. Remove the MOVs if high AC voltages are used as part of these tests.
AC discrimination
Each rectifier has two internal fast-acting fuses. Under certain internal fault conditions these
fuses will blow.
If there is insufficient discrimination between these fuses and any upstream AC
supply-disconnect device then the upstream AC supply-disconnect device will operate
before a rectifier fuse blows. This will disconnect the AC supply to all rectifiers.
The average time-current curve of the rectifier internal fuses is shown in the following graph.
To ensure there is adequate discrimination, the time-current curve of the upstream AC
supply-disconnect device must be entirely outside (to the right of) the curve shown.
Sources: Littelfuse AC Fast-Acting Type KLK Series Data Sheet (NPR). Littelfuse Electronic Designer’s Guide,
November 2000, p60 (APR/APU)
AC Distribution Description
Terminal Label
L Live/Phase/Active of a single-phase system
L1 Phase 1 of a 2-phase or 3-phase system
L2 Phase 2 of a 2-phase or 3-phase system
L3 Phase 3 of a 3-phase system
N Neutral
E (Note 4) Protective Earth/Ground
Notes:
1 Refer to the warnings and AC installation practices on page 17.
2 All phase cable connection lugs must be insulated with heat shrink wrap.
3 Cable-tie all phase conductors close to their terminations. This prevents the bare end of a
conductor from touching metal parts, if it becomes loose.
4 The AC Distribution earth terminal is also used to reference the DC output to AC
earth/ground for surge protection. A factory-installed AC-DC earth link is connected to
this point for this purpose. See details on page 24.
Position of AC distribution
The AC supply cable is terminated at the AC distribution module. The position of the AC
distribution module depends on the system type and configuration. It is located either above
the rectifier magazines or behind the door covering the AC/DC distribution space.
E N L1 L2 L3 E L1 L2 L3
2 2
Typical arrangement Typical arrangement
with Neutral without Neutral
$ AC isolator switch (1, 2 or 3-phase as required). May be fitted next to MOVs depending on model.
If necessary, remove the back and/or side cabinet panel to route the cables to
the AC Distribution.
1 Route the AC earth cable to the rack earth stud (located behind the
isolator switch) and terminate.
2 Route the AC phase and neutral (if fitted) cables to the AC Distribution.
3 Terminate the phase cable(s) on the isolator switch.
4 If fitted, terminate the neutral cable on the neutral connector.
5 Secure all cables with cable ties.
Procedure complete
2
" AC isolator switch (shaft not shown) ! Rectifier MCBs (3 only shown)
$ AC cable entry glands 3 MOV MCB (located next to rectifier MCBs in some
models)
% Isolator switch terminals
If necessary, remove the back and/or side cabinet panel to route the cables and
access the back of the AC Distribution.
1 Route the AC earth cable to the earth stud on the back of the AC
Distribution.
2 Route the AC phase and neutral (if fitted) cables through the AC cable
entry glands in the back of the AC Distribution.
3 Fit suitable size crimp lugs to the AC cables.
4 Insulate all phase cable lugs with heat shrink wrap.
1 Check all terminations are correct and all bolts are tightened.
2 Test the insulation resistance of the cables according to local AC wiring
regulations..
DC earth connection
Install a separate conductor connected from the DC common busbar to earth. This conductor
must be rated to carry the combined fault current of battery strings.
If this conductor is not installed then battery fault current will be carried by the AC-DC earth
link and the AC earth conductor which are typically too small for such currents.
$ DC Common
# AC earth (ground)
% DC Common
The transient protective device bonds the AC and communications earth during transient
activity to prevent damage to the rectifiers. The preferred transient protective device is a
transient earth clamp (TEC).
DC Installation Practices
Read the following DC Installation Practices before connecting the DC load and battery
cables:
• To avoid excessive voltage drop and overheating, ensure that the DC load and battery
cables are appropriately sized to handle the maximum DC output current of the specific
NPS. We recommend multi-strand cable with insulation rating of 600-1000V.
• Run the DC load and battery cables through cable glands where they pass through metal
parts or covers. Also ensure that each cable gland provides firm strain relief and
adequate anchorage for the cable.
• Secure and support all DC load and battery cabling inside the NPS (especially at their
connection points) to prevent excessive strain on these cables.
• To reduce inductive coupling, separate DC load, battery and control cabling from AC
supply cables. If the cables have to cross, run them at right angles to the AC supply
cables.
• In order to minimize parasitic cable inductance and reduce electromagnetic interference
(EMI), route all DC load cables in close proximity to one another, and avoid large
current loops. The same applies to battery cables.
• Ensure that MCBs/fuses in the DC distribution(s) are clearly labeled.
• Only perform electrical insulation and continuity tests, once all DC load and battery
cabling are in place and DC Common has been earthed.
In systems with
integrated batteries
the battery MCBs are
mounted individually
at the battery shelves.
$ Ensure that the fuse fail detection wires are properly terminated as shown.
% Battery fuses are fitted with a Battery fuse fail detection board. When replacing a fuse ensure that the board
is removed from the blown fuse and re-fitted to a new striker type fuse.
•
polarity BEFORE connecting the batteries or closing the battery disconnect device.
Connecting batteries to the system with incorrect system polarity will void all
warranty claims.
Because of the wide range of battery types and sizes available, battery installation in not
included in this guide. Always install batteries according to the battery manufacturer’s
instructions.
The following are our recommended Battery Installation Practices. These supplement the
specific installation instructions of the relevant battery manufacturer.
General
• Do not wear a synthetic dust-coat or overalls. Synthetic fabrics can hold a static electric
charge, creating sparks during discharge.
• Remove rings, wristwatch and other metal jewelry that might be exposed to battery
terminals, before installing batteries.
• Only use a clean soft damp cloth for cleaning the batteries. Do not use cleaning
detergents or chemicals.
• Flooded cell and VRLA lead acid batteries can emit explosive gases and must be
installed with adequate ventilation. Refer to the battery manufacturer or supplier for
advice on minimum ventilation levels.
• Ensure that the battery shelves are disconnected from the DC power system, by
switching off all battery MCBs or removing all battery fuses.
Commissioning
C h a p t e r 4
Commissioning
Overview
Topic Page
Inserting Rectifiers 30
Pre-Power-Up Checklist 31
Applying AC Power 32
Inserting Rectifiers
• Ensure the room has been cleaned and is dust free BEFORE unpacking the
•
rectifiers.
DO NOT switch on the AC supply at this stage.
Unpack the rectifiers and inspect them carefully for possible transport
damage. Report any damage immediately, using a copy of the Equipment
Incident Report on page 61.
Keep the original packaging. You will need this if any equipment needs to be
returned for replacement or repair.
1 Align the rectifier with the guide rails in the magazine
2 Slowly push in the rectifier.
3 Move the handle into its closed position (NPR type rectifiers only).
The retaining screw must be properly tightened to secure the rectifier in the
magazine and ensure reliable operation.
Procedure complete
Pre-Power-Up Checklist
Complete the checklist to confirm initial work is complete before progressing further.
Upstream surge protection is fitted (see Input Transient Protection on page 13)
System earthing is correctly installed (see Connecting the DC Output to Earth on page 24)
A registered electrician or other suitable approved person has checked the integrity of the
installed cabling
All panels are in place and all empty rectifier slots are covered with blanking panels
AC supply is isolated at each point of isolation leading back to the external AC distribution
Applying AC Power
• A registered electrician (or suitably qualified person) must check the integrity of
With NPR rectifiers the yellow = Non-urgent alarm LEDs will flash while the
supervisory module initializes (up to 2 minutes).
On all other rectifiers the red Urgent < alarm LEDs will be on.
Refer to Troubleshooting on page 38 for further explanation of alarm LEDs.
7 Check that the supervisory module has powered up and that the green B Power On
LED on the supervisory module is on.
Only those configuration parameters that are most likely to be changed on-site can be
configured from the supervisory module keypad. A PC or laptop with DCTools is required to
edit all other configuration parameters (such as mapping of alarms to relays and setting up
communications).
We recommend using DCTools (available from www.powerquality.eaton.com/downloads)
for all configuration tasks.
1 Connect the null modem cable from the supervisory module RS-232
port to the laptop or PC. Refer to Communications Options in the
supervisory module handbook.
2 Start DCTools.
1 Double-click the DCTools icon in the Windows task bar to display the
DCTools Connection List. The default connection is COM1.
2 If the port properties are correct, enable the connection by selecting the
Active check box E of that connection.
The correct port properties are: Protocol: S3P and S3P Address: 0.
If the port properties are incorrect, select the relevant connection from
the Connection List and click the toolbar button. In the Comms
Properties dialog, edit the properties as necessary and click OK.
If the connection is successful, the DCTools System Summary (Home)
screen is displayed.
Step 3 - Check through the loaded configuration file and make changes as required
Check through the configuration file in DCTools by clicking on the hotlinks
at the top of the DCTools System Summary (Home) screen. Make changes as
required.
The following table shows the main hotlinks and a list of the items that can
be configured.
Hotlink Click to …
Configuration Enter site specific information and synchronize the real time
clock (SM65 only) under Identity
Set keypad access control, configure modem settings and set-up
SMS messaging (SM60 only); setup Ethernet communications
and SNMP traps (SM65 only) under Communications
Configure SiteSure module addresses under External IOM
For further details refer to the supervisory module handbook.
Alarms Configure system alarms (see following section)
Analogs Configure analog inputs, AC three-phase metering (SM60 only),
current inputs and external analog inputs
Digitals Set-up user alarms (see Setting Up User Alarms in the
supervisory module handbook)
Relays Toggle relay states when performing a Relay Test (see details on
page 35) and configure external digital inputs (see External
Alarm and User Digital Inputs in the supervisory module
handbook).
Control Configure the settings of control functions such as Manual
Equalize, Temperature Compensation, Battery Test, Fast Charge,
Battery Current Limit and Active Voltage Control (for
descriptions see Control Functions).
LVD Enable/disable LVD(s) and configure the LVD settings (for
description see Control Functions).
Rectifiers Configure rectifier settings and magazine addressing (if
required, see details on page 57).
Step 1 - For each alarm relay used, simulate an alarm at the supervisory module
Step 2 - Check if the alarm signal has been received at the remote location
Procedure complete
Check the DC output voltage and polarity of the power system and the
battery string(s).
1 Switch on the Battery MCB(s) and/or fit the battery fuses.
2 Check that the Battery Fuse Fail alarm clears.
1 Switch on the Load MCB(s) and/or fit the Load fuses.
2 Check that the equipment powers up and that the Load Fuse Fail alarm
clears.
1 Check the rectifier currents.
2 Verify that the load current is representative of what the load and
battery draws.
3 Verify that the DC power system has sufficient capacity.
1 Charge the batteries according to the battery manufacturer’s
recommendations.
2 If required start Manual Equalize from DCTools or the keypad.
Procedure complete
Maintenance
C h a p t e r 5
Maintenance
Overview
Topic Page
Troubleshooting 38
Replacing a Rectifier 42
Troubleshooting
Use the table to troubleshoot minor installation and operational problems. For additional
assistance see Worldwide Support on page 63. Return items for replacement or repair with a
copy of the Equipment Incident Report on page 61.
Rectifier numbers are offset Incorrect setting in Use DCTools to verify that the
by one. configuration file. Rectifier Offset is set to 0.
Low system output voltage Rectifiers off. Restore AC power.
(rectifiers not in current
limit.) Battery Test and/or Disable active function(s) if not
Temperature Compensation is required.
active.
Activate the battery current limit
control function.
Incorrect float voltage setting at Check the float voltage setting of the
supervisory module. supervisory module.
Record new setting.
Low system output voltage Load is too high for rectifier Install additional rectifiers.
and rectifier yellow LEDs capacity.
are on (rectifiers are in
current limit.) Battery is recharging after AC Check battery has recharged within
power outage. expected time.
Faulty MOV Fail alarm wiring. Check the MOV Fail alarm wiring.
Red or Green LVD LED is LVD auto or manual operation. See details on page 50.
on or flashing.
Both LVD controller LEDs LVD controller not powered or Check power connection to the LVD
off. faulty. controller. Replace LVD controller if
faulty.
LVD controller LEDs flash Faulty contactor auxiliary Check the electrical and mechanical
simultaneously. switch. operation of the contactor auxiliary
switch.
Faulty wiring/connectors. Check all wiring and connectors.
LVD controller LEDs Short circuit in contactor coil. Ensure that the correct contactor is
flashing alternately. used for the system.
Contactor Coil Type jumpers Check and configure the jumpers
incorrectly set (LVDCS only). correctly. See details on page 49.
LVD contactor fails to trip Faulty LVD controller or Replace faulty LVD controller or
after recognition time. contactor. contactor.
Faulty wiring/connections. Check the wiring/connections
between the contactor and the
supervisory module.
Supervisory module Faulty current shunt/sensor. Replace the faulty current
displays current value(s) as shunt/sensor.
AAA
Incorrect connection from Check RJ45 cable from port XU1 on
-OR- current shunts/sensors to the current shunt/sensor to port XS6
DCTools displays current supervisory module. on the supervisory module.
value(s) as N/A. Check that all interconnecting cables
are plugged into the correct ports.
Replacing a Rectifier
Wait 20 seconds after removing a rectifier before re-inserting it. This allows the rectifier to clear
its internal settings.
Rectifiers can be replaced without switching off the DC power system and disconnecting the
equipment it powers.
• To reduce the risk of electric shock and maintain optimum system cooling, always
I •
•
cover empty rectifier slots with blanking panels.
To avoid electric shock do not place hands inside the rectifier shelf.
Do not attempt to disassemble faulty rectifiers. Return them (in their original
packaging) with a copy of the Equipment Incident Report on page 61.
Removing a Rectifier
Step 2 - Pull out the rectifier
•
suitable gloves.
To avoid damage to the connector do not rest the rectifier on its
connector, once it has been removed from the shelf.
Procedure complete
You must now insert a replacement rectifier into the empty slot or fit a blanking panel to
maintain optimum system cooling.
Inserting a Rectifier
Step 2 - Push in the rectifier
The urgent alarm LED < turns on for about 1 second when the rectifier
powers up. The rectifier will then automatically register with the
supervisory module and download its operating parameters. No
adjustments are required.
Procedure complete
We strongly recommend inspecting the MOVs in the main AC switchboard at the same time
and replacing them as appropriate.
If any MOV or other transient protection device has failed then the design of the primary and
secondary transient protection systems, and the maintenance plan, at that site must be
reviewed.
Specifications
A p p e n d i x A
Specifications
System DC Output
DC Output Voltage (nominal) NPR24: 24 V
NPR48: 48V
DC Output Power (maximum) NPR24: 38.4 kW for a 24 rectifier system
NPR48: 72 kW for a 24 rectifier system
DC Output Voltage Range NPR24: 20 - 29 V
NPR48: 40 - 58 V
2-5% minimum load required below 45V
Over Voltage Shutdown Trip Point NPR24: 29.8 – 30 V (fixed)
NPR48: 59.4 – 60 V (fixed)
Environment
Ambient Temperature Range (operating) -25°C – +70°C [-13°F – 158°F]
Output current derates above 50 °C [122°F]
Relative Humidity (operating and storage) <95% (non condensing)
Dimensions H, W, D
System (H, W, D) 2000mm [78.7"], 600 mm [23.6”], 600 mm
[23.6”]*
Rectifier (H, W, D) 5U: 220 mm [8.75”], 70 mm [2.75”], 360mm
[14.2”] overall
* Additional clear air space is required at rear for rectifier exhaust air venting (see details on page 12).
Weight
System 165 kg [364 lb]*
Alarm Relays
Refer to the Specifications section of the supervisory module handbook.
Digital Inputs
Refer to the Specifications section of the supervisory module handbook.
Comprehensive supervisory module and rectifier data sheets are available. Refer to Worldwide
Support on page 63.
System DC Output
DC Output Voltage (nominal) APR24: 24 V
APU48/APR48: 48V
DC Output Power (maximum) APR24: 18 kW for a 24 rectifier system
APU48: 17.3 kW for a 24 rectifier system
APR48: 36 kW for a 24 rectifier system
DC Output Voltage Range APR24: 21.5 - 29 V
APU48/APR48: 43 - 57.5 V
Over Voltage Shutdown Trip Point APR24: 29 V
APU48/APR48: 58 V
Environment
Ambient Temperature Range (operating) -40°C – +70°C [-40°F – 158°F]
Output current derates above 50 °C [122°F]
Relative Humidity (operating and storage) <95% (non condensing)
Dimensions H, W, D
System (H, W, D) 2000mm [78.7"], 600 mm [23.6”], 600 mm
[23.6”]*
Rectifier (H, W, D) 3U: 133 mm [5.25"], 66 mm [2.6”], 280 mm [11”]
overall
* Additional clear air space is required at rear for rectifier exhaust air venting (see details on page 12).
Weight
System 165 kg [364 lb]*
Alarm Relays
Refer to the Specifications section of the supervisory module handbook.
Digital Inputs
Refer to the Specifications section of the supervisory module handbook.
Comprehensive supervisory module and rectifier data sheets are available. Refer to Worldwide
Support on page 63.
System Components
A p p e n d i x B
System Components
% Automatic/Manual Selector
Switch. See details on page 50.
Jumpers
LVDCS are pre-configured at the factory and do not require jumper changes under normal
conditions. However, if there is a problem, check the positions of the three jumpers shown in
following table.
Notes:
1 If a selector switch is set to manual (disconnect or connect) during servicing, ensure that
the switch is reset to AUTO when servicing is complete.
2 The LEDs also indicate LVD faults. Refer Troubleshooting on page 38.
Current shunts
Eaton current shunts are to be mounted in the LIVE bus and have a current sense signal of
55mV at maximum rated current. A typical current shunt is shown in the following diagram.
Actual current shunt(s) supplied may vary from that shown.
# Connection to rectifiers
% Calibration Potentiometer
Installation
Eaton current shunts are factory-calibrated for easy set-up, and do not require re-calibration,
under normal conditions. However, if you observe significant measurement inaccuracies, use
the calibration potentiometer to re-calibrate the current shunt.
The two RJ45 sockets are used to interconnect current shunts in a serial fashion.
$ Input inductor
Step 2 – Determine the need for a CS04 current sensor extension PCB
If the required gain of the current sensor is greater than 40, then calculate the
new required gain of the current sensor as follows:
Measure the resistance of the inductor located at the back of the CS04 current
sensor PCB as shown.
16 – 21 13 – 18 12 – 16
19 – 29 16 – 24 15 – 22
27 – 52 22 – 42 20 – 39
38 – 132 31 – 108 29 – 99
The jumper connection points are located on the back of the CS04-A11 current sensor PCB.
To obtain the required jumper configuration, you might have to break the track between
connection points 1 and 3 and solder additional jumpers between connection points.
Procedure complete
CS04-A11 current sensors must always be mounted onto the LIVE bus bar.
(See following diagram.)
Wherever possible, do not mount the CS04-A11 current sensor closer than
150mm (6”) from:
• A bus bar joint
• Termination bolts
• Bolts joining laminated bus bars
Ensure correct orientation of the CS04-A11 current sensor before drilling the
mounting holes into the bus bar. (See following diagram.)
# To load or battery
Drill two mounting holes according to the template below and tap if the
threaded-hole mounting option is used.
Through-hole Threaded-hole
Drill size M3.5 M2.5
Thread size and pitch - M3 x 0.5 ISO
Coarse
Procedure complete
Magazine Addressing
A p p e n d i x C
Magazine Addressing
1 17 97-102
2 18 103-108
3 19 109-114
4 20 115-120
5 21 121-126
" Address board (located at the rear of magazine). Not required on Magazine 1 (or set SW1 to 0).
$ Link (R17) - fitted on address boards in magazines 1 to 16 and removed from magazines 17 to 21.
# Magazine Number Selector Switch (SW) for setting magazine numbers according to the following table.
0 1 1-2
1 2 3-4
2 3 5-6
3 4 7-8
4 5 9 - 10
5 6 11 - 12
6 7 13 - 14
7 8 15 - 16
8 9 17 - 18
9 10 19 - 20
A 11 21 - 22
B 12 23 - 24
C 13 25 - 26
D 14 27 - 28
E 15 29 - 30
F 16 31 - 32
Backplane interconnections
The RJ45 communications cables between the rectifier magazine backplanes and the
supervisory module, and the J4 and J5 jumpers must be connected as shown in the following
diagram.
Please enter as much information as you can. Send the completed form, together with the item for repair to your
nearest authorized service agent. NOTE: Only one fault to be recorded per form.
For further information contact Eaton Corporation, Telecommunications Solutions Division. Telephone:
+64 3 343 3314, Fax: +64 3 343 7446. Or email: [email protected]
Date:
Customer Information
Company:
Postal Address:
Return Address:
(Not PO Box)
Location of Failure
Product code: Serial number: Document number:
System type installed in: Serial number:
Site name or location:
SG/03 ISS04
For product information and a complete listing of worldwide sales offices, visit Eaton's
website at: www.eaton.com/telecompower or email: [email protected]
For technical support contact either your local Eaton DC product representative, the closest
office from the following list, telephone (+64) 3 343-7448, or email
[email protected]