HPCO2 Component Description
Flex Hose - 3/4 in.
Effective: January 2019
P/N: WK-251821-000 K-81-1090 Rev AE
FEATURES
• ¾" NPT (DN20) Outlet Fitting • Underwriters' Laboratories Listed - File Number EX923
• Swivel Connection onto Discharge Head • Factory Mutual Approved - Standard 5420
• Perforated Outer Jacket • United States Coast Guard Approved
• 0°F (-18°C) to 130°F (55°C) agency temperature range
DESCRIPTION
The discharge hose attaches to the discharge head on a
Kidde High Pressure Carbon Dioxide (CO2) cylinder
assembly secured at the project site.
The discharge hose connects each discharge head to the
system manifold. The hose's flexibility mitigates any mis-
alignment when connecting multiple cylinders onto a
common manifold.
A discharge hose needs to be ordered for each cylinder
assembly.
NFPA 12 requires either replacement or hydrostatic test-
ing of each hose every five years from the original date of
manufacture, which is marked onto a hose fitting.
ORDERING INFORMATION
Description Part Number
Flex Hose - 3/4 in. WK-251821-000
REFERENCED COMPONENTS
Reference Data
Description
Sheet
Cylinder & Valve Assembly, 75/100-lbm K-81-1010
Discharge Head, Plain Nut K-81-1060
Discharge Head, Groove Nut K-81-1070
1
16.4"
SWAGED OR CRIMPED
HOSE WITH PERFORATED COVER
MALE COUPLING
FEMALE SWIVEL COUPLING
3/4" NPT 3/4" NPS
MATERIALS:
Body: Reinforced rubber with wire braid.
Fittings: Steel, Trivalent Chromate
SPECIFICATIONS
Max. Hydro
Temperature Minimum Industrial DIOM Marine DIOM
Description Weight Test
Rating Burst Pressure Manual P/N Manual P/N
Pressure
Flexible Hose, 3/4” Outlet 1 lb -40°F to 250°F 6000 PSI 2500 PSI 81-CO2MAN-001 220610
(-40°C to 121°C) (414 bar) (173 bar)
EXPORT INFORMATION (USA)
Jurisdiction: EAR
Classification: EAR99
This document contains technical data subject to the EAR.
KIDDE is a registered trademark of Kidde-Fenwal, Inc., or its parents, subsidiaries or affiliates.
This literature is provided for informational purposes only. KIDDE-FENWAL, INC. believes this data to be accurate, but it is published and presented without any guarantee
or warranty whatsoever. KIDDE-FENWAL, INC. assumes no responsibility for the product's suitability for a particular application. Product features specified are only
applicable when the fire suppression system is correctly designed, installed, maintained and serviced by trained, authorized Kidde Fire Systems distributors as per the
applicable design, installation, operation, and maintenance manuals. If you need more information on this product, or if you have a particular problem or question, contact:
KIDDE-FENWAL, INC., Ashland, MA 01721 USA, Telephone: (508) 881-2000.
2 Kidde Fire Systems
400 Main Street
Ashland, MA 01721
K-81-1090 Rev AE Ph: 508.881.2000
Fax: 508.881.8920
©2019 Kidde-Fenwal, Inc. [Link]